EASYLAB
Controller TCU3
for Fume Cupboards and Air Management Systems
The EASYLAB controller TCU3 is the core of the TROX Air terminal units
EASYLAB system. With EASYLAB, good functionality and high – TVLK, variable volume flow controller for laboratories
levels of safety can be easily combined with optimum energy – TVRK, plastic variable volume flow controller
efficiency. The system is prepared for future expansions or
– TVR, circular variable volume flow controller for supply or
changes in use.
extract air
The TCU3 controller was developed for fume cupboard control, – TVJ · TVT, rectangular variable volume flow controller for
for the supply or extract air control of laboratories, and for supply or extract air
various tasks in hospitals and clean rooms.
– TVZ · TVA, variable volume flow terminal units for supply or
Additional functions such as the integration into a LonWorks extract air
network can be achieved with various expansion modules.
Characteristics, dimensions, and technical data on the air
The TCU3 automatic controller is combined with an air terminal terminal units can be found in the corresponding technical
unit to provide a flow rate control package. Every controller is leaflets.
factory tested and set to the required flow rates.
Further, current information on design can be found on our
Website and in our “Air Management Systems” design manual.
2
EASYLAB system
The EASYLAB system makes it possible to control Advantages of the EASYLAB system
safety-related flow rates in a rapid, reliable, and demand-based • Modular, expandable system
manner. Among other things, this includes fume cupboard • Innovative operating mode and room control strategies to
control and the supply air, extract air, and differential pressure meet individual project requirements
control in laboratories, clean rooms, and rooms in hospitals with
• Configurable monitoring functions and fault signalling
similar requirements.
(e.g. consolidated alarms)
In addition to the controller, expansion modules, sensors, and • Simple plug-and-play installation and plug-in communication
control panels, EASYLAB mainly comprises extensive software cable
for solving control-issues. The TCU3 controller forms the basis
for all closed-loop and open-loop control tasks and for this • Easy installation due to user-guided EasyConnect
purpose is combined with the corresponding air terminal units, configuration software
actuators, and pressure transducers. • Easily visible alarm indicator lights on both sides of the outer
casing
The modular structure offers numerous function expansion
options to adapt to project-specific requirements. Complicated • Central configuration of all parameters for higher order room
room air management is possible with numerous configurable functions (room management function)
closed-loop control strategies. The optimum EM-LON
expansion, for example, allows integration into a LonWorks
network.
Areas of application
TVRK
EASYLAB
TVJ · TVT
TVR
3
Expansion modules
Function expansion
Expansion module Order code
The TCU3 controller can be adapted to the particular
requirements with various expansion modules.
EM-TRF
With the exception of the battery, all expansion modules are Supply voltage 230 V AC
T
connected to the TCU3 within the controller casing. The battery
is attached to the TVLK casing. The expansion modules can be
EM-TRF-USV
delivered already installed at the factory or retrofitted. U
Supply voltage 230 V AC and UPS
EM-LON
L
LonWorks interface
EM-AUTOZERO
Z
Automatic zero balance
EM-LIGHT
S¹
Lighting connecting socket
Expansion modules
EM-TRF
Power pack for connection of the controller to a 230 V AC
supply voltage.
For more information, see Technical Leaflet No. 5.3/4/EN/..
EM-TRF
EM-TRF-USV
Power pack with uninterruptible power supply for connection
of the controller to a 230 V AC supply voltage. An electronic
system with an emergency power supply battery keeps the
controller running in case of a supply voltage failure.
For more information, see Technical Leaflet No. 5.3/4/EN/..
Battery pack
EM-TRF-USV
EM-AUTOZERO
Automatic zero balance with a solenoid valve for the
long-term stabilisation of the flow rate measurement. The
zero point voltage of the pressure transducer is measured
EM-AUTOZERO cyclically and the slow zero point drift is thus reliably
prevented. A manual zero balance during maintenance
is no longer necessary.
EM-LON
LonWorks communication interface FT10 for integrating the
controller into the centralised BMS.
For more information, see Technical Leaflet No. 5.3/5/EN/..
EM-LON
EM-LIGHT
The lighting control system enables the control of the fume
cupboard interior lighting on the control panel. 230 V AC
is controlled with a maximum of 500 W. EM-LIGHT enables
the simple plug-in connection of the lighting using a WAGO
WINSTA Midi Type 770 plug. EM-LIGHT is possible only in
EM-LIGHT connection with EM-TRF or EM-TRF-USV.
4
Areas of application · control strategies
Fume cupboard control Extract air control in extract air master system
FH function RE/LAB function
Control of the flow rates required due to the testing of the Control of the room extract air and limitation of the total extract
fume cupboards according to EN 14175. The monitoring of air flow rate of the room to a defined value. The flow rates of all
the aerodynamic function is integrated. Ideally, this closed-loop extract air controllers are taken into consideration. If a difference
control is used with an adaptively variable flow rate in order to in comparison with the required total extract air flow rate exists,
achieve energy savings with optimum safety. this difference will be controlled with the room extract.
Supply air control in extract air master system Differential pressure control in extract air master
RS/LAB function system
Control of the demand-based supply air flow rate related to RC/LAB function
the current overall extract air flow rate of the room. In the Link the room air balance control with the differential pressure
process, a configurable difference to achieve the underpressure control to achieve a rapidly balanced and stable pressure. The
required in DIN 1946, Part 7, is taken into consideration. difference between supply and extract air is variable in the case
of differential pressure control.
Communication cable
500 mm
Fume Fume
cupboard 1 cupboard n
RN RMF
BE-LCD-01
5
Fume cupboard control
TCU3
VS-TRD
TVLK velocity transducer
6
Fume cupboard control
Control diagrams
FH-VS FH-3P
V
V 1
Flow rate
Incoming flow velocity V₃
Vmax
V₂ Flow rate
0.5 v in m/s
V₁
Vmin
0
Closed Open S₁ S₂ Switch
FH-DS FH-2P
V
V 1
Flow rate
Vmax
Incoming flow velocity
V₂ Flow rate
0.5 v in m/s
V₁
Vmin
0
Closed Open S₁ Switch
FH-DV FH-F
V 1 V
Flow rate
Incoming flow velocity
Vmax
Vmin
0
Closed Open Closed Open
7
Fume cupboard control
open 4
open 3
open 2
oard
oard
oard
cupb e
cupb e
cupb e
oard
cupb e
Fum
Fum
Fum
Fum
Sash open
Sash close
Total room extract air
2 Lighting
Local control
open 4
oard
cupb e
Fum
8
Fume cupboard control
BMS
Analogue
LonWorks Switch contacts
0 - 10 V DC
Communication cable
TROX
adapter module
(TAM)
9
Room control
TCU3 for room control Differential pressure control in extract air master system
PC/LAB
For the control of variable supply or extract air flow rates, the
electronic controller TCU3 is used in combination with an air Link the room air balance control with the differential pressure
terminal unit types TVR · TVRK · TVJ · TVT · TVZ · TVA. control to achieve a rapidly balanced and stable pressure. The
difference between supply and extract air is variable in the case
Equipment functions and control strategies of differential pressure control.
Extract air control in extract air master system RE/LAB Balancing
Control of the room extract air and limitation of the total extract
air flow rate of the room to a defined value. The flow rates of all For balancing, all supply and extract flow rates of a room
extract air controllers are taken into consideration. If a difference are recorded and summed. The following are taken into
in comparison with the required total extract air flow rate exists, consideration:
this difference will be controlled with the room extract. – Maximum of 24 EASYLAB controllers
Supply air control in extract air master system RS/LAB – Analogue inputs
Control of the demand-based supply air flow rate related to the – Digital inputs
current overall extract air flow rate of the room. In the process, a – Parameters
configurable difference to achieve the underpressure required in
DIN 1946, Part 7, is taken into consideration.
RS equipment function
Communication line X
X
X
Fume Fume
cupboard 1 cupboard 2
RE equipment function
10
Room control
Room control
∆p V
0 Pa
−10 Pa
11
Room control
Room management function RMF
RMF
Change signal
Central
temperature
selections
control
12
Room control
Room management function RMF
LonWorks interface for the room with EM-LON expansion Interface to the centralised BMS
module Analogue signal (0 - 10 V)
– Selection of the room operating mode – Actual flow rate of the controller
– Prioritisation of the operating mode selections – Controller damper blade position
(centralised BMS/local)
– Total extract air flow rate, total supply air flow rate, or setpoint
– Connection of a volume flow change signal for temperature value of the total supply air flow rate
or differential pressure control
Digital switch contact
– Switchover between two setpoint values of a differential
– Alarm state of the controller (change-over contact)
pressure control
LonWorks interface with EM-LON expansion module
– Feedback signals from the EASYLAB system (room)
The current operating values and fault messages of the room
– Actual room operation mode
controller are transferred via the network:
– Total extract air flow rate actual value actual flow rate, setpoint flow rate, and operating mode.
– Total supply air flow rate actual value
Further information on this topic, especially on the interface
– Evaluated damper positions
definitions, can be found in Technical Leaflet No. 5.3/4/EN...
– Consolidated alarm
– Setpoint and actual value of the internal room pressure
control
– Room pressure alarm
Room control
BMS
LON
Communication cable
13
Room control
Controller inputs and outputs · Air terminal units
Air terminal units with EASYLAB controller TCU3 for room control
14
Construction · Dimensions
TCU3
122
220¹
27¹
267
282
15
Technical data
Technical data
Power rating
Fume cupboard controller with control panel 35 VA
Room controller 29 VA
Room controller with room control panel 33 VA
with all expansion modules max. 40 VA
Temperature range
Operation 0°C to +50°C
Storage −10°C to +70°C
Humidity
Operation <90%, non-condensing
Storage <90%, non-condensing
16
Fume cupboard controller
Specification text
Specification text for the fume cupboard Alarm monitoring and signalling which is individually configurable,
controller* e.g. for alarm suppression in certain operating modes or compilation
of a consolidated alarm.
Circular variable volume flow controller made of flame-resistant
polypropylene (PPs) for variable volume flow systems and fume Operating mode selection of main control point, room control
cupboards. For the flow rate control of extract air containing panel, or fume cupboard control panel with flexible isolation and
contaminated or aggressive materials since all components coming prioritisation options. Supported special operating modes: increased
into contact with the air stream are made of plastic. operation, reduced operation, shut-off, and open position
... (The complete text can be found in Technical Leaflet No. Additional special functions
5.3/1/EN/..) – Support of fume cupboards with supportive flow technology
Control components: – Safe control of an extract air fume scrubber
Electronic controller for demand-based, variable flow rate control – Connection of motion sensors
of fume cupboards including the integrated monitoring of the – Smoke extract function
aerodynamic function according to EN 14175 with optical and – Control of the fume cupboard interior lighting
acoustic signalling. – Control of a sash moving mechanism
Supported equipment functions: – Consideration of diversity factors in connection with
– FH-VS TROX EASYLAB room controllers
Flow rate control on the basis of the measured incoming flow 5 analogue inputs for connecting the sensor system and integrating
velocity under consideration of thermal loads. Monitoring of up to 4 variable flow rates.
the flow rate and incoming flow velocity. 6 floating digital inputs for the integration of constant flow rates
– FH-DS and/or the control of special functions.
Flow rate control based on the measured opening height of the 3 analogue outputs for signalling actual flow rates and the controller
sash, with linear characteristic. Monitoring and signalling of the damper blade position as well as the total flow rate of the room
maximum set sash opening according to EN 14175. (supply or extract air).
– FH-DV 1 digital output for flow rate alarm with configurable alarm
Safety-optimised flow rate control based on the measured conditions.
opening height of the sash. Monitoring and signalling of the
5 digital outputs for supporting the various special functions.
maximum set sash opening according to EN 14175.
– FH-2P Rapid response actuator (run time 90° < 3 s)
Flow rate control with two setpoint values and monitoring of Supply voltage 24 V AC
the flow rate. Expansion modules:
– FH-3P – EM-TRF
Flow rate control with three setpoint values and monitoring of Supply voltage 230 V AC
the flow rate. – EM-TRF
– FH-F Supply voltage 230 V AC with uninterruptible power supply.
Constant value flow rate control and monitoring of the flow rate. Range of functions in UPS operation: alarm in case of power
Control electronics on microprocessor basis with configuration supply failure, monitoring and alarm for the controller function,
settings in EEPROM memory and thus secured in case of power continuation of normal control operation or, alternatively: open
failure. 5 analogue inputs, 6 floating digital inputs, 3 analogue position, shut-off, or lock damper blade position.
outputs, and 6 digital outputs as relay change-over contacts. Static – EM-AUTOZERO
diaphragm pressure transducer with room air induction to protect the Automatic zero point correction
measuring point. Maintaining of the flow rates through a permanent – EM-LON
setpoint/actual value comparison in a closed loop with a limitation to
minimum and maximum flow rates. LonWorks interface
– EM-LIGHT
Special characteristics:
Connection socket for simple connection of the fume cupboard
– Integrated system and sensor monitoring
interior lighting
– Intelligent communication system (plug-and-play)
* Text for a volume flow controller type TVLK with EASYLAB
– Easy configuration, commissioning, and diagnosis with
user-guided EasyConnect service software
All important communication and periphery connections on the
outside of the casing and thus easy to connect. Indicator lights on
the outside of the casing for alarm display (on both sides), controller
function (heartbeat), and communication.
Communication system with plug-in communication cables,
automatic connection setup without manual network configuration,
easy to expand with additional controllers (usually without
integration issues).
Integration of variable or constant flow rates in the room balance
using analogue signals, switch contacts, or constant values.
Signalling of actual flow rate values, damper blade positions, faults,
and status messages to centralised BMS with analogue or switch
outputs.
Connection of one or two (for fume cupboards with double sided
openings) adaptable EASYLAB control panels BE-SEG-01 or
BE-LCD-01 with optical and acoustic signalling. Acoustic alarm can
be deactivated and limited in terms of time.
17
Fume cupboard controller
Order code
Order code
Make: TROX
Type: TVLK-FL / 250-0 / GK / ELAB / FH-VS / TZS / 300 – 1200 m³/h
18
Room controller
Specification text
Specification text for room controller* Additional functions with activated room management function:
Variable volume flow controller in circular construction for variable – Connection of one or two adaptable EASYLAB room control
volume flow systems, for supply or extract air, in 7 nominal sizes. panels BE-LCD-01
Consisting of the casing with control damper, differential pressure – Central operating mode selection for all controllers in a room
sensor, and control components. Control damper closed blade – Central transfer point for individual or consolidated faults
leakage complies with EN 1751, Class 4 (nominal sizes 100 and – Monitoring of the room functions for an exceedence of the
125, class 3). Position of the control damper blade visible from the minimum total extract air flow rate and exceedence of the total
outside on the shaft extension. extract air flow rate (diversity)
... (The complete text can be found in Technical Leaflet No. 5/3/EN/..) – Limitation of the total extract air flow rate (diversity control)
Control components: – Operating mode selection of main control point, room control
Electronic controller for demand-based, variable flow rate control of panel, or fume cupboard control panel with flexible lisolation
supply or extract air in laboratories and for various tasks in hospitals and prioritisation options. Supported special operating modes:
and clean rooms. increased operation, reduced operation, shut-off, and open
position
Supported equipment functions:
– Central configuration of the room parameters
– RE / LAB
– Flow rate change for temperature control
Control of the room extract air and limitation of the total extract air
flow rate of the room to a defined value. The flow rates of all – Flow rate change for external pressure control
extract air controllers are taken into consideration. If a difference in – Connection of the pressure transducer for differential pressure
comparison with the required total extract air flow rate exists, this control
difference will be controlled with the room extract. – Individually configurable consolidated alarms
– RS / LAB 5 analogue inputs for connecting the sensor system and integrating
Control of the demand-based supply air flow rate related to the up to 4 variable flow rates or, in case the room management function
current overall extract air flow rate of the room. In the process, a is activated, for connection of the temperature flow rate change, the
configurable difference to achieve the underpressure required in pressure flow rate change, or the pressure transducer.
DIN 1946, Part 7, is taken into consideration. 6 volt-free digital inputs for the integration of constant flow rates or, in
– PC / LAB case the room management function is activated, for room operating
Linking of the closed loops for room air balance and pressure mode selection and prioritisation, switchover between two setpoint
for rapid response and stable differential control. The difference pressure values, or the connection of a door contact.
between supply and extract air is variable in the case of differential 3 analogue outputs for the signalling first actual flow rate, second
pressure control. controller damper blade position and third total extract air flow rate,
Control electronics on microprocessor basis with configuration or total supply air flow rate, or setpoint value of the total supply air
settings in EEPROM memory and thus secured in case of power flow rate
failure. 5 analogue inputs, 6 floating digital inputs, 3 analogue 1 digital output for flow rate alarm with configurable alarm conditions.
outputs, and 6 digital outputs as relay change-over contacts. Static
5 digital outputs for supporting the activated room management
diaphragm pressure transducer with room air induction to protect the
function: configurable consolidated alarm, pressure alarm (in case of
measuring point. Maintaining of the flow rates through a permanent
differential pressure control), or lighting control.
setpoint/actual value comparison in a closed loop with a limitation to
minimum and maximum flow rates. Rapid response actuator (run time 90° < 3 s)
Special characteristics: Supply voltage 24 V AC
– Integrated system and sensor monitoring Expansion modules:
– Intelligent communication system (plug-and-play) – EM-TRF
– Easy configuration, commissioning, and diagnosis with Supply voltage 230 V AC
user-guided EasyConnect service software – EM-TRF-USV
All important communication and periphery connections on the Supply voltage 230 V AC with uninterruptible power supply.
outside of the casing and thus easy to connect. Indicator lights on Range of functions in UPS operation: alarm in case of power
the outside of the casing for alarm display (on both sides), controller supply failure, monitoring and alarm for the controller function,
function (heartbeat), and communication. continuation of balancing function and normal control operation
Communication system with plug-in communication cables, or, alternatively: open position, shut-off, or lock damper blade
automatic connection setup without manual network configuration, position.
easy to expand with additional controllers (usually without integration – EM-AUTOZERO
issues). Automatic zero point correction
Integration of variable or constant flow rates in the room balance – EM-LON
using analogue signals, switch contacts, or constant values. LonWorks interface for the integration of the room into a higher
Signalling of actual flow rate values, damper blade positions, faults, level network.
and status messages to centralised BMS with analogue or switch
outputs. * Text for a volume flow controller type TVR with EASYLAB
19
Room controller
Order code
Order code
10
Make: TROX
Type: TVRD-FL /160/ ELAB / RS / Z / LAB
20