Installation calculation report

New_project
Full
Page 2/32

Project: New_project 22/04/2018


Page 3/32

Content

1 Project description.................................................................................................................. 4
1.1 Project general settings................................................................................................................... 4

1.2 Settings for wiring device calculation............................................................................................ 4

1.3 List of loads...................................................................................................................................... 4

2 Installation general design.....................................................................................................6


2.1 List of devices.................................................................................................................................. 6

3 Calculation notes.................................................................................................................. 14
3.1 Source circuits............................................................................................................................... 14

3.2 Generator circuits.......................................................................................................................... 23

3.3 LV Source circuits.......................................................................................................................... 23

3.4 UPS circuits.................................................................................................................................... 24

3.5 Surge Arrester circuits................................................................................................................... 24

3.6 Capacitor bank circuits.................................................................................................................. 24

3.7 Feeder circuits................................................................................................................................ 24

3.8 LV Transformer circuits................................................................................................................. 25

3.9 Couplers circuits............................................................................................................................ 27

3.10 Generic load circuits................................................................................................................. 27

3.11 Lighting load circuits................................................................................................................ 27

3.12 Power socket load circuits....................................................................................................... 28

3.13 Motor starter combination........................................................................................................ 28

3.14 Busbar circuits.......................................................................................................................... 29

3.15 Busbar trunking system circuits............................................................................................. 29

3.16 Busbar trunking system circuits............................................................................................. 29

3.17 Lighting Busbar trunking system circuits..............................................................................29

Project: New_project 22/04/2018


Page 4/32

1 Project description
1.1 Project general settings
Installation standard IEC60364

Calculation standard TR50480


Circuit breaker standard IEC 60947-2
Frequency 50 Hz

1.2 Settings for wiring device calculation


Maximal CSA 300 mm²

1.3 List of loads


1.3.1 Generic loads
Name Sr (kVA) Pr (kW) Ir (A) Cos Nbr Polarity Non linear load THDi 3 (%)
AA 12 17.3 14.7 25 0.85 1 3Ph+N No 0
AA 15 13.9 11.8 20 0.85 1 3Ph+N No 0

1.3.2 Lighting distribution


Name Type of lamp P Lamp (W) P ballast (W) Nb of lamp/light Nb of light
EA 14 Standard 150 0 1 10
incandescent
lamp
1.3.3 Motor loads
Name Sr (kVA) Pr (kW) Ir (A) Cos Nbr Polarity Non linear load THDi 3 (%)
MA 11 135 118 195 0.87 1 3Ph No 0
MA 16 24.2 20.9 35 0.86 1 3Ph No 0

Project: New_project 22/04/2018


Page 5/32

2 Installation general design


2.1 List of devices
2.1.1 MV/LV transformer
Nbr Range Insulation Sr (kVA) ukrT (%) Connection U2 (V) SEA Rb
Name
(m)
TA 3 1 Trihal Dry-type 250 6 D 420 TN-S 10000

2.1.2 LV backup generator


Name Nbr Sr (kVA) x”d (%) x’d (%) x0 (%) U (V) SEA Rb
(m)
G 17 1 45 20 30 6 400 TN-S 10000

2.1.3 LV switchboards and busbar


Switchboard name Range Rating (A) IP
UC 8 No preference 0.00 Undefined

Busbar name Switchboard Ks Polarity SEA Equipotential bounding


name
WC 7 UC 8 1 3Ph+N TN-S With

2.1.4 Circuit breaker


Name Nbr Range - Rating (A) Poles Trip unit/Curve RCD RCD class
Designation
QA 3 1 Compact 400 4P4d Micrologic 5.3 A
NSX -
NSX400F
QA 11 1 Compact 250 3P3d MA
NSX -
NSX250F
QA 12 1 Acti9 iC60 - 25 4P4d C
iC60N
QA 14 1 Acti9 iC60 - 3 4P4d C
iC60N
QA 15 1 Acti9 iC60 - 20 4P4d C
iC60N
QA 16 1 Compact 100 3P3d Micrologic 2.2 M
NSX -
NSX100F
QA 17 1 Acti9 C120 - 80 3P3d B Vigi C120 A
C120N

2.1.5 Cable schedule


Name Nbr Incomer Feeder Type Insulation L (m) L1/L2/L3 N PE/PEN
WD 16 1 QA 16 MA 16 Multi-core XLPE 20 1x4 Copper 1x4 Copper
WD 15 1 QA 15 AA 15 Multi-core XLPE 20 1x2.5 1x2.5 1x4 Copper
Copper Copper
WD 14 1 QA 14 EA 14 Multi-core XLPE 20 1x1.5 1x1.5 1x4 Copper
Copper Copper
WD 12 1 QA 12 AA 12 Multi-core XLPE 20 1x2.5 1x2.5 1x4 Copper
Copper Copper
WD 11 1 QA 11 MA 11 Multi-core XLPE 20 1x70 1x35
Copper Copper
WD 17 0 G 17 QA 17 Multi-core XLPE 5 1x16 1x16
Copper Copper
Project: New_project 22/04/2018
Page 6/32

WD 3 1 TA 3 QA 3 Multi-core XLPE 5 1x150 1x150 1x95


Copper Copper Copper

2.1.6 MV Cable
Name Nbr Designation CSA (mm²) Icc (A) In (A) Un (kV)
MVWD 1 NA 1 x 240 Al 21.3 418 24
3

Project: New_project 22/04/2018


Page 7/32

3 Calculation notes

3.1 Source circuits


3.1.1 Circuit Source 3
MV power supply W3
Max. upstream short circuit power 500 MVA
Min. upstream short circuit power 250 MVA
MV Cable MVWD 3
Parameters
Length 10 m
Type of cable Single core
Ib 7A
Nb of conductor per phase 1
Cross section area 1 x 240 Al mm²
Core Aluminium
Short circuit withstand 21.3 kA
Assigned voltage 20 kV
Insulation voltage 24 kV

MV/LV transformer TA 3
Range Trihal
Technology Dry-type
Rated power 250 kVA
ukrT 6%
Type of losses AoAk
PkrT 3.4 kW
System earthing arrangement TN-S
MV Connection D
LV Connection yn
No load secondary voltage Ur0 420V
Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Cable WD 3
Parameters
Length 5m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 361 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Project: New_project 22/04/2018
Page 8/32

Standard table reference B-52-16


Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x150 mm²
Core Copper
Iz under real conditions 399 A
Selected neutral
Cross section area 1x150 mm²
Core Copper
Iz under real conditions 399 A
Selected PE
Cross section area 1x95 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Emergency


(kA) NA NA NA NA NA NA NA

Operating mode normal


(kA) 6.70 5.80 6.62 4.35 4.95 5.03 0.00

Operating mode Copy of normal


(kA) 6.70 5.80 6.62 4.35 4.95 5.03 0.00

Synthesis for all operating mode


(kA) 6.70 5.80 6.62 4.35 4.95 5.03 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 3
Ib 361 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX400F
Circuit breaker rating 400 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.3 A
Trip unit rating 400 A
Long delay settings
Ir 361 A
Tr 16 s
Short delay settings
Project: New_project 22/04/2018
Page 9/32

Isd current 3610 A


Tsd 0.4 s
Instantaneous tripping
Ii current 4800 A

Discrimination Results
UpStream Discrimination Limit

Operating mode Emergency


NA Discrimination can't be determinated : no
upstream Lv Breaker

Operating mode normal


NA Discrimination can't be determinated : no
upstream Lv Breaker

Operating mode Copy of normal


NA Discrimination can't be determinated : no
upstream Lv Breaker

Design current
IL1 IL2 IL3 IN

Operating mode Emergency


(A) 0.000 0.000 0.000 0

Operating mode normal


(A) 277.598 276.949 276.949 0.65

Operating mode Copy of normal


(A) 277.598 276.949 276.949 0.65

Synthesis for all operating mode


(A) 277.598 276.949 276.949 0.65
Voltage drop
Cumulated from upstream Circuit

Operating mode Emergency


U3L (%) 0.000 0.000
UL1L2 (%) 0.000 0.000
UL2L3 (%) 0.000 0.000
UL3L1 (%) 0.000 0.000
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Operating mode normal


U3L (%) 0.138 0.138
UL1L2 (%) 0.160 0.160
UL2L3 (%) 0.160 0.160
UL3L1 (%) 0.160 0.160
UL1N (%) 0.138 0.138

Project: New_project 22/04/2018


Page 10/32

UL2N (%) 0.138 0.138


UL3N (%) 0.138 0.138

Operating mode Copy of normal


U3L (%) 0.138 0.138
UL1L2 (%) 0.160 0.160
UL2L3 (%) 0.160 0.160
UL3L1 (%) 0.160 0.160
UL1N (%) 0.138 0.138
UL2N (%) 0.138 0.138
UL3N (%) 0.138 0.138

3.2 Generator circuits


3.2.1 Circuit Source 17
LV generator G 17
Rated power 45 kVA
Subtransient reactance x”d 20 %
Transient reactance x’d 30 %
Zero sequence reactance x0 6%
System earthing arrangement TN-S
Ur 400 V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Cable WD 17
Parameters
Length 5m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 65 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x16 mm²
Project: New_project 22/04/2018
Page 11/32

Core Copper
Iz under real conditions 100 A
Selected PE
Cross section area 1x16 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Emergency


(kA) 0.36 0.31 0.00 0.18 0.00 0.28 0.00

Operating mode normal


(kA) 0.36 0.31 0.00 0.18 0.00 0.28 0.00

Operating mode Copy of normal


(kA) 0.36 0.31 0.00 0.18 0.00 0.28 0.00

Synthesis for all operating mode


(kA) 0.36 0.31 0.00 0.18 0.00 0.28 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 17
Ib 65 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 C120
Designation C120N
Circuit breaker rating 80 A
Breaking capacity 10 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation B
Trip unit rating 80 A
Long delay settings
Ir 80 A
Tr NA
Short delay settings
Isd current 320 A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Emergency


NA Discrimination can't be determinated : no
upstream Lv Breaker

Operating mode normal


NA Discrimination can't be determinated : no
upstream Lv Breaker
Project: New_project 22/04/2018
Page 12/32

Operating mode Copy of normal


NA Discrimination can't be determinated : no
upstream Lv Breaker

RCD designation Vigi C120


Class A
In 1000 mA
Break Time 0.17 s
t 0.14 s
Discrimination NA
Normative required break time [0.00 ; 5.00] s
Normative required sensitivity [0.03 ; NA] mA

Discrimination Results
UpStream Discrimination Limit

Operating mode Emergency


NA Discrimination not analyzed

Operating mode normal


NA Discrimination not analyzed

Operating mode Copy of normal


NA Discrimination not analyzed

Design current
IL1 IL2 IL3 IN

Operating mode Emergency


(A) 0.000 0.000 0.000 0

Operating mode normal


(A) 0.000 0.000 0.000 0

Operating mode Copy of normal


(A) 0.000 0.000 0.000 0

Synthesis for all operating mode


(A) 0.000 0.000 0.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Emergency


U3L (%) 0.000 0.000
UL1L2 (%) 0.000 0.000
UL2L3 (%) 0.000 0.000
Project: New_project 22/04/2018
Page 13/32

UL3L1 (%) 0.000 0.000


UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Operating mode normal


U3L (%) 0.000 0.000
UL1L2 (%) 0.000 0.000
UL2L3 (%) 0.000 0.000
UL3L1 (%) 0.000 0.000
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Operating mode Copy of normal


U3L (%) 0.000 0.000
UL1L2 (%) 0.000 0.000
UL2L3 (%) 0.000 0.000
UL3L1 (%) 0.000 0.000
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Project: New_project 22/04/2018


Page 14/32

3.3 Generic load circuits

3.3.1 Circuit Load 12


Circuit breaker QA 12
Ib 25 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60N
Circuit breaker rating 25 A
Breaking capacity 10 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 25 A
Long delay settings
Ir 25 A
Tr NA
Short delay settings
Isd current 200 A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Emergency


NA Discrimination can't be determinated : no
upstream Lv Breaker

Operating mode normal


QA 3 Full Discrimination
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Operating mode Copy of normal


QA 3 Full Discrimination
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Cable WD 12
Parameters
Length 20 m
Max length 47.8 m
Project: New_project 22/04/2018
Page 15/32

Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 25 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x2.5 mm²
Core Copper
Iz under real conditions 32 A
Selected neutral
Cross section area 1x2.5 mm²
Core Copper
Iz under real conditions 32 A
Selected PE
Cross section area 1x4 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Emergency


(kA) NA NA NA NA NA NA NA

Operating mode normal


(kA) 1.57 1.36 0.82 0.93 0.56 0.68 0.00

Operating mode Copy of normal


(kA) 1.57 1.36 0.82 0.93 0.56 0.68 0.00

Synthesis for all operating mode


(kA) 1.57 1.36 0.82 0.93 0.56 0.68 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge AA 12
Project: New_project 22/04/2018
Page 16/32

U 400 V
S 17.3 kVA
P 14.7 kW
I 25 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Emergency) 1
Harmonic generator No
THDI3 0
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Emergency


(A) 0.000 0.000 0.000 0

Operating mode normal


(A) 25.000 25.000 25.000 0

Operating mode Copy of normal


(A) 25.000 25.000 25.000 0

Synthesis for all operating mode


(A) 25.000 25.000 25.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Emergency


U3L (%) 0.000 0.000
UL1L2 (%) 0.000 0.000
UL2L3 (%) 0.000 0.000
UL3L1 (%) 0.000 0.000
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Operating mode normal


U3L (%) 1.891 1.753
UL1L2 (%) 2.184 2.024
UL2L3 (%) 2.184 2.024
UL3L1 (%) 2.184 2.024
UL1N (%) 1.891 1.753
UL2N (%) 1.891 1.753
UL3N (%) 1.891 1.753

Operating mode Copy of normal


U3L (%) 1.891 1.753
UL1L2 (%) 2.184 2.024
UL2L3 (%) 2.184 2.024
UL3L1 (%) 2.184 2.024
UL1N (%) 1.891 1.753
UL2N (%) 1.891 1.753
UL3N (%) 1.891 1.753

Synthesis for all operating mode


U3L (%) 1.891
Project: New_project 22/04/2018
Page 17/32

UL1L2 (%) 2.184


UL2L3 (%) 2.184
UL3L1 (%) 2.184
UL1N (%) 1.891
UL2N (%) 1.891
UL3N (%) 1.891

Project: New_project 22/04/2018


Page 18/32

3.3.2 Circuit Load 15


Circuit breaker QA 15
Ib 20 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60N
Circuit breaker rating 20 A
Breaking capacity 10 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 20 A
Long delay settings
Ir 20 A
Tr NA
Short delay settings
Isd current 160 A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Emergency


NA Discrimination can't be determinated : no
upstream Lv Breaker

Operating mode normal


QA 3 Full Discrimination
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Operating mode Copy of normal


QA 3 Full Discrimination
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Cable WD 15
Parameters
Length 20 m
Max length 59.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Project: New_project 22/04/2018
Page 19/32

Type of cable Multi-core


Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 20 A
Sizing constraint Voltage drop
Sizing Information The CSA of cable WD 15 has
been increased from 1.5 to 2.5 to
comply with the voltage drop in
the circuit.
Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x2.5 mm²
Core Copper
Iz under real conditions 32 A
Selected neutral
Cross section area 1x2.5 mm²
Core Copper
Iz under real conditions 32 A
Selected PE
Cross section area 1x4 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Emergency


(kA) NA NA NA NA NA NA NA

Operating mode normal


(kA) 1.57 1.36 0.82 0.93 0.56 0.68 0.00

Operating mode Copy of normal


(kA) 1.57 1.36 0.82 0.93 0.56 0.68 0.00

Synthesis for all operating mode


(kA) 1.57 1.36 0.82 0.93 0.56 0.68 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge AA 15
Project: New_project 22/04/2018
Page 20/32

U 400 V
S 13.9 kVA
P 11.8 kW
I 20 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Emergency) 1
Harmonic generator No
THDI3 0
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Emergency


(A) 0.000 0.000 0.000 0

Operating mode normal


(A) 20.000 20.000 20.000 0

Operating mode Copy of normal


(A) 20.000 20.000 20.000 0

Synthesis for all operating mode


(A) 20.000 20.000 20.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Emergency


U3L (%) 0.000 0.000
UL1L2 (%) 0.000 0.000
UL2L3 (%) 0.000 0.000
UL3L1 (%) 0.000 0.000
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Operating mode normal


U3L (%) 1.541 1.403
UL1L2 (%) 1.779 1.620
UL2L3 (%) 1.779 1.620
UL3L1 (%) 1.779 1.620
UL1N (%) 1.541 1.403
UL2N (%) 1.541 1.403
UL3N (%) 1.541 1.403

Operating mode Copy of normal


U3L (%) 1.541 1.403
UL1L2 (%) 1.779 1.620
UL2L3 (%) 1.779 1.620
UL3L1 (%) 1.779 1.620
UL1N (%) 1.541 1.403
UL2N (%) 1.541 1.403
UL3N (%) 1.541 1.403

Synthesis for all operating mode


U3L (%) 1.541
Project: New_project 22/04/2018
Page 21/32

UL1L2 (%) 1.779


UL2L3 (%) 1.779
UL3L1 (%) 1.779
UL1N (%) 1.541
UL2N (%) 1.541
UL3N (%) 1.541

Project: New_project 22/04/2018


Page 22/32

3.4 Lighting load circuits

3.4.1 Circuit Load 14


Circuit breaker QA 14
Ib 2.6 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60N
Circuit breaker rating 3A
Breaking capacity 50 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 3A
Long delay settings
Ir 3A
Tr NA
Short delay settings
Isd current 24 A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Emergency


NA Discrimination can't be determinated : no
upstream Lv Breaker

Operating mode normal


QA 3 Full Discrimination
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Operating mode Copy of normal


QA 3 Full Discrimination
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Cable WD 14
Parameters
Length 20 m
Max length 264 m
Project: New_project 22/04/2018
Page 23/32

Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 3A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 23 A
Selected neutral
Cross section area 1x1.5 mm²
Core Copper
Iz under real conditions 23 A
Selected PE
Cross section area 1x4 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Emergency


(kA) NA NA NA NA NA NA NA

Operating mode normal


(kA) 0.98 0.85 0.50 0.58 0.34 0.49 0.00

Operating mode Copy of normal


(kA) 0.98 0.85 0.50 0.58 0.34 0.49 0.00

Synthesis for all operating mode


(kA) 0.98 0.85 0.50 0.58 0.34 0.49 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge EA 14
Project: New_project 22/04/2018
Page 24/32

U 400 V
S 1.8 kVA
P 1.5 kW
I 2.6 A
cos 1
Ku (Emergency) 1
Number of circuit 1
Polarity 3Ph+N
Phase connection
Type of luminaries Standard incandescent lamp
Nb of luminaries 10
Nb of lights/luminaries 1
Lights power 150 W
Ballast power 0W
Ia 2.6 A
Harmonic generator No
THDI3 0
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Emergency


(A) 0.000 0.000 0.000 0

Operating mode normal


(A) 2.598 1.949 1.949 0.65

Operating mode Copy of normal


(A) 2.598 1.949 1.949 0.65

Synthesis for all operating mode


(A) 2.598 1.949 1.949 0.65
Voltage drop
Cumulated from upstream Circuit

Operating mode Emergency


U3L (%) 0.000 0.000
UL1L2 (%) 0.000 0.000
UL2L3 (%) 0.000 0.000
UL3L1 (%) 0.000 0.000
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Operating mode normal


U3L (%) 0.494 0.355
UL1L2 (%) 0.519 0.359
UL2L3 (%) 0.467 0.308
UL3L1 (%) 0.519 0.359
UL1N (%) 0.582 0.444
UL2N (%) 0.494 0.355
UL3N (%) 0.494 0.355

Operating mode Copy of normal


U3L (%) 0.494 0.355
UL1L2 (%) 0.519 0.359
UL2L3 (%) 0.467 0.308
UL3L1 (%) 0.519 0.359
UL1N (%) 0.582 0.444
UL2N (%) 0.494 0.355
Project: New_project 22/04/2018
Page 25/32

UL3N (%) 0.494 0.355

Synthesis for all operating mode


U3L (%) 0.494
UL1L2 (%) 0.519
UL2L3 (%) 0.467
UL3L1 (%) 0.519
UL1N (%) 0.582
UL2N (%) 0.494
UL3N (%) 0.494

Project: New_project 22/04/2018


Page 26/32

3.5 Motor starter combination


3.5.1 Circuit Motor Load 11
Circuit breaker QA 11
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX250F
Circuit breaker rating 250 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation MA
Trip unit rating 220 A
Long delay settings
Ir 220 A
Tr NA
Short delay settings
Isd current 2420 A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Emergency


NA Discrimination can't be determinated : no
upstream Lv Breaker

Operating mode normal


QA 3 Full Discrimination
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Operating mode Copy of normal


QA 3 Full Discrimination
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Contactor LC1F225
Designation LC1F225
Type of coordination T1

Thermal relay LR9F5371


Designation LR9F5371

Project: New_project 22/04/2018


Page 27/32

Ir 195

Cable WD 11
Parameters
Length 20 m
Max length 40.1 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 195 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x70 mm²
Core Copper
Iz under real conditions 246 A
Selected PE
Cross section area 1x35 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Emergency


(kA) NA NA NA NA NA NA NA

Operating mode normal


(kA) 6.20 5.37 0.00 4.03 0.00 3.85 0.00

Operating mode Copy of normal


(kA) 6.20 5.37 0.00 4.03 0.00 3.85 0.00

Synthesis for all operating mode


(kA) 6.20 5.37 0.00 4.03 0.00 3.85 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Project: New_project 22/04/2018
Page 28/32

Asynchronous LV Motor MA 11
Startup type Direct
U 400 V
Mechanical power 110 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 195 A
Sr for sizing 135 kVA
Pr for sizing 118 kW
cos 0.87
Polarity 3Ph
Number of circuit 1
Ku (mode Emergency) 1
Harmonic generator No
THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Emergency


(A) 0.000 0.000 0.000 0

Operating mode normal


(A) 195.000 195.000 195.000 0

Operating mode Copy of normal


(A) 195.000 195.000 195.000 0

Synthesis for all operating mode


(A) 195.000 195.000 195.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Emergency


U3L (%) 0.000 0.000
UL1L2 (%) 0.000 0.000
UL2L3 (%) 0.000 0.000
UL3L1 (%) 0.000 0.000
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Operating mode normal


U3L (%) 0.702 0.564
UL1L2 (%) 0.811 0.651
UL2L3 (%) 0.811 0.651
UL3L1 (%) 0.811 0.651
UL1N (%) 0.138 0.000
UL2N (%) 0.138 0.000
UL3N (%) 0.138 0.000

Operating mode Copy of normal


U3L (%) 0.702 0.564
UL1L2 (%) 0.811 0.651
UL2L3 (%) 0.811 0.651
UL3L1 (%) 0.811 0.651
UL1N (%) 0.138 0.000
UL2N (%) 0.138 0.000
Project: New_project 22/04/2018
Page 29/32

UL3N (%) 0.138 0.000

Startup Voltage drop


UStartUp 2.156
3.5.2 Circuit Motor Load 16
Circuit breaker QA 16
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.2 M
Trip unit rating 50 A
Long delay settings
Ir 36 A
Tr 5s
Short delay settings
Isd current 468 A
Tsd 0.03 s
Instantaneous tripping
Ii current 750 A

Discrimination Results
UpStream Discrimination Limit

Operating mode Emergency


NA Discrimination can't be determinated : no
upstream Lv Breaker

Operating mode normal


QA 3 Full Discrimination
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Operating mode Copy of normal


QA 3 Full Discrimination
NSX400F
Micrologic 5.3 A
400 A / 4P4d

Contactor LC1D40A
Designation LC1D40A
Type of coordination T1

Cable WD 16
Project: New_project 22/04/2018
Page 30/32

Parameters
Length 20 m
Max length 70.4 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 35 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 42 A
Selected PE
Cross section area 1x4 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Emergency


(kA) NA NA NA NA NA NA NA

Operating mode normal


(kA) 2.34 2.03 0.00 1.39 0.00 0.87 0.00

Operating mode Copy of normal


(kA) 2.34 2.03 0.00 1.39 0.00 0.87 0.00

Synthesis for all operating mode


(kA) 2.34 2.03 0.00 1.39 0.00 0.87 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MA 16
Startup type Direct

Project: New_project 22/04/2018


Page 31/32

U 400 V
Mechanical power 18.5 kW
Startup current Id/Ir 7.2
Transient current I’’d/Ir <=19
Ir for sizing 35 A
Sr for sizing 24.2 kVA
Pr for sizing 20.9 kW
cos 0.86
Polarity 3Ph
Number of circuit 1
Ku (mode Emergency) 1
Harmonic generator No
THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Emergency


(A) 0.000 0.000 0.000 0

Operating mode normal


(A) 35.000 35.000 35.000 0

Operating mode Copy of normal


(A) 35.000 35.000 35.000 0

Synthesis for all operating mode


(A) 35.000 35.000 35.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Emergency


U3L (%) 0.000 0.000
UL1L2 (%) 0.000 0.000
UL2L3 (%) 0.000 0.000
UL3L1 (%) 0.000 0.000
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Operating mode normal


U3L (%) 1.695 1.556
UL1L2 (%) 1.957 1.797
UL2L3 (%) 1.957 1.797
UL3L1 (%) 1.957 1.797
UL1N (%) 0.138 0.000
UL2N (%) 0.138 0.000
UL3N (%) 0.138 0.000

Operating mode Copy of normal


U3L (%) 1.695 1.556
UL1L2 (%) 1.957 1.797
UL2L3 (%) 1.957 1.797
UL3L1 (%) 1.957 1.797
UL1N (%) 0.138 0.000
UL2N (%) 0.138 0.000
UL3N (%) 0.138 0.000

Startup Voltage drop


Project: New_project 22/04/2018
Page 32/32

UStartUp 2.728

3.6 Busbar circuits


3.6.1 Circuit WC 7
Busbar WC 7
Parameters
Switchboard Name UC 8
Switchboard Range No preference
Rating (A) 0
IP Undefined
Feeder
Circuit name Protection name Protection type

Motor Load 11 QA 11 NSX250F

Load 12 QA 12 iC60N

Load 14 QA 14 iC60N

Load 15 QA 15 iC60N

Motor Load 16 QA 16 NSX100F

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

Operating mode Emergency


(kA) NA NA NA NA NA NA NA

Operating mode normal


(kA) 6.70 5.80 6.62 4.36 4.96 5.03 0.00

Operating mode Copy of normal


(kA) 6.70 5.80 6.62 4.36 4.96 5.03 0.00

Synthesis for all operating mode


(kA) 6.70 5.80 6.62 4.36 4.96 5.03 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.