DaØ
DØ
a
Pre cold-drawn
Material
l Bellow : 1.4541 (SS 321)
l Type 7119 00X up to DN150
l Internal sleeve : 1.0305/1.0319 (carbon steel)
l Type 7117 00X from DN200 up
l Flange Connection :
l Order text : 7119 00X DN ../PN ../ax ../Bl ..
DIN PN16/25/40 , ANSI 150 L5 , JIS 10k/20k
L1 = max.2 X DN + 2 (mm) DN L1 L2 L3
L2 = 0,7 X L3 (mm) mm mm mm
L3 = 400 DN (mm) 80 + ∆/2 1 750 2 500
40
50 100 + ∆/2 1 950 2 800
65 130 + ∆/2 2 250 3 200
FP FP
80 160 + ∆/2 2 500 3 550
100 200 + ∆/2 2 800 4 000
L3 L3 L2 L1 L1 L2 L3 L3 2 125 250 + ∆/2 3 100 4 450
150 300 + ∆/2 3 450 4 900
200 400 + ∆/2 3 950 5 650
Note = FP : Fix point
= Previous Type 307/224 250 500 +∆/2 4 400 6 300
*last updated 03/16
139 Soi Nuanchan 34, Nuanchan Road, Nuanchan, Buengkum, Bangkok 10230
Tel : 02 792 9333 Fax : 02 946 1755-6 Email : sales@alphagroup.co.th www.alphagroup.co.th
32
AXIAL EXPANSION JOINT
WITH INTERNAL SLEEVE, PRE COLD-DRAWN,SELF-RELEASING
TYPE 711900X/711700X
Installation Instructions
Temperature Difference (°C)
50 100 150 200 250
220
200 300
350
400
450
500
100
50
Length of Pipeline (m)
40
30
20
10
5
10 20 30 40 50 100 200 300 400 500 800
Expansion of Pipeline (mm)
Pipe Guides
Align pipeline along axis in all directions. Assure adequate distance if one single axial expansion joints is not able to compensate the
between pipes as indicated in fig. 1. and 2. Main anchor points have whole expansion of the pipe. Round steel shackles according to
to be installed at bends. A gradient must be provided for drainage. DIN 3570 without limitation stops are not suitable as anchor points
to avoid longitudinal movement of the pipe. Anchor points must be
Pipe Supports capable to support tractive forces if the pipe works under vacuum.
Sliding or roller bearings are the safest type of pipe supports to
protect the lines from buckling and lifting. Filling of the System
Spring hangers and spring supports are not to be considered as Anchor points and supports must be fixed in position before the
pipe supports for axial expansion joints. system is filled and pressure tested. The permissible test pressure of
the expansion joints must not be exceeded during the pressure test.
Anchor Points
Each section of the pipe to be compensated must be fixed between Movement Capacity
two anchor points. Only one expansion joint may be installed The maximum permissible movement capacity is marked on the
between any two anchor point. expansion joint. This value should not be fully used if the
Main anchor points must be provided at bends. temperature fluctuate very frequently
These have to be designed for the deflection force and the pressure (see fatigue diagram in the expansion joints brochure).
reaction force of the expansion joint plus the friction forces of the The expansion joint has to be installed according to the example
pipe supports shown in fig. 1 if the expansion joint has to absorb lateral movements.
Intermediate anchor points and expansion joints between them The maximum permissible lateral movement capacity shown in the
have to be provided in long line sections expansion joints brochure must not be exceeded.
*last updated 03/16
139 Soi Nuanchan 34, Nuanchan Road, Nuanchan, Buengkum, Bangkok 10230
Tel : 02 792 9333 Fax : 02 946 1755-6 Email : sales@alphagroup.co.th www.alphagroup.co.th
33