You are on page 1of 2

Product data sheet SM6240630PR0003

Characteristics SM6 24kV AIS range protection circuit breaker


SF6 or vaccum unit

Main

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range of product SM6
Device short name DM 630A
Product or component type Circuit breaker
Width 750 mm
Technology type Air insulated switchgear cubicle
SF6 gas circuit breaker
Integral instant protection 12.5 kA 1 s
16 kA 1 s
20 kA 1 s
25 kA 1 s
Name of test Internal arc class AFL
Internal arc class AFLR
Network type AC
Network frequency 50/60 Hz
Rated voltage 24 kV
[In] rated current 630 A
[Icw] rated short-time withstand current 12.5 kA 1 s
16 kA 1 s
20 kA 1 s
25 kA 1 s
[Ui] rated insulation voltage 20...50 kV 50 Hz 1 min (rms)
[Uimp] rated impulse withstand voltage 60 kV peak
125 kV
95 kV
Measurement voltage limits 0...24 kV
Sensor type Current transformer 3 (optional)
Voltage transformer 3 (optional)
Number of cables 1 x 240 mm² per phase (bottom)
2 x 240 mm² per phase (bottom)
1 x 240 mm² per phase (top)
2 x 240 mm² per phase (top)

Complementary
Bus rated current 400 A
630 A
1250 A

Apr 30, 2018


1
[Uc] control circuit voltage Closing coil - 24...240 V DC
Opening coil - 24...240 V DC
Motor - 24...240 V DC
Product compatibility Relay (optional)
Flair 21D - fault passage indicator (optional)
Flair 22D - fault passage indicator (optional)
Flair 23DM - fault passage indicator (optional)
Amp 21D - ammeter (optional)
TH110 - thermal sensor (optional)
SC110 - universal intelligent controller (optional)
VIP 40 - relay (optional)
VIP 45 - relay (optional)
VIP 400 - relay (optional)
Thermal monitoring option Yes - SMD (ordered separately)
Arc fault detector option Yes - Vamp 121 (ordered separately)
Circuit breaker type SF1 type 1
SF1 type 2
SFset
Mounting mode Withdrawable
Fixed
Operating position Left-hand side - (B1)
Right-hand side - (A1)
Poles description 3P
Rated switching sequence O - 0.3 sec - CO - 15 sec - CO
O - 0.3 sec - CO - 3 min - CO
O - 3 min - CO - 3 min - CO
Charging time <= 15 s
Operating time <= 50 ms
Maximum breaking time <= 65 ms
Closing response time <= 70 ms
Mechanical durability M2 - 10000 cyclesoperation cycles
Electrical endurance class E2

Environment
Height 1600 mm
Depth 1220 mm
Standards GOST-R 52565 2006
IEC 62271-200 2012
Ambient air temperature for operation -5...40 °C
Ambient air temperature for storage -40...70 °C
IP degree of protection IP3x
Vibration resistance 0.5 gn horizontal class 2
0.4 gn vertical class 2
Operating altitude <= 1000 m
Pole distance 200 mm