Professional Documents
Culture Documents
Main
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range of product SM6
Device short name DM 630A
Product or component type Circuit breaker
Width 750 mm
Technology type Air insulated switchgear cubicle
SF6 gas circuit breaker
Integral instant protection 12.5 kA 1 s
16 kA 1 s
20 kA 1 s
25 kA 1 s
Name of test Internal arc class AFL
Internal arc class AFLR
Network type AC
Network frequency 50/60 Hz
Rated voltage 24 kV
[In] rated current 630 A
[Icw] rated short-time withstand current 12.5 kA 1 s
16 kA 1 s
20 kA 1 s
25 kA 1 s
[Ui] rated insulation voltage 20...50 kV 50 Hz 1 min (rms)
[Uimp] rated impulse withstand voltage 60 kV peak
125 kV
95 kV
Measurement voltage limits 0...24 kV
Sensor type Current transformer 3 (optional)
Voltage transformer 3 (optional)
Number of cables 1 x 240 mm² per phase (bottom)
2 x 240 mm² per phase (bottom)
1 x 240 mm² per phase (top)
2 x 240 mm² per phase (top)
Complementary
Bus rated current 400 A
630 A
1250 A
Environment
Height 1600 mm
Depth 1220 mm
Standards GOST-R 52565 2006
IEC 62271-200 2012
Ambient air temperature for operation -5...40 °C
Ambient air temperature for storage -40...70 °C
IP degree of protection IP3x
Vibration resistance 0.5 gn horizontal class 2
0.4 gn vertical class 2
Operating altitude <= 1000 m
Pole distance 200 mm