With the rapid advance in medical technology, hospitals, medical clinics and laboratories increasingly
rely on sophisticated electronic devices for diagnosis, treatment and monitoring. This reliance, in
turn, demands a high degree of power quality and reliability to prevent disruption of mission-critical
operations and procedures. Power quality disturbances can be caused by a range of internal and
Even a external phenomena and often re-occur because the location and nature of the event is not well

small power understood or identified. Continuous monitoring can detect deterioration in power quality before
equipment problems arise.
interruption
can cause A leading hospital, Trillium Health Centre chose the Signature
System to protect mission-critical systems and diagnostic
critical equipment.
equipment
failure— Signature System Benefits
Signature The Signature System is a key element of the uninterruptible power supply (UPS) system for a

System quickly leading hospital’s mission-critical systems, particularly its Angio Suite-Cath Lab. The Cath Lab
requires 125 Amps RMS (peak draw of 380 Amps) per phase during high mVA angioplasty x-rays.
identifies Clean, continuous power is a requirement of this crucial diagnostic equipment.

the location Although a Piller UPS system was installed to protect the x-ray systems, the Signature System was
employed as a proactive verification and maintenance resource. The Signature System included
and nature three key monitoring points throughout the hospital to monitor the utility supply at the UPS input,
of the problem the output of the critically important UPS, and the downstream input to the Cath Lab.

so it can be The Signature System was selected for its comprehensive power quality monitoring capabilities,
including its ability to capture and pinpoint difficult-to-find power quality problems that can result
rectified in costly downtime and equipment erosion. Plus, the real time response of the Signature System

immediately and its web-browser interface enables the customer to address problems quickly and prevent
them from recurring.
Signature System™
Results
When a lightning strike triggered a fault on the utility feed causing a momentary outage of the Cath
Lab, the Signature System identified the location and nature of the problem. The Signature System
revealed that there was indeed an interruption of the utility supply but the UPS provided a “clean”
supply to the load and operated properly. The data provided by the Signature System enabled the
customer to determine that the x-ray EPO (Emergency Power Off) switch was fed from emergency
— not UPS — power. Inspection revealed a wiring error that was immediately corected. As a result,
Trillium is looking to expand their Signature System application and incorporate it within their IT network.

DataNodes: monitor voltage & current,


one DataNode each for input and output
for 3-phase power

Voltage and Current connectors from


panels. Enclosure is 36”x36”x12”
Nema 4/12 box

InfoNode: web-based communication


device that accomodates up to 32
DataNodes with a 4-port hub for
networkability

ONEAC Power conditioner for system


protection

The Signature System at Trillum


monitors incoming and

outgoing power from a UPS

supplying critical power to the


Cath Lab X-Ray System—a

mission critical environment.

1-800-372-6832 1-800-554-4767
SM

www.dranetz-bmi.com www.electrotek.com
A WPT Company

tel. +1.732.287.3680 fax +1.732.248.1834 tel. +1.865.470.9222 fax +1.865.470.9223

©2001 Dranetz-BMI and Electrotek Concepts. All rights reserved. Printed in the United States. Specifications subject to change without notice.
AnswerModule™, DataNode®, InfoNode®, and Signature System™ are trademarks of Dranetz-BMI and Electrotek Concepts.

You might also like