You are on page 1of 5

0 1 2 3 4 5 6 7 8 9

INITIAL RELEASE
NOTE: REV /
23.62
[600] 1. DIMENSIONS ARE IN INCHES (mm) DES MGR DATE
ISSUE
JTM SCS 13-AUG-2015 1

A ADD ELECTRICAL DETAIL A


2. OPERATING TEMP. RANGE: REV /
0 C-40 C (32 F-104 F) DES MGR DATE
ISSUE
QLW SCS 7-MAR-2016 2

3. FRONT AND TOP ACCESS REQUIRED


HEAT REJECTION FOR SERVICE AND MAINTENANCE

B 4. DO NOT TILT UPS MORE THAN 10 B


5. CENTER OF GRAVITY DIMENSIONS ARE
ESTIMATED. THE REAL CENTER OF
GRAVITY IS ON THE CARTON PACKAGE
29.32
[744,8]
28.54 6. MINIMUM CLEARANCE FOR HEAT
[725]
C REJECTION: C
16" (400mm) ABOVE UNIT
32" (800mm) IN FRONT OF UNIT

D D

E E
75.00
[1905]

F F

37.13
[943,1]
CENTER OF
GRAVITY

7
[180]
G G

© 2012
SWIVEL CASTERS 11.8
GE ENERGY (USA), LLC AND/OR ITS GE CLASS II (INTERNAL CRITICAL)
.52 13.7 AFFILIATES. All rights reserved. The
GE PROPRIETARY INFORMATION
[13,3] [300] [349] information contained herein is GE Energy C &
CENTER OF PE COE Proprietary Technical Information that
CENTER OF belongs to the General Electric Company, GE
THIRD ANGLE PROJECTION

GRAVITY GRAVITY Energy (USA), LLC and/or their affiliates, which


has been provided solely for the express reason GE Energy
of restricted private use. All persons, firms, or PLANO, TX
corporations who receive such information shall
H H
TITLE / DESCRIPTION

KVA WEIGHT HEAT REJECTION FLOOR LOADING be deemed by the act of their receiving the
same to have agreed to make no duplication, or MECHANICAL OUTLINE
other disclosure, or use whatsoever for any, or SIZE PART NUMBER REV.
20 6380 BTU/HR all such information except as expressly
LP33_30-40KVA_PLANO
LP33_S2_20-30_MECH
PART NUM
DRAWING
0
0
authorized in writing by the General Electric
Company, GE Energy (USA), LLC and/or its
B LP33 S2 UL UPS 20-30 KVA MECH-ELECT 2
FILE NAME FILE TYPE REVISION VERSION
30 9656 BTU/HR affiliates. SHEET 1 OF 5

0 1 2 3 4 5 6 7 8 9
0 1 2 3 4 5 6 7 8 9

SHOWN WITH OPTIONAL


TOP FEED ASSEMBLY
A 29.66 A
[753,4] 6.04
[153,4]
7X KNOCKOUTS FOR
2" CONDUIT

B B

C .85
C
[21,5]

D D

E E

TOP FEED
AC ROUTING

F F

G G

© 2012
GE ENERGY (USA), LLC AND/OR ITS GE CLASS II (INTERNAL CRITICAL)
AFFILIATES. All rights reserved. The
information contained herein is GE Energy C & GE PROPRIETARY INFORMATION
PE COE Proprietary Technical Information that
.50 belongs to the General Electric Company, GE
THIRD ANGLE PROJECTION

[12,7] Energy (USA), LLC and/or their affiliates, which


has been provided solely for the express reason GE Energy
of restricted private use. All persons, firms, or PLANO, TX
corporations who receive such information shall
H H
TITLE / DESCRIPTION
be deemed by the act of their receiving the
same to have agreed to make no duplication, or MECHANICAL OUTLINE
other disclosure, or use whatsoever for any, or SIZE PART NUMBER REV.
all such information except as expressly
authorized in writing by the General Electric
Company, GE Energy (USA), LLC and/or its
B LP33 S2 UL UPS 20-30 KVA MECH-ELECT 2
affiliates. SHEET 2 OF 5

C2FORMAT.FRM DEC 2002


0 1 2 3 4 5 6 7 8 9
0 1 2 3 4 5 6 7 8 9

A A

B X2 X3 B

X4 X1 INPUT
BYPASS LOAD
INPUT (OPTIONAL)
RECTIFIER
BATTERY

C C

PE
N2
L3
L2
L1
PE
L3-2
L2-2

N
L1-2
L3-1

PE
L2-1

N1
L1-1
PE
- 0 +

D D
RECOMMENDED CABLE DIA. FOR TERMINAL BLOCKS
(REFER TO MANUAL FOR TORQUE SPECS) (AWG)
RECTIFIER BYPASS DC AC
KVA GROUND
INPUT INPUT INPUT OUTPUT
20 1/0 1/0 1/0 1/0 1/0

30 4/0 4/0 4/0 4/0 4/0


E E

SHOWN WITH OUT


SAFETY COVERS

F F

G G
X4 X1 X2 X3 © 2012
GE ENERGY (USA), LLC AND/OR ITS GE CLASS II (INTERNAL CRITICAL)
AFFILIATES. All rights reserved. The
information contained herein is GE Energy C & GE PROPRIETARY INFORMATION
PE COE Proprietary Technical Information that
THIRD ANGLE PROJECTION
belongs to the General Electric Company, GE
Energy (USA), LLC and/or their affiliates, which
has been provided solely for the express reason GE Energy
of restricted private use. All persons, firms, or PLANO, TX
corporations who receive such information shall
H H
TITLE / DESCRIPTION
be deemed by the act of their receiving the
same to have agreed to make no duplication, or MECHANICAL OUTLINE
other disclosure, or use whatsoever for any, or SIZE PART NUMBER REV.
all such information except as expressly
authorized in writing by the General Electric
Company, GE Energy (USA), LLC and/or its
B LP33 S2 UL UPS 20-30 KVA MECH-ELECT 2
affiliates. SHEET 3 OF 5

C2FORMAT.FRM DEC 2002


0 1 2 3 4 5 6 7 8 9
0 1 2 3 4 5 6 7 8 9

A A
18.00
[457,2]
2.81 2.00 2.00 .750
[71,4] [50,8] [50,8] [19,05]

1.14
[28,9]

B B
ANCHOR LOCATIONS

7.70
[195,5]
ANCHOR LOCATIONS

C C

4.96
[126]

D D
24.55
[623,7]

E E

BOTTOM CABLE ENTRY


AREA 100 SQ IN (64500 SQ mm)

F F

G G

© 2012
ANCHOR LOCATIONS GE ENERGY (USA), LLC AND/OR ITS GE CLASS II (INTERNAL CRITICAL)
4X LEVELING FEET AFFILIATES. All rights reserved. The
information contained herein is GE Energy C & GE PROPRIETARY INFORMATION
PE COE Proprietary Technical Information that
THIRD ANGLE PROJECTION
4.25 9.50 belongs to the General Electric Company, GE
[107,9] [241,3] Energy (USA), LLC and/or their affiliates, which
has been provided solely for the express reason GE Energy
of restricted private use. All persons, firms, or PLANO, TX
20.16 1.73 corporations who receive such information shall
H H
TITLE / DESCRIPTION
be deemed by the act of their receiving the
[512] [44] same to have agreed to make no duplication, or MECHANICAL OUTLINE
other disclosure, or use whatsoever for any, or SIZE PART NUMBER REV.
all such information except as expressly
authorized in writing by the General Electric
Company, GE Energy (USA), LLC and/or its
B LP33 S2 UL UPS 20-30 KVA MECH-ELECT 2
affiliates. SHEET 4 OF 5

C2FORMAT.FRM DEC 2002


0 1 2 3 4 5 6 7 8 9
0 1 2 3 4 5 6 7 8 9

A A

B B

C C

Inverter

D D

E E

F F

AC INPUTS - UPS
UPS MODEL AC OUTPUT AC INPUT-BYPASS DC INPUT
NOM. MAX
LP SERRIES 20kVA 57A 63A 57A 57A 68A
G LP SERRIES 30kVA 87A 96A 87A 87A 87A G

© 2012
GE ENERGY (USA), LLC AND/OR ITS GE CLASS II (INTERNAL CRITICAL)
AFFILIATES. All rights reserved. The
information contained herein is GE Energy C & GE PROPRIETARY INFORMATION
PE COE Proprietary Technical Information that
THIRD ANGLE PROJECTION
belongs to the General Electric Company, GE
Energy (USA), LLC and/or their affiliates, which
has been provided solely for the express reason GE Energy
of restricted private use. All persons, firms, or
UPS MODEL AC INPUT - UPS AC OUTPUT AC INPUT-BYPASS DC INPUT
PLANO, TX
corporations who receive such information shall
H H
TITLE / DESCRIPTION
be deemed by the act of their receiving the
same to have agreed to make no duplication, or ELECTRICAL DETAIL
other disclosure, or use whatsoever for any, or SIZE PART NUMBER REV.

LP SERRIES 20kVA 80A 80A 80A 90A all such information except as expressly
authorized in writing by the General Electric
Company, GE Energy (USA), LLC and/or its
B LP33 S2 UL UPS 20-30 KVA MECH-ELECT 2
LP SERRIES 30kVA 125A 125A 125A 110A affiliates. SHEET 5 OF 5

C2FORMAT.FRM DEC 2002