Air Insulated Compact Substations

Albano M. 1*, Haddad A. 1, Griffiths H.1, Coventry P.2


1
Cardiff University, U.K., *albanom@cf.ac.uk
2
National Grid, U.K.

Abstract - In this work, a 400kV compact substation layout is proposed adopting the lower
IEC Basic Insulation Level and Switching Impulse Level, and consequently, reduced
clearances. Simulation studies using EMTP are performed to evaluate the lightning and
switching performance of the proposed compact substation using different surge arrester
locations and ratings. Further proposals for compaction are investigated through the
introduction of innovative high voltage equipment.

SUMMARY

The increase in electricity demand and In order to investigate voltage stresses that can
difficulties with obtaining land for new be experienced by substation equipment in a
developments introduces the challenge of conventional and compact layout, various
building new compact substations with higher switching and lightning simulations were
voltage ratings on existing sites. The adoption performed using EMTP software using a
of Gas Insulated Substations (GIS) permits a typical 400kV air insulated substation.
significant reduction in substation area. A number of new compact and innovative
However, the growing concern of climate solutions for high voltage plant are proposed
change makes this solution less attractive by manufacturers to include disconnecting
because of the known greenhouse effect of SF6. circuit breakers, integration of surge arrester
The aim of this research is to evaluate the within plant and non-conventional instrument
reduction in footprint of transmission transformers.
substations using air-insulated designs. In this study, four compact substation layouts
In this paper, the following options for were considered. Each successive compact
compaction are investigated; (i) the adoption of layout involves an additional step of
minimum clearances according to IEC 60071, compaction, using the conventional substation
taking advantage of modern overvoltage layout as the reference case.
protective devices, and (ii) the use of
innovative high voltage equipment such as the Conclusion
circuit breaker disconnector and non Overvoltage studies of a compact substation
conventional instrument transformers. design based on IEC minimum clearances
demonstrate that the application of surge
Substation Compaction arresters reduces successfully the overvoltages
IEC 60071 includes a range of Basic Insulation in the substation to below the selected
Level (BIL) and Switching Impulse Level Lightning and Switching Impulse Withstand
(SIL) values for 400kV systems. It is possible Voltages.
to adopt the lower values if ZnO surge arresters A review of compact HV substation technology
were applied to control overvoltage levels. has been carried out, and a number of compact
Consequently, phase-to-phase and phase-to- solutions have been identified. It is shown that
ground clearances can be reduced in the application of combinations of these
comparison with conventional substations used solutions to a standard 400kV switch-bay
by utilities. indicates that a reduction of up to 52% in
ground area can be achieved.