Professional Documents
Culture Documents
a r t i c l e i n f o a b s t r a c t
Article history: Distributed generators (DGs) provide many benefits for distribution networks, however they increase
Received 17 October 2014 the fault current level and cause miscoordination between the protective devices. This paper presents a
Received in revised form 11 June 2015 framework to determine the optimal locations and permissible capacity limits of inserting DGs in the dis-
Accepted 9 July 2015
tribution system using the genetic algorithm (GA). A multi-objective function is developed based on the
Available online 28 July 2015
overall maximum capacity of DGs, voltage enhancement, power loss reduction, and fault current level.
The optimization process considers the voltage level and protective-devices coordination as two main
Keywords:
constraints. The coordination constraint including fuse–recloser and recloser–relay schemes is added
Distributed generation
Distribution systems
to the multi-objective function in an augmented fitness function. Furthermore, the effects of modifying
Optimization techniques the setting of overcurrent relay on the DGs capacity are investigated. The proposed framework has been
Protection coordination implemented on a typical 11 kV overhead distribution feeder. The results show the possibility of integrat-
ing large DGs and achieving considerable loss reduction, voltage profile improvement and fault current
reduction without replacing the existing protection systems.
© 2015 Elsevier B.V. All rights reserved.
1. Introduction losses, the suitable location of DGs within the system has to be
investigated [4,5]. On the other hand, high penetration of DGs in
Recently, the connection and exploitation of distributed genera- distribution systems has adverse impacts on the existing protec-
tors and their controlling technologies into distribution systems tion scheme. This is attributed to the variation of fault current
(DS) have become a necessity around the world. The advantages level and its direction, which causes coordination mismatch and
of utilizing DGs include economical, environmental and technical false tripping [5–8]. Typical electrical distribution systems have
benefits [1,2]. The economical aspects include their high efficiency radial structure with a single source, where the protection schemes
and the lower power losses. An example of the environmental depend on relay, reclosers, and fuses. In this structure, the main
benefits is the reduction of greenhouse gas emissions. Finally, the feeders are protected against temporary faults using reclosers,
technical advantages include voltage support and higher reliability. while fuses are located at the beginning of laterals and sub-laterals
The one-way energy nature of radial distribution systems results to protect against persistent faults [3–10].
in increasing voltage regulation. The voltage is regulated by insert- Recloser–fuse miscoordination problems may appear due to the
ing load tap-changing transformers at substations, line regulators current contribution of DGs. The recloser–fuse coordination is usu-
into distribution feeders and shunt capacitors into feeders or along ally performed based on fuse-saving principles [6]. In addition, the
the line [3]. The voltage profile along a certain feeder may be distribution-system short-circuit currents increase due to the con-
changed when the DGs are connected due to changing the direction tribution of DGs. This might cause a trip to healthy lines before
and magnitude of real and reactive power flows [1–3]. clearing the faulty lines. If the power flow in feeders remains uni-
The connection of DGs also affects the feeder losses, where DGs directional, classical protections can still be used [6].
supply local active and reactive powers. In order to reduce the In [5], operation of different protection schemes after connect-
ing DGs in distribution system is discussed. The effect of DGs on
protective device coordination is explored with different schemes
such as fuse–fuse, fuse–recloser and relay–relay arrangements.
∗ Corresponding author. Tel.: +20 10 97 1000 43.
In addition, the impact of DGs’ on protection coordination and
E-mail addresses: hossam saleh2000@yahoo.com (H.A. Abdel-Ghany),
azmy@f-eng.tanta.edu.eg (A.M. Azmy), nagy.elkalashy@sh-eng.menofia.edu.eg operation of distribution network is analyzed in [7,8]. The study
(N.I. Elkalashy), emrashad@ieee.org (E.M. Rashad). included the increase of fault current level, malfunctioning of
http://dx.doi.org/10.1016/j.epsr.2015.07.005
0378-7796/© 2015 Elsevier B.V. All rights reserved.
114 H.A. Abdel-Ghany et al. / Electric Power Systems Research 128 (2015) 113–122
protective devices and protection coordination. The performance of where, t is the fuse operating time; I is the fault current seen by
directional recloser is evaluated for different faults using real-time the fuse and a, b, c, and d are the fuse constants. A fuse setting
power system simulator [9]. IEEE standard 1457 recommended that means defining the constants a, b, c and d, which are calculated
the DGs should be disconnected during system abnormality [11]. using the curve fitting based on fuse characteristics. This proposed
This is attributed to the fact that the conventional protection coor- formula is to facilitate the fuse characteristics implementation in
dination cannot clear the fault current supplied from DGs [11]. The the optimization framework.
optimal size of DG has been calculated using Optimal Power Flow
(OPF), and considering recloser–fuse coordination in [12]. The max-
imum capacity of DG at each node of the distribution system has 2.2. Modified recloser characteristics
been determined considering the protection coordination. In [13],
a single DG in the distribution system has been studied at the first The recloser has the priority to protect the distribution system
stage. At the second stage, two or more DGs in separate nodes prior fuse operation with suitable coordination margin. After con-
have been considered. However, the optimum DG capacities are necting DGs with high penetrations into the recloser–fuse section,
not generalized with concerning wide objectives simultaneously. the selectivity of protection scheme between fuse and recloser is
In this paper, a generic framework is developed to define the not achieved. To handle this problem, it is proposed to shift the fast
optimal location and limits of DGs within distribution systems curve characteristic of recloser to operate before the fuse melting.
to maintain a correction operation of the traditional protection Section 4 describes the effect of such modified recloser character-
scheme. One more issue considered in this paper is to study the istics on the permissible DG ratings.
effect of DGs penetration on technical impacts and fault current lev-
els. The genetic algorithm (GA) is used to perform the optimization
process due to its capability to handle economic dispatch prob- 3. Investigated overhead distribution system
lems, optimal sizing and setting problems and unit commitment
problems. Sequentially, the optimization approach is performed to An Egyptian overhead distribution system is used as a typical
find the maximum optimal capacity limit of the inserted DG that case study that represents a rural system (Nediba feeder) supplied
not affecting on the protection coordination to find this limit with from 66/11 kV (Khairy) substation. This system is used to study
adding the voltage profile objectives, and then with adding either the effect of DGs on the recloser–fuse coordination. Fig. 1 shows
the power losses or the fault current level. The last generalized the one-line diagram of the adopted system, which contains 47
approach is developed considering all the above objectives. buses, 45 overhead sections, and one underground cable. In this
distribution feeder, each lateral is protected by a fuse, however the
2. Distribution feeder protective devices fuse of last lateral is only present in this figure and considered for
the optimization study, first. Then, the study is done considering
Distribution feeders are commonly radial with the loads con- multi fusses protecting the laterals branched from the feeder. For
sumed the power from upper voltage levels connected to the radial correct protection coordination, all fuses downstream the recloser
feeders. The conventional distribution systems are protected by are to be coordinated with its fast and slow curves and the corre-
a combination of simple protective devices as overcurrent relays, sponding DG capacity limit should be evaluated correspondingly.
reclosers, and fuses. The feeder protection scheme objectives are to The adopted distribution system is simulated using Matlab® code.
ensure the service continuity to the maximum number of users. The total supplied current through Nediba feeder equals 196 A. The
feeder supplies loads through 16 km-Aluminum Conductor Steel
Reinforced (ACSR 70/12) overhead transmission line. The main
2.1. Functions and equations of protective devices
transformer in Khairy substation is of 25 MVA, 66/11 kV delta/star
and has an impedance of 10%. The feeder is considered with the
Before defining the DGs locations and penetration limits, fault
recloser located at 10.65 km and the fuse at 13.5 km, however, the
calculations and protection settings are carried out for the origi-
study is not limited to this fuse location. More details about this
nal system. Since the highest fault current is caused usually from
system are found in [3]. A DG is connected at different locations
a three-phase fault, it is used in defining the generation pene-
in the main feeder through an 11/0.4 kV delta/star earthed trans-
tration limits. This is to ensure that the installation of DGs with
former with the same rating of the DG. This transformer connection
this penetration limits will not cause miscoordination for the
that its delta is on the utility side is considered to open the zero
other phase fault types. However, DG transformer connection is
sequence loop at the transformer point during earth fault (phase
used to prevent and open the zero sequence current contributed
to earth fault type) in the distribution feeder. The delta connec-
by the DG. Accordingly the earth faults are not involved in the
tion can be replaced by a star connection that not earthed. This
study.
condition prevents the change of the distribution of earth fault
The protection coordination setting for relay and recloser is
currents in the feeder due to the DG transformer interconnection.
performed based on (1), provided that no DG is connected. The
In other words, the earth fault current distribution in the feeder is
equation has very inverse characteristic according to IEC standard
the same whenever the DG is interconnected or not interconnected
[5]:
that prevents the DG interconnection effects on the protection
coordination. The second benefit of opening zero-sequence loop at
k
t = 13.5 (1) the DG transformer interconnection is to prevent DG contributing
I/IPic-up − 1 current into earth faults in the feeder that will also solve com-
pletely the effect of DG on the protection coordination of earth
where, t is the trip time in sec; K is the time multiplier; I is the
faults. Accordingly, the study is directed to evaluate the DG max-
rms measured current and IPic-up is the setting current. For the
imum capacity limit concerning protection coordination for only
current-time characteristic of fuses, it has an inverse form that is
phase fault types in practically the three-phase faults. The faults
usually plotted as a log–log curve. For its accurate representation,
are occurred behind the fuse, recloser and relay points with and
the following expression is suggested:
without different DGs penetrations. Also, the actual characteristics
t = aeb×I + ced×I (2) of the distribution system and different DGs ratings are taken into
consideration.
H.A. Abdel-Ghany et al. / Electric Power Systems Research 128 (2015) 113–122 115
15+j8
31 kVA
0.7km
40+j12 600+j40 40+j10 70+j20 180+j20 190+j30 280+j50 50+j20
35/6
kVA kVA kVA 80+j20 kVA kVA kVA kVA kVA
32 kVA
35/6
250+j40 30 50+j10
kVA 150+j30 28 0.7km 40+j12 kVA 40+j20
25 kVA 29 80+j20 34 kVA 41 kVA
36 46 47
kVA
0.2km
0.6km
70/12
70/12
70/12
0.2km
0.4km
35/6
35/6
0.4km
1km
1.2km
0.6km
35/6
70/12
70/12
70/12
0.6km
66/11KV sum
25MVA 2 Relay 3 4 5 8 9 10 0.3km11 12 13 14 15 16 17 F4 18 19 20 21 22 2 3 Fuse 2.5km 24
1 1.7km 3.5km 0.5km 0.45km6 0.5km7 0.4km 0.1km 0.1km 0.3km 0.8km 0.4km 1km 0.3km 0.3km 0.2km 0.1km 0.5km 0.2km 1.2km 0.7km
3*240XLPE F3 150/25 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12 70/12
F2 Recloser F1
Main 680+j120
kVA
0.45km
0.5km
35/6
70/12
0.4km
0.9km
35/6
0.2km
0.5km
70/12
70/12
0.5km
70/12
Substaon
70/12
0.3km
70/12
20+j5 35 42
6+j1MVA 50+j20 80+j20 40+j10 33 40 150+j40 180+j20 80+j20
kVA kVA kVA 26 27 kVA 40+j20 kVA kVA kVA
40+j15 kVA
kVA 43 70+j20
50+j15 70+j20 37 110+j30 kVA
0.16km
kVA kVA 50+j10 50+j25 kVA
70/12
kVA
0.1km
70/12
kVA 70+j20
kVA
44
38
115+j20
0.1km
15+j8
70/12
0.8km
70/12
kVA kVA
30+j10
kVA 30+j8
39 45 kVA
Fig. 1. Single line diagram of Egyptian Nediba distribution system with its protection scheme (47 bus System).
For setting the reclosers, it is assumed that they are equipped Protective devices Time-current characteristic setting
with relays having very inverse characteristics. The recloser pickup Fuse (100 A) a = 45.68, b = 0.006984, c = 1.681, and
current is [11]: d = −0.00145
Recloser (fast curve) Current setting = 140 A, Kf = 0.05, very
IPic-up = OLF × Inom (3) inverse
Recloser (slow curve) Current setting = 250 A, Kr = 0.15, very
where OLF is an overload factor that depends on the protected inverse
equipment; Inom is the recloser and relay currents obtained from Feeder-relay Current setting = 390 A, K = 0.14, very
the load-flow results. inverse
Modified-recloser (fast curve) Current setting = 250 A, time
The recloser on the main line has to be coordinated with the
setting = 0.05 s, instantaneous
fuse for all faults taking place in the fuse section, where currents
of the fuse and recloser are close to each other. The operating time
related to the fault currents of the fuse and recloser are shown in Table 2 shows the fault currents seen by relay, recloser, and fuse
Fig. 2. Both devices must be coordinated for the whole range of fault in three different cases. In case 1 with a DG located in recloser–fuse
currents on the fuse section. region and a fault occurs at F1, fault current seen by the fuse is
The coordination procedure is considered depending on fast and greater than the fault current seen by the recloser. Therefore, mis-
slow recloser curves. The time-current characteristics of feeder- coordination between fuse and recloser may occur since the fuse
relay, fuse and recloser fast and slow curves are shown in Table 1. operates before the fast mode operation of recloser. In case 2 with
The minimum margin between recloser and fuse is 0.1 sec. It is a DG inserted in relay–recloser region and a fault occurs at F1, the
required to study the range (limits) of DGs penetration without fuse operates since the fault current flowing from DG is much less
affecting the protective-devices coordination with different fault than that from substation. In this case, miscoordination between
locations. The adopted DG is a synchronous generator connected to fuse and recloser may occur for large DGs capacity. Under the
the medium voltage of the distribution system through a delta/star same conditions but with a fault at F4, fault current seen by the
transformer and 0.1 km length cable. recloser is greater than that seen by the relay. Therefore, miscoor-
Regarding the microprocessor based reclosers, there are multi- dination between the fuse and recloser may occur since the relay
functions that allow the change of the recloser characteristics in may operate before the slaw mode operation of recloser. In case
a wide range of operating times and selected suitable currents. 3 with a DG inserted along feeder and a fault occurs at F1, fault
As shown in Fig. 3, it is suggested to modify the fast curve of currents seen by both fuse and recloser are increased due to the
the recloser from very inverse to instantaneous characteristics as presence of DGs. In this case, miscoordination may occur when the
shown in Table 1. fuse operates before the fast operation mode of recloser, due to
10 Fuse 100A TC
Fault current seen by Fuse
848.7A
Fuse 100A MM 10 Fault current see n by Fuse Fuse100A MM
5 Fast Recloser Curve 848.7A Rec slaw
5
Slow Recloser Curve Relay
Feeder Relay Fuse100A
Rec fast
1 1
Time (s)
Tim e (sec)
Coordination Margin
C.M Coordination Margin
C.M
0.1 0.1
0.01
0.01 200 400 600 800 1000 1200 1400 1600
400 600 800 1000 1200 1400 1600
Current (A) Current (A)
Fig. 2. Relay, recloser and fuse characteristics. Fig. 3. Relay, modified-recloser and fuse characteristics.
116 H.A. Abdel-Ghany et al. / Electric Power Systems Research 128 (2015) 113–122
F1 = DGCi (5)
and Irelay = Isubstation
i=1
where DGCi is the capacity of the installed DGs at the ith generation
the increased DG capacity. If the short circuit capacity of DG unit in MW and NDG is the number of DGs.
increases, the probability of miscoordination is also increased. The
DG capacity inserted in relay–recloser region is adjusted to a suit-
able value. This value is given from case 2 to satisfy the coordination 5.1.2. Voltage level
between relay and recloser when fault occurs at F4. The DG impacts The voltage level improvement (F2 ) is one of the goals of setting
on protective-device coordination are investigated based on the sizing
and of DGs. It is required to reduce the voltage deviations
(V ) from the nominal value (Vnom ). The value of the voltage
three cases summarized in Table 2.
deviations V can be defined as:
5. Problem formulation N
Vnom − Vj
F2 = V =
j=1
(6)
For the single-objective optimization problems, the optimal Vnom
solution is single. However, in multi-objective problem there is
where Vj is the jth bus voltage and N is the number of buses.
rather a set of different optimal solutions, not a unique solution.
When all objectives are simultaneously considered, these solu-
tions are optimal in point of view of the decision-making. There 5.1.3. Fault current level
are no other solutions in the search space that are superior to The fault current level of the network increases due to increasing
them, in which the decision maker has flexibility to expect the the DGs capacity. When a DG is placed in parallel with the network,
optimality solution. The previous meaning is the definition of the the calculated impedance from a fault point diminishes and the
Pareto—front. The objective function of the problem understudy fault current level increases. Therefore, the objective term related to
incorporates terms of different nature, as to the maximize capacity the fault current, which is equal to summation of the fault currents
of DGs, the maximize voltage enhancement, the minimize power from the substation (Ifs )and the DG (IfDG ) is defined as:
loss and the minimize fault current level.
The proposed optimization problem can be described math-
NDG
ematically using a four-part objective function with three F3 = If = If DG + Ifs (7)
constraints. The proposed four parts are the capacity limits (F1 ) i=1
of DGs, the voltage regulation (F2 ), the total fault current level (F3 )
and the power loss (F4 ) for the distribution system. The first part 5.1.4. Power losses
has to be maximized, while the other three parts have to be min- Voltage profile is improved by controlling the production,
imized. The upper limit of DG capacity is the main objective to be absorption and flow of reactive power throughout the network.
defined without affecting on the protection coordination point of Reactive power flows can be minimized to reduce system losses.
view. Thus, the upper limit in this study is not to decide for the Many researches are provided just to minimize loss due to the
DG capacity, but to define the limits that have not to be violated. reactive current. From these researches, it is well known that the
Other technical factors such, as voltage drop, fault current level, distribution losses can be calculated based on the natural properties
and power losses, are considered and the same optimal location is of components in the power system: resistance, reactance, capaci-
obtained near the load location. Any other factors can be introduced tance, voltage, current, and power, which are routinely calculated
but the main concern here is to the coordination problem. Unfortu- by utility companies as a way to specify what components will be
nately, the scope of this study does not include the costs of DG units. added to the systems, in order to reduce losses and improve the
However, this study is for estimating the optimal DG limit capacity voltage levels. The centralized voltage reactive control is one such
that enhances the protection coordination concerning DG intercon- control which can help not only to keep the system voltages within
nection without any additional protection expense. Regarding the specified limits, but also to preserve the reactive power balances
DG interconnecting places, the DG optimal limit capacity is evalu- for enhanced security and to decrease the transmission losses for
ated at different allocations along with the feeder that covers the the efficient system operation.
availability of DG at specific points. The losses due to the active and reactive current components
between ith and jth buses and the corresponding objective term
5.1. Multi-objective function are defined as:
The general multi-objective function can be given in the fol- Plossi−j + jQlossi−j = Si−j + Sj−i (8)
lowing form with the different terms described in the following
sections:
N
N
F4 = Plossi−j + Qlossi−j (9)
max F = max (W1 · F1 − W2 · F2 − W3 · F3 − W4 · F4 ) (4) j=0 i=1
H.A. Abdel-Ghany et al. / Electric Power Systems Research 128 (2015) 113–122 117
In order to achieve the DGs limits and location in distribution constraints (∅CM ). The formulation of the proposed fitness function
systems, the multi-objective function is given by: (∅f ) can be expressed as [17,18]:
NDG
N
∅f (x) = F = (W1 · F1 ) − W2 · (C2 · F2 ) − W3 · (C3 · F3 )
F = W1 DGCi − W2 Vnom − Vj /Vnom − W3
− W4 · (C4 · F4 ) (14)
i=1 j=1
N where W1 , W2 , . . . are weights of a positive constant. C2 , C3 and C4
DG
N
N
× If DG + Ifs − W4 Plossi−j + Qlossi−j (10) are scaling factors for maximization problem. The scaling factors
are assigned in terms of the objective function in order to obtain
i=1 j=0 i=1
the same effect on fitness function [20].
The constraint representing coordination margin between fuse
and recloser is formulated as:
5.2. System constraints
5.2.1. Fuse–recloser coordination constraints ∅CM2 (x) = min 0, trelay − treclslow − min CMrelayrecl
tfuse − treclfast ≥ min CMfusereclfast (11)
Start Table 3
Weight values for the five approaches.
Read system data
Approach W1 W2 W3 W4
Perform Load flow, short circuit and protection App1 1 0 0 0
devices sitting calculations App2 0.5 0.5 0 0
App3 0.333 0.333 0 0.333
Calculate the coordination margin (CM) between App4 0.333 0.333 0.333 0
the protection devices without DG App5 0.25 0.25 0.25 0.25
Insert DG buses.
Initialize chromosome population randomly voltage drop to the DG capacity, and so on. W2, W3 and W4 are
Perform Load flow, short circuit, coordination margin, voltage positive constant factors for maximization problem. The weight
profile, power losses, and total fault current calculations values for the five approaches are summarized in Table 3. These
approaches are studied to evaluate the effect of fitness function
Evaluate fitness function (Eqn. (16) or (17)) weights on the limits and locations of DGs.
Table 4 shows the optimization results of DG at different loca-
tions in recloser–fuse region for App5 with different weights. This
Select Parent from the population
table just shows a sample of results. When it is required to consider
Creation of offspring chromosomes via a certain term in the objective function, except for the first term,
crossover & mutation the corresponding weighting factor, i.e. W2, W3 and/or W4, is set
to zero. However, it is required to consider all terms in the objective
Perform Load flow, short circuit, coordination margin, voltage
function, the corresponding weighting factors, i.e. W2, W3 and W4,
profile, power losses, and total fault current calculations
are set to 0.25. Weights are selected considering the four terms of
the multi-objective function as the same, while the operator has
Evaluate fitness function (Equ. (16) or (17))
Extract offspring
the freedom of choice to determine the weights. The selection of
population's the coordination margin constraint weight (W5 = 1000) is based
Yes fitness statistics
Termination criteria on merging the constraint with the objective function so that the
satisfied? & perform fitness function equals the resulting value of objective function. In
No crossover and
mutation addition, the product of coordination margin and its weight is equal
Print unit output power and power flow results to zero.
Stop
7.1. Case 1: DGs located in recloser–fuse region
Fig. 4. Flowchart of GA evaluation process for the proposed framework.
For a fault at F1, the fuse operating time decreases with the
increase of the DGs rating. On the other hand, the recloser operating
Optimal Power Flow (OPF) is developed to calculate the volt- time is not affected because the fault occurred at the DGs terminals.
age profile, power losses, and per fault voltage for each individual. At the same time, the network fault current decreases due to the
This step depends on update the system data while DG unit insert- increase of the terminal voltage of recloser. Thus, the operating
ing through cable and transformer. The previous processes are times of recloser and feeder-relay decrease maintaining their coor-
repeated while changing the DG location and penetration level in dination for a wide range of DG ratings. On the other hand, the fault
order to recloser modified. currents through recloser and feeder-relay are still the same com-
pared to the case without DGs since DG is located at fuse terminals
7. Results and discussions only.
The maximum capacity of DG that can be installed in the
The proposed fitness function, including the multi-objective recloser–fuse zone is 2.55 MW at bus 23 alone. Alternatively, the
function and system constraints, which refer to the problem formu- maximum capacity of DG unit at bus 17 alone is 4.69 MW. This
lation is implemented on the adopted distribution system shown capacity satisfies the coordination between the recloser and fuse
in Fig. 1. The optimization process considers the coordination for traditional protection scheme. Fig. 5 shows the maximum lim-
between the protective devices with and without modifying the its of a single DG unit at different locations with a fault at F1 for
recloser fast curve. The fitness function is investigated based on five conventional and modified recloser characteristics. In addition, all
approaches. The first approach (App1) considers only the capac- values shown in this figure are obtained according to App 1.
ity limits in the objective function. The second approach (App2) is To verify the validity of the various cases shown in Fig. 5, the
when voltage regulation is also considered in the objective function. fault currents of the fuse and recloser are investigated for a fault
The third approach (App3) is when the power losses is added in the
objective function. The fourth approach (App4) considers the volt-
12 11.348 10.852 Convenonal
age regulation and total fault current level but not the power losses.
Modified recloser
DG Capacity (MW)
Finally, the fifth approach (App5) is when all terms are incorporated 10 8.858
7.436
in the objective function. 8 6.975
Different scaling factors are used for different terms in the objec-
4.69
4.59
6 5.014 4.267
4.11
3.71
3.57
2.55
4
range. From experience, the proposed normalization values are set
as: voltage profile (C2 = 100), total system fault current (C3 = 0.001) 2
and power losses (C4 = 10). The selection of these normalization 0
factors is based on normalization of the different terms of the objec- Bus 17 Bus 18 Bus 19 Bus 20 Bus 21 Bus 22 Bus 23
DG locaon
tive function so the resulting value of the objective function is
still meaningful. The corresponding scaling factors are refers to the Fig. 5. Max limits of a single DG at different location with a fault at F1 for conven-
reference value (DG capacity), C2 is the relation between the pu tional and modified recloser.
H.A. Abdel-Ghany et al. / Electric Power Systems Research 128 (2015) 113–122 119
10 Fuse 100A TC
0.25
0.75
0.91
0.53
0.34
0.27
0.27
0.28
0.16
98.23
0.04
Fuse 100A MM
3.6
5 Fast Recloser Curve
0
0
1371
S low Recloser Curve
15
Feeder Relay
0.75
0.25
1.44
1.33
0.17
4.07
0.06
98.06
Time (s)
1.3
0
0
0
0
0
0
1344
14
Recloser-Fuse
C.M 0.0242 s
0.1
0.13
0.22
4.42
0.22
97.93
4.07
0.06
0.8
0.2
0
0
0
0
0
0
13411
13
4.11
0.18
0.06
98.05
400 600 800 1000 1200 1400 1600
0.2
0.8
0
0
0
0
0
0
12465
Current (A)
12
4.56
4.56
0.25
97.48
0.06
0
0
0
0
0
0
0
0
1336
at F1 after inserting a 2.55 MW DG unit at bus 23as an example.
11
The calculated fault currents are shown in Fig. 6. It is clear that the
coordination margin is satisfied. Similar results are obtained for
0.33
0.67
4.56
4.56
0.25
97.48
0.06
0
0
0
0
0
1336
10
4.69
4.69
0.24
0.06
97.4
1336.9
0
0
0
0
0
0
and fuse. It can be concluded that App5 results in the highest pen-
9
4.69
0.24
0.06
97.4
1336.9
0
0
0
0
0
0
0
0
3.67
0.16
1.08
0.06
98.05
0.5
0.5
1339.7
0
0
0
0
penetration.
Optimization results of DG at different location in recloser–fuse region for App5 with different weights.
4.59
0.25
97.48
0.06
0.5
0.5
1339.8
0
0
0
0
0
beside the loads near fuse zone. The minimum value of Nediba
feeder voltage profiles from substation to fuse location and total
0.95
0.74
0.43
0.48
3.64
0.16
98.22
1.04
0.04
0.3
0.3
0.2
0.2
1358.2
fault current at fault bus are given in this table. Similarly, the volt-
0
age profile and fault current level under best situation considering
5
0.15
97.97
0.06
0.1
0.3
0.3
0.3
other words, all objective terms are enhanced at the same time
1500
0.44
0.47
3.65
0.16
0.98
1.06
0.04
0.4
0.2
0.2
0.2
1358.4
0.35
0.19
3.05
0.07
0.7
0.1
0.1
0.1
1348.4
0
4
98
near recloser.
Table 8 shows the results when a fault occurs at F1 with modified
0.25
0.25
0.25
0.25
0.57
0.48
0.54
3.67
0.16
1.08
0.06
98.05
0
0
all objective functions at the same time. The total fault current
1
becomes the same for all approaches due to the high DG pene-
tration.
Min voltage%
Loss-MVAR
Max. limit
Bus 21
Bus 22
Bus 23
Bus 20
Table 4
Case
When the fault occurs at F1, the fuse and recloser operat-
W1
W2
W3
W4
If
Table 5
DG penetration limits with different DG locations in recloser–fuse region with a fault at F1.
Location of DG
App. Bus 17 Bus 18 Bus 19 Bus 20 Bus 21 Bus 22 Bus 23 Max. limits
At one bus 4.69 4.59 4.11 3.71 3.57 2.87 2.55 4.69
App1 4.69 0 0 0 0 0 0 4.69
App2 0 4.59 0 0 0 0 0 4.59
App3 1.08 1 0.57 0.48 0.54 0 0 3.67
App4 4.69 0 0 0 0 0 0 4.69
App5 1.08 1 0.57 0.48 0.54 0 0 3.67
Table 6
Optimal system variables with different approaches for DG located in recloser–fuse region with a fault at F1.
Table 7
DG penetration limits with different DG locations in recloser–fuse region with a fault at F1 with modified recloser fast curve.
Location of DG
App Bus 17 Bus 18 Bus 19 Bus 20 Bus 21 Bus 22 Bus 23 Max. limits
At one bus 11.35 10.85 8.86 7.44 6.98 5.01 4.27 11.35
App1 11.35 0 0 0 0 0 0 11.35
App2 10.08 0 0 0 0.38 0 0 10.46
App3 5.28 0.78 0.61 0.35 0.05 0.37 0.35 7.79
App4 8.07 0 1.63 0 0 0 0 9.7
App5 5.43 0.76 0.47 0.33 0.22 0.28 0.36 7.85
Table 8
Optimal system variables with different approaches for DG located in recloser–fuse region with a fault at F1with modified recloser fast curve.
Table 9
DG penetration limits with different DG positions in relay–recloser region with a fault at F4.
Location of DG
App Bus 4 Bus 7 Bus 10 Bus 12 Bus 13 Bus 15 Bus 16 Max. limit
At one bus 1.68 1.4 1.32 1.26 1.23 1.15 1.14 1.68
App1 1.68 0 0 0 0 0 0 1.68
App2 0 0 0 0 0 0 1.14 1.14
App3 0 0 0 0 0 0 1.14 1.14
App4 0 0 0 0 0 0 1.14 1.14
App5 0 0 0 0 0 0 1.14 1.14
relay–recloser region. The operating times of protective devices 35 33.10 33.10 33.10 33.10 33.10
F1 F4
decrease when DG units are located near the relay, and it is higher in
30
case when DG units are located near the recloser. This is attributed
DG Capacity (MW)
1.40
1.32
1.26
1.23
1.15
1.14
Table 10
Active and reactive power loss, total fault current and minimum value of voltage profile with different DG positions in relay–recloser region and a fault at F1 and F4.
Table 11
DG penetration limits with different DG positions along feeder.
Bus 4 to 15 Bus 16 Bus 17 Bus 18 Bus 19 Bus 20 Bus 21 Bus 22 Bus 23 Max. limit
F1 33.1 10.78 4.69 4.59 4.11 3.71 3.57 2.87 2.55 33.1
F1 & F4 0 1.14 0.73 0.60 0.30 0.19 0.16 0.32 0.47 3.91
Table 12
DG penetration limits with different DG positions at all buses and fault locations at F1 with modified recloser fast curve.
Bus 4 to 15 Bus 16 Bus 17 Bus 18 Bus 19 Bus 20 Bus 21 Bus 22 Bus 23 Max. limit
F1 33.1 10.78 11.35 10.85 8.86 7.44 6.98 5.01 4.27 33.1
F1 & F4 0 1.14 5.99 0.55 0.33 0.22 0.01 0.37 0.01 8.62
modified recloser setting. From the figure, the best location of the Following the same procedure, Table 14 shows the limits of DG
distributed generation is a DG unit located in relay–recloser section ratings with their different locations in recloser–fuse region and
and close to the relay. different approaches for a multi fuse after modifying recloser fast
Table 9 shows the DG penetration limits with different DG pos- curve. The results summarized in this table are attained consid-
itions in relay–recloser region for a fault at F4. The best location ering all terms in the objective function (as in App5). The best
and maximum sizing of the DGs are the combination of DG units alternatives to distribute units at different buses keep coordination
keeping a suitable coordination margin between recloser and relay. margin between recloser and multi fuses with the recloser. Thus,
Omitting the voltage profile, total fault current and power losses it is logic to obtain reduced value compared to 2.605 MW when
and considering only the DG capacity in the objective function considering the coordination between recloser–fuse as shown in
results in placing the DG near the relay. On the other hand, consid- Table 14.
ering the voltage profile, total fault current and/or power losses in The results of the network with DG units include the cases of
the objective function, results in locating the DG near the recloser. conventional protection scheme and modified recloser fast curve.
Thus similar results are obtained for App2, App3, App4, and App5 The voltage profile and power losses are improved in case 3 as com-
as shown in the table. Table 10 shows the active and reactive power pared to case 1 and case 2. On the other hand the fault current level
loss, total fault current and minimum value of voltage profile with is increased as shown in Table 13. This is due to the insertion of DG
different DG positions in relay–recloser region and a fault at F1 and units with high capacity beside the loads (along the feeder).
F4. The optimization problem is formulated considering the four
commonly-used factors affecting the selection of DG units. When
7.3. Case 3: DG located along feeder it is not required to consider a certain term in the objective function,
except for the first term, the corresponding weighting factor is set to
DG rating limits for different DG positions along feeder for a zero. In addition, any other factor, such as total harmonic distortion
fault at F1 considering all terms in the objective function (App5) (THD) and number of control actions, can be added without any
are shown in Table 11. The best alternative is to distribute units at modification of the methodology. For example a term describing
different buses keeping coordination margin between recloser and the summation of total harmonic distortion can be added to the
fuse. objective function using a suitable weighting factor. However, THD-
From Table 11, the maximum penetration of DG is reached when based objective function can be ignored as the THD of inverter-
seven units are connected at different buses in the recloser–fuse based distributed generation can be generally improved either by
region. On the other hand, the maximum capacity of DG units when involving harmonic filters or using suitable control.
located in relay–recloser region is found to be 1.14 MW. This value The algorithm is used in the planning stage to define the maxi-
is obtained from a single unit located at bus 16. This value takes mum limits of DG units that can be inserted in the network without
into account the coordination for the entire feeder. Thus, it is logic affecting the coordination problem. In addition, it defines the best
to obtain reduced value compared to 4.36 MW when considering
the coordination between recloser–fuse as shown in Table 10. In a Table 13
similar way, the DG penetration limits with different DG positions Active and reactive power loss, total fault current and minimum value of voltage
at all buses and different fault locations with modified recloser fast with different DG positions along feeder fault locations at F1 and F4.
Table 14
DG penetration limits with different DG positions at all buses and multi fuse with modified recloser fast curve.
location of these units with maximizing capacity to increase the feeder, in: Proceedings of the 15th International Middle East Power Systems
benefits. The methodology deals only with this problem, while the Conference (MEPCON’12), December, 2012, Alexandria University, Egypt, 2012,
pp. 23–25.
operation is another problem that can be handled by the operator [4] P.P. Barker, R.W. Mello, Determining the impact of distributed generation on
of an independent system operator (ISO) of the system. power systems: Part 1—Radial distribution systems, Power Eng. Soc. 3 (2000)
1645–1656 (Summer Meeting, 2000. IEEE).
[5] S.A.M. Javadian, M.-R. Haghifam, S.M.T. Bathaee, M. Fotuhi Firoozabad, Adap-
8. Conclusion tive centralized protection scheme for distribution systems with DG using risk
analysis for protective devices placement, Int. J. Electr. Power Energy Syst. 44
A proposed multi-objective function is developed to define (1) (2013) 337–345.
[6] A. Kamel, M.A. Alaam, A.M. Azmy, A.Y. Abdelaziz, Protection coordination for
the setting and sizing of DGs in the distribution system keeping distribution systems in presence of distributed generators, Electr. Power Com-
the classical protection scheme unchanged. The coordination con- pon. Syst. 41 (15) (2013) 1555–1566.
straint, including fuse–recloser and recloser–relay schemes, has [7] S. Kwon, C. Shin, W. Jung, Evaluation of protection coordination with distributed
generation in distributed networks, in: Proceedings of the 10th IET Interna-
been added to the multi-objective function in an augmented fit-
tional Conference on Developments in Power System Protection (DPSP 2010),
ness function. The modified fast curve-based recloser setting has January 2010, pp. 74–78.
been used with the DG in order to increase the sizing of DG. The [8] V. Calderaro, V. Galdi, A. Piccolo, P. Siano, A Petri net based protection monitor-
ing system for distribution networks with distributed generation, Elect. Power
possibility of minimizing the network power losses, improving
Syst. Res. 79 (9) (2009) 1300–1307.
voltage profile and reducing fault current level without replacing [9] A.F. Naiem, Y. Hegazy, A.Y. Abdelaziz, M.A. Elsharkawy, A classification tech-
the existing protection system have been emphasized in the results nique for recloser–fuse coordination in distribution systems with distributed
considering single and multi DG units. generation, IEEE Trans. Power Delivery 27 (1) (2012) 176–185.
[10] J.C. Hernandez, J. De la Cruz, B. Ogayar, Electrical protection for the grid-
In practice, the choice of the best location may not be always interconnection of photovoltaic-distributed generation, Elect. Power Syst. Res.
possible owing to many constraints. However, the analysis recom- 89 (2012) 85–99.
mends that the maximum levels of DGs can be achieved when [11] IEEE Standards Coordinating Committee 21 (IEEE SCC21), IEEE Standard for
Interconnecting Distributed Resources with Electric Power Systems, IEEE Std.,
located in recloser–fuse region, especially near recloser location 2003, pp. 1–28, http://dx.doi.org/10.1109/IEEESTD.2003.94285
without considering other factors. On the other hand, if the tech- [12] S. Chaitusaney, A. Yokoyama, An appropriate distributed generation sizing
nical constraints are taken into account, the optimal location of considering recloser–fuse coordination, in: Proc. IEEE Power Eng. Soc. Trans-
mission and Distribution Conf. Exhibit., 2005, pp. 1–6.
the DG units will be close to the fuse location. As a result, the [13] J. Sadeh, M. Bashir, E. Kamyab, Effect of Distributed Generation Capacity on the
maximum capacity of the DG units will be reduced by 21% com- Coordination of Protection System of Distribution Network, Transmission and
pared with its value when the technical constraints were not taken Distribution Conf. and Exp., IEEE Press, New Orleans, Louisiana, USA, 2010, pp.
110–115.
into account. In brief, the optimal setting and sizing of DG depends
[14] M. Thakur, S.S. Meghwani, H. Jalota, A modified real coded genetic algorithm
on the optimization strategy of the operator according to the con- for constrained optimization, Elect. Power Syst. Res. 235 (4) (2014) 292–317.
cerned priorities and status of power system. [15] J.O. Kim, D.J. Shin, J.N. Park, C. Singh, Atavistic genetic algorithm for economic
dispatch with valve point effect, Elect. Power Syst. Res. 62 (3) (2002) 201–207.
[16] L. Sun, Y. Zhang, C. Jiang, A matrix real-coded genetic algorithm to the unit
References commitment problem, Elect. Power Syst. Res. 76 (9–10) (2005) 716–728.
[17] D. He, F. Wang, Z. Mao, Hybrid genetic algorithm for economic dispatch with
[1] P. Trichakis1, P.C. Taylor, P.F. Lyons, R. Hair, Predicting the technical impacts of valve-point effect, Elect. Power Syst. Res. 78 (4) (2008) 626–633.
high levels of small-scale embedded generators on low-voltage networks, IET [18] S. Porkar, P. Poure, A. Abbaspour Tehrani-fard, S. Saadate, Optimal allocation
Renew. Power Gener. 2 (4) (2008) 249–262. of distributed generation using a two-stage multi-objective mixed-integer-
[2] H. Zayandehroodi, A. Mohamed, H. Shareef, M. Mohammad Jafari, M. Farhood- nonlinear programming, Eur. Trans. Electr. Power 21 (2010) 1072–1087.
nea, A novel protection coordination strategy using back tracking algorithm for [19] S.A. Hossini, S.S.K. Madahi, F. Razavi, M. Karami, A.A. Ghadimi, Optimal sizing
distribution systems with high penetration of DG, in: 2012 IEEE International, and siting distributed generation resources using a multi objective algorithm,
Power Engineering and Optimization Conference (PEDCO), Melaka, Malaysia, Turk. J. Electr. Eng. Comp. Sci. 21 (2013) 825–850.
2012, pp. 187–192. [20] M.A. Abido, A novel multiobjective evolutionary algorithm for environmen-
[3] N.I. Elkalashy, N.F. Sherbilla, A.I. Taalab, T.A. Kawady, Distributed generation tal/economic power dispatch, Elect. Power Syst. Res. 65 (1) (2003) 71–81.
with fault current limiter impacts on recloser–fuse protection for distribution