You are on page 1of 2

JUBAIL - RIYADH WATER TRANSMISSION SYSTEM

Subject DATA SHEETS Number


Steel Water Storage Tanks 1010
Doc. - No.: Q A 1 0 - G - 1 0 6 0

No. Description Unit Required Guaranteed Notes


General

1 Tank Manufacturer

Matrix Applied
2 Aluminum Dome Roof Manufacturer
Technologies
Flat Bottom Welded Flat Bottom Welded
Steel Tank with Steel Tank with
3 Type of Construction/Design Note 1,2
Aluminium Dome Aluminium Dome
Roof, G02, M09 Roof, G02, M09
4 Standards M09, API 650 M09, API 650 Note 1
5 Project Specification M09 M09 Note 1
Pumping Station PS1
6 Location of Installation
Highpoint Terminal
7 Altitude of Terminal m.a.s.l
8 Number of Tanks G02 14 Note 2
Process Design Data
9 Stored Media G02 G02 Note 2
10 Medium Analysis G02 G02 Note 3
11 Capacity m³ G02 170,000 m³ Note 2
Mechanical Design Data
12 Design Metal Temperature ̊C G02 G02 Note 2
Corrosion Allowance Shell / Bottom
13 mm 0 0
/ Roof
Shell Design
14 G02, API 650 yes yes
Data
15 Roof API 650A, Appendix G yes yes
16 Design Pressure bar g atm atm
17 Uniform Live Load kPa acc. To Code acc. To Code
18 Earthquake Design SBC and API 650 SBC and API 650 Note 4
19 Seismic Zone / Factor 2A Note 4
20 Design Wind Velocity km/h G02 G02 Note 2
21 Maximum Rainfall per Day mm/day G02 G02 Note 2
22 Diameter m 106
23 Height m 20
24 Foundation Type G02, API 650 G02, API 650 Note 2
Construction Details
25 Material of Construction Shell Carbon Steel Carbon Steel
26 Material Specification Bottom Carbon Steel Carbon Steel
27 Material Specification Roof Aluminium Aluminium
Carbon Steel / Carbon Steel /
28 Material Specification Structural
Aluminium Aluminium
29 Material of Internals Carbon Steel Carbon Steel Note 5
30 No. of Courses 8
31 Plate Width mm 2500
32 Plate Thickness Bottom Course mm 45
33 Bottom Plate Thickness mm 6

Page 1 of 2
No. Description Unit Required Guaranteed Notes
34 Bottom Slope From Center From Center
35 Bottom Annular Plate Width mm 1400
36 Intermediate Wind Girder Yes / No Yes
37 Top Wind Girder used as Walkway - Yes / No Yes
38 Roof Type Aluminium Dome Roof Aluminium Dome Roof
aac. To API 650, aac. To API 650,
39 Roof Slope mm
Appendix G Appendix G
40 Roof Plate Thickness mm 1.27
aac. To API 650, aac. To API 650,
41 Welding Standard
Appendix G Appendix G
42 Vent Size Inch According to Design
43 Vent Number According to Design
G02, M09 acc. To G02, M09 acc. To Note 1,
44 Nozzles (Shell, Roof, Bottom)
P&IDs P&IDs 2, 6
45 Tank Weight t 2078
46 Coating Tank Exterior M09 M09 Note 1
47 Lining Tank Interior M09 M09 Note 1
48 Paint Bottom Underside M09 M09 Note 1
49 Paint Structural Steel M09 M09 Note 1
Notes for Steel Water Storage Tanks (DS1010)
1 M09 = Specification “M09 Steel Tanks”, Doc. No.: QC10-H-049
2 G02 = The data are defined in “G02 Description of Project and Works”.
3 The water quality data is defined in “G02 Description of Project and Works”.
4 Seismic effect is according to “Saudi Building Code”
All internal tank surfaces except for stainless steel shall be protected by suitable food-proof materials.
5 Respective documents from an approved laboratory / testing organization, certifying the food-proof quality
of the materials shall be supplied by the Bidder.

6 Bidder shall issue one data sheet per each required tank size including a sketch with all required nozzles

Page 2 of 2