Low-voltage electrical installations -


Part 5-559: Selection and erection of electrical equipment -
Luminaires and lighting installations

To be completed Errichten von Niederspannungsanlagen -


Teil 5-559: Auswahl und Errichtung
elektrischer Betriebsmittel -
Leuchten und Beleuchtungsanlagen

This draft amendment FprAA, if approved, will modify the Harmonization Document FprHD 60364-5-559:2011; it
is submitted to CENELEC members for formal vote.
Deadline for CENELEC: 2011-12-02.

It has been drawn up by CENELEC TC 64.

If this draft becomes an amendment, CENELEC members are bound to comply with the CEN/CENELEC Internal
Regulations which stipulate the conditions for implementation of this amendment on a national level.

This draft amendment, was established by CENELEC in three official versions (English, French, German).

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of
which they are aware and to provide supporting documentation.

Warning : This document is not a Harmonization Document. It is distributed for review and comments. It is
subject to change without notice and shall not be referred to as a Harmonization Document.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Management Centre: Avenue Marnix 17, B - 1000 Brussels

© 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Project: 23624 Ref. No. FprHD 60364-5-559:2011/FprAA:2011 E


FprHD 60364-5-559:2011/FprAA:2011 –2–

1 Foreword
2
3 This draft amendment to the draft Harmonization Document FprHD 60364-5-559:2011 was prepared by
4 CLC/TC 64 "Electrical installations and protection against electric shock". It contains common modifications
5 to 64/1805/FDIS (future IEC 60364-5-55, Ed. 2) and is submitted to the formal vote.
6
7 If approved, this draft amendment will be merged together with FprHD 60364-5-559:2011 and both drafts will
8 be published as one single document, i.e. HD 60364-5-559:201X (based on IEC 60364-5-55:201X, modified),
9 with the implementation dates of this FprAA.
10
11 The following dates are proposed:
12
• latest date by which the existence of (doa) dor + 6 months
this document has to be announced
at national level
• latest date by which this document has (dop) dor + 12 months
to be implemented at national level
by publication of an identical
national standard or by endorsement
• latest date by which the national (dow) dor + 36 months
standards conflicting with this document (to be confirmed or
have to be withdrawn modified when voting)
13
14 Annexes ZA to ZC have been added by CENELEC.

15 __________
16
–3– FprHD 60364-5-559:2011/FprAA:2011

17 Text of FprAA to FprHD 60364-5-559

18
19 559.3 General requirements for installations
20 Replace note 2 by:
21 NOTE 2 Concerning the correct selection of the protection and control devices, information about the currents (starting current,
22 harmonics, leakage current, primary ignition current, etc.) generated by the lamps should be provided.

23 Add Annexes ZA to ZC as follows.


FprHD 60364-5-559:2011/FprAA:2011 –4–

24 Annex ZA
25 (normative)
26
27 Normative references to international publications
28 with their corresponding European publications
29
30 NOTE This annex will be completed once HD 60364-5-559 and FprAA are merged to be published as one single document.
–5– FprHD 60364-5-559:2011/FprAA:2011

31 Annex ZB
32 (normative)
33
34 Special national conditions
35
36 Special national condition: National characteristic or practice that cannot be changed even over a long
37 period, e.g. climatic conditions, electrical earthing conditions.
38
39 NOTE If it affects harmonization, it forms part of the Harmonization Document.
40
41 For the countries in which the relevant special national conditions apply these provisions are normative, for
42 other countries they are informative.
43
Country Clause Special national condition
UK 559.5.1 In the UK one of the following is also acceptable.
a) A ceiling rose to BS67
b) A luminaire supporting coupler to BS6972 or BS7001
c) A batten lamp holder or a pendant set to BS EN 60598
d) A luminaire to BS EN 60598
e) A suitable socket-outlet to BS 1363-2, BS546 or BS EN 60309-2
f) A plug-in lighting distribution unit to BS5733
g) A connection unit to BS 1363-4
h) Appropriate terminals enclosed in a box complying with BS 4662
DK 559.5.1 In Denmark, a luminaire supporting plug and socket-outlet system in accordance with
Information sheet, Electrical equipment no. 16/09 (Meddelelse el-materiel nr. 16/09) is
used.
DK 559.5.3 In Denmark if no information is given in the luminaire manufacturer’s information sheet
regarding the current carrying value of the through wiring in the luminaire depending of
the installation method, the biggest fuse allowed up-stream in the installation is 10A,
2
which on the safe side corresponds to the current carrying capacity for a 1,5 mm Cu
conductor
DK 559.5.3 In Denmark the third paragraph is replaced by the following requirement:
Cables for through wiring in luminaires prepared for through wiring but not delivered by
the manufacturer, shall be selected in accordance with the manufacturer’s instruction
sheet.
NOTE In accordance to EN 60598-1 if special cables or sleeves, e.g. due to high temperatures,
are necessary, the through wiring shall always be factory assembled.
FprHD 60364-5-559:2011/FprAA:2011 –6–

Country Clause Special national condition


DE 559.10 In Germany, Table A.1 of EN 60598-2-13:2006 is included for information.

DE Annex In Germany, Table B.1 apply.


B Table B.1 – Selection of luminaires and lamp controlgear according to the location and
surface of installation [ for Annex B; Germany; Clause 559.4 ; There is a use of the
following selection]
–7– FprHD 60364-5-559:2011/FprAA:2011

Country Clause Special national condition


DE Annex In Germany, Table B.2 applies.
B Table B.2 – Explanation of additional symbols used for luminaires and controlgear for
lamps
Luminaires with fluorescent lamps suitable for installation in and
on equipment, e.g. furniture, as specified in DIN VDE 0710-14
"Luminaires for furniture".

Provided one of the types of mounting stated by the manufacturer


is applied (see Table B.3) such luminaires may be fixed on
equipment
consisting of materials comparable to non-combustible materials,
heavily or normally inflammable building materials even such
materials
are coated, painted or veneered.
Luminaires with limited surface temperature, suitable for
installation in or on equipment, e.g. furniture, as specified in DIN
VDE 0710-14 "Luminaires for furniture".

Provided one of the types of mounting stated by the manufacturer


is applied (see Table B.3) such luminaires may be fixed on
equipment consisting of materials the fire resisting capability of
which is not known and on surfaces which are coated, painted or
veneered.
Independent lamp controlgear, which may be fixed directly on non
combustible, heavily or normally inflammable building materials.
Such lamp controlgear may not reach a surface temperature
exceeding 130 °C.
Independent lamp controlgear which may be fixed also in and on
equipment (furniture). The materials of the equipment may be
coated, painted or veneered and their fire resistant capability
must not be
known. Such lamp controlgear may not reach a surface
temperature exceeding 110 °C.
Type tested luminaires suitable for locations with explosion risk.
FprHD 60364-5-559:2011/FprAA:2011 –8–

Country Clause Special national condition


DE Annex In Germany, Table B.3 applies.
B Table B.3 – Explanation of additional symbols used for the mounting of luminaires

marked with the symbols or

44
45
–9– FprHD 60364-5-559:2011/FprAA:2011

46 Annex ZC
47 (informative)
48
49 A-deviations
50
51 A-deviation: National deviation due to regulations, the alteration of which is for the time being outside the
52 competence of the CENELEC national member.
53
54 This Harmonization Document does not fall under any Directive of the EC.
55
56 In the relevant CENELEC countries these A-deviations are valid instead of the provisions of the
57 Harmonization Document until they have been removed.
58
59 Add the following A-deviations:

Country Clause Deviation

60 NOTE National committees are invited to add their A-deviation if needed.