6 Surge arresters
Fig. 10-34
Current-voltage characteristic of a metal oxide resistor; a Lower linear part, b Knee
point, c Strongly non-linear part, d Upper linear part (“turn up” area), A Operating point
(continuous persistent voltage)
The protective level of the MO arrester is set by its residual voltage UP. The residual
voltage is defined as the peak value of the voltage at the terminals of the arrester when
a surge current flows. A surge current with a front time of about 1 µs, a time to half-
value of up to 10 µs and a current of up to 10 kA represents very steep overvoltage
waves, and the associated residual voltage is comparable to the front sparkover
voltage of spark-gapped arresters.
482
10
Fig.10-35
Cutaway view (principle
design) of a metal oxide surge
arrester, type POLIM-H
483
Fig.10-36
Arrester selection for a low-resistance
earthed network (cE = 1,4) in range II (Um
p.u.
≥ 245 kV) as per DIN EN 600099-5 (VDE
0675 Part 5) 4 d
a maximum power frequency Uwl
U
conductor-ground voltage in the
normally operating network 3 Uws
(1 p.u. = peak value)
b peak value of the maximum Ups
temporary power frequency 2
conductor-ground voltage at earth b
➝
485
Table 10-13
Recommended values for MO arresters according to the continuous operating voltage
Uc and the associated rated voltage Ur
After specifying the continuous operating voltage and the rated voltage of the arrester
that is to be used, selection is based on the energy-absorption capability required by
the system conditions (rated discharge current and line discharge class). The following
selection recommendation for rated discharge current can be set as a general
guideline:
Distribution networks of up to 52 kV
– sufficient under standard conditions 5 kA
– at higher lightning intensity, cable units,
capacitors, specially important analogues 10 kA
– specially high lightning loads 20 kA
Transmission networks of up to 420 kV 10 kA
Transmission networks over 420 kV 20 kA
486
Table 10-14
Guidance values for the protection range of MO arresters
24 80 125 31)/152)
123 350 550 24
420 900 1425 32
1)
Overhead line with timber masts (without grounding)
2)
Overhead line with grounded cross-arms
The ABB travelling wave program for testing larger switchgear installations can be used
to calculate the temporal course of the voltage at all interesting points of the installation.
In overhead lines with cable feed, the travelling wave through the cable with
overvoltages must be calculated by reflection in spite of the depression. Arrester A1 is
to be provided for protection of the cable in short cable units (lk ≤ 5 m) and arrester A3
for protection of the transformer, see fig. 10-37. however, if lk > 5 m, the cable must be
protected on both sides with arresters A1 and A2. In this case, arrester A3 can only be
omitted with the transformer if the protection range of arrester A2 is greater thanl1.
487
lk l1
Fig.10-37
Overvoltage protection of the cable link of overhead lines, lK: length of cable unit,
l1: distance cable / transformer, A1 & A2 arresters for protection of the cable,
A3 arrester for protection of the transformer
488