Professional Documents
Culture Documents
ABB is a global leader in Power and Automation The product offering covers a wide spectrum of
technologies that enable utility and industry technologies across the entire voltage range including
customers to improve performance while lowering indoor and outdoor circuit breakers, air and gas
environmental impact. The ABB Group of companies insulated switchgear, disconnectors, capacitor banks,
operate in around 100 countries. reactive power compensators, power transformers,
distribution transformers, instrument transformers,
In India, ABB serves customers with the complete
Compact Substations (CSS) and Ring Main Units
range of power and automation technologies. The
(RMU).
company has a vast installed base, extensive
manufacturing facilities and a countrywide marketing
and service presence. Advantage ABB
The Power Technologies division offers electric, gas
120 years of technology and innovation
and water utilities as well as industrial and commercial
customers a wide range of products, systems and Unparalleled domain competence
services for power generation, transmission and A vast global experience
distribution. ABB’s turnkey solution capabilities in the
sector range from Electrical Balance of Plant (EBOP) Total solution provider
for power plants, bulk power transmission, Large installed base
substations and complete electrification to utility
automation and distribution systems.
Environment-friendly technologies
2 ABB
High Voltage Capacitor Voltage Transformers, type WN/WP/WS
ABB offers mixed dielectric type capacitor voltage transformers that cater to the dual application needs of
measurement and carrier communication.
Main features
Hermetically sealed with metallic bellows High protection against corrosion – all ferrous
cushion on top parts and housing (tank) are hot dip galvanized
EMU (electro magnetic unit) protection Cost-effective design
by spark gap across primary winding of Dual application – designed for measurement,
intermediate PT protection and carrier communication
Ratio error adjustment by compensating High reliability – robust design ensures
winding on PT primary winding, phase excellent surge withstand level
angle error adjustment by variable choke Low weight, compact and easy to install
with adjustable air gap Ease of transportation – shipped in
Intermediate capacitor tap connection easy-to-assemble parts
through an epoxy bushing housed in the It can be connected without danger at the end
porcelain insulator and tank of unloaded line
Quality Assurance
The CVTs and CCs are designed to
comply with IEC: 60186/ 60358 and IS: 3156.
CVTs complying with ANSI/IEEE standards
C57.13 or other standards can also be provided
on request.
ABB 3
High Voltage Capacitor Voltage Transformers, type WN/WP/WS
Schematic drawing
Dimensional drawing
Technical data
Parameter Rated System Voltage
66kV 132kV 220kV 400kV
Type WN 73N2 WN 145N2 WP 245N2 WS 420/N2
Rated Capacitance in pF 4400-8800 4400-13200 4400-8800 4400-8800
Rated freq. in Hz 50/60 50/60 50/60 50/60
Rated Sec. Voltage 110, 110/rt3, 100, 100/rt3, 183.3/3, 183.3/rt3 V
Rated Burden 100VA/300VA/500VA
Class of Accuracy 0.2/0.5/3P
Rated Thermal Burden at line to ground vol. 1000VA (simultaneously 3 windings)
No. of Secondary 3 max
Rated Voltage factor 1.2 continuous & 1.5 for 30 sec
Wind Velocity 150 km/h
4 ABB
High Voltage Coupling Capacitors, type KN/KP
ABB offers mixed dielectric type coupling capacitors that cater to the needs of carrier communication.
Main features
Hermetically sealed with metal bellows High reliability – robust design ensures
cushion on top excellent surge withstand level
Protection against corrosion – all ferrous Low weight, compact and easy to install
parts and bottom stand are hot dip Ease of transportation – shipped in
galvanized
easy-to-assemble parts
Cost-effective due to optimal design
Dimensional drawing
Technical data
Parameter Rated System Voltage
66kV 132kV 220kV
Type KN 73N2 KN 145N2 KP 245N2
Rated Capacitance in pF 4400-8800 4400-13200 4400-8800
Rated Freq. in Hz 50/60 50/60 50/60
Rated Voltage factor 1.2 continuous & 1.5 for 30 sec
Wind Velocity 150 km/h
ABB 5
Additional data as per IEC:60186 and IS:3156 for Capacitor Voltage Transformers type WN/WP/WS and
Coupling Capacitors type KN/KP
CVT & Power Freq. Impulse Test Switching RIV Test Max. PD test Max. PD
CC Withstand Voltage Impulse Test Voltage RIV level Level Level
Voltage (1.2/50 Voltage
micro sec.) (250/2500
micro sec.)
Type Dry KV Wet KV peak KV Peak KV rms Micro KV rms PC
WN/WP/WS rms KV rms Volt.
& KN/KP
73 140 140 325 – – – 46/73 5/10
145 230/ 230/ 550/ – 78/ 2500/ 78/123 5/10
275 275 650 – 92 2500 92/145 5/10
245 460 460 1050 – 156 2500 156/245 5/10
420 630 630 1425 1050 267 2500 267/420 5/10
Note: The above data are not limiting values. Additional data will be provided on request.
Data and illustration are without engagement. We reserve the right to make changes in the course of technical developments.
1HYT800001-502/Rev.A,2005-06