You are on page 1of 1

DESCRIPTION

1. CODE / STANDARD: Base on API Std 650-Add.4 Dec. 2005


2. NOMINAL CAPACITY / NET WORKING CAPACITY: 289 m³/ 264 m³
3. TANK SIZE: DIAMETER: ±6000mm TOTAL HEIGHT: ±10230mm MAX. LIQUID HEIGHT: ±9345mm
Handrail 4. PRODUCT STORED: WATER
5. CORROSION ALLOWANCE (mm): SHELL: 0 BOTTOM: 0 ROOF and STRUCK: 0 STRUCTURALS: 0
6. SHEEL DESIGN: APPENDIX A JOINT EFFICIENCY: 0,70
V1
M3 L3 7. ROOF DESIGN: § 3.10 SLOPE: 1/5 FRANGIBLE JOINT: No
Roof Plates Thk. = 5mm 8. MAX. DESIGN PRESSURE ( *) +0.60/-20 kPa WORKING PRESSURE: Atmospheric
Upper Ring 9. DESIGN TEMPERATURE: 40°C WORKING TEMPERATURE:
Spiral Stairway
L90 X 90 10. EARTHQUAKE DESIGN: API 650-Add. 4 Dec. 2005
12. WIND LOADS: Defined later on
13. WELD EXAMINATION / LIQUID PENETRANT: API STANDARD 650
MATERIAL SPECIFICATION / TYPES OF INSPECTION DOCUMENTS
885

1630

Max. Water Level 5th Sheel Course Thk.= 5mm 3.1


1. SHEEL PLATES: S235JR-EN 10025-2-2004 MAT.No.1.0038
2. ROOF PLATES: S235JR-EN 10025-2-2004 MAT.No.1.0038 3.1
3. BOTTOM PLATES: S235JR-EN 10025-2-2004 MAT.No.1.0038 3.1
1850

4th Sheel Course Thk.= 5mm 4. MAIN STRUCTURES: S235JR-EN 10025-2-2004 MAT.No.1.0038 3.1
5. SECONDARY STRUCT: S235JR-EN 10025-2-2004 MAT.No.1.0038 2.2 EN 10204-2004
6. FLANGES: ASTM A 150/ANSI B16.5 3.1
7. PIPES: ASTM A 106 Gr. B/ANSI B36.10 3.1
8. BOLTS: ASTM A 193 Gr.B7 - GALVANIZED
1850

3.1
10230

3rd Sheel Course Thk.= 5mm


Vol.= 289m³/ 264m³ 9. NUTS: ASTM A 194 Gr.2H - GALVANIZED 3.1
9345

10. GASKETS: AFM (Asbestos Free Material) Similiar to 2.2


C1 11. PAINTING:
N1
(*) ONLY FOR VENTILATION SYSTEM DESIGN
2450

2nd Sheel Course Thk.= 5mm


N3
M1 N4 L2 L1
2450
1st Sheel Course Thk.= 8mm
Slope.1% TOTAL WEIGHT= app. 18 Ton
N2
S1 N5 Bottom Plates Thk. = 6mm
QUANTITY x 1
∅NOMINAL= ±6000
NOT BINDING FOR EXECUTION
Handrail Spiral Stairway
N1
N2
0° NOTES: - LOCATION OF NOZZLES MUST BE DEFINED LATER ON
M1 (*)- DIMENSION OF NOZZLES MUST BE CONFIRMED LATER ON
N5
APPURTENANCES
V1 1. STAIRWAY STYLE: SPIRAL STAIRWAY: LADDER: HANDRAIL:
N4
2. NO. AND SIZES OFF SHEEL MANHOLES (SEE FIG.: 3-4A/B AND TABLES 3-3 AND 3-4) 2∅24"- Opposite Diam.
3. NO. AND SIZE OF ROOF MANHOLES (SEE FIG.: 3-13 AND TABLES 3-13) 1∅24"- See Scheme
4. SHEEL NOZZLES (SEE FIGURES 3-4B, 3-5 AND 3-7 AND TABLES 3-6 TO 3-8)
N3 NOZZLES FLANGES
270° 90° MARK QUANT. SIZE SERVICE NOTES
TYPE TYPE
N1 1 6" (*) SGL ASME B16.5/150# Overflow Outlet
N2 1 6" (*) SGL ASME B16.5/150# Drain
L2 L3 N3 1 6" (*) SGL ASME B16.5/150# Inlet
N4 1 6" (*) SGL ASME B16.5/150# Outlet-Demi Feed Pumps
M2 N5 1 10"(*) SGL ASME B16.5/150# Outlet-Fire Fighting Pumps Rev. Date Issued Checked Released Details of Revision
S1 1 4" (*) SGL ASME B16.5/150# Spare With Blind FL Handling Instruction No. of Appendix Format
S1 SGL
CONFIDENTIAL N.A. (A2)
L1 1 3" (*) ASME B16.5/150# Level Transmitter
Project
L2 1 21/2"(*) SGL ASME B16.5/150# Level Switch KKS
M1 L3 1 3" (*) SGL ASME B16.5/150# Level Switch - LSA ++ PLTG KAMPUNG SATU TARAKAN - KALIMANTAN TIMUR UGA
180°
C1 Date Name Scale
Partial Document No.
000
L1 Issued Title
Checked
5. ROOF NOZZLES, INCLUDING VENTING CONNECTION (SEE FIGURES 3-14, 3-5 AND 3-15 AND TABLES 3-16 TO 3-17) Released
RAW WATER TANK - CAP. 289 m³
SPECIFICATION DRAWING
PLAN VIEW
NOZZLES FLANGES
MARK QUANT. SIZE SERVICE NOTES
TYPE TYPE UGA 01
C1 1 - - ASME B16.5/150# LI-Level Indicator Acc. Sub-Supplier
V1 2 6" - Vent With Mesh Anti Bird Document-No. Sheet of sheet Revision
M1 2 24" - Sheel Manhole PK1527 - DWG - 010264 1 1 01
M2 1 24" - Roof Manhole