DISTRIBUTION TRANSFORMER - DATA SHEET

Instructions:
1 Kindly do not alter the contents of the cell which contain formulas
2 Click the appropriate TABS to select/go to the respective sheets.
3 Cells/Columns colour coding
Data Contain standard / Formulas / Results
Data to be Entered Manually
Select from Drop down
Resp. Dept. Prepared by

Doc No: PTC-BFT-D-009B, Rev. 0 Date Approved by


Title: Distribution transformer - Dry Type - Technical Datasheet 21/06/2017

DISTRIBUTION TRANSFORMER - DRY TYPE – DATA SHEET

Sl. No Description Unit Requirement Data Vendor Confirmation

1.0 General Information


1.1 Design Standard IEC 60076-11,12 Yes / No
1.2 Quantity As per RFQ
1.3 Type of installation Outdoor
1.4 Average ambient temperature °C 40
1.5 Altitude m <1000

2.0 Distribution transformer data


2.1 Transformer type Dry Type- epoxy cast resin
2.2 Number of windings 2
2.3 Rated frequency Hz 50
2.4 Type of cooling AN
2.5 Rated power at average ambient MVA 2
2.5.1.1 AN MVA 2
2.5.1.2 AF MVA Not applicable
2.6 Rated voltage
2.6.1 HV kV 11
2.6.2 LV kV 0.4
2.7 Connections
2.7.1 HV Delta
2.7.2 LV Star
2.8 Vector group Dyn11
2.9 Tap changer OCTC
2.9.1 Tap range +5% to -5% in steps of 2.5%
2.10 Protective enclosure Enclosed
2.11 Ingress protection class IP 3X
2.12 Climatic class C2
2.13 Environmental class E2
2.14 Fire behaviour class F1
Temperature rise of winding at average ambient
2.15 °C 60
temperature of yearly average ###
2.16 Conductor material Copper
2.17 No load losses at rated voltage and ratio Vendor to specify

2.18 Load loss at rated voltage and ratio Vendor to specify

2.19 Efficiency at rated voltage and unity power factor Vendor to specify
Impedance at rated voltage and power (with tolerances as
2.2 % 6
per IEC 60076) ###
2.21 Rated lightining impulse voltage
2.21.1 HV kVp 75 ###
2.21.2 LV kVp - ###
2.22 Rated power frequency withstand level
2.22.1 HV kV 28 ###
2.22.2 LV kV 3 ###
2.23 Terminals
2.23.1 HV Cable Box
2.23.2 LV Cable Box
2.23.3 Neutral terminal Cable for solid earthing
2.24 Dimension
2.24.1 Overall dimensions LxWxH mm Vendor to specify
2.24.2 Transport dimensions LxWxH mm Vendor to specify
2.25 Weight
2.25.1 Total kg Vendor to specify
2.25.2 Transport kg Vendor to specify
2.26 Painting shade Grey - RAL 7030
2.27 Sound pressure level As per NEMA-TR1
2.28 Acessories
2.28.1 Winding temperature indicator with alarm and trip contacts Required
2.28.2 Rating plate, lifting lug, jacking pad, grounding terminals Required

Page 2 of 3
Resp. Dept. Prepared by

Doc No: PTC-BFT-D-009B, Rev. 0 Date Approved by


Title: Distribution transformer - Dry Type - Technical Datasheet 21/06/2017

DISTRIBUTION TRANSFORMER - DRY TYPE – DATA SHEET

Sl. No Description Unit Requirement Data Vendor Confirmation

2.30 Neutral Current transformer


2.30.1 Neutral Current transformer Required
2.30.2 Rated ratio - 3000/5 A
2.30.3 Accuracy - 5P20
2.30.4 Rated burden VA 20
2.30.5 Knee point voltage V Not applicable

Page 3 of 3