Datasheet
For part no. and prices: see pricelist
VITOCAL 200-S Type AWB 201.B VITOCAL 200-S Type AWB-AC 201.B
Heat pump with electric drive in split design with external and Equipment level as per type AWB 201.B, with additional active
internal unit. cooling function plus integral instantaneous heating water
For central heating and DHW heating in heating systems. heater.
■ Low operating costs through high COP (COP = Coefficient of Per- ■ Easy to use Vitotronic control unit with plain text and graphic display
formance) to EN 14511: Up to 4.6 (air 7 °C/water 35 °C) and up to ■ Highly convenient through reversible system that enables heating
3.5 (air 2 °C/water 35 °C). Output control and DC inverter for high and cooling.
efficiency in partial load operation.
■ Maximum flow temperature: Up to 55 °C at -15 °C outside temper-
ature (with reduced output). EHPA quality seal as proof of the COP for subsidy according
■ Weather-proof external unit with evaporator, compressor, expansion to the German market incentive programme.
valve and fan.
■ Internal unit with high efficiency heating circuit pump (to Energy
Label A), heat exchanger, 3-way diverter valve, safety assembly and
control unit; for the heating/cooling versions with an integral instan-
taneous heating water heater.
5822 525 GB
Specification
Vitocal 200-S
Type AWB/AWB-AC 201.B04 201.B07 201.B10 201.B13
Output details, heating
to EN 14511 (A2/W35 °C, 5 K spread)
Rated heating output kW 3.00 5.60 7.70 10.60
Compressor frequency Hz 60 65 55 75
Fan speed rpm 870 650 650 650
Power consumption kW 0.91 1.73 2.20 3.25
Coefficient of performance ε (COP) in 3.27 3.24 3.50 3.26
heating mode
Output control kW 1.10 – 3.80 1.30 – 7.70 4.40 – 9.90 5.00 – 11.90
Heating output data
to EN 14511 (A7/W35 °C, 5 K spread)
Rated heating output kW 4.50 8.00 10.90 14.60
Compressor frequency Hz 60 65 55 75
Fan speed rpm 870 650 650 650
Power consumption kW 0.97 1.88 2.36 3.40
Coefficient of performance ε (COP) in 4.64 4.26 4.62 4.29
heating mode
Cooling capacity data
to EN 14511 (A35/W7 °C, 5 K spread)
Rated cooling capacity kW 3.20 6.20 7.40 9.10
Compressor frequency Hz 60 65 55 70
Fan speed rpm 870 650 650 650
Power consumption kW 1.08 2.40 2.69 3.64
Energy efficiency ratio EER 2.96 2.60 2.75 2.50
Output control kW 1.2 – 3.8 1.6 – 8.0 2.4 – 8.5 2.4 – 10.0
Cooling capacity data
to EN 14511 (A35/W18 °C, 5 K spread)
Rated cooling capacity kW 4.20 8.80 10.00 12.60
Compressor frequency Hz 60 65 55 70
Fan speed rpm 870 650 650 650
Power consumption kW 1.13 2.63 2.80 4.20
Energy efficiency ratio EER 3.72 3.35 3.57 3.00
Air intake temperature
Cooling mode (type AWB-AC)
– Min. °C 15 15 15 15
– Max. °C 45 45 45 45
Heating mode (type AWB, AWB-AC)
– Min. °C –15 –15 –15 –15
– Max. °C 35 35 35 35
Heating water
at 10 K spread
Content l 2.2 2.2 3.2 3.2
Minimum flow rate (always maintain) l/h 600 820 1200 1380
Max. flow temperature °C 55 55 55 55
Electrical values
External unit
– Rated voltage, compressor 1/N/PE 230 V/50 Hz
– Max. rated current, compressor A 5 9 10 15
– Starting current, compressor A 10.5 15 10 10
– Compressor starting current with stalled A 20 25 25 32
armature
– Starting current (charging DC capaci- A 45 < 35 30 30
tors)
– Internal fuse/MCB A 3.5 3.5 3.15 3.15
– IP rating IP 24 24 24 24
5822 525 GB
A B 450 /
AB
150
360 360
960
905
50
40
58
41
+
75
1105
147
219
294
369
A B
100 100
1000
Hydraulic connections
Symbol Meaning Connection
Refrigerant lines from/to the external unit: 7 connection pipe UNF thread
– Liquid line 10 mm ⅝
For type AWB-AC 201.B04, a reduction from 10 to 6 mm is required
downstream from the internal unit connection (reducer ⅝ to ⁷⁄₁₆
supplied).
– Hot gas line 16 mm ⅞
For type AWB-AC 201.B04, a reduction from 16 to 12 mm is
required downstream from the internal unit connection (reducer ⅞
to ¾ supplied).
DHW cylinder flow (heating water side) G 1¼
5822 525 GB
869
290 610 795
74
500
40
308
5822 525 GB
1040
340 950
865
527 90
48
378
5822 525 GB
340 903
1255
357 705 97
50
357
5822 525 GB