Professional Documents
Culture Documents
This is the procedure for calculating the proper humidification requirements for any application.
The procedure is outlined in the calculation form below. However, should you need assistance of any kind,
call Aprilaire tech support at 800-334-6011.
NOTE: If refrigerated cooling is in operation simultaneously with humidifier, the humidifier(s) must have capacity
to replace the moisture removed from the air by the cooling equipment. Use latent heat loads off data plate.
A general guideline is to add 4 lbs./hr. of moisture per ton of cooling to the humidification requirement
calculated above.
Printed in U.S.A.
Psychrometric Chart
1015 E. WASHINGTON AVE. • MADISON, WI 53703 • PHONE: 800/334-6011 • FAX: 608/257-4357 • www.aprilairecontractor.com
PSYCHROMETRIC CHART EXAMPLE:
70° air and 30% R.H. = 0.005 lbs. moisture per lb. of air.
• Determine cubic footage to be humidified from fresh air make-up, exhaust air,
or building value, whichever is larger. (See step 1 on reverse side.)
• Chart cannot be used if cooling unit operates simultaneously with humidifier.
(See note on reverse side.)