Professional Documents
Culture Documents
Terminal X1:7 is
low voltage neutral
1. Test the door so that you are sure of the type of problem.
2. Disengage the door and position it centrally (so that no limit positions are activated).
Engage the door and check (by pulling the door up and down) whether the disengaged
mode is active.
3. Check that the running timer has not tripped. (Cuts the supply voltage 5 sec.)
Pin terminal
X2:1 - 18
Terminal
Terminal X6:1 - 3
X1:1 - 19
for connection of
ext. deadman's grip
X13
(X15 on older
revisions)
PROCESSOR BOARD
X2
Regulator IC1
LED D23 indicates
the running time
X3
Dipswitch S2:1 - 8
Dipswitch S1:1 - 6
Open the cover on the controller and activate the up and down buttons manually -
1:1 Do the contactors make?
Yes No
Yes Cont. overleaf. No Faulty ctrl cable or limit pos. switch in mec. unit
Trouble shooting guide ECS 430P /DK
K038248 Rev. E
- 3 of 8 -
1:11 12V DC across + (positive) side of LED D22 and X6:3?
Yes No
1:13 Activate the up and down button, 5V DC between cooling flange on IC 1 and
X3:2 resp. X2:4? (on the processor board)
3:2 No Yes Activate the up button, 24V AC across X1:9 and X1:7?
Yes
Check the control cable
(connector #4) and the
switch for the upper limit
pos. in the mec. unit and ev.
adapter board (CDM5).
3:3 Activate the up button, 5V DC between cooling flange
on IC 1 and X3:2? (on the processor board)
5:1 Is there voltage 24VAC between X1:3 and X1:7 when the mechanical unit runs but not
when it stops?
Check the operation and setting of the rev. monitor in the mec. unit.
6: The door runs not out of deadman's grip. (Indicated by LED D22)
6:1 Is the lower limit position correctly adjusted? (disengages 40-50mm from the floor)
6:2 Is the pinch guard, pneumatic switch and the end plugs OK?
7:1 Is the lower limit position correctly adjusted? (disengages 40-50mm from the floor)
7:2 Is the control cable (connector #5) and the lower limit switch in the mec.unit OK?
7:3 24V AC between X1:7 and X1:5 on the adapter board after activated lower limit switch?
8:1 If the running timer has tripped (diode D23) when the
door is open.
It´s probably the rev monitor that causes the trouble. The control unit stops on the upper limit
switch, but if the switch for the rev monitor´s not cutting-off as it should it trips the running timer.
This indicates that the rev monitor could have an unsatisfactory function. This is altered in revi-
sion A on the processor card.
8:2 If the running timer has tripped (diode D23) when the
door is closed or nearly closed.
430 P function: When the door reaches the lower limit switch the control unit goes into "hold to run"-
function. If the air acknowledge signal against the ground is correct (minimum 200 ms) the door stops
and reset the control system to impuls function again. If the air acknowledge signal comes to quick
after the door activates the lower limit switch, the electronics have problem to register acknowledge
signal.
For that reason it´s very important that the lower limit switch is adjusted at a
minimum of 30 mm from the ground.
If the limit switch should be adjusted to low or something or some part of somebody
should be under the door, the door will stop because the lower limit switch has disconnected the
reversing function. But as the contol unit has not gone over to "hold to run"-mode yet, (diode D22
lightning) a 5 seconds run timer will start and trip out.
The timer is in this mode only 5s in order to minimize the damage risk on the object who might be under
the door, otherwise it´s 35 sec.
The running timer always resets when the door reverses.
a) The reverse function will not be immediately disconnected when the lower limit switch is ac
tivated. It will still be active for a short time. This brings the possibility to adjust the lower
limit switch a little higher than five cm (ap. seven cm) and still manage to fulfil the demand
not to disconnect the reverse function higher than five cm from the floor. (This is not a de
mand in all countries.) This also brings that that a to low adjustment of the lower limit
switch, much more frequently than in general today, not will trip the running timer but in-
stead reverse the door.
b) If the door has started down and has not left the upper limit switch and the additional safety
is activated, there will be a delay of 350 ms before the door reverses. This has been done in
order to assure that the door always reverses to full opening when the additional safety is
activated. If the door has left the upper limit switch when the additional safety is activated,
there will be no delay.