Fire inspection checklist

Passive systems
Construction and load bearing walls
Construction and load bearing walls, should meet the fire rating requirements as shown below.
Please submit test evidence according to NFPA 221 or ASTM E 119 and clarify that the intended
use of this material including the overall thickness and characteristics is as per approved FSSR
and NFPA.

Supporting more than one floor, columns, or other bearing walls


-
Supporting one floor only
Supporting a roof only -

Interior Bearing Walls

Supporting more than one floor, columns, or other bearing walls


-
Supporting one floor only
Supporting roofs only -
Columns
Supporting more than one floor, columns, or other bearing walls
-
Supporting one floor only
Supporting roofs only -

Beams, Girders, Trusses, and Arches

Supporting more than one floor, columns, or other bearing walls


-
Supporting one floor only
Supporting roofs only -
Floor-Ceiling Assemblies -
Roof-Ceiling Assemblies -

C-114 One Hour Fire Rated Intumescent Paint

MK-08 Two Hour Fire Rated Intumescent Paint

C-016A,Alt 01Fire Rated Sealant

Interior floor systems


Interior floor systems shall - depending on the areas to be located - meet the requirements of
Class I or Class II floors for critical heat flux.

Walls and ceilings surface


Walls and ceilings surface finishes spread of flame and smoke development shall meet the
requirements of Class A or Class B for spread of flame and smoke development

Fire rated doors


Fire rated doors - depending on the areas to be located – shall meet the requirements of NFPA
80 and NFPA 252.

Active systems
Sprinkler
Butterfly valve ,drain valve,water flow switch

Pump system and watertanks

Breeching inlets

Sprinkler Head

Hose reel system


Please verify that the system complies as per approved FSSR and NFPA
Approval of drawings
Fire hose valve
Fire hose cabinet

Fire hydrants system


Please submit documentation showing /verifying that the Fire hydrant system is in complies as
per approved FSSR and NFPA.
Approval of drawings

Data on fire pumps, amount of water storage and Emergency power system NFPA

Fire hydrants

Fire detection and alarm system

Please verify that the system is in complies as per approved FSSR and NFPA 72.
Data of type of detectors as well as Emergency or standby power system described in NFPA 70

Data on alarm system as well as the designed sound level

Smoke control system

MEP drawings showing the smoke control system design

Fire proof wrapping for pre insulated ducts

Design data on smoke extraction fans and fresh air inlets.

Fire Resistant Cable for Car Park Ventilation System

Fire Resistant Cable

carpark ventilation system

Exit signs and Emergency lighting

Please submit the latest MEP drawings showing the positioning of Emergency lighting

Data on Emergency or standby power system

Fire rated doors and door closers


Please submit the latest drawings showing Fire rated doors and Fire rated doors on auto closers
or door hold-opens close release.

Fire Exit Hardware. Please provide the location as well at data on the actual system of any door-
latching assembly incorporating an actuating member or bar that releases the latch bolt upon
the application of a force in the direction of egress travel.

Ventilation system
Location of the fire/smoke dampers.

Fire dampers

Duct works

Fire control room


Please submit the layout of the fire control room showing the positioning of the differed fire
control and information systems.
Other fire suppression systems
Please submit the latest MEP drawings showing other fire suppression systems as FM200 or
similar.
We also need design data these systems.
FM200 system

CO2 fire fighting extinguisher


fire blanket
A B C D
Approved Not Approved Approved as noted Approved as noted Date Engineer
No Resubmission Resubmission
Required Required Before
work can Proceed
Have

location and fire rading of Walls


location and fire rading of Walls
location and fire rading of Walls

location and fire rading of Walls


location and fire rading of Walls
location and fire rading of Walls

location and fire rading of Walls


location and fire rading of Walls
location and fire rading of Walls

location and fire rading of Walls


location and fire rading of Walls
location and fire rading of Walls
location and fire rading of Walls
location and fire rading of Walls

Have test Certificate of compliance

Product info

Have Certificate of compliance

No info
Details on False Ceiling Ground & First Floor - Paint is
declared non - (in) flammable.

location and fire rading of doors

MEP drawings showing the sprinkler system

Product info on water tanks

BS 5041-3-1975

Product info

MEP drawings showing the Hose Reel system


Product info
Product info

MEP drawings showing the Fire hydrants system

Product info

EN 54 Fire detection and fire alarm systems. Part 2 Control


and indicating equipment (Fire alarm control panel)
Part 4 Fire detection and fire alarm systems (Power supply
equipment) Part 5 Heat detectors. Point detectors. Part 7
Smoke detector. Point detectors using scattered light,
transmitted light or ionization. Part 11 Manual call point

Part 3 Fire alarm devices. Sounders and Part 17 Short circuit


isolators

MEP drawings showing the positioning of fans and inlets

UL Underwriters Laboratories
Sliding doors is use for fresh air inlets

BS 7846

BS 7846

EN 12101-3 Certificated

MEP drawings showing the positioning of Emergency lighting

No info

No info

No info

Drawings showing location of the fire/smoke dampers.

UL 555 classeified fire damper

Fire Propagation; Class 0 BS 476 Part 6 Surface Spread of


Flame; Class 1 BS 476 Part 7

No info
Product info
Test Certificated outdated

BSEN3
BS EN 1869: 1997
Missing

Please submit test evidence clarifying the fire raiding


Please submit test evidence clarifying the fire raiding
Please submit test evidence clarifying the fire raiding

Please submit test evidence clarifying the fire raiding


Please submit test evidence clarifying the fire raiding
Please submit test evidence clarifying the fire raiding

Please submit test evidence clarifying the fire raiding


Please submit test evidence clarifying the fire raiding
Please submit test evidence clarifying the fire raiding

Please submit test evidence clarifying the fire raiding


Please submit test evidence clarifying the fire raiding
Please submit test evidence clarifying the fire raiding
Please submit test evidence clarifying the fire raiding
Please submit test evidence clarifying the fire raiding

Please submit test evidence clarifying the 2 hour fire raiding

Please submit test evidence clarifying the 2 hour fire raiding


Please submit test evidence ASTM (UL) BS476, BS EN1366
and DIN 4102

Please submit test evidence according to NFPA 253 or ASTM E


648 and clarify that the intended use of this material is as per
approved FSSR and NFPA.
Please submit test evidence of used of material. Test
evidence shall be according to table A.10.2 in NFPA 101 and
please verify that the use of this material is as per approved
FSSR and NFPA.

Please submit test evidence according to NFPA 252 and as per


approved by FSSR and NFPA 80.

Please submit the latest MEP drawings showing waterflow


switches.

Data on fire pumps, amount of water storage and Emergency


power system NFPA 110

Please submit the Certificate of compliance

Please submit the Certificate of compliance (FM approval)

Please submit the Certificate of compliance

Please submit the Certificate of compliance

Data on fire pumps, amount of water storage and Emergency


power system NFPA 110
Please submit test evidence that the fireproof wrapping can
be use on pre insulated ductwork
Please submit test evidence according to NFPA 252 and as per
approved by FSSR and NFPA 80.

Please submit test evidence according UL.

Please submit test evidence according BS 476


Provide a valid certificate

Please submit test evidence according to BSEN3


Please submit test evidence according to BS EN 1869: 1997
Note
http://www.redbooklive.com/browse/displaycompany.jsp?partid=3&sectionid=19&companyid=364&productgroupid=843&
http://www.redbooklive.com/browse/displaycompany.jsp?partid=3&sectionid=24&companyid=949&productgroupid=1631

http://www.redbooklive.com/search/displaycompany.jsp?partid=3&sectionid=24&companyid=86&productid=0&productg

Meets UL and NFPA for instalations in floors and walls less than 3
hr fire rading
NFPA 101 requirem LIST OF MATERIALS - FIRE ENGINEERING DISCIPLINE

INTERIOR FINISHES, CONTENTS AND FURNITURE


FIRE RESISTANCE RATING ELEMENTS

ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, and ANSI/UL 263, Standard for Fire T
NFPA 221, Standard for High Challenge Fire Walls, Fire Walls, and Fire Barrier Walls.
FIRE RATED DOORS AND WINDOWS

Smoke doors
ANSI/UL 1784, Standard for Air Leakage Tests for Door Assemblies.

Fire Door s
NFPA 80, Standard for Fire Doors and Other Opening Protectives, except as otherwise specified in this Code.
NFPA 252, Standard Methods of Fire Tests of Door Assemblies; ANSI/UL 10B, Standard for Fire Tests of Door Assemblies;
ANSI/UL 10C, Standard for Positive Pressure Fire Tests of Door Assemblies;
NFPA 257, Standard on Fire Test for Window and Glass Block Assemblies; or ANSI/UL 9, Standard for Fire Tests of Window Asse
NFPA 288, Standard Methods of Fire Tests of Floor Fire Door Assemblies Installed Horizontally in Fire Resistance–Rated Floor Sy

Glazing in door
ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials, and ANSI/UL 263, Standard for Fire T

Fire protection–rated glazing shall be evaluated under positive pressure in accordance with NFPA 257, Standard on Fire Test for

PENETRATIONS AND FIRE STOPS


ASTM E 814, Standard Test Method for Fire Tests of Through Penetration Fire Stops,
or ANSI/UL 1479, Standard for Fire Tests of Through-Penetration Firestops,
at a minimum positive pressure differential of 0.01 in. water column (2.5 N/m2) between the exposed and the unexposed surfa

ASTM E 2307, Standard Test Method for Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale, Multi-story Appara
FOR FIRE BARRIER TO CURTAIN WALLS

ANSI/UL 555S, Standard for Smoke Damper


FOR SMOKE DAMPERS
CURTAINS AND CONTENTS (ATC and others)

Testing per NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films, applies to textiles and films u
- FIRE ENGINEERING DISCIPLINE BS 'Peer' Standard

BS 476 Fire tests on building materials and str

Pt.6:1989 Method of test for fire prop


Pt.7:1997 Method of test to determina
Pt.22:1987 Method for determination

BS 476 Fire tests on building materials and str

Pt.6:1989 Method of test for fire prop


Pt.7:1997 Method of test to determina
Pt.22:1987 Method for determination
BS 5438:1Flammability of textile fabrics when su
BS 5867-2Fabrics for curtains and drapes
BS 5438:1Flammability of textile fabrics when su
BS 5867-2Fabrics for curtains and drapes
BS 5852:1Assessment of the ignitability of upho
BS 4790:1Method for the determination of the e
BS 5287:1Assessment and labeling of textile floo

BS 4790:1Method for the determination of the e


BS 5287:1Assessment and labeling of textile floo

BS 4790:1Method for the determination of the e


BS 5287:1Assessment and labeling of textile floo

BS 4790:1Method for the determination of the e


BS 5287:1Assessment and labeling of textile floo

BS 4790:1Method for the determination of the e


BS 5287:1Assessment and labeling of textile floo

BS 5268 Structural use of timber.


ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials,
Pt.4:1978 Fire resistance of timber str
Sect.4.1: Fire resistance of timber mem
Pt.4:1990 Fire resistance of timber str
Sect.4.2: Fire resistance of timber stud

BS 476 Fire tests on building materials and str


Pt.11:1982 Method for assesing the he
Pt.20:1987 Method for determination
Pt.21:1987 Method for determination
Pt.22:1987 Method for determination
Pt.23:1987 Methods for determination

d in this Code.
Tests of Door Assemblies; BS 7175:1The ignitability of bedcovers and pillow
BS 7176:1Resistance to ignition of upholstered f
rd for Fire Tests of Window Assemblies. BS 7177:1Resistance to ignition of mattresses, d
n Fire Resistance–Rated Floor Systems BS EN 102Furniture - Assessment of the ignitabil
Pt.1:1994 Ignition source: smouldering
Pt.2:1994 Ignition source: match flame

ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials,

PA 257, Standard on Fire Test for Window and Glass Block Assemblies.
BS 476 Fire tests on building materials and str
Pt.24:1987 Methods for determination
Pt.31:1983 Methods for measuring sm

xposed and the unexposed surface of the test assembly. BS 476 Pt.20:1987 Method for determination

ediate-Scale, Multi-story Apparatus.


ms, applies to textiles and films used in a hanging configuration.

BS 5852:1Assessment of the ignitability of upho


s on building materials and structures.

9 Method of test for fire propagation for products.


7 Method of test to determinate the classification of the surface spread of flame of products.
87 Method for determination of the fire resistance of non-loadbearing elements of construction.

s on building materials and structures.

9 Method of test for fire propagation for products.


7 Method of test to determinate the classification of the surface spread of flame of products.
87 Method for determination of the fire resistance of non-loadbearing elements of construction.
bility of textile fabrics when subjected to a small igniting flame applied to the face or (...)
or curtains and drapes
bility of textile fabrics when subjected to a small igniting flame applied to the face or (...)
or curtains and drapes
ent of the ignitability of upholstered seating by smouldering and flaming ignition sources.
for the determination of the effects of a small source of ignition on textile floor coverings.
ent and labeling of textile floor coverings

for the determination of the effects of a small source of ignition on textile floor coverings.
ent and labeling of textile floor coverings

for the determination of the effects of a small source of ignition on textile floor coverings.
ent and labeling of textile floor coverings

for the determination of the effects of a small source of ignition on textile floor coverings.
ent and labeling of textile floor coverings

for the determination of the effects of a small source of ignition on textile floor coverings.
ent and labeling of textile floor coverings

al use of timber.

8 Fire resistance of timber structures.


Fire resistance of timber members.
0 Fire resistance of timber structures.
Fire resistance of timber stud walls and joisted floor constructions.

s on building materials and structures.


82 Method for assesing the heat emission from building materials.
87 Method for determination of the fire resistance of elements of construction.
87 Method for determination of the fire resistance of loadbearing elements of construction.
87 Method for determination of the fire resistance of non-loadbearing elements of construction.
87 Methods for determination of the contribution of components to the fire resistance of a structure.

ability of bedcovers and pillows by smouldering and flaming ignition sources.


ce to ignition of upholstered furniture for non-domestic seating (...)
ce to ignition of mattresses, divans and bed bases.
e - Assessment of the ignitability of upholstered furniture
4 Ignition source: smouldering cigarette.
4 Ignition source: match flame equivalent.

s on building materials and structures.


87 Methods for determination of the fire resistance of ventilation ducts.
83 Methods for measuring smoke penetration through doorsets and shutter assemblies.

87 Method for determination of the fire resistance of elements of construction.


ent of the ignitability of upholstered seating by smouldering and flaming ignition sources.