Professional Documents
Culture Documents
Relays have 3 current inputs and are housed in E6 cases. ¡ 15kV pilot isolation option
¡ Easily reconnected as either Solkor Rf or Solkor R
¡ Pilot Supervision schemes available
¡ Remote end injection intertripping via pilot
cores available
¡ Test points at relay fascia
¡ Option of 15kv pilot isolation
¡ Option of pilot supervision
siemens.com/reyrolle
15kV Isolation Overcurrent Guard
The Solkor R/Rf relay has an insulation level of 5kV between The Solkor relay can be used with an Overcurrent Guard
pilot connections and the local ground to withstand relay to avoid operation for damaged pilots during normal
voltages induced on the pilot cable due to coupling with the load levels.
fault current and to withstand differential ground voltages
caused by the flow of fault current. Experience has shown The 7SR11 numeric relay from the Argus range can connect
that 5kV insulation is usually adequate for most distribution to the same CT’s and will have negligible additional AC
feeders. burden. The numeric relay also provides the traditional
Solkor scheme with waveform recording functions, data
For higher voltage systems where feeders may be longer storage and remote communications facilities.
and fault levels higher, an additional external isolation
transformer is available for use with the relay in Rf mode to
increase the voltage withstand to 15kV. Relays and components
5kV systems may be suitable for higher voltage systems Model Ordering Notes
where fault levels are low or feeder lengths are short. One code
isolation transformer is fitted at each end of the pilot circuit.
Feeder Solkor R/Rf 7PG211 0.5A, 1A,
differential 2A, 5A
Pilot supervision Pilot 15kV isolating 7PG112 Rf mode
isolation transformer
Communication via the pilots between the relay pair is
Guard relay Argus 7PG2170
essential for correct operation of the Current Differential
/ 7SR1
protection system.
Pilot Supply transf / 7PG2120 5kV
Additional external Pilot Supervision equipment can be supervision rectifier, B22 supply 7PG2134 scheme
supplied to detect pilot cable open circuit which can lead send end supvn relay
to protection operation or short circuit pilots which will (PSSE) 7PG2120 15kV
greatly reduce the sensitivity of the relays under 7PG2132 scheme
subsequent fault conditions. Pilot Receive / repeat 7PG2144 5kV
supervision B74 + B75 scheme
Pilot supervision will not block relay operation but will receive end
provide an alarm. The supervision equipment is available (PSRE) Receive B75, 7PG2154 15kV
to suit the 5kV or 15kV insulation level of the scheme. receive repeat B74 7PG2164 scheme
Siemens Protection For enquires please contact our Article No. EMDG-B10076-00-76GB Printed in the UK
Devices Limited Customer Support Center
Subject to changes and errors. The information given in this document only contains general descriptions and / or
P.O. Box 8 Phone: +49 180/524 8437 performance features which may not always specifically reflect those described or which may undergo modification
North Farm Road (24hrs) in the course of further development of the products. The requested performance features are binding only when
Hebburn Fax: +49 180/524 24 71 they are expressly agreed upon in the concluded contract.
Tyne & Wear E-mail: support.ic@siemens.com
NE31 1TZ www.siemens.com/protection
United Kingdom