You are on page 1of 13

HEAT LOAD CALCULATION

Space Used : FIRST FLOOR- Office 2


Size : 513 x 8.75 = 4488.75

Area / Qty Sun Gain / Factor BTU / HR


Temp. Diff.
(AA) Sensible Heat Gain
Solar Heat Gain
North 0 x 16 x 0.56 0
South 81 x 11 x 0.56 499
East 0 x 11 x 0.56 0
Glass West 0 x 163 x 0.56 0
NE 0 x 11 x 0.56 0
SE 0 x 11 x 0.56 0
SW 0 x 94 x 0.56 0
NW 0 x 130 x 0.56 0
Solar Transmission Walls & Roof
North 0 x 13 x 0.36 0
South 864 x 25 x 0.36 7776
East 43.75 x 27 x 0.36 425
Walls West 0 x 21 x 0.36 0
NE 0 x 19 x 0.36 0
SE 0 x 27 x 0.36 0
SW 0 x 23 x 0.36 0
NW 0 x 15 x 0.36 0
Other Transmission Gains
All Glass 0 x 24 x 1.13 0
Partition 341.25 x 19 x 0.4 2594
Ceiling 513 x 19 x 0.4 3899
Exp.Roof 0 x 44 x 0.12 0
Floor 513 x 19 x 0.4 3899
Outdoor Air 240 x 24 x 0.12x1.08 746
People 12 x 269 x 3228
Lights 150 x 1.25 x 3.4 638
Equipment/Comp load 700 x 1 x 3.4 2380
Others 0 x 1 x 3400 0
R.S.H. 26083
Fan + S.Factor 3141
R.T.S.H. (AA) 29225
(BB) Latent Heat Gain
People 15 x 209 x 1 3135
Outdoor Air 240 x 52 x .012 x .68 1018
R.L.H. 4153
S.Factor 208
R.T.L.H. (BB) 4361
R.T.H 33586
(CC) Outside Air Heat
Sensible Heat 240 x 24 x 0.88 x 1.08 5474
Latent Heat 240 x 52 x 0.88 x 0.68 7468
R.A.Heat Gain. 4122
R.T.OA.H. (CC) 17065

Grand Total Heat (AA+BB+CC) 50650

Tonnage 4.22
ULATION

Basis Of Design
Estimate for : Summer
Total Height =
Conditions DB WB RH Gr/Lb Area F/c Height
Ambient 96 78 116 513 8.75
Inside 72 55 64
Difference 24 52 One air Change =

One fresh air change Length


North 0
South 81
East 0
West 0
Glass
NE 0
SE 0
R.S .H. F 0.87 SW 0
NW 0

North 0
South 108
East 0
West 0
Walls
A.D.P. 53.8 NE 0
SE 0
Dehum. Rise 16.016 SW 0
NW 0
Dehum.Cfm 1689.56
All Glass 0
Check Figures Partition 39
Ceiling 513
Sft / Person 43 Exp.Roof 0
Sft / TR 122 Floor 513
Cfm / Sft 3.29 Outdoor Air 10
Cfm / TR 400 People 15
Lights 150
Equipment 700
Others 0
R.A. Gain above false
North 0
South 0
unit configuration East 0
West 0
Glass
NE 0
SE 0
SW 0
NW 0

North 0
South 108
East 0
West 0
Walls
NE 0
SE 0
SW 0
NW 0
Partition 39
TOTAL R.A GAIN
12
Volume
4488.75

74.8125

Height Area
1 0
1 81
1 0
1 0
1 0
1 0
1 0
1 0

8.75 0
8.75 945
8.75 0
8.75 0
8.75 0
8.75 0
8.75 0
8.75 0

1 0
8.75 341.25
1 513
1 0
1 513
15 150
1 15
1 150
1 700
1 0
R.A. Gain above false ceiling
1 16 0.56 0
1 11 0.56 0
1 11 0.56 0
1 163 0.56 0
1 11 0.56 0
1 11 0.56 0
1 94 0.56 0
1 130 0.56 0

3.25 13 0.36 0
3.25 25 0.36 3159
3.25 27 0.36 0
3.25 21 0.36 0
3.25 19 0.36 0
3.25 27 0.36 0
3.25 23 0.36 0
3.25 15 0.36 0
3.25 19 0.4 963.3
TOTAL R.A GAIN 4122.3
76 - 50 72 - 50

0.77 51 0.77 46
0.78 51.3 0.78 46.5
0.79 51.6 0.79 47
0.8 52 0.8 47.5
0.81 52.3 0.81 48
0.82 52.6 0.82 48.5
0.83 53 0.83 49
0.84 53.2 0.84 49.5
0.85 53.4 0.85 50
0.86 53.6 0.86 50.1
0.87 53.8 0.87 50.3
0.88 54 0.88 50.4
0.89 54.2 0.89 50.6
0.9 54.4 0.9 50.7
0.91 54.6 0.91 50.9
0.92 54.8 0.92 51.2
0.93 55 0.93 51.4
0.94 55.2 0.94 51.5
0.95 55.3 0.95 51.7
0.96 55.5 0.96 51.9
0.97 55.7 0.97 52
0.98 55.8 0.98 52.2
0.99 56 0.99 52.3
1 56.2 1 52.4
HEAT LOAD CALCULATION

B
Estimate for : Sum

Conditions
Ambient
Space Used : GROUND FLOOR- Office1 Inside
Size : 800 x 11 = 8800 Difference

Area / Qty Sun Gain / Factor BTU / HR


Temp. Diff.
(AA) Sensible Heat Gain
Solar Heat Gain
North 0 x 16 x 0.56 0
South 0 x 11 x 0.56 0
East 20 x 11 x 0.56 123
Glass West 0 x 163 x 0.56 0
NE 0 x 11 x 0.56 0
SE 0 x 11 x 0.56 0
SW 0 x 94 x 0.56 0
NW 0 x 130 x 0.56 0
Solar Transmission Walls & Roof
North 275 x 13 x 0.36 1287
South 275 x 25 x 0.36 2475
East 332 x 27 x 0.36 3227
Walls West 352 x 21 x 0.36 2661
NE 0 x 19 x 0.36 0
SE 0 x 27 x 0.36 0
SW 0 x 23 x 0.36 0
NW 0 x 15 x 0.36 0
Other Transmission Gains
All Glass 20 x 24 x 1.13 542
Partition 0 x 19 x 0.4 0 C
Ceiling 800 x 19 x 0.4 6080
Exp.Roof 0 x 44 x 0.12 0
Floor 800 x 19 x 0.4 6080
Outdoor Air 200 x 24 x 0.15x1.08 622
People 10 x 269 x 2690
Lights 1000 x 1.25 x 3.4 4250
Equipment/Comp load 2 x 250 x 3.4 1700
Others 0 x 1 x 3400 0
R.S.H. 31738
Fan + S.Factor 3882
R.T.S.H. (AA) 35620
(BB) Latent Heat Gain un
People 10 x 209 x 1 2090
Outdoor Air 200 x 52 x .015 x .68 849
R.L.H. 2939
S.Factor 147
R.T.L.H. (BB) 3086
R.T.H 38706
(CC) Outside Air Heat
Sensible Heat 200 x 24 x 0.85 x 1.08 4562
Latent Heat 200 x 52 x 0.85 x 0.68 6223
R.A.Heat Gain. 0
R.T.OA.H. (CC) 10785

Grand Total Heat (AA+BB+CC) 49491

Tonnage 4.12
Basis Of Design
e for : Summer
Total Height = 12
DB WB RH Gr/Lb Area F/c Height Volume
96 78 116 800 11 8800
72 55 64
24 52 One air Change = 146.666667

One fresh air change Length Height Area


North 0 0 0
South 0 0 0
East 4 5 20
West 0 0 0
Glass
NE 0 0 0
SE 0 0 0
R.S .H. F 0.92 SW 0 0 0
NW 0 0 0

North 25 11 275
South 25 11 275
East 32 11 352
West 32 11 352
Walls
A.D.P. 55 NE 0 0 0
SE 0 0 0
Dehum. Rise 14.96 SW 0 0 0
NW 0 0 0
Dehum.Cfm 2204.65
All Glass 4 5 20
Check Figures Partition 0 11 0
Ceiling 800 1 800
Sft / Person 80 Exp.Roof 0 1 0
Sft / TR 194 Floor 800 1 800
Cfm / Sft 2.76 Outdoor Air 10 20 200
Cfm / TR 535 People 10 1 10
Lights 800 1.25 1000
Equipment 2 1 2
Others 0 1 0
R.A. Gain above false ceiling
North 0 1 16
South 0 1 11
unit configuration East 0 1 11
West 0 1 163
Glass
NE 0 1 11
SE 0 1 11
SW 0 1 94
NW 0 1 130

North 0 1 13
South 0 1 25
East 0 1 27
West 0 1 21
Walls
NE 0 1 19
SE 0 1 27
SW 0 1 23
NW 0 1 15
Partition 0 1 19
TOTAL R.A GAIN
0.56 0
0.56 0
0.56 0
0.56 0
0.56 0
0.56 0
0.56 0
0.56 0

0.36 0
0.36 0
0.36 0
0.36 0
0.36 0
0.36 0
0.36 0
0.36 0