Project = DESIGNER

slab panel = DATE

Cantilever length, L1 = 1740 mm brick load


Fcu = 28 N/mm2
Fy = 500 N/mm2 UDL
Slab Thickness = 150 mm
SDL = 0.8 kN/m2 distance of point load, x
Live Load = 1.5 kN/m2
brick wall on L2 (Y/N) : Y Wall on L1
x= 1700 mm yes/no : N
brick thickness = 150 mm no. = 2
brick wall height = 500 mm height = 1200 mm
Brick load length, L2 = 19217 mm

Ultimate floor load = 8.56 kN/m2 K= 0.05089176


brick load = 1.8 kN/m 2.52 z= 103 mm
As min = 195 mm2/m
UDL = 8.56 kN/m As = 383 mm2/m
point load = 2.52 kN
383
Shear at support, V = 17.4144 kN 195
moment, m = 17.24213 kNm
As min = 195 mm2/m
As req. = 383 mm2/m
TOP H 10 @ 200 ok As prov. = 393 mm2/m
BOT H 10 @ 250 ok As prov. = 314 mm2/m

transverse
bars H 10 @ 200 ok As prov. = 393 mm2/m

fs = 305.1 0.28559933
M.F = 2.0 1.08692458
M.F (Comp) = 1.09 Adjusted bas
DEFLECTION
allowable L/D = 13.2 X Deflection Fail m.f = 2.141628
13.1567377 13.15674
actual L/D = 15.8
L1

Y
L2 N

kN kN/m2
DL = 3.6 11.83896 0 0
d= 110 1.8 1.8

103.3817

75
100
125
150
175
200
250
300

5 78.53982 392.6991
4 78.53982 314.1593

5 78.53982 392.6991

K udl = 0.25 M udl = 12.95813


K point = 0.33 M point = 4.284
Adjusted basic ratio = 6.578369
brick

As req. = 383 mm2/m


As req. = 383 mm2/m