You are on page 1of 168

MS ISO/IEC TR 10037 : 1995

MALAYSIAN
STANDARD
MS 930 : 1986
ICS : 75.200

CODE OF PRACTICE FOR


THE INSTALLATION OF
FUEL GAS PIPING SYSTEMS
AND APPLIANCES

STANDARDS & INDUSTRIAL RESEARCH INSTITUTE OF MALAYSIA


© Copyright
/

MS 930: 1986

This Malaysian Standard, which had been approved by the Mechanical Engineering
Industry Standards Committee and endorsed by the Council of the Standards and
Industrial Research Institute of Malaysia (SIRIM) was published under the authority of
the SIRIM Council in September. 1 986.

SIRIM wishes to draw attention to the fact that this Malaysian Standard does not
purport to include all the necessary provisions of a contract.

The Malaysian Standards are subject to periodical review to keep abreast of progress
in the industries concerned. Suggestions for improvements will be recorded and in
due course brought to the notice of the Committees charged with the revision of the
standards to which they refer.

Amendments issued since nublicat~on

Amd. No. Date of issue Text affected

The following references relate to the work on this standard:

Committee reference: SIRIM 402/2/8/7


Draft for comment : D66 (ISC F)

1
MS 930 : 1986

CONTENTS

Committee representation 10
Foreword 11

SECTION ONE: GENERAL


1.1 Scope 12
1 .2 Alternate materials, equipment and procedures 13
1 .3 Retroactivity 13
1.4 Qualified agency 13
1 .5 Interruption of service 14
1 .6 Prevention of accidental ignition 14
1 .7 Definitions 14

SECTION iWO: GAS PIPING SYSTEM DESIGN, MATERIALS AND


COMPONENTS
2.1 Piping plan 31
2.2 Provision for location of point of delivery 31
2.3 Interconnections between gas piping systems 31
2.4 Sizing of gas piping systems 31
2.5 Piping system operating pressure limitations 32
2.6 Acceptable piping materials and joining methods 32
2.7 Gas meters 37
‘2.8 Gas pressure regulators 38
2.9 Overpressure protection devices 38
2.1 0 Back pressure protection 40
2.11 Low pressure protection 41
2.12 Shutoffvalves 41
2.13 Expansion and flexibility 41

SECTION THREE: GAS PIPING INSTALLATION


3.1 Piping underground 42
3.2 Aboveground piping outside 43
3.3 Piping in buildings

2
MS 930: 1986

CONTENTS (Contd.)
Page

3.4 Concealed piping in b~tildings 44


3.5 Piping in vertical chases 44
3.6 Gas pipe turns
3.7 Drips and sediment traps ‘ 46
3.8 Outlets 46
3.9 Branch pipe connection 46
3.10 Manual gas shutoff valves 46
3.11 Prohibited devices
3.1 2 Systems containing gas-air mixtures outside the flammable
range 47
3.13 Systems containing flammable gas-air mixtures 47
3.14 Electrical bonding and grounding 49

3.15 Electricalcircuits
3.16 ‘Electrical connections

SECTION FOUR: INSPECTION, TESTING AND PURGING


4i Pressure testing and inspection 50
4.2 Leakage check after gas turn on 52
4.3 Purging 52

SECTION FIVE: EQUIPMENT INSTALLATION


5.1 General 54
5.2 Accessibility and clearance 57
5.3 Air for combustion and ventilation 57

5.4 Equipment on roofs 60


5.5 Equipment connections to building piping 61
5.6 Electrical 0 - 62
5.7 Room temperature thermostats 63

SECTION SIX: INSTALLATION OF SPECIFIC EQUIPMENT


6.1 ‘ General 64
6.2 Air conditioning equipment 64

3
/

MS 930: 1986

CONTENTS (Contd~)
Page
6.3 Central heating boilers and furnaces 65
6.4 Clothes dryers 70
6.5 Commercial cooking equipment, floor-mounted 71
6.6 Commercial counter appliances 0~.~

6.7 Conversion burners 73


6.8 Hot plates and laundry stoves 73
6.9 Household cooking appliances 73
6.10 Illuminating appliances 75
6.1 1 Incinerators, commercial-industrial 76
6.1 2 Incinerators, domestic 76
6.1 3 Infrared heaters , ‘ 77
6.14 Open top broiler units 78
6.1 5 Outdoor cooking appliances 78
6.16 Pool heaters 78
6.17 Refrigerators 79
6.18 Room heaters 79
6.19 Sauna heaters 80
6.20 Stationary gas engines 82
6.21 Unit heaters 82
6.22 Wall furnaces 82
6.23 Water heaters 84

SECTION SEVEN: VENTING OF EQUIPMENT


7.1 Specification for venting 86
7.2 Minimum safe performance 86
7.3 Type of venting system to be used 87
7.4 Masonry, metal and factory-built chimneys 88
7.5 Type B. type B-W and type L vents 89
7.6 Single-wall metal pipe 90
7.7 Venting system location 92
7.8 Outside vents and chimneys 93
7.9 Vent connectors 93

4
MS 930: 1986

CONTENTS (Contd.)

Page
7.10 Draft hoods and draft controls 96
7.1 1 Manually operated dampers 97
7.1 2 Automatically operated vent dampers 101
7.13 Obstructions 101
7.14 Special venting arrangements 101

SECTION EIGHT: PROCEDURES TO BE FOLLOWED TO PLACE EQUIPMENT


IN OPERATION
8.1 Adjusting the burner input 103
8.2 Primary air adjustment 103
8.3 Safety shutoff devices ‘ 103
8.4 Automatic ignition 1 03
8.5 Protective devices 1 04
8.6 Checking the draft 104
8.7 Operating instructions 104
8.8 Notification of completion 1 04

SECTION NINE: MODIFICATIONS TO EXISTING APPLIANCE


INSTALLATIONS FOR THE PURPOSE OF FUEL CONSERVATION
9.1 Safety inspection 105
9.2 Reduction of vent connector size 105
9.3 Automatic vent damper device installation 1 06
Figures
1 Equipment located in confined spaces; all air from inside the
building 58
2 Equipment located in confined spaces; all air from outdoor-Inlet
air from ventilated crawl space and outlet air to ventilated attic 58
3 Equipment located in confined spaces; all air from outdoors
through ventilated attic 59
4 Equipment located in confined spaces; all air from outdoors 59
5 A method of installing a trap 62
6 Extent of protection necessary to reduce clearances from gas
equipment or vent connectors 66

5
/

MS 930 : 1986

CONTENTS (Contd,)
Page

7 Typical sauna heater installation 81


8 Installation of type B-W gas vents for vented wall furnaces 83
9 Suggested location for anti-siphon opening in cold w~aterinlet 85
10 Typical termination locations for chimneys and metal pipes
serving residential-type and low-heat equipment 91
11 Suggested general dimensions for a vertical draft hood 98
12 Suggested general dimensions for a horizontal draft hood 99
13 Suggested general dimensions for a horizontal to vertical draft
hood . 100
14 Example of pipe sizing using NFPA method no. 54 11 9
15 Example in sizing the lines of a domestic installation ‘ 1 28
16 Solution showing how line A of fig. 1 5 is sized with the use of
table 28 129
17 Two methods for finding the value of ‘h’ for a problem in high
pressure pipe sizing 133

18 A high pressure pipe sizing problem involving branch lines 135

19 High pressure pipe sizing chart 139


20 Double wall or asbestos cement type B vents of single-wall metal
vents serving a single appliance 149
21 Masonry chimney serving a single appliance - 149
22 Double-waIl or asbestos cement type B vents or single-wall metal
vents serving two or more appliances 1 52
23 Masonry chimney serving two or more appliances 1 52
24 Example of multiple vent-design using table 42 double-waIl type
Bvent 154

Tables
1 Specifications for threading metallic pipe 35
2 Support of piping 44
3 Length of gas line requiring purging for servicing or modification 52
4 Length of piping requiring purging before placing in operation 53
5 Clearances to combustible material for furnaces and boilers
installed in rooms which are large in comparison with size of
equipment, except as provided in 6.3.1.1 67

6
/

MS 930:1986

CONTENTS (Contd.)’
Page
6 Clearances (mm) with ~pecified forms of protection 68
7 Clearances to combustible material for unlisted open flame
illuminating appliances 75
8 Clearances for connectors 90
9 Minimum thickness for galvanized steel vent connectors for low-
heat appliances 93
10 Minimum thickness for steel vent connectors for medium heat
equipment and commercial and industrial incinerators 94
11 Approximate gas input for typical appliances 11 9
12 Equivalent lengths. in feet of straight pipe, of bends, fittings, and
valves 0 120
13 Maximum capacity of pipe in cubic feet of gas per hour for gas
pressures of 0.5 psig or less and a pressure drop of 0.3 inch
water column 121
14 Maximum capacity of pipe in cubic feet of gas per hour for gas
pressures of 0.5 psig or less and a pressure drop of 0.5 inch
watercolumn 0 121
15 Maximum capacity of semi-rigid tubing in cubic feet of gas per
hour for gas pressures of 0.5 psig or less and pressure drop of
0.3 inch water column 1 21
16 Maximum capacity of semi-rigid tubing in cubic feet of gas per
hour for gas pressures of 0.5 psig or less and a pressure drop of
0.5 inch water column ‘ 122
17 Pipe sizing table for pressures under 1 pound approximate
capacity of pipes of different diameters and lengths in cubic feet
per hour with pressure drop of 0.3 inch water column and 0.6
specific gravity 1 22
18 Pipe sizing table for pressures under 1 pound approximate
capacity of pipes of different diameters and lengths in cubic feet
per hour with pressure drop of 0.5 inch water column and 0.6
specific gravity 1 22
19 Pipe sizing table for 1 pound pressure capacity of pipes of
different diameters and lengths in cubic feet per hour for an
initial pressure of 1 .0 psig with a 10 per cent pressure drop and a
gas of 0.6 specific gravity 1 23
20 Pipe sizing table for 2 pounds pressure capacity of pipes of
different diameters and lengths in cubicfeet per hourfor an initial
pressure of 2.0 psigwith a l0percentpressuredropandagasof
0.6 specific gravity 0 1 23

.7
MS 930:1986

CONTENTS (Contd~)

21 Pipe sizing table for 5 pounds pressure capacity of pipes of


different diameters and lengths in cubic feet per hour for an initial
pressure of 5.0 psig with a 1 0 per cent pressure drop and a gas of
0.6 specific gravity 0 1 23
22 Pipe sizing table for 10 pounds pressure capacity of pipes of
different diameters and lengths in, cubic feet per hour for an initial
pressure of 10.0 psig with a 1 0 per cent pressure drop and a gas
of 0.6 specific gravity 1 24
23 Pipe sizing table for 20 pounds pressure capacity of pipes of
different diameters and lengths in cubic feet per hour for an initial
pressure of 20.0 psig with a 10 per cent pressure drop and a gas
of 0.6 specific gravity 1 24
24 Pipe sizing table for 50 pounds pressure capacity of pipes of
different diameters and lengths in cubic feet per hour for an initial
pressure of 50.0 psig with a 10 per cent pressure drop and a gas
of 0.6 specific gravity 0 1 24
25 Multipliers to be used with tables 14 through 25 when the
specific gravity of the gas is other than 0.60 1 25
26 Maximum capacity of pipe in thousands of Btu per hour of un-
diluted liquefied petroleum gases (at 11 inches water column
inlet pressure) 1 25
27 Maximum capacity of semi-regid tubing in thousands of Btu per
hour of undiluted liquefied petroleum gases (at 11 inches water
column inlet pressure) 1 25
28 LP - Gas low pressure pipe sizing table 1 26
29 Equivalent length of pipe for various fittings 1 26
30 Solution summary of pipe sizing of a domestic installation shown
in fig. 15 130
31 High pressure pipe sizing table 131
32 High pressure pipe sizing table 134
33 Values of ‘h’ for high pressure pipe sizing 138
34 Values of ‘h’ for high pressure pipe sizing 138
35 Utility gases 143
36 Lp-gases 145
37 Multipliers for utility gases of another specific gravity 146

8 -
0 MS930:1986

CONTENTS (Contd.)
Page

38 Equivalent orifice sizes at high altitudes (Includes 4% input re-


duction for each 1 .000 feet) 1 47
39 Capacity of type B double-wall vents with type B double-wall
connectors serving a single appliance 1 50
40 Capacity of single-wall metal pipe of type B asbestos cement
vents serving a single appliance , 1 51
41 Capacity of masonry chimneys and single-wall vent connectors
serving a single appliance 151
42 Capacity of type B double-wallvents with type B double-wall con-
nectors serving two or more appliances 152,153
43 Capacity of a single-wall metal pipe of type B asbestos cement
vent servirrg two or more appliances 1 55
44 Capacity of a masonry chimney and single-wall vent connectors
serving two or more appliances 1 55
45 Masonry chimney liner dimensions with circular equivalents 156

Appendices
A List of reference standards 1 06
B Coordination of gas utilization equipment design, construction
and maintenance 11 2
C Sizing and capacity of gas piping 11 6
D Suggested method for checking for leakage 140
E Suggested emergency procedure for gas leaks 141
F Flow of gas through fixed orifices 1 42
G Sizing of venting systems serving appliances equipped with draft
hoods and appliances listed for use with type B vents 1 49
H Recommended procedure for safety inspection of an existing
appliance installation 1 57
J Recommended procedure for installing electrically operated
automatic vent damper devices on existing appliances 1 59
K Recommended procedure for installing mechanically actuated
automatic vent damper devices on existing appliances 161
L Recommended procedure for installing thermally actuated auto-
matic vent damper devices on existing appliances 1 63

9
MS 930: 1986

Committee representation

The Mechanical Engineering Industry Standards committee under whose supervision this Malaysian Standard v~oizj
prepared. comprises representatives from the following Government Ministries. tr~do.commerce end rnanufacturci
associations and scientific and professional bodies.

Association of Consulting Engineers (Malaysia)

Federation of Malaysian Manufacturers

Institution of Engineers. Malaysia

Malaysian Motor Vehicle Assemblers Association

Ministry of Defence

Ministry of Labour and Manpower


(Factories and Machinery Department)

Ministry of Trade and Industry


(Malaysian Industrial Development Authority)

Ministry of Works and utilities


(Public Works Department)

National Chambers of Commerce and Industry of Malaysia

university of Malaya

The Task Force on Storage and utilization of Petroleum and Petroleum Products which prepared this Malaysian Stenderd
consists of the following representatives:

Tuan HaliAbdul Jalil Mahmud (Chairman) Factories and Machinery Department

Encik Abdul IRahim Kechof Civil Aviation Department

Encik M. Chelliah Fire Department

Encik Rahim Kamil Sulaiman Petronas

Encik Lee Herig Keng Ministry of Science. Technology and the Environment
(Division of Environment)

Encik Manmohan Singh/ Town and Country Planning Department


Encik Basant Singh

Encik Lum Kon Woon Chemistry Department

Encik Mohd. Hazis Ngah Ministry of Trade and Industry

Encik Leong Chew Kum Factories and Machinery Department

Encik Zulkarnain bin Ibrahim Prime Ministers Oepartrnent (Petroleum Development Unitl

Encik Shaart bin Mat Isa Ministry of Transport


Encik Cleopas Urn!
Encik Zeinal Abidin Abdullah

Encik Khaw Cheng Liang/ Shell Malaysia Trading Sdn. Bhd.


Encik Lau Chu Fong

Encik Lawrence Chin Esso Malaysia Bhd.

Encik Soo Lin Hwa/ 8.P. Malaysia Sdn. Bhd.


Encik Woon Teik

Encik Low Keng Huat/ Mobil Malaysia Bhd.


Encik Lim Yoke Lan

Encik Ooi Cheng Lee (Secretary( Standards and Industrial Research Institute of Malaysia

10
- MS930:1986

FOREWORD

The preparation of this Code of Practice was initiated as a result of steps taken to
review the Petroleum Ordinance 1 949. The Government established the Committee
on, the Review of Petroleum Safety Laws and Regulations with a view to updating and
developing relevant codes in the area of petroleum and gas industry. This Committee
subsequently formed three sub-committees, namely the Sub-commIttee on Storage,
Sub-committee on Utilization and Sub-committee on Transportation to entail work in
the different areas of the petroleum and gas industry. To consider and prepare the
Code of Practice for the installation of fuel gas piping systems and appliances, a
technical Task Force on Storage and Utilization of Petroleum and Petroleum Products
was formed jointly by the Sub-committees on Storage and Utilization.

In the preparation of this Code close reference was made to the United States National
Fire Protection Association Standard No. 54 - National fuel gas code.
Acknowledgement is hereby made for the use of this standard.

This Code provides coverage of all facets of fuel gas piping and appliance installation
downstream from meter set assemblies or other facilities comprising the gas service
entrance.to consumers’ premises and additionally as set out in the scope of this Code.
The coverage of piping systems is limited to maximum operating pressure of 420 kPa
(gauge) except that piping systems for gas air mixture within the flammable range are
-

limited to maximum pressure of 70 kPa (gauge). Generally the Code attempts to fulfill
minimum requirements and standardsforappliances, accessories and equipment and
wherever possible energy conservation measures. Further, the Code requires
reference to several other standards, a listing of which is given in appendix A.

In the main, the body of the Code is comprehensively in the metric system. However.
appendices C. F and G appear in the imperial system of measurements. The
appendices C, F and G contain field data and therefore, translation to the metric units
are not attempted because ‘approximated conversion would materially give rise to
significant alterations of physical constants and consequently distortion of design
specifications. It is however recognized that further review of this Code may be
necessary for purposes of incorporating metrication and moreover, to appropriately
reflect the pace of development and innovation of practices in the installation of fuel
gas piping and equipment.

11
MS 930: 1986

CODE OF PRACTICE FOR THE INSTALLA11ON OF FUEL GAS


PIPING SYSTEMS AND APPUANCES

SECTION ONE: GENERAL

1.1 Scope (gauge) [60 psig] except that piping systems for
gas-air mixtures within the flammable range ai’c.t
1 .1 .1 Applicability limited to a maximum pressure of 70 kPa (gauge)
[10 psig].

1.1.1.1 This Code is a safety code which (d) Coverage of piping systems includes desiçjri,
applies to the installation of fuel gas piping materials, components. fabrication, assembly.
systems, fuel gas utilization equipment and installation, testing. inspection, operation and
related accessories as follows: maintenance.

(a) Fuel gases include natural gas. mariu-


(e) Coverage of gas utilization equipment and
factured gas. liquefied petroleum ~(LP)gas in the related accessories includes installation, com~
vapour phase only, liquefied petroleum gas-air bustion and ventilation air, and venting.
mixtures, and mixtures of these gases, plus gas-
air mixtures within the flammable range. with the 1.1.1.2 This Code does not apply to the
fuel gas ortheflammablecomponentofamixture following:
being a commercially distributed product.
(a) Portable LP-gas equipment of all types which
(b) Coverage of piping systems extends from are not connected to a fixed fuel piping system.
the point of delivery to the connections with each
gas utilization device. For other than undiluted (b) Installation of farm equipment such as
liquefied petroleum gas systems, the point of brooders. dehydrators. dryers and irrigation
delivery is the outlet of the service meter equipment.
assembly, or the outletof the service regulator or
service shutoff valve when no meter is provided. (c) Raw material (feed stock) applications
For undiluted liquefied petroleum gas systems. except for piping to special atmosphere
the point of delivery is the outlet of the first stage generators.
pressure regulator.
(d) Oxygen-fuel gas cutting and welding
(c) The maximum operating pressure is 420 kPa systems.

12
MS 930 : 1986

(e) Industrial gas applications using such gases other standards which may be used, see
as acetylene and acetylenic compounds. appendix A.
hydrogen, ammonia, carbon monoxide., oxygen
and nitrogen.
1 .2 Alternate ‘ materials, equipment and
(f) Petroleum refineries, pipeline compressor or procedures
pumping stations, loading terminals, com-
pounding plants, refinery tank farms and natural 1.2.1 The provisions of this Code are not
gas processing plants. intended to prevent the use of any material,
method of construction. or installation procedure
(g) Large integrated chemical plants or portions
not specifically prescribed by this Code, provided
of such plants where flammable or combustible
liquids or gases are produced by chemical any such.alternate is acceptable to the authority
having jurisdiction. The authority having
reactions or used in chemical reactions.
jurisdiction shall require that sufficient evidence
(h) LP-gas installations at utility gas plants. be submitted to substantiate any claims made
(j) Liquefied ‘natural gas (LNG) installations. regarding the safety of such alternates.

(k) Fuel gas piping in power and atomic energy


plants.
1 .3 Retroactivity
(I) Proprietory items of equipment, apparatus or
instruments such as gas generating sets. 1.3.1 Unless otherwise required by the
compressors and calorimeters. authority having jurisdiction, it is not intended
(m) LP-gas equipment for vaporization, gas that the provisions of this Code be retroactive to
mixing and gas manufacturing. existing systems in compliance with the pro-
visions of the Code in effect at the time of
(n) LP gas piping for buildings under cons-

installation.
truction or renovations which is not to become
part of the permanent building piping system. i.e..
temporary fixed piping for building heat. 1 .4 Qualified agency
(p) Installation of LP-gas systems for railroad
switch heating. 1.4.1 Installation and replacement of gas
piping, gas utilization equipment or accessories
(q) Installation of LP-gas and compressed and repair and servicing of equipment shall be
natural gas.(CNG) systems on vehicles. performed only by a qualified agency. The term
(r) Gas piping, meters. gas pressure regulators ‘qualified agency’ means any individual, firm,
and other appurtenances used by the serving gas corporation or company which either in person or
supplier in distribution of gas, other than through a representative is engaged in and is
undiluted LP-gas. responsible for (a) the installation or replacement
of gas piping or (b) the connection, installation,
1.1.2 Other standards. In applying this Code. repair. or servicing of equipment, who is
reference should also be made to the manu- experienced in such work, familiar with all
facturer’s instructions and the serving gas precautions required, and h~scomplied with all
supplier regulations. For a list of standards the requirements of the authority having
specifically referenced in applying this Code and jurisdiction.

13
MS 930: 1986

1 .5 Interruption- of service working on piping which contains or has


contained gas:
1 .5.1 Notification of interrupted service.
Except in the case of an emergency, it shall be the (a) Provisions for electrical- continuity shall be
duty of the qualified agency, when the gas supply made before alterations are made in a metallic
is to be turned off, to notify all affected users. piping system.

(b) Smoking, open flames, lanterns. welding or


When two or more users are served from the same
supply system, precautions shall be exercised to other sources of ignition shall not be permitted.
assure that only service to the proper user is (c) A metallic electrical bond shall be installed
turned off. around the location of cuts in metallic gas pipes
made by other than cutting torches. If cutting
1.5.2 Before turning gas off. Before turning off
torches, welding or other sources of ignition are
the gas to the premises, or section of piping to be
unavoidable, it shall be determined that all
serviced, for the purpose of installation, repair.
replacement or maintenance of gas piping or gas sources of gas or gas-air mixture have been
secured and that allflammable gas orliquids have
utilization equipment, all equipment valves shall
be turned off. been cleared from the area. Piping shall be
purged as required in 4.3 before welding or
A leakage test shall be made, as specified in cutting with a torch is attempted.
appendix D. to determine that all equipment is (d) Artificial illumination shall be restricted to
turned off in the piping section to be affected. listed safety type flashlights and safety lamps.
Electric switches shall not be operated, on or off.
1.5.3 Turn gas off. All gas piping installations.
equipment installations and modifications to 1.6.2 Handling of flammable liquids
existing systems shall normally be performed
with the gas turned off to eliminate hazards from (a) Drip liquids. Liquid which is removed from a
leakage of gas, except as outlined in (b) below. drip in existing gas piping shall be handled
cautiously to avoid spillage or ignition and the
(a) Reduce gas pressure and purge section to be ‘gas supplier shall be notified.
worked on as specified in 4.3.
(b) Other flammable liquids. Flammable liquids
(b) Hot taps may be made if they are installed by used bythe installer shall be handled with proper
trained and experienced crews utilizing equip- precautions and shall not be left within the
ment specifically designed for such purpose. premises from the end of one working day to the
beginning of the next.
1 .5.4~ Work interruptions. When interruptions in
work occur while repairs or alterations are being
made to an existing piping system, the system
1.7 Definitions
shall be left in safe condition, such as by not
leaving any open-ended piping. For the purpose of this Code, the following
definitions shall apply:

1.6 Prevention of accidental ignition 1.7.1 Air mixer. That portion of an injection
(Bunsen) type burner into which the primary air is
1.6.1 Potential ignition sources. When introduced.

14
MS 930: 1986

1.7.2 Air shutter. An adjustable device for Fuel-gas burning heating appliances, except
varying the size of the primary.’sir ii,let(s~. high-pressure steam boilers, for heating building
spaces having a volume of not more than 700
1.7.3 AppliancO (equipment) Any device cubic metres, and other heat producing
which utilizes gas as a fuel or.ráW material to appliances of the type mainly used in residences.
produce light, heat, power. ref,cigeration or air such as cooking stoves and ranges. clothes
conditioning. dryers, fireplace stoves, domestic incinerators,
laundry stoves, water heaters and heat pumps.
1 .7.4 Appliance, automatlOally controlled.
Appliances equipped with anautomatic burner
ignition and safety shutoff device and other 1.7.8 Appliance flue. The flue passages within
automatic devices which: the appli~nce.

(a) Accomplish complete turr ~:onand shutoff of 1.7.9 Approved. Acceptable to the authority
the gas to the main burner or burners. having jurisdiction. In determining the accep-
tability of installations or procedures. equipment
(b) Graduate the gas supply ~tothe burner or or materials, the authority having jurisdiction may
burners, but do not effectcomplete shutoff of the base acceptance on compliancewith appropriate
gas. standards. In the absence of such standards, said
authority may require evidence of proper
1 .7.5 Appliance, low-heat: An appliance such installation, procedure or use. The authority
as a commercial cooking range. pressing having jurisdiction may also referto the listings or
machine boiler at any pressure; bake oven, candy labelling practices of nationally recognized
furnace, stereo type furnace; i~ryingan&curing testing laboratories, inspection agencies. or
appliance, and other process appliances in which other organizations concerned with product
materials are heated or melted at temperatures evaluations which are in a position to determine
(excluding flue-gas temperature’s)~notexceeding compliance with appropriate standards for the
315°C. current production of listed items, and the
satisfactory performance of such equipment or
1.7.6 Appliance, medium-heat. An industrial materials in actual usage.
appliance such as an annealingfiirnace (glass or
metal), charcoal furnace, galvanizing furnace, 1.7.10 Authority having jurisdiction. The
gas producer. commercial o~ industrial organization, office or individual responsible for
incinerator, and steam boiler op~ratingat over ‘approving’ equipment, an installation or a
345 kPa (gauge) [50 psig] pressure when such procedure.
appliance is larger than 2.8 cubic metres in size.
and other furnaces classified a’s medium-heat 1.7.11 Automatic damper regulator. A
appliances in accordance with nationally recog- mechanically or electrically actuated device
nized good practice. Appiiances otherwise designed to maintain a constant draft on
classed as medium-heat appliances may be combustion equipment.
considered as low-heat appliances if not larger
than 2.8 cubic metres in size; excluding any 1.7.12 Automatic f/recheck. A device for
burner equipment and blower compartment. stopping the progress of a flame front in bUrner
mixture lines (flashback) and for automatically
1 .7.7 Appliance, residential-type heating. shutting off the fuel-air mixture.

15
MS930: 1986

Present units are customarily equipped with spring 1.7.20 Breeching. See Vent connector.
or weight loaded valves released for closure by a
fusible link or by movement of bimetallic 1.7.21 Broiler. A general term including
elements; they are also equipped with metallic broilers, salamanders. barbecues. and other
screens for stopping the progress of a flame front. devices cooking primarily by ra’diated heat.
excepting toasters.
1.7.13 A~tomaticgasshuroffdevice.A device
constructed so that the attainment of a water 1.7.22 Burner. A device for the final con-
temperature in a hot water supply system in veyance of the gas, or a mixture of gas and air. to
excess of some predetermined limit acts in such a the combustion zone.
way as to cause the gas to the system to be shut
off. (a) Forced-draft burner. See Power burner.

1.7.14 Automatic ignition. Ignition of gas at (b) Induced-draft burner. A burner which
the burner(s) when the gas controlling device is depends on the draft induced bya fan beyond the
turned on, including reignition if the flames on appliance for its proper operation.
the burner(s) have been extinguished by means
(c) Injection (Bunsen) type burner. A burner
other than by the closing of the gas contrplling
employing the energy of a jet of gas to inject air
device.
for combustion into the burner and mix itwith the
gas.
1.7.15 Backfire preventer. See Safety blowout.
(i) Atmospheric injection type burner. A burner
1.7.16 Back pressure. Pressure against which
in which the air at atmospheric pressure is
a fluid is flowing, resulting from friction in lines.
injected into the burner by a jet of gas.
restrictions in pipes, valves, pressure in vessel to
which fluid is flowing, hydrostatic head, or other (d) Luminous or yellow flame burner. A burner
impediment that causes resistance to fluid flow. in which secondary air only is depended on’ for
combustion of the gas.
1.7.17 Baffle. An object placed in an appliance
to change the direction of, or retard, the flow of (e) Power burner. A burner in which either gas
air, air-gas mixtures, or flue gases. or air or both are supplied at a pressure
exceeding, for gas. the line pressure. and for air,
1.7.18 Barometric draft regulator. A balanced
atmospheric pressure; this added pressure being
damper device attached to a chimney, vent
applied at the burner. A burner for which air for
connector. breeching or flue gas manifold to
combustion is supplied by a fan ahead of the
protect combustion equipment by controlling
appliance is commonly designated as a forced-
chimney draft. A double acting barometric draft
draft burner. ‘

regulator is one whose balancing damper is free


to move in either direction to protect combustion
(I) Premixing burner. A power burner in which
equipment from both excessive draft and all or neariy all of the air for combustion is mixed
backdraft. with the gas as primary air.

1.7.19 Branch line. Gas piping which conveys 1.7.23 Chimney. One or more passageways.
gas from a supply line to the appliance. vertical or nearly so. for conveying flue gases to

16
‘MS 930:1986

the outside atmosphere. See also gas vent, vent 1.7.31 Conversion burner, gas. A unit con-
and venting system. sisting of a burner and its controls. utilizing
gaseous fuel for installation in an appliance
1.7.24 Clearing. The act of replacing one originally utilizing another fuel.
atmosphere with another by direct displacement
so rapidly as to cause a minimum of mixing (a) Firing door type. A conversion burner
between’the two atmospheres. By this means specifically for boiler or furnace firing door
duration of any explosive mixture is reduced to a installation.
minimum, the gases are vented into a large open
area high (2.5 m or more) aboveground. and (b) Inshot type. A conversion burner normally
means of ignition are excluded. for boiler or furnace ash pit installation and fired
in a horizontal position.
1 .7.25 Closed water piping system. A system
of water piping where a check valve or other (c) Upshot type. A conversion burner normally
device prevents the free return of water or steam for boiler or furnace ash pit installation and fired
to the water main. in a vertical position at approximately grate level.

1.7.26 Clothes dryer. A device used to dry wet


1.7.32 Counter. appliances, gas. Appliances
laundry by means of ,heat derived from the
such as fuel-gas burning coffee brewers and
combustion of fuel gases.
coffee urns and any appurtenant water heating
equipment. food’ and dish warmers, hot plates
1 .7.27 Combustible material. As pertaining to
and griddles.
materials adjacent to or in contact with heat
producing appliances, vent connectors. gas
vents, chimneys, steam and hot water pipes, and 1.7.33 Cubic metre (m3) of gas. The amount of
gas which would occupyone cubic metrewhen at
warm air ducts. shall mean materials made of or
a temperature of 1 5.6°C. saturated with water
surfaced with wood, compressed paper, plant
fibers, or other materials’that are capable of being vapour and under a pressure equivalent to thatof
ignited and burned. Such material shall be 760 mm mercury column.
considered éombustible even though flame-
proofed, fire-retardant treated, or plastered. 1 .7.34 Differential pressure. The pressure
difference between two points in a system.
1.7.28 Concealed gas piping. Gas piping,
which, when in place in a finished building.would 1.7.35 Dilution air. Air which enters a draft
require removal of permanent construction to hood or draft regulator and mixes with the flue
gain access to the piping. gases.

1.7.29 Control piping. All piping, valves and 1 .7.36 Direct-fired oven. An oven in which the
fittings used to inter~connect air. gas, or flue gases flow through the oven compartment.
hydraulically operated control apparatus or
instrument transmitters and receivers. 1 .7.37 Direct vent appliances. Appliances
which are constructed and installed so that all air
1 .7.30 Controls. Devices designed to regulate for combustion is derived directly from the
the gas. air, water or electrical supply to a gas outside atmosphere and all flue gases are
appliance. These may be manual or automatic. discharged to the outside atmosphere.

17
MS 930: 1986

1.7.38 Diversity factor. Ratio of the maximum pressure in a premix system by bursting of a
probable demand to the maximum possible rupturable disc.
demand. ‘ . -

1~.7.45 Flame arrester. A non-valve device for


1.7.39 Draft. The flow of gases or air through use in a gas-air mixture line containing a means
chimney, flue or equipment caused by pressure for temporarily stopping the progress of a flame
differences front (flashback).

(a) Mechanical or induced. The draft developed 1.7.46 F/ames


by fan or air or steam jet or other mechanical
(a) Bunsen. The flame produced by premixing
means.
some of the air required for combustion with the
(b) Natural. The draft developed by the gas before it reaches the burner ports or point of
difference in temperature of hot gases and ignition.
outside atmosphere.
(b) Yellow, luminous or non-bunsen, The flame
1.7.40 Draft hood. A device built into an produced by burning gas without any premixing
appliance, or made a part of the vent connector of air with the gas.
from an appliance, which is designed to (a)
1.7.47 Flue collar. That portion of an appliance
provide for the ready escape of the flue gases
designed for the attachment of the draft hood or
from the appliance in the event of no draft,
vent connector.
backd raft. or stoppage beyond the draft hood. (b)
prevent a backdraft from entering the appliance,~
ana (c) neutralize the effect of stack action of the 1.7.48 Furnace, central. A self-contained, gas-
chimney or gas vent upon the operation of the burning appliance for heating air by transfer of
appliance. heat of combustion through metal to the air and
designed to supply heated air through ducts to
1.7.41 Draft regulator. A device which spaces remote from or adjacent to the appliance
functions to maintain a desired draft in the location.
appliance by automatically reducing the draft to
the desired value. (a) Forced air furnace. A furnace equipped with
a fan orblowerwhich provides the primary means
1.7.42 Dry gas. A gas having a moisture and for circulation of air.
hydrocarbon dew point below any normal
temperature to which the gas piping is exposed. (i) Horizontal furnace. A furnace designed for
low headroom installation with airflow across the
1.7.43 Duct furnace. A furnace normally ins- heating element essentially in a horizontal path.
talled in distribution ducts of air conditioning
systems to supply warm air for heating. This (ii) Upflow furnace. A furnace designed with air
definition applies only to an appliance which flow discharge vertically upward at or near the top
depends for air circulation on a blower not of the furnace. This classification includes
furnished as part of the furnace. ‘highboy’ furnaces with the blower mounted
below the heating element and ‘lowboy’ furnaces
1,7.44 E’xp/os,’on heads (Soft heads or rupture with the blower mounted beside the heating
discs). A protective device for relieving excessive element.

18
MS 930 : 1986

(iii) Downflow furnace. A furnace designed furnace and a vent’ cap supplied ‘by the
.

with air flow discharge vertically downward at or manufacturer, and ‘-(-a). .combustion air con-
near the bottom of the furnace. nections between the’ central’ furnace and the
outside atmosphere and (b) flue gas connections
(b) Forced air furnace with cooling unit. A between ‘the central furnace ádd”vént cap (of a
single-package unit, consisting of a gas-fired type(s) ‘specified by the m’anufacturer but
forced ai’r furnace of one of the types listed in (a) supplied by the installer), constructed so that when
above combined with an electrically or gas- i istalléd ‘in accordance with the manufacturer’s
operated summer air conditioning system. ins’iructions, ai’r’for cOri~ibüstidhis obtained from
contained in a common casing. the outside ‘atrr~daphe’~’eand flue gases are
discha’rged to ‘the ‘oUt~ide~tmosphere.
(c) Gravity furnace. A furnace depending
primarily on circulation of air by gravity.
1’.7.52 G~.E’Jei gas, such as natural gas.
(d) Gravity furnace with integral fan. A furnace manufactured gas undiluted liquefied petroleum
equipped with a fan or blower as an integral part of its gas ‘(vapour pha~e’oniy).liquefied petroleum gas-
air mixtures, or mixtures of these gases.
construction and operable on gravity systems
only. The fan or blower is used only to overcome
the ‘internal furnace resistance to air flow. 1 .7.53 Gas utilization equipment. Any device
- whichutilizes gas as a fuel or raw material or both.
(e) Gravity furnace with booster fan. A furnace
equipped with a booster fan which does not 1.7.54 Gas main..or~disrrib,utionmain. A pipe
materially restrict free circulation of air by gravity installed i’n a community to convey gas to
flow when the fan is not in operation. individual services or.oth’er mains.

1 .7.49 Furnace, direct vent central. A system 1.7.55 Ga’s-mixing machine: Any combination
consisting of (a) a central furnace for indoor of automatic proportioning control devices.
installation, (b) combustion air connections blowersor compressorswhich supply mixtures of
between the central furnace and the outdoor gas and air to multiple burnerinstallations where
atmosphere, (c) flue gas connections between control devices or other accessories are installed
the central furnace and the vent cap, and (d) vent between the mixing device and burner.
cap for installation outdoors, supplied by the
manufacturer and constructed so that all air for 1.7.56 Gas venr. A passageway, vertical or
combustion is obtained from the outdoor nearly so’. cdmposed of listed factory-built
atmosphere and all flue gases are discharged to components assembled in’ accordance with the
the outdoor atmosphere. terms of listing conveying flue gases from gas
appliances’or their vent connectors to the outside
1 .7.50 Furnace, enclosed. A specific heating. atmosphere. “ , ‘ -

or heating and ventilating, furnace incorporating


an integral total enclosure and using only outside (a) Type Bgas vent. A vent for venting listed gas
air for combustion. appliances with draft ,hoods and other g’as
appliances listed for use ~vithtype B vents.
1 .7.5 1 Furnace, separated combustion system
central. A system for installation in non- (b) Type B-W gas vent. A vent for venting listed
residential structures consisting of a central gas-fired vented wall furnaces.

19
MS 930:1986

1.7.57 Governor, zero. A regulating device source of radiant heat is below the surface on
which is normally adjusted to deliver gas at which cooking is done.
atmospheric pressure within its flow rating.
(ii) Enclosed broiler. A broiler in which the
1.7.58 Header. A pipe or fitting to which a source of radiant heat is above the surface on
number of branch pipes are connected. which cooking is done.

1.7.59 Heating value (total). The number of (b) Built-in unit. A unit designed to be recessed
kilojoules (British Thermal Units) produced by the into, placed upon. or attached tothe construction
combustion, at constant pressure. of one cubic of a building. but not for installation on the floor.
metre (foot) of gas when the products of Built-in units are further classified as:
combustion ‘are cooled to the initial temperature
of the gas and air, when the water vapour formed (i) Top or surface unit. A unit for installation in
during combustion is condensed, and when all or on a counter top. It may have top burners, a
the necessary corrections have beerr applied. griddle, a deep well cooker or any combination
thereof. -

1.7.60 Hot plate, commercial. See Counter


appliances, gas. (ii) Ovenunit. Aunitforinstallationinacabinet,
wall or partition. or for installation on a counter. It
1.7.61 Hotp/ate,.domestic. A fuel-gas burning may be a separate oven, may be equipped with a
appliance consisting of one or more open-top broiler that uses the oven burner, or the oven may
type burners mounted on short legs or a base. serve as a broiler with a burner in the upper
portion of the oven.
1.7.62 Hottaps. Piping connections made to
operating pipelines or mains or other facilities (iii) Broiler unit. May have ~n open top or be
while they are in operation. The connection of the enclosed, may be a separate broiler, or may be
branch piping to the operating line and the combined with a rotisserie.
tapping of the operating line are done while it is
under gas pressure. (iv) Combination of (i), (ii) or (iii) above, or any
other household cooking device that may be for
1,7.63 Hotel and restaurant range. A self- similar installation.
contained fuel-gas burning range providing for
cooking, roasting. baking or broiling, or any Cc) Floor mounted unit. A self-contained
combination of these functions, and not designed cooking appliance for installation directly on the
specifically for domestic use. floor. It has a top section and an oven section. It
may have additional sections. Included in this
1.7.64 Household cooking gas appliance. A classification are:
gas appliance for domestic food preparation,
providing at least one function of(a)Xop or surface (i) Bungalow (Utility type). A cooking appliance
cooking. (b) oven cooking, or Cc) broiling. having a gas oven and top section, and a gas.
solid or liquid fuel section for space heating and
(a) Broiler. A unit which cooks primarily by heating a solid top section but not for oven
radiated heat. Broilers are further classified as: heating.

(i) Open top broiler. A broiler in which the (ii) Room heater type. A cooking appliance

20
MS 930:1986

having a gas oven and top section, and a separate the authority having jurisdiction and concerned
room heater section designed for gas fuel. with product evaluation that maintains periodic
inspection of production of labelled equipment or
1.7.65 Indirect oven. An indirect oven is one in materials and by whose labelling the manu-
which the flue gases do notflowthrough the oven facturer indicates compliance with appropriate
compartment. standards or performance in a specified manner.

1 .7.66 Infrared heater. A heater which directs 1.7.71 Leak detector. An instrument for
a substantial amount of its energy output in the determining concentration of gas in air.
form of infrared energy into the area to be heated.
Such heaters may be of either the vented or 1.7.72 Leakage surveys. Systematic surveys
unvented type. made fQr the purpose of locating leaks in a gas
piping system.

1.7.67 Joint. A connection between two


1.7.73 Limit control. A device responsive to
lengths of pipe or between a length of pipe and a
changes in pre~sure.temperature or liquid level
fitting.
for turning on. shutting off, or throttling the gas
supply to an appliance.
(a) Adhesive. A joint made in plastic piping by
the use of an adhesive substance which forms a 1.7.74 Listed. Equipment or materials
continuous bond between the mating surfaces included in a list published by an organization
without dissolving either one of them. acceptable to the authority having jurisdiction
and concerned with product evaluation that
(b) Heat fusion. A joint made in thermoplastic
maintains periodic inspection of production of
piping by heating the parts sufficiently to permit
listed equipment or materials and whose listing
fusion of the materials when the parts are pressed
states either that the equipment or material meets
together.
appropriate standards or has been tested and
(c) Solvent cement. A joint made in thermo- found suitable for use in a specified manner.
plastic piping by the use of a solvent or solvent
1.7.75 Loads, connected. Sum of the rated kJ
cement which forms a continuous bond between
(Btu) input to individual gas utilization equipment
the mating surfaces.
connected to a piping system. May also’ be
expressed in cubic metres per hour. (cubic feet
1.7.68 Joint compounds. Nonhardenung
per hour).
materials used on pipe threads to insure a seal.
1.7.76 Main burner. A device or group of
1.7.69 Kettle, gas-fired. An appliance with a
devices essentiallyforming an integral unitforthe
cooking chamber which is heated either by a
final conveyance of gas or a mixtureof gas and air
steam jacket in which steam is generated by gas
to the combustion zone. and on which com-
heat or by direct gas heat applied to the cooking
bustion takes place to accomplish the function
chamber.
for which the appliance is designed.

1.7.70 Labelled. Equipment or materials to 1 .7.77 ‘Manifold, gas. The conduit of an


which has been attached a label. symbol or other appliance which supplies gas to the individual
identifying mark of an organization acceptable to burners.

21
MS 930 : ‘1 986

1.7.78 Measured gas. Gas which has passed taneously. No valves or other obstructions shall
through and the volume of which has been be installed between the blower discharge and
measured by a meter, or gas which has been the burner or burners.
otherwise measured such as by liquid volume or
weight. 1.7.84 Outdoor cooking gas appliance. As
used in this Code. a post-mounted, fuel-gas
1 .7.79 Mechanical exhaust system. Equip- burning outdoor cooking appliance for
ment installed in and made a part of the vent, installation directly on and attachment to a post
which will provide a positive induced draft. provided as a part of the appliance by the
manufacturer.
1.7.80 Meter. An instrument installed to
measure the volumé’of gas delivered through it. 1 .7.85 Oven, commercial gas baking and
roasting. An oven primaril~iintended for volume
food preparation which may be composed of one
1 .7.81 Mixer. The combination of mixer head.
or more sections or units of the following types:
mixer throat and mixer tube.
(a) Cabinet oven. An oven having one or more
(a) Mixer head. The portion of an injection
cavities heated by a single burner or group of
(Bunsen) type burner, usually enlarged, into
burners.
which primary air flows to mix with the gas
stream. (b) Sectional oven. An oven composed of one on
more independently heated cavities.
(b) Mixer throat. The portion of the mixerwhich
has the smallest cross-sectional area and which
(c) Reel-type oven. An oven employing trays
lies between the mixer head and the mixer tube.
that are moved by mechanical means.

(c) Mixer tube. The portion of the mixer which 1.7.86 Parking structure. A building. structure
lies between the throat and the burner head. or portion thereof used for the parking of motor
vehicles.
1.7.82 Mi’xerface. Theairinletend ofthe mixer
head. (a) Basement or underground. A parking
‘‘~,:;~ it’-
structure or portion thereof located below
1.7.8’3’)~Mixingblower. A motor-driven blower
ground level.
to produce gas-air mixtures for combustion
thro4H~”6neor more gas burners or nozzles on a (b) Enclosed. Having exterior enclosing walls
s~’h’g~-~one industrial heating appliance or on which have less than 25% of the total wall area
~~Ydontrol zone of a multi-zone industrial open to atmosphere at each level using at least
appliance or on each control zone of a multi-zone two sides of the structure.
ins~alIation,The blower shall be equipped with a
gas-control valve at its air entrance so arranged 1.7.87 Pilot. A small flame which is utilized to
that gas is admitted to the airstream, entering the ignite the gas at the main burner or burners.
blower in proper proportions for correct com-
bustion by the type of burners employed; the said 1 .7.88 Pioe, equivalent length. The resistance
gas-contr,ol valve being of either the zero of valves, controls and fittings to, gas flow
governor or mechanical ratio valve type which expressed as equivalent length of straight pipe for
controls the gas and air adjustment simul- convenience in calculating pipe sizes.

22
MS 930: 1986

1 .7.89 Piping. As used in this Code, either pipe 1 .7.94 Pressure or vacuum limit switch. A
or tubing. or both. device in a control system actuated by pressure or
vacuum within the air or gas piping system.
(a) Pipe. Rigid conduit of iron, steel, copper. 1.7.95 Primary air. The air introduced into a
brass, aluminium or plastic.
burner which mixes with the gas before it reaches
the port or ports.
(b) Tubing. Semi-rigid conduit of copper, steel,
aluminium or plastic. 1.7.96 Protective equipment. Safety devices
designed to forestall the development of a
1.7.90 Piping system. All piping, valves and hazardous or undesirable condition in the fuel
fittings used to connect gas utilization equipment supply piping, in the gas equipment. in the’
to the point of delivery. medium. being treated. or in the combustion
products.
1 .7.9 1 Plastic
1.7.97 Purge. To free a gas conduit of air, or
(a) Thermoplastic. A plastic which is capable of gas, or a mixture of gas and air.
being repeatedly softened by increase of tempe-
rature and hardened by decrease of temperature. 1 .7.98 Quick-o7sconnect device. A’ hand-
operated device which provides a means for
(b) Thermosetting. A plastic which is capable of connecting and disconnecting an appliance or an
being changed into a substantially infusible or appliance connector or a gas supply and which is
insoluble product when cured under application equipped with an automatic means to shut off the
of heat or chemical means. gas supply when the device is disconnected.

1.7.92 Poolheater. An appliance designed for 1 .7.99 Refrigerator (using gas fuel). A fuel-gas
heating nonportable water stored at atmospheric burning appliance which is designed to extract
pressure, such as water in swimming pools. heat from a suitable chamber.
therapeutic pools, and similar applications.
1.7.100 Regulator. gas appliance pressure. A
(a) Coil type pool heater. A type of pool heater device for controlling and maintaining a uniform
whose heat exchanger surfaces are composed pressure to the manifold of gas equipment.
primarily of water tubes whose inside diameters
are less than 32 mm. (a) Adjustable

(b) Indirect type pool heater. A type of pool (i) Spring type, standard adjustment. A
heater that utilizes water in a primary heat regulator in which the regulating force acting
exchanger to transmit heat from the gas upon the diaphragm is derived principally from a
combustion process by means of a secondary spring, the loading of which is adjustable. The
heat exchanger to the pool water. adjustment means shall be concealed.

1 .7.93 Pressure limiting device. Equipment (ii) Spring type, limited adjustment. A regulator
which under abnormal conditions will act to in which the regulating force acting upon the
reduce, restrict or shut off the supply of gas diaphragm is derived principally from a spring.
flowing into a system in order to prevent the gas the loading of which is adjustable over a range of
pressure in that system from exceeding a not more than ±1 5% of th~outlet pressure at the
predetermined value. midpoint of the adjustment range.

23
MS 930: 1986

(b) Nonadjustable regulator for the purpose of automatically taking


over in an emergency the control of the pressure
(i) Spring type, nonadjustable. A regulator in downstream of the regulator in case that pressure
which the regulating force acting upon the tends to exceed a set maximum.
diaphragm is derived principally from a spring.
the loading of which is not adjustable. 1.7.105 Regulator series. A pressure regulator
in series with one or more other pressure
(ii) Weight type. A regulator in which the regulators. The regulator nearest to the gas
regulating force acting upon the diaphragm is supply source is set to continuously limit the
derived from a weight or combination of weights. pressure on the inlet to the regulator downstream
to some predetermined value (between the
(c) Convertible. A regulator for conversion pressure of the gas supply source and the
between gases having different heating values pressure of the system being controlled) which
whose adjustment means can be positioned from can be tolerated in the downstream system.
one predetermined outlet pressure setting,for
one gas to another predetermined outlet pressure 1.7.106 Regulator. service pressure. A device
setting of the other gas with no intermediate installed by the serving gas supplier to reduce
pressure settings and without addition, deletion and limit the service line gas pressure to delivery
or substitution of parts. pressure.

(d) Multi-rate. A standard adjustment


regulator, the multi-rate adjustment means of 1.7.107 Regulator vent. The opening in the
which is not concealed and which provides atmospheric side of the regulator housing
nonfield adjustable high-and nonfield adjustable permitting the in and out movement of air to
low-pressure settings for high-low rates on compensate for the movement of the regulator
appliances. diaphragm.

1.7.101 Regulator. line gas pressure. A device 1.7.108 Relief opening. The opening provided
placed in a gas line between the service pressure in a draft hood to permit the ready escape to the
regulator and the gas appliance regulator for ‘atmosphere of the flue products from the draft
controlling, maintaining or reducing the pressure hood in the event of no draft, backdraft or
in that portion of the piping system downstream stoppage beyond the draft hood. and to permit
of the device. inspiration of air into the draft hood in the event of
a strong chimney updraft.
1 .7.102 Regulator. LP-gas. first stage. On
undiluted LP-gas systems. the first pressure 1.7.109 Room heater. unvented. An unvented.
regulator reducing the storage container self-contained, free-standing. non-recessed
pressure. (except as noted under (b) of the following
classifications), fuel-gas burning appliance for
1.7.103 Regulator, LP-gas. second stage. A furnishing warm airbygravityorfan circulation to
line gas pressure regulator for service on the space in which installed, directly from the
undiluted LP-gas systems, reducing an inter- heater without duct connection. Unvented room
mediate high pressure to utilization pressure. heaters do not normally have input ratings in
excess of 42,200 kJ (40.000 Btu) per hour.
1.7.104 Regulator, monitoring. A pressure
regulator set in series with another pressure (a) Unvented circulator. A room heater

24
MS 930:1986

designed to convert the energy in fuel gas to is no mixing of flue gases with the air of the space
convected and radiant heat by direct mixing of air being heated.
to be heated with the combustion products and
excess air inside the jacket. Unvented circulators 1.7.111 Safetyblowout(Backfirepreventer). A
have an external jacket surrounding the burner protective device located in the discharge piping
and may be equipped with radiants with the jacket of large mixing machines. incorporating a
open in front of the radiants. bursting disc for excessive pressure release.
means for stopping a flame front and an electric
(b) Wall heater, unvented closed front. An switch or other release mechanism for actuating
unvented circulator having a closed front, for a built-in or separate safety shutoff. Acheckvalve.
insertion in or attachment to a wall or partition. signalling means, or both, may also be incorporated.
These heaters are marked, ‘UNVENTED HEATER’
and do not have normal input ratings in excess of
1.7.112 Safety shutoff device. A device that
26,300 kJ (25,000 Btu) per hour.
will shut off the gas supply to the controlled
burner(s) in the event the source of ignition fails.
1.7.110 Room heater, vented. A vented, self- This device may interrupt the flow of gas to main
contained, free-standing, non-recessed, fuel-gas burner(s) only or to pilot(s) and main burner(s)
burning appliance for furnishing warm air to the under its supervision.
space in which installed, directly from the heater
without duct connections.
1.7.113 Sauna heater. A vented heater
(a) Vented circulator. A room heater designed designed to raise the temperature of an occupied
room to a temperature in excess of 38°C. The
to convert the energy in fuel gas to convected and
radiant heat, by transfer of heat from flue gases to appliance may or may not include the means for
a heat exchanger surface, without mixing of flue altering the humidity within the room.
gases with circulating heated air. Vente.d
(a) Direct vent sauna heater. A system con-
circulators may be equipped with transparent
sisting of an appliance, combustion air and flue
panels and radiating surfaces to increase radiant
gas connections between the appliance and the
heat transfer as long as separation of flue gases
outside atmosphere and a vent cap supplied by
from circulating air is maintained. Vented
the manufacturer and constructed so that all air
circulators may also be equipped with an optional
for combustion is obtained from the outside
circulating air fan, but should perform satis-
atmosphere. The appliance should be completed
factorily with or without the fan in operation.
with grilles or equivalent, designed for incor-
poration in or permanent attachment to the
(b) Vented circulator, fan type. A vented
circulator equipped with an integral circulating structure of a building, and should furnish heated
air fan, the operation of which is necessary for air circulated directly into the space to be heated
satisfactory appliance performance. through openings in the casing. Such appliances
should not be provided with duct extensions.
(c) Vented overhead heater. A room heater
(b) Flue-connected sauna heater. An appliance
designed for suspension from or attachmentto or
adjacent to the ceiling of the room being heated designed for connection to a chimney or gas vent.
All air for combustion and draft hood dilution is
and transferring the energy of the fuel gas to the
obtained from a room effectively sealed from the
space being heated primarily by radiation
heated room but not from ‘outside the structure
downward from a hot surface, and in which there
containing the heated room.

25
MS 930: 1986

1.7.114 Secondary air. The air externally components. the flow of gas to the burners to
supplied to the flame at the point of combustion. maintain selected temperatures.

1.7.115 Service meter set assembly. The 1.7.124 Thermostat, integral gas valve type.
piping and fittings installed by the serving gas An automatic device, actuated by temperature
supplier to connect the inlet side of the ~neterto changes, designed to control the gas supply to
the gas service and to connect the outlet side of the burners in order to maintain temperatures
the meter to the customer’s house or yard piping. between predetermined limits, and in which the
thermal actuating. element is an integral part of
1.7.116 Service pipe. The pipe which brings the device.
the gas from the gas main to the meter.
(a) Graduating thermostat. A thermostat in
1.7.117 Service regulator. See Regulator, which the motion of the valve is approximately in
service pressure. direct proportion to the effective motion of the
thermal element induced bytemperature change.
1 .7.118 Shutoff. See Valve.
(b) Snap-acting thermostat. A thermostat in
1.7.119 Space, confined. For the purposes of which the therfruostatic valve travels instantly
thisCode,aspacewhosevolumeislessthan 1.34 from the closed to the open position, and vice versa.
cubic metres per 1 .000 kJ per hour (50 cubic feet
per 1 .000 Btu per hour) of the aggregate input
1.7.125 Type B gas vent. See Gas vent.
rating of all appliances installed in the space.
1.7.126 Type B-Wgas vent. See Gas vent.
1.7.120 Space, unconfined. For purposes of
this Code, a space whose volume is not less than 1 .7.1 27 Type L vent. A passageway, vertical or
1.34 cubic metres per 1,000 kJ per hour (50 nearly so, composed of listed factory-built
cubic feet per 1.000 Stu per hour) of the components assembled in accordance with the
aggregate input rating of all appliances installed terms of listing for conveying flue gases from
in that space. Rooms communicating directly listed appliances for use with type L vents or their
with the space in which the appliances are vent connectors to the outside atmosphere
installed, through openings not furnished with
doors, are considered a part of the unconfined 1.7.128 Unitbroier. A broiler constructed as a”
space. separate appliance.

1.7.121 Steam cooker. A fuel-gas burning 1.7.129 Unit heater.


appliance which cooks, defrosts or reconstitutes
(a) High static pressure A self-contained.
- .
food by direct contact with steam.
automatically controlled. vented, fuel-gas
1.7.122 Steam generator. A separate burning appliance having integral means for
appliance primarily intended to supply steam for circulation of air against 5 mm or greater static
use with commercial cooking equipment. pressure. It is equipped with provisions for
attaching an outlet air duct and, when the
1.7.123 Thermostat, electric switch type. A appliance is for indoor installation remote from
device which senses changes in temperature and the space to be heated, is also equipped with
controls electrically, by means of separate provisions for attaching an inlet air duct.

26
MS 930: 1986

(b) Low static pressure A


- . self-contained. which controls the gas supply to the main burner
automatically controlled, vented, fuel-gas manifold.
burning appliance, intended for installatioh in the
space to be heated without the use of ducts. 1.7.137 Valve, manual main gas-control. A
having integral means for circulation of air, manually operated valve in the gas line for the
normally by a propeller fan(s), and may be purpose of completely turning on or shutting off
equipped with louvers or face extensions made in the gas supply to the appliance except to pilot or
accordance with the manufacturer’s speci- pilots which are provided with independent
fications. shutoff.

1.7.130 Unmeasured gas. Gas which has not 1.7.138 Valve, manual reset. An automatic
passed through and the volume of which has not shutoff valve installed in the gas supply piping
been measured by a meter. or gas which has not and set to shut off when unsafe conditions occur.
otherwise been measured such as by liquid The device remains closed until manually
volume or weight. reopened.

1.7.131 Utility gases. Natural gas, manu- ‘1.7.139 Valve, relief. A safety valve designed
factured gas, liquefied petroleum gas-air to forestall the development of a dangerous
-

mixtures, or mixtures of any of these gases. condition by relieving either pressure, tempe-
rature or vacuum in a hot water supply system.
1.7.132 Valve. A device used in piping to
control the gas supply to any section of a system (a) Pressure. A valve which automatically
of piping or to an appliance. opens and closes a relief vent, depending on
whether the pressure is above or below a
1.7.133 Valve, automatic. An automatic or predetermined value.
semi-automatic device consisting essentially of a
valve and operatorthat controls the gas supplyto (b) Temperature. A valve which automatically
be burner(s) during operation of an appliance. opens and automatically closes a relief vent.
The operator may be actuated by application of depending on whether the temperature is above
gas pressure on a flexible diaphragm, by or below a predetermined value.
electrical means, by mechanical means or by
(c) Vacuum. A valve which automatically opens
other means.
and closes a vent for relieving a vacuum within
1.7.134 Valve, automatic gas shutoff. A valve the hot water supply system depending on
used in conjunction with an automatic gas whether the vacuum is above or below a
shutoff device to shut off the gas supply to a fuel- predetermined value.
gas burning water heating system. It may be
constructed integrally with the gas shutoff 1.7.140 Valve, service shutoff. A valve,
device, or be a separate assembly. installed by the serving gas supplier between the
service meter or source of supply and the
1 .7.135 Valve, individual main burner. A valve customer piping system, to shutt off the entire
which controls the gas supply to an individual piping system.
main burner.
1.7.141 Valve, shutoff. A valve (located in the
1.7.136 Valve, main burner control. A valve piping system and readily accessible and

27
MS 930: 1986

operable by the consumer) used to shut off clusively upon the direct conversion of the
individual equipment. thermal energy of the vent gases into mechanical
energy.
1.7.142 Valve. tamperproof. Valves designed
and constructed to minimize the possibility of the 1.7.146 Vent gases. Products of combustior’l
removal of the core of the valve accidentally or from fuel-gas burning appliances plus excess air.
willfully with ordinary household tools. plus dilution air in the venting system above the
draft hood or draft regulator.
1.7.143 Vent. A passageway, vertical or nearly
so. used to convey flue gases f~omgas utilization 1.7.147 Vented wa/Ifurnace, A self-contained,
equipment, or their vent connectors, to the vented, fuel-gas burning appliance complete with
outside atmosphere. grilles or equivalent, designed for incorporation
in or permanent attachment to the structure of a
1.7.144 Vent connector. The pipe or duct building and furnishing heated air. circulated by
which connects a fuel-gas burning appliance toa gravity or by a fan directly into the space to be
vent or chimney. heated through openings in the c~sing.Such
appliances should not be provided with duct
NOTE 1. Since a vent is a verticai or nearly vertical passageway. t extensions beyond the vertical and horizontal
follows that any pipe or duct used to connect an appliance(s) to such
vertical vent is a vent connector, However if the vertical vent is limits of the casing proper, except that boots not
connected directly to an appliance draft hood or flue collar, a vent
to exceed 250 mm beyond the horizontal limits of
connector is not invoived,
the casing for extension through walls of nominal
thickness are permitted. When such boots arc
1.7.145 Vent damper device, automatic. A
provided they shall be supplied by the manu
device intended for installation in the venting facturer as an integral part of the appliance. This
system, in the outlet of or downstream of the definition excludes floor furnaces, unit heaters,
appliance draft hood, of an individual auto- direct vent wall furnaces and central furnaces.
matically operated fuel-gas burning appliance
and which is designed to automatically open the (a) Fan type vented wall furnace. A wall furnacc
venting system when the appliance is in operation equipped with a fan.
and to automatically close off the venting system
when the appliance is in a standby or shutdown (b) Gravity type vented wall furnace. A w&!
condition. furnace depending on circulation of air by gravi’L’\’.

(a) Electrically operated. An automatic vent 1.7.148 Venting. Removal of combustion pro-
damper device that employs electrical energy to ducts as well as noxious ortoxic processfumes to
control the device. the outer air by means of roof openings, natum’
draft chimneys, flue stacks, or mechanical
(b)Mechanically actuated. An automatic vent
exhaust systems.
damper device dependent for operation upon the
direct application or transmission of mechanical
energy without employing any type of energy 1.7.149 Venting system.,A continuous open
conversion. passageway from the flue collar or draft hood of a
fuel-gas burning appliance to the outside
(c) Thermally actuated. An automatic vent atmosphere for the purpose of removing flue
damper device dependent for operation ex- gases.

28
MS 930: 1986

NOTE 2. A venting system for exhausting flue gases usualiy is water heater which fu”rnishes hot water to be
composed of a vent or a chimney and vent connector)s(, if used.
assembled to form the open passageway. stored in a separate vessel. Storage tank
temperatures are controlled by means of a
1.7.150 Wall furnace, direct vent. A system thermostat installed on the water heater.
consisting of an appliance, combustion air and Circulation may be either gravity or forced.
flue gas connections between the appliance and
the outdoor atmosphere, and a vent cap supplied (ii) Nonautomatic circulating tank water heater.
by the manufacturer and constructed so that all A water heater which furnishes hot water to be
air for combustion is obtained from the outdoor stored in a separate vessel. Storage tank
atmosphere and all flue gases are discharged to temperatures are controlled by means of a
the outdoor atmosphere. The appliance shall be thermostat installed in the storage vessel.
complete with grilles or equivalent, designed for
incorporation in or permanent attachment to the (c) Coil circulation water heater. A water heater
structure of a building. mobile home or re- whose heat transfer surface is composed
creational vehicle and shall furnish heated air primarily of water tubes less than 38 mm in
circulated by gravity or by a fan directly into the internal diameter and which requires circulation.
space to be heated through openings in the
(d) Commercial storage heater. A water heater
casing. Such appliances shall not be provided
that heats and stores water at a thermostatically
with duct extensions beyond the vertical and
controlled temperature for delivery on demand.
horizontal limits of the appliance casing. except
Input rating: 79.000 kJ (75.000 Btu) per hour or
that boots not to exceed 250 mm beyond the
more.
horizontal limits of the casing for extension
through walls or nominal thickness may be
(e) Counter top domestic storage heater
permitted. This definition excludes floor
furnaces, unit heaters, vented wall lurnaces and (t) Concealed type. A vented automatic storage
central furnaces. heater which is designed for flush installation
beneath a counter top 1 m high, wherein the
1.7.151 Water heater. An
appliance for
entire heater is concealed.
supplying hot water for domestic or commercial
purposes other than for space heating.
(ii) Flush type. A vented automatic storage
water heater with flat sides. top, front and back,
(a) Automatic instantaneous water heater. A
water heater which has a rated input of at least which is designed primarily for flush installation
in conjunction with or adjacent to a counter 1 m
1 .11 5 kJ per hour per litre (4,000 Btu per hour
high, wherein the front and top of the heater
per gallon) of self-stored water. Automatic
control is obtained by water-actuated control. casing are exposed.
thermostatic control. or combination ot water-
(iii) Recessed type. A vented automatic storage
actuated control and thermostatic control. This
water heater with flat sides. top. front and back.
classification includes faucet type water heaters
which is designed for flush installation beneath a
designed to deliver water through a single faucet
counter 1 m high. wherein thefront of the heater
integral with or directlyadjacentto theappliance.
casing is exposed.
(b) Circulating heaters
(f) Domestic storage heater. A water heater that
(i) Automatic circulating tank water heater. A heats and stores water at a thermostatically

29
MS 930: 1986

controlled temperature for delivery on demand. combustion is obtained from the outside
Input rating may not exceed 79.000 kJ (75,000 atmosphere and all flue gases are discharged to
Ecu) per hour. the outside atmosphere.

(g) Side-arm type water heater. A water heater 1.7.153 Zone 0. An area in which any
designed for use with auxiliary storage systems.
flammable atmosphere is continuously present,
usually containing water-carrying parts of the
or present for long periods, in concentrations
tubular or cast element design.
within the lower and upper limits of flammability.
1.7.152 Water hearer, direct vent. A system
consisting of (a) a water heater for indoor 1.7.154 Zone 7. An area in which a dangerous
installation, (b) combustion air connections atmosphere is likely to occur in normal operating
between the water heater and the outside conditions. .

atmosphere. (c) flue gas connections between


the water heater and the vent cap, and (d)vent cap 1.7.155 Zone 2. An area in which a dangerous
for installation outdoors, supplied by the manu- atmosphere can occur only in abnormal con-
facturer and constructed so that all air for ditions and not in normal operation.

30
MS 930: 1986

SECTION TWO: GAS PIPING SYSTEM DESIGN, MATERIALS AND COMPONENTS

2.1 Piping plan three-way valve installed to admit the stand-by


supply and at the same time shutt off the regular
2.1.1 Installation of piping system. Before supply may be used for this purpose.
proceeding with the installation of a gas piping
system, a piping sketch or plan shall be prepared
2.4 Sizing of gas piping systems
showing the proposed location of piping, the size
of different branches, the various load demands 2.4.1 General considerations. Gas piping shall
and the location of the point of delivery. An be of such size and so installed as to provide a
example of a piping sketch or plan may be found supply of gas sufficient to meet the maximum
in appendix C. demand without undue loss of pressure betwen
the point of delivery and the gas utilization
2.1 .2 Addition to existing system. When
equipment. The size of gas piping depends upon
connecting additional gas utilization equipment
the following factors:
to a gas piping system, the existing piping shall be
checked to determine if it has adequate capacity (a) Allowable loss in pressure (see 2.4.4) from
(see 2.4.3). If inadequate, the existing system point of delivery to equipment.
shall be enlarged as required or separate gas
piping of adequate capacity shall be provided. lb) Maximum gas demand.

(c) Length of piping and number of fittings.


2.2 Provision for location of point of delivery

2.2.1 The location of the point of delivery shall (d) Specific gravity of the gas.
be acceptable to the serving gas supplier.
(e) Diversity factor.

2.3 Interconnections between gas piping (f) Foreseeable future demand.


systems
2.4.2 Maximum gas demand. The volume of
2.3.1 Interconnections supplying separate gas to be provided [in cubic metres (or cubic feet)
users. When two or more meters. or two or more per hour] shall be determined directly from the
service regulators when meters are not provided. manufacturer’s input ratings of the gas utilization
are located on the same premises and supply equipment served. When input rating is not
separate users, the gas piping systems shall not indicated. the gas supplier, equipment manu-
be interconnected on the outlet side of the meters facturer. or a qualified agency shall be contacted
or service regulators. for estimating the volume of gas to be supplied.

2.3.2 Interconnections for stand-by fuels. NOTE 3. To obtain the cubic metres (cubic feet) per hour of gas
When a supplementary gas for stand-by use is required, divide the kJ (Btu) per hour rating by the kJ per cubic metre
(Btu per cubic foot) heating value of the gas supplied. The heatingvalue
connected downstream from a meter or a service of the gas may be obtained from the local gas supplier.

regulator when a meter is not provided, a suitable


device to prevent backflow shall be installed. A The total connected hourly load shall be used as

31
MS 930:1986

the basis for piping sizing since all equipment otherwise enclosed for protection against
may be operating at full capacity simultaneously. accidental gas accumulation.
If, however, a diversity of load can be established,
smaller sized piping may be used. (c) The piping is located inside buildings or
separate areas of buildings used exclusively for:
In case the ratings of the equipment to be (i) industrial processing or heating;
installed are not known, table II of appendix C (ii) research;
shows the approximate demand of typical (iii) warehousing; or
appliances by types. (iv) boiler or mechanical equipment rooms.

2.4.3 Allowable pressure drop. The design (d) The piping is a temporary installatiorl for
pressure loss in any piping system under buildings under construction.
maximum. probable flow conditions, from the
point of delivery to the inlet connection of the gas 2.5.2 Gas-air mixture systems. Piping systems
utilization equipment, shall be such that the for gas-air mixtures within the flammable range
supply pressure at the equipment is greater than are limited to a maximum pressure of 70 kPa
the minimum ~~ressure required for proper (gauge) [10 psig].
equipment operation.
2.5.3 Liquefied petroleum gas systems. In no
2.4.4 Pipe sizing methods. For any gas piping case shall the maximum design operating
system, for special gas utilization equipment or pressure for undiluted LP-gas systems exceed
for conditions other than those covered by the 1 40 kPa (gauge) [20 psig], except for buildings, or
capacity tables in appendix C. such as longer separate areas of buildings. (note 4) used
runs, greater gas demands, or greater pressure exclusively to house industrial processes.
drops, the size of each gas piping system shall be research and experimental laboratories, or
determined by standard engineering methods equipment or processing having similar hazards.
acceptable to the authority having jurisdiction.
NOTE 4. separate areas of buildings means fire-isolated areas unless
Two entirely different methods of pipe sizing are otherwise approved by the relevant authority.

presented in appendix C.

2.6 Acceptable piping mate~1aI~


and joining
methods
2.5 Piping system operating pressure limi-
tations 2.6.1 General

2.5.1 Maximum design operatingpressure. The 2.6.1.1 Materials and components conforming
maximum design operating pressure for piping to standards or specifications listed herein
systems located inside buildings shall notexceed and/or acceptable to the authority having
35 kPa (gauge) [5 psig] unless approved by the jurisdiction (see clause A14) may be used for
authority having jurisdiction and one or more of appropriate applications, as prescribed and
the following conditions are met: limited by this Code.

(a) The piping system is welded. 2.6.1.2 Usedmaterials. Pipe, fittings, valves or
other materials shall not be used again unless
(b) The piping is located in a ventilated chase or they are free of foreign materials and have been

32
MS 930: 1986

ascertained to be adequate for the service pipe. centrifugally cast. in metal molds on
intended, sand—lined molds. for gas.

2.6.1.3 Other materials. Materials not covered (b) ASTM A377 Specification for gray iron and
by the standards, specifications listed herein shall ductile iron pressure pipe.
be investigated and tested to determine that it is
safe suitable for the proposed service, and, in Such pipe shall be not less than 80 mm (3-inch)
addition, shall be recommended for that service size, shall not be welded and shall be used only
by the manufacturer and shall be acceptable to underground outside building foundation
the authority having jurisdiction. boundaries, or aboveground. provided thatjoints
are properly restrained against movement and
2.6.2 Metallic pipes separation.

2.6.2.1 Cast-iron pipe shall not be used. 2.6.2.4 Copper and brass pipe shall not be
used if the gas contains more than an average of
2.6.2.2 Steel and wrought-iron pipe shall be at 0.1 grain of hydrogen sulphide per standard
least of standard weight (schedule 40) or cubic metre of gas. This is equivalent to a trace as
equivalent and shall comply with one of the determined by the following applicable standard:
following standards:
(a) ANSI/ASTM D2385 Test for hydrogen
(a) MS 862 Specification for welded and sulphide and mercaptan sulphur in natural gas.
seamless steel pipes for general pressure (Cadmium sulphate-iodometric titration
purposes. method), or

(b) MS 863 Specification for welded and (b) ANSI/ASTM D2420 Test for hydrogen
seamless steel pipes (6 mm 1 50 mm), screwed-
-
sulphide in liquefied petroleum LP gases (Lead
type. acetate method).

(c) ANSI B36.10 The Standard for welded and Threaded copper. brass or aluminium alloy pipe
seamless wrought-steel pipe. in iron pipe sizes may be used with gases not
corrosive to such material.
(d) ANSI/ASTM A53 Specification for black and
hot-dipped, zinc-coated welded and seamless 2.6.2.5 Aluminium alloy pipe shall comply with
steel pipe. ANSI/ASTM B24l ‘Standard specification for
aluminium-alloy seamless pipe and seamless
(e)ANSI/ASTM Al 06 Specification for seamless extruded tube, (except that the use of alloy 5456 is
carbon steel pipe for high-temperature service. cjrohibited), and shall be suitably marked ateach
end of each length indicating compliance.
(f) ANSI/ASTM Al 20 Specification for black Aluminium alloy pipe shall be coated to protect
and hot-dipped zinc-coated (galvanized) welded against external corrosion where it is in contact
and seamless steel pipe for ordinary uses. with masonry, plaster. or insulation or is subject
to repeated wettings by such liquids as water.
2.6.2.3 Nodular (ductile) iron pipe shall comply detergents or sewage.
with one of the following standards:
Aluminium alloy pipe shall not be used in exterior
(a) ANSI A21 .52 The standard for ductile-iron locations or underground.

33
MS 930 : 1 986

2.6.3 Metallic tubing. Seamless copper. Aluminium-alloy tubing shall be coated to protect
aluminium alloy or steel tubing may be used with against external corrosion where it is in contact
gases not corrosive to such material.. with masonry. plaster, or insulation or is subject
to repeated wettings by such liquids as water,
(a) Steel tubing shall comply with: detergents or sewage.

(i) ANSI/ASTM A539 Standard specification for Aluminium-alloy tubing shall not be used in
electric-resistance-welded coiled steel tubing for exterior locations or underground.
gas and fuel oil lines, or
2.6.4 Plastic pipe, tubing and fittings. Plastic
(ii) ANSI/ASTM A254 Standard specification pipe or tubing and compatible fittings shall be
for coper brazed steel tubing. used outside underground only and -shall
conform with
(b) Copper tubing shall comply with-standard
type K or L. of (a) ASTM 02513 Specification for thermo-
plastic gas pressure pipe, tubing and fittings. or
(i). ANSI/ASTM B88 Standard specification for
seamless copper water tube, on (b) ASTM D25 1 7 Specification for reinforced
(ii) ANSI/ASTM 8280 Standard specification expoxy resin gas pressure pipe and fittings, or
for seamless copper tube for air conditioning and
refrigeration field service. (c) equivalent standards approved by the
authority having jurisdiction (see clause Al 4).
Copper and brass tubing and fittings (except tin-
lined copper tubing) shall not be used if the gas 2.6.5 Workmanship and defects. Gas pipe or
contains more than an average of 0.1 grain tubing and fittings shall be clear and free from
hydrogen sulphide per standard cubic metre of cutting burrs and defects- in. structure or
gas. This is equivalent to a trace as determined by threading and shall be thoroughly brushed, and
the following applicable standard: chip and scale blown.

(i) ANSI/ASTM D2385 Test for hydrogen Defects in pipe or tubing or fittings shall not be
sulphide and mercaptan sulphur natural gas repaired. When defects in pipe, tubing orfittirtgs
(cadmium sulphate-iodometnic titration method). are located in a system, the defective material
or shall be replaced.

(ii) ANSI/ASTM D2420 Test for hydrogen 2.6.6 Protective coating. When in contact with
sulphide in liquefied petroleum (LP) gases (lead material or atmosphere exerting a corrosive
acetate method) action, metallic piping and fittings coated with a
corrosion-resistant material shall be used.
(c) Aluminium alloy tubing shall comply with
External or internal coatings or linings used or~
(i) ANSI/ASTM B2 1 0 Standard specification for piping or components shall not be considered as
aluminium-alloy drawn seamless tubes. or adding strength.

(ii) ANSI/ASTM B241 Standard specification 2.6.7 Metallic pipe threads


for aluminium-alloy seamless pipe and seamless
extruded tube. 2.6.7.1 Specif~ations for pipe threads. Metallic

34
MS 930: 1986

pipe and fitting threads shall be taper pipe threads 2.6.8.1 Pipe joints shall be threaded.flanged or
and shall comply with ANSI B2.l. ‘Standard for pipe welded, and nonferrous pipe may also be
threads (Except dryseal)’. soldered or brazed with materials having a
melting point in excess of 540°C. Brazing alloys
2.6.7.2 Damaged threads. Pipe with threads shall not contain phosphorous.
which are stripped, chipped, corroded or
otherwise damaged shall not be used. If a weld Threaded joints shall not be used in annealed.
opens during the operation of cutting or tempered aluminium pipe.
threading, that portion of the pipe shall not be
used. 2.6.8.2 Tubing joints shall either be made with
approved gas tubing fittings or be soldered or
2.6.7.3 Number of threads. Table 1 may be
brazed with a material having a melting point in
used as a guide for field threading of metallic
excess of 540°C. Brazing alloys shall not contain
pipe.
phosphorous. Metallic ball sleeve compression
type tubing fittings shall not be used for this
Table 1. Specifications for threading metallic purpose.
pipe
2.6.8.3 Flared joints shall be used only in
Iron pipe Approximate length Approximate number1
systems constructed from nonferrous pipe and
size of threaded portion of threads to be
mm (inches) mm cut tubing where experience or tests have demons-
trated that the joint is suitable for the conditions
15 (½) 20 10
20 (34) 20 10
and where adequate provisions are made in the
25 (1) 22 10 design to prevent separation of the joints.
32 (11/4) 25 11
40 (1½) 25 11
50 (2) 25
2.6.8.4 Approved couplings and proprietary
11
65 (2½) 40 12 type joints may be used within the manufacturer’s
80 (3) 40 12 pressure-temperature recommendations, pro-
100 (4) 42 13
vided adequate provision is made to prevent
separation of the joint due to vibration, fatigue
2.6.7.4 Threaded pipe sizes. Threaded pipe in and thermal expansion or contraction.
sizes larger than 100 mm (4 inches) shall not be
used unless acceptable to the authority having 2.6.8.5 Metallic fittings (except valves.
jurisdiction. strainers or filters) shall be steel, brass or
malleable and cast iron or ductile iron when used
2.6.8 Metallic piping joints and fittings. The with steel orwrought-iron pipe: shall becopperor
type of piping joint used shall be suitable for the brass when used with copper or brass pipe; and
pressure-temperature conditions and shall be shall be aluminium alloy when used ~ivith
selected giving consideration to joint tightness aluminium alloy pipe.
and mechanical strength under the service
conditions. The joint shall be able to sustain the (a) When approved by the authority having
maximum end force due to the internal pressure jurisdiction, special fittings. such as saddle tees
and any additional forces due to temperature and gland-type compression couplings. may be
expansion or contraction. vibration, fatigue onto used to connect steel or wrought-iron pipe If
the weight of the pipe and its contents. adequately braced so that neither the gas

35
MS 930:1986

pressure nor external physical damage will force method used shall be compatible with the
the joint apart. materials being joined and the recommendations
of the manufacturer. The following shall be
(b) Cast-iron fittings (including valves, strainers observed when making such joints:
and filters) in sizes 1 50 mm (6 inches) and larger
may be used to connect steel and wrought-iron (a) Plastic pipe or tubing shall not be threaded.
pipe when approved by the authority having
jurisdiction. (b) The joint shall be designed and installed so
that the longitudinal pull-out resistance of the
(c) Cast-iron fittings in sizes 1 00 mm (4 inches) jointwill beatleastequaltothetensilestrength of
and larger shall not be used indoors unless the plastic piping material.
approved by the authority having jurisdiction.
(c) Solvent cement joints, adhesive joints and
(d) Cast-iron fittings and zinc-aluminium valves heat-fusion joints shall be made in accordance
and fittings shall not be used in systems with qualified procedures which have been
containing flammable gas-air mixtures. established and proven by test to produce
gastight joints at least as strong as the pipe or
(ej Cast-iron flanges may be used. tubing being joined.

(f) Fittings in copper or brass piping systems. if (d) Solvent cement or heat-fusion joints shall
exposed to soil, shall be made of bronze,. copper not be made between different kinds of plastics.
,or brass containing not less than 80% copper.
(e) Heat-fusion, electro-fusion or rniechanical
(g) Approved flared, flareless or compression joints shall be used when joining polyethylene
(other than metallic ball sleeve) type tubing pipe, tubing or fittings.
fittings may be used provided they meet the
manufacturer’s pressure-temperature recom- (f) Flanges or special joints may be used
mendations for the fittings and the service provided they are properly qualified and utilized.
conditions anticipated, such as vibration, fatigue
and thermal expansion or contraction. (g) When compression type mechanical joints
are used, the gasket material in the fitting shall be
2.6.8.6 Bushings. Cast-iron or plastic compatible with the plastic piping and with the
bushings, orange-peel bull plugs. orange-peel gas distributed by the system. An internal tubular
swages and fish tails shall not be used. rigid stiffener shall be used in conjunction with
the fitting, and the stiffener shall be flush with the
2.8.8.7 Joint compounds. Joint compounds end of the pipe or tubing and extend at least to the
(pipe dope) shall be resistant to the action of outside end of the compression fitting when
liquefied petroleum gas or to any other chemical installed. The stiffener shall be free of rough or
constituents of the gases to be conducted s’harp edges and shall not be a force fit in the
through the piping. plastic. A split tubular stiffener shall not be used.

2.3.9 Plastic piping joints and fittings. Plastic (h) For plastic piping joints and fittings for use in
pipe, tubing and fittings. shall be joined by either liquefied petroleum gas piping systems, see
the solvent cement method, adhesive method. MS 830 : 1 983(P). ‘Code of Practice for the
heat-fusion me~hod.electro-fusion or by means storage. handling and transportation of liquefied
of compression couplings or flanges. The joining petroleum gases’.

36
MS 930:1986

(j) Compatibility of materials being joined when 2.6.11.2 When a flanged joint is opened, the
supplied by different suppliers or made of ‘gasket shall be replaced.
dissimilar resins must first be established to the
satisfaction of the authority having jurisdiction. 2.6.11.3 Full-face gaskets shall be used with all
The compatibility may be established if any of the bronze and cast-iron flanges.
following conditions is met:

(i) compatibility of materials declared by the 2.7 Gas meters


manufacturer,
2.7.1 Capacity. Gas meters shall be properly
(ii) attestation by accredited laboratories. selected for the maximum expected pressure and
permissible pressure drop.
2.6.10 Flanges. All flanges shall comply with
the standards and specifications as listed in 2.7.2 Location
appendix A. The pressure-temperature ratings
shall equal or exceed that required by the 2.7.2.1 Gas meters shall be located in
ventilated spaces readily accessible for
application.
examination, reading, replacement or necessary
(a) Flange facings. Standard facings are maintenance.
suitable for use under this Code. When 68 kg
steel flanges are bolted to Class 1 25 cast-iron 2.7.2.2 Gas meters shall not be placed where
flanges, the raised face on the steel flange shall they will be subjected to damage, such as
be removed. adjacent to a driveway, under a fire es~apé,in
public passages. halls, coal bins, or where they
(b) Lapped flanges. Lapped flanges may be will be subject to excessive corrosion or vibration.
used only aboveground or in exposed locations
accessible for inspection. 2.7.2.3 Gas meters shall be located at least 1 m
from sources of ignition.
2.6.11 Flange gaskets. Material for gaskets
shall be capable of withstanding the design 2.7.2.4 Gas meters shall not be located where
they will be subjected to extreme temperatures or
temperature and pressure of the piping system,
sudden extreme changes in temperature. Meter
and the chemical constituents of the gas being
manufacturers shall furnish information re-
conducted. without change to its chemical and
garding safe temperature limits.
physical properties. The effects of fire exposure to
the joint shall be considered in choosing material.
2.7.3 Supports. Gas meters shall be securely
supported or connected to rigid piping so as not
2.6.11.1 Acceptable materials include:
to exert a strain on the meters. When flexible
(a) Metal or metal-jacketed asbestos (plain or connectors are used to connect a gas meter to
corrugated). downstream piping at mobile homes in mobile
home parks, the meter shall be supported by a
(b) Asbestos. post or bracket placed in a firm footing or other
means providing equivalent support.
(c) Aluminium ‘0’ rings and spiral wound metal
gaskets. 2.7.4 Meter protection. Meters shall be pro-

37
MS930:1986

tected against overpressure. backpressure and (d) A line pressure regulator shall not be vented
vacuum, if necessary. to the gas equipment flue or exhaust system.

2.7.5 ldentifióation. Gas piping at multiple 2.8.4.2 Gas appliance pressure regulators. Fe
meter installations shall be plainly marked by a venting of gas appliance pressure regulators. see
metal tag or other permanent means attached by 5.1.15.
the installing agency. designating the building or
the part of the building being supplied. 2.8.5 Bypass piping. Suitably valved end
regulated bypasses may be placed around gas
line pressure regulators where continuity of
2.8 Gas pressure regulators service is imperative.

2.8.1 When required. When the gas supply


2.8.6 Identification. Line pressure regulators
pressure is higher than that at which the branch
at multiple regulator installations shall be plainly
supply line or gas utilization equipment is
marked by a metal tag or other permanent means
designed to operate or varies beyond design
designating the building or the part of the
pressure limits, a line gas pressure regulator or
building being supplied.
gas equipment pressure regulator. as applicable.
shall be installed.
2.8.7 Second stage LP-gas regulators. Second
2.8.2 Location. The gas pressure regulator stage regulators on undiluted liquefied petro
location shall be such that the connections are leum gas piping systems shall comply witli
readily accessible for servicing. ANSI/UL 144, ‘Standard for pressure regulating
valves for LP-gas.’ and shall be installec.l in
2.8.3 Regulator protection. Pressure re- accordance with MS 830 : 1 983(P), ‘Code ci
gulators shall be protected or so located against Practice for the storage. handling and trans-
accidental damage. portation of liquefied petroleum gases’.

2.8.4 Venting
2.9 Overpressure protection devices
2.8.4.1 Line gas pressure regulators
2.9.1 General
(a) An adequately sized independent vent to the
outside of the building shall be provided when the Overpressure protection devices shall be pro-
line pressure regulator at its location is such that vided to prevent the pressure in the piping system
a ruptured diaphragm will cause a hazard. See from exceeding that value which would caine
2.9.7 for properly locating the vent. unsafe operation of any connected and propoiN,.’
adjusted gas utiliz~ationequipment. (See 2.9.5).
(b) The vent shall be designed to prevent the
entry of water, insects or other foreign materials 2.9.1.1 The requirements of this section shaH
that could cause blockage. be met and a piping system deemed to hove
adequate overpressure protection when there are
(c) At locations where line pressure regulators two acceptable devices (a service or line pressure
might be submerged during floods, a special anti- regulator plus one other device), each limiting the
flood type breather vent fitting shall be installed. pressure to a value’ that does not exceed the
or the vent line shall be extended above the height maximum working pressure of the downstream
of the expected flood waters. system. both of which must fail simultaneously in

38
MS 930 : 1986

order to overpressure the downstream system. 2.9.2 Devices. Any of the following pressure
(Note 5). The pressure regulating. limiting and relieving or pressure limiting devices may be
relieving devices shall be properly maintained used:
and inspection procedures shall be devised or
suitable instrumentation installed to detect (a) Spring loaded relief device.
failures or malfunctions of such devices and
replacements or repairs shall be promptly made. (b) Pilot loaded backpressure regulator used as
a relief valve so designed that failure of the pilot
NOTES. A pressure regulator with a buiit in safety device is deemed system or external control piping will cause the
sufficient to meet this requirement or if the regulators are arranged in regulator relief valve to open.
parallel.

(c) A monitoring regulator installed in series


2.9.1.2 No pressure relieving or limiting device with the service or line pressure regulator.
is required if the gas does not contain materials
that could seriously interfere with the operation (d) A series regulator installed upsiream from
of the service or line pressure regulator and if the the service or line regulator and set to
service or line pressure regulator has all of the continuously limit the pressure on the inlet of the
following design features or characteristics: service or line regulator to the maximum working
pressure of the downstream piping system.
(a) Pipe connections to the service or line
regulator do not exceed 50 mm (2 inches) (c) An automatic shutoff device installed in
nominal diameter. series with the service or line pressure regulator
and set to shut off when the pressure on the
(b) It is self-contained with no external static or downstream piping system reaches the maximum
control piping. working pressure or some other predetermined
pressure less than the maximum working
(c) It has a single port valve with an orifice pressure. This device shall be designed so that it
diameter no greater than that recommended by will remain closed until manually reset.
the manufacturer for the maximum gas pressure
at the regulator inlet. (f) A liquid seal relief device that can be set to
open accurately and consistently at the desired
(d) The valve seat is made of resilient material pressure.
designed to withstand abrasion of- the gas.
impurities in the gas and cutting by the valve and The above devices may be installed as an integral
to resist permanent deformation when it is part of the service or line pressure regulator or as
pressed against the valve port. separate units. If separate pressure relieving or
pressure limiting devices are installed, they shall
(e) It is capable, under normal operating comply with 2.9.3 through 2.9.8.
conditions, of regulating the downstream
pressure within the necessary limits of accuracy 2.9.3 Construction and installation. All
and of limiting the discharge pressure under no- pressure relief or pressure limiting devices shall:
flow conditions to not more than 1 50% of the
discharge pressure maintained under flow (a) Be constructed of materials so that the
conditions. operation of the device will not normally be
MS 930: 1986

impaired by corrosion of external -parts bV the outlet parts. of all pressure relief and pressure
atmosphere or of internal part-s. by the gas. limiting devices shall.be located so that gas is
discharged into the atmosphere without undue
(b) Be designed and installed so they can be hazard. Discharge stacks or vents shall be
readily operated to determine if the.valve is free. designed to prevent the entry of water, insects or
The devices shall also be designed and installed other foreign material that could cause blockage.
so they can be tested to determinethe pressure at The discharge stack or vent line shall be atleast
which the-y will operate and examined for leakage the same size as the outlet of the pressure
when in the closed position.~ relieving device.

2.9.4 External control piping. External control 2.9.8 Size of fittings. pipe and openings. The
piping shall be reasonably protected from falling openings. pipe and fittings located between the
objects. excavations or other causes of damage s~’stemto be ptotected and the pressure relieving
and shall be designed and installed so that device shalF be of adequate size to prevent
damage to -any control piping shall not render hammering of the valve and to prevent
both ~he r~gulatorand the overpressure pro- impairment of relief capacity.
tective device inoperative.

2.9.5 Setting. Each pressure limiting or


pressure relieving device shall be set so that the 2.10 Back pressure protection
pressure shall not exceed a safe level beyond the
2.10.1 When to install. When. the design of
ma$<imum allowable workiitg pressure for the
utilization equipment connected is such that air,
piping and appliances connected:
oxygen or stand-by gases may be forced into the
gas supply system.. suitable protective devices
2.9.6 Unauthorized operation. Precautions
.

shall be installed as close to the utilization


shall be taken to prevent unauthorized operation
equipment as practical. Gas and air combustion
of any shutoff valve which will make a pressure
relief valve or pressure -limitin9 device -in- mixers incorporating double diaphragm ‘zero’ or
operative. Acceptable methods for complying ‘atmosphere’ governors or regulators require no
further protection unless connected directly to
vVith this provision are: - -

compressed air or oxygen at pressures of 35 kPa


(a) Lock the valve in the open position. Instruct (gauge) [5 psig] or more.
authorized personnel of the importance of
lea~vingthe shutoff valve open and of being 2.10.2 Suitable devices. Suitable protective
present’while the-shutoff valve is closed’so that it devices include but are not limited to the
can be locked in the open position before leaving following:
the premises. -. . -

(a) Check valves.


(b) Install duplicate relief valves. each having
adequate capacity to protect the system~’a’nd (b) Three-wayvalves (of the typethat completely
arrange the isolating valvesor-3-wayvalve so that closes one side before starting to open the other
only one safety device can be rendered in- side). -

operative at a time. . -

(c) Reverse flow indicators controlling positive


2.9.7 Vents. The discharge stacks, vents or shutoff valves.

40
MS 930:1986

(d) Normally closed air-actuated positive- excessive stresses in the piping material,
shutoff pressure regulators. excessive bending or loads at joints. or
undesirable forces or moments at points of
connections to equipment and at anchorage or
2.1 1 Low pressure protection
guide points. Formal calculations or model tests
shall be required only where reasonable doubt
2.11.1 A suitable protective device shall be
exists as to the adequate flexibility of the system.
installed between the meter and the gas
utilization equipment if the operation of the Flexibility shall be provided by the use of bends.
equipment is such (i.e. gas compressors) that it loops, offsets or couplings of the slip type.
may produce a vacuum or a dangerous reduction
Provision shall be made to absorb thermal
in gas pressure at the meter. Such devices changes by the use of expansion joints of the
include, but are not limited to mechanical.
bellows type. or by the use of ‘ball’ or ‘swivel’
diaphragm-operated or electrically operated low-
joints. Expansion joints of the slip type shall not
pressure shutoff valves.
be used inside buildings or for thermal
expansion. If expansion joints are used, anchors
2.12 Shutoff valves or ties of sufficient strength and rigidity shall be
installed to provide for end forces due to fluid
2.12.1 Shutoff valves shall be approved and pressure and other causes.
shall be selected giving considerationto pressure
drop. service involved, emergency use and Pipe alignment guides shall be used with
reliability of operation. expansion joints according to the recommended
practice of the joint manufacturer.

2.13 Expansion and flexibility 2.13.2 Sç5ecial local conditions. Where local
conditions include unstable ground or flood
2.13.1 Design. Piping systems shall be hazards, special consideration shall be given to
designed to have sufficient flexibility to prevent increased strength and flexibility of piping
thermal expansion or contraction from causing supports and connections.

41
MS 930:1986

SECTION THREE: GAS PIPING INSTALLATION

3.1 Piping underground (c) Backfilling. Where flooding of the trench is


done to consolidate the backfill, care shall be
3.1.1 Clearances. Underground gas piping exercised to see that the pipe is not floated from
shall be installed with enough clearancefrom any its firm bearing on the trench bottom.
other underground structure to avoid contact
therewith, to allow proper maintenance and to 3.1.3 Protection against corrosion. Gas piping
protect against damage that might result from in contact with earth, or other material which may
proximity to other structures. In addition, corrode the piping, shall be protected against
underground plastic piping shall be installed with corrosion in an approved manner. When dis-
sufficient clearance, or shall be insulated, from similar metals are joined underground, an
any source of heat so as to prevent the heat from insulating coupling orfitting shall be used. Piping
impairing the serviceability of the pipe. shall not be laid in contact with cinders.

3.1.2 Protection against damage. Where soil Uncoated threaded or socket welded joints
conditions are unstable and settling of piping or shall not be used in piping in contact with soil or
foundation walls or heavy vehicular traffic may where internal or external crevice corrosion may
occur, adequate measures shall be provided to occur.
prevent excessive stressing of the piping. Piping
shall be buried a sufficiertt depth or covered in a 3.1.4 Connection of plastic piping. Con~-
manner so as to protect the piping from physical nections between metallic and plastic piping
damage. shall be made only outside, underground and
with approved transition fittings.
Consideration should be given to protecting the
piping from physical damage when it passes 3.1.5 Piping through foundation wall. Under-
through flower beds, shrub beds and other such ground piping. when installed below ground level
cultivated areas. through the outer foundation or basement wall of
a building. shall be encased in a protective pipe.
(a) Cover requirements. Underground piping The annular space between the gas piping and
systems shall be installed with at least 450mm of the sleeve shall be sealed at the foundation or
cover. The cover may be reduced to 300 mm if basement wall to prevent entry of gas or water.
external damage to the pipe is not likely to result.
If a minimum of 300 mm of cover cannot be 3.1.6 Piping underground beneath buildings.
maintained, the pipe shall be installed in conduit When the installation of gas piping underground
or bridged (shielded). beneath buildings is unavoidable, the piping shall
be encased in an approved conduit designed to
(b) Trenches. The trench shall be graded so withstand the superimposed loads. The conduit
that the pipe has a firm, substantially continuous shall extend into a normally usable and
bearing on the bottom of the trench. accessible portion of the building and atthe point

42
MS 930: 1986

where the conduit terminates in the building, the than 15 mm in 10 metres to prevent traps.
space between the conduit and the gas piping Horizontal lines shall slope upward to risers and
shall be sealed to prevent the possible entrance of from the risers to meter, or service regulatorwhen
anygas leakage. lftheend sealing isofatypethat a meter is not provided, or to the appliance.
will retain the full pressure of the pipe. the conduit
shall be designed for the same pressure as the 3.3.4 Above-ceiling locations. Gas piping may
pipe. The conduit shall extend at least 1 00 mm be installed in accessible above-ceiling spaces,
outside the building, be vented above ground but if. such spaces are used as a plenum, the gas
level to the outside and be installed so as to piping must be welded. Valves shall not be
prevent the entrance of water and insects. located in such spaces.

3.3.5 Prohibited locations. Gas piping inside


3.2 Aboveground piping outside any building shall not be run in or through a
circulating air duct, clothes chute. chimney or
3.2.1 Piping installed aboveground shall be gas vent, ventilating duct, dumb waiter, enclosed
securely supported and located where it will be staircase or elevator shaft. This provision shall
protected from physical damage. When passing not apply to ducts used to provide combustion
through an outside wall, the piping shall also be and ventilation air in accordance with 5.3 or to
protected against corrosion by coating or above-ceiling spaces as covered in 3.3.4.
wrapping with an inner material. When piping is
encased in a protective pipe sleeve, the annular 3.3.6 Hangers. supports and anchors’
space between the gas piping and the sleeve shall
3.3.6.1 Piping shall be supported in a
be sealed at the wall to prevent the entry of water,
substantial and workmanlike manner with pipe
insects or rodents.
hooks, metal pipe straps, bands, brackets or
hangers suitable for the size of piping, of
3.3. Piping in buildings adequate strength and quality, and located at
proper intervals so as to prevent or damp out
3.3.1 Building structure excessive vibration. Piping shall be anchored
sufficiently to prevent undue strains on
3.3.1.1 The installation of gas piping shall not connected equi~mentand shall not be supported
cause structural stresses within building by other piping. Pipe hangers and supports shall
components to exceed allowable design limits. conform to the requirements of MSS SP-58.
‘Standard practices for pipe hangers and
3.3.1.2 Before any beams or joists are cut or supports—materials, design and manufacture’.
notched, permission shall be obtained from the
authority having jurisdiction. 3.3.6.2 Spacings of supports in gas piping
installations shall not be greater than shown in
3.3.2 Other than dry gas. Drips, sloping, and table 2.
branch pipe connections, as provided for in
3.3.3, 3.7.1 and 3.9.1, shall apply only when 3.3.6.3 Supports, hangers and anchors shall
other than dry gas is distributed. be installed so as not to interfere with the free
expansion and contraction of the piping between
3.3.3 Gas piping to be sloped. Piping for other anchors. Suitable spring hangers, sway bracing.
than dry gas conditions shall be sloped not less etc. shall be provided where necessary. All parts

43
MS 930:1986

of the supporting equipment shall be designed laid in channels in the floor suitably covered to
and installed so that they will not be disengaged permit access to the piping with a minimum of
by movement of the supported piping. damage to the building. When piping in floor
channels may be exposed to excessive moisture
3.3.7 Removal ofpipe. If piping containing gas or corrosive substances, it shall be suitably
is to be removed, the line shall be first protected.
disconnected from all sources of gas and then
thoroughly purged with air, water or with inert gas 3.4.3.2 In other than industrial occupancies
before any cutting or welding is done. (See 4.3). and when approved by the authority having
jurisdiction, gas piping may be embedded in
Table 2. Support of piping concrete floor slabs constructed with Portland
cement. Piping shall be surrounded with a
Steel pipe, Nominal
nominal Spacing of size of Spacing of minimum of 40 mm of concrete and shall not be
size of pipe supports tubing supports in physical contact with other metallic structures
mm m mm m
(inches) (inches O.D.) such as reinforcing rods or electrically neutral
conductors. All piping, fittings and risers shall be
15 (½) 1.8 15 (½) 1.2
protected against corrosion in accordance with
2.6.6. Piping shall not be embedded in concrete
20 (3,4) or 2.4 16 (%) or 1.8
25(1) slabs containing quickset additives or cinder
2O(~A)
aggregate.
32 (1¼) or 3.0 22 (Ye) or 2.4
larger 25 (1)
[horizontal] 3.4.4 Connections in original installations.
32 (1%) or every floor
When installing gas piping, which is to be
larger level concealed, unions, tubing fittings, running
[vertical]
threads, right and left couplings, bushings. and
swing joints made by combinations of fittings
shall not be used.

3.4 Concealed piping in buildings 3.4.5 Reconnections. When necessaryto insert


fittings in gas pipe which has been installed in a
3.4.1 General. Gas piping may be installed in concealed location, the pipe may be reconnected
concealed locations in accordance with the by welding. flanges. or the use of a ground joint
following: union with the nut centre punched to prevent
loosening by vibration. Reconnection of tubing in
3.4.2 Piping in partitions. Concealed gas
a concealed location is prohibited.
piping shall not be located in solid partitions.
Tubing shall not be run inside hollow walls or
partitions unless protected against physical
damage. This provision does not apply to tubing 3.5 Piping in vetrical chases
which passes through walls or partitions.
3.5.1 Pressure reduction. If pressure reduction
3.4.3 Piping in floors. is needed in branch connection for compliance
with 2.5.1, such reduction shall take place either
3.4.3.1 Except as provided in 3.4.3.2 gas inside the chase or immediately adjacent to the
piping in solid floors such as concrete shall be outside wall of the chase. Regulator venting and

44
MS 930:1986

downstream over-pressure protection shall buckling, cracks or other evidence of mechanical


comply with 2.8.3 and 2.9. The regulator shall be damage.
accessible for service and repair.
(c) The longitudinal weld of the pipe shall be
(a) Regulators equipped with a vent limiting near the neutral axis of the bend.
means may be vented into the chase.
(d) Pipe shall not be bent through an arc of
(b) Regulators not equipped with a vent limiting more than 90 degrees.
means shall be vented directly to the outdoors or
to a point within the top 300 mm of the chase. (e) The inside radius of a bend shall be not less
than 6 times the outside diameter of the pipe.
3.5.2 Construction, Chase construction shall
comply with the Uniform Building By-Laws with 3.6.1.2 ‘Plastic pipe.
respect to fire resistance and protection of
horizontal and vertical openings. (a) Plastic pipe may be bent provided that the
pipe is not damaged and the internal diameter of
3.5.3 Ventilation. A chase shall be ventilated to the pipe is not effectively reduced.
the outdoors and only at the top. The opening(s)
shall have a minimum free area equal to the (b) The radius of the inner curve of such bends
product of one-half of the maximum pressure in shall not be less than 25 times the inside diameter
the piping times the largest nominal diameter of of the pipe.
that piping. Or the cross-sectional area of the . .

- - (c) When the piping manufacturer specifies the


chase, whichever is smaller: When more than one - . -

use of special bending equipment or procedures.


fuel gas piping system is present the free area for
-

such equipment or procedures shall be used.


each system shall be calculated and the largest
area used. 3.6.1.3 Mitred bends. Mitred bends are
permitted subject to the following limitations:
NOTE 6. Only vertical chases are recognized by the coverage. it is
beiievedthatweided~ointsforahorizontaigasiinewouidbepreferabie (a) Mitres shall not be used in systems having a
to a horizontal chase.
design pressure greater than 345 kPa (gauge)
[50 psig]. Deflections caused by misalignments
up to 3 degrees are not considered as mit-res.
3.6 Gas pipe turns
(b) The total deflection angle of each mitre shall
3.6.1 Changes in direction of gas pipe may be not exceed 90 degrees.
made by the use of fittings, factory bends or field
bends. (c) Care shall be taken in making mitred joints
to provide proper root opening and alignment
3.6.1.1 Metallic pipe and full weld penetration.

(a) Bends shall be made only with bending 3.6.1.4 Elbows. Factory made welding elbows
equipment and procedures especially intended or transverse segments cut therefrom may be
for that purpose. used for changes in direction provided that the
arc length measured along the crotch is at least
(b) All bends shall be smooth and free from 25 mm in pipe sizes 50 mm (2 inches) and larger.

45
MS 930:1986

3.7 Drips and sediment traps installed in accordance with the manufacturer’s
installation instructions.
3.7.1 Provide drips where necessary. A drip
shall be provided at any point in the line of pipe 3.8.2 Cap all outlets
where condensate may collect. When con-
densation is excessive, a drip should be provided 3.8.2.1 Each outlet, including a valve or cock
at the outlet of the meter. This drip should be so outlet, shall be securely closed gastight with a
installed as to constitute a trap wherein an threaded piug or cap immediately after
accumulation of condensate will shut off the flow installation and shall be left closed until the gas
of gas before it will run back into the meter. utilization equipment is connected thereto.
Likewise, when the equipment is disconnected
3.7.2 Location of drips. All drips shall be from an outlet and the outlet is not to be used
installed only in such location that they will be again immediately. it shall be securely closed
readily accessible to permit cleaning or emptying. gastight. The outlet shall not be closed with tin
A drip shall not be located where the condensate caps, wooden plugs, corks, or by other
is likely to freeze. improvised methods.

3.7.3 Sediment traps. See 5.5.6. 3.8.2.2 The above provision does not prohibit
the normal use of a listed quick-disconnect
-

device.
3.8 Outlets

3.8.1 Location and installation 3.9 Branch pipe connection

3.8.1.1 The outlet fittings or piping shall be 3.9.1 Except on undiluted liquefied petroleum
securely fastened in place. gas supply systems. all branch outlet pipes shall
be taken from the top or sides of horizontal lines
3.8.1,2 Outlets shall not be located behind and not from the bottom.
doors.
3.9.2 When a branch outlet is placed on a main
3.8.1.3 Outlets shall be located far enough supply line before it is known what size pipe will
from floors, walls, patios, slabs and ceilings to be connected to it, the outlet shall be of the same
permit the use of proper wrenches without size as the line which supplies it.
straining, bending or damaging the piping.

3.8.1.4 The unthreaded portion of gas piping


outlets shall extend not less than 25 mm through 3.10 Manual gas shutoffvalve (Also see 5.5.4)
finished ceilings or indoor or outdoor walls.
3.10.1 Valves at regulators. An accessible gas
3.8.1.5 The unthreaded portion of gas piping shutoff valve shall be provided upstream of each
outlets shall extend not less than 50 mm above gas pressure regulator. Where two gas pressure
the surface of floors or outdoor patios or slabs. regulators are installed in series in a single gas
line, a manual valve is not required at the second
3.8.1.6 The provisions of 3.8.1.4 and 3.8.1.5 regulator.
do not apply to listed quick-disconnect devices of
the flush-mounted type. Such devices shall be 3.10.2 Valves controlling multiple systems

4~
MS 930:1986

3.10.2.1 Accessibility of gas valves. Main gas the flammable range, they shall be provided with
shutoff valves controlling several gas piping suitable stops to prevent adjustment of the
systems shall be readily accessible for operation mixture to within or approaching the flammable
and installed so as to be protected from physical range.
damage. They shall be plainly marked with a metal
tag attached by the installing agency so that the
gas piping systems supplied through them can be 3.13 System containing flammable gas-air
readily identified. mixtures

3.10.2.2 Shutoff valves for multiple house 3.13.1 Required components. A central premix
lines. In multiple tenant buildings supplied system with a flammable mixture in the blower or
through a master meter, or one service regulator compressor shall consist of the following
when a meter is not provided, or where meters or cpmponents:
service regulators are not readily accessible from
the equipment location, an individual shutoff (a) Gas-mixing machine in the form of an
valve for each apartment or tenant line shall be automatic gas-air proportioning device com-
provided at a convenient point of general bined with a downstream blower or compressor.
accessibility.
(b) Flammable mixture piping, minimum
In a common system serving a number of Schedule 40 NPS or equivalent.
individual buildings, shutoff valves shall be
installed at each building. (c) Automatic firecheck(s).

3.10.3 Emergency shutoff valves. An exterior (d) Safety blowout(s) or backfire preventers for
shutoff valve to permitturning of the gas supplyto systems utilizing flammable mixture lines above
each building in an emergencyshall be provided. 65 mm (21/2 inches) nominal pipe size or
The emergency shutoff valves shall be plainly equivalent.
marked as such and their locations posted at
3.13.2 Optional components. The following
appropriate points.
components may also be utilized in any type
central premix system:
3.11 Prohibited devices
(a) Flowmeter(s).
3.11.1 No device shall be placed inside the gas (b) Flame arrester(s).
piping or fittings that will reduce the cross-
sectional area or otherwise obstruct the freeflow 3.13.3 Additional requirements. Gas-mixing
of gas, except when proper allowance has been machines shall have nonsparking blowers and
made for such a device. shall be so constructed that a flashback will not
rupture machine casings.

3.12 Systems containing gas-air mixtures 3.13.4 Limitations. A mixing blower system
outside the flammable range shall be limited to applications with minimum
practical lengths of mixture piping, limited to a
3.12.1 When gas-air mixing machines are maximum mixture pressure of 250 mm water
employed to produce mixtures above or below column, and limited to gases containing no more

47
MS 930:1986

than 10% hydrogen. The blower shall be outdoors whenever practical.


equipped with a gas-control valve at its air
entrance so arranged that gas is admitted to the 3.13.5.4 Controls for gas-mixing machines
air stream, entering the blower in proper shall include interlocks and a safety shutoff valve
proportions for correct combustion bythe type of of the manual reset type in the gas supply
burners employed; the said gas-control valve connection to each machine arranged to
being of either the zero governor or mechanical automatically shut off the gas supply in the event
ratio valve type which controls the gas and air of high or low gas pressure. Except for opcr;
adjustment simultaneously. No valves or other burner installations only, this shall be interlocked
obstructions..,-shall be installed between the so that the blower or compressor will stop
blower discharge and the~-bur-I9eror burners. operating following a gas supply failure. When a
system employs pressure air, suitable means
NOTE 7. The mixing blower is acknowledged as a special case because shall be provided to shut off the gas supply in the
of its inability to toierate control valves or comparabie restrictions
event of air failure.
between mixing blower and burner(s). With these iimitations. mixing
blower installations are not required to utilize sat ety biowouts. backfire
preventers, explosion heads. fiame arresters or automatic firechecks NOTE 8. Additional interlocks may be necessary for safe operation of
which introduce pressure iosses. equipment supplied by the gas-mixing machine.

3.13.5 Installation of gas-mixing machines


3.13.5.5 Centrifugal gas-mixing machines in
parallel can cause troublesome downstream
3.13.5.1 The machine shall be located in a
pulsation or equipment overload. Such systems
large, well-ventilated area or in a small detached
shall be carefully reviewed by user and equipment
building or cut-off room provided with room
manufacturer before installation and means Oi
construction and explosion vents in accordance
plans for minimizing these effects shall be
with NFPA No. 68. ‘Guide for explosion venting’.
prepared and utilized as required.
Such rooms shall have adequate positive
ventilation.
3.13.6 Use of automatic firechecks. safely
3.13.5.2 When gas-mixing machines are blowouts or backfire preventers. Automatic
installed in well-ventilated areas, the type of firechecks and safety blowouts or backfire
electrical equipment shall be governed by the preventers shall be provided in piping system’~
requirements of the Electricity Regulations 1951 distributing flammable air-gas mixture from gas-
(Revised 1 977). for general service conditions mixing machines to protect the piping and the
unless other hazards in the area prevail. machines in the event of flashback in accordance
with the following recommendations:
When gas-mixing machines are installed in small
detached buildings or cut-off rooms, the (a) Approved automatic firechecks shall he
electrical equipment and wiring shall be installed
installed upstream as close as practicable to the
in accordance with the requirements for a Zone 2
burner inlets following the firechock
area. [See section 1 4 of MS 830:1 983 (P), ‘Code
manufacturer’s instructions.
of Practice for the storage. handling and
transportation of liquefied petroleum gases’.]
NOTE 9. Two basic methods are generally used. One calls for a separate
firecheck at each burner; the other a firecheck at each group of
3.13,5.3 Air intake for gas-mixing machines burners. The second method is generally more practical if a sy~terfl
using compressors or blowers shall be taken from consists of many closely spaced burners.

48
MS 930: 1986

NOTE 10.An approved automatic firecheck shall be installed as near as location. Provisions shall be provided for
practicable upstream from a flame arrester used for local protection
where test burners or lighting torches are employed.
automatically shutting off the supply of gas-air
mixture in the event of rupture.
(b) Aseparatemanuallyoperatedgasvalveshall
be provided at each automatic firecheck for
shutting off the flow of the gas-air mixture
3.14 Electrical bonding and grounding
through the firecheck after a flashback has
occured. The valve shall be located upstream as 3.14.1 Each aboveground portion of a gas
close as practicable to the inlet of the automatic piping system upstream from the equipment
firecheck. shutoff valve shall be electrically continuous and
bonded to any grounding electrode. NFPA 70
CAUTION: These valves shall not be reopened National Electrical Code, provides further in-
after a flashback has occurred until the firecheck
fdrmation on this subject.
has cooled sufficiently to prevent reignition of the
flammable mixture and has been properly reset. 3.14.2 Gas piping shall not be used as a
grounding electrode.
(c) A safety blowout or backfiring preventer
shall be provided in the mixture line near the
outlet of each gas-mixing machine where the 3.15 Electrical circuits
size of the piping is larger than 65 mm (21/2
inches) NPS or equivalent, to protect the mixing 3.15.1 Electrical circuits shall not utilize gas
equipment in the event of an explosion passing piping or components except that low-voltage
through an automatic firecheck. The (50 volts or less) control circuits, ignition circuits,
manufacturer’s instructions shall be followed and electronic flame detection device circuits
when installing these devices, particularly after a may make use of piping or compondnts for a part
disc has burst. of an electric circuit.

The discharge from the safety blowout or backfire


preventer shall be located or shielded so that 3.16 Electrical connections
particles from the ruptured disc cannot be
directed towa~rdpersonnel. Whenever there are 3.16.1 All electrical connections between
intercon nected installations of gas-mixing wiring and electrically operated control devices
machines with safety blowouts or backfire in a piping system shall conform to the
preventers. provision shall be made to keep the requirements for a Zone 0 or Zone 1 area. [See
mixture from other machines from reaching any section 14 of MS 830:1983 (P), ‘Codes of
ruptured disc opening. Check valves shall not be Practice for the storage. handling and
used for this purpose. transportation of liquefied petroleum gases’].

(d) Explosion heads (rupture disc) may be 3.16.2 Any essential safety control depending
provided in large capacity premix systems to upon electrical current as the operating medium
relieve excessive pressure in pipelines. They shall shall be of a type which will shut off (fail safe) the
be located at and vented to a safe outdoor flow of gas in the event of current failure.

49
MS 930: 1986

SECTION FOUR: INSPECTION, TESTING AND PURGING

4.1 Pressure testing and inspection 4.1.1.5 The test procedure used shall he
capable of disclosing all leaks in the SOCliCh hcinçj
4.1.1 General tested and shall be selected after giving due
consideration to the volumetric content of the
4.1.1.1 Prior to acceptance and initial section and to its location.
operation, all piping installations shall be
inspected and tested to determine that the
materials. design. fabrication and installation 4.1.1.6 A piping system may be tested as a
complete unit or in sections as the construction
practices comply with the requirements of this
progresses. Under no circumstances shall a valve
Code.
in a line be used as a bulkhead between gas in one
4.1.1.2 Inspection shall consist of visual section of the piping system and test rned:uii: ri
examination, during or after manufacture. an adjacent section, unless two valves are
fabrication, assembly or pressure tests as installed in series with a valved ‘tell-tale’ ioc~ted
appropriate. Supplementary types of non- between these valves. A valve shall riot be
destructive inspection techniques. such as subjected to the test pressure unless it cart he
magnetic-particle. radiographic, ultrasonic. etc. determined that the valve, includirlg tie valve
although desirable, are not required unless closing mechanism, is designed 1:0 safely
specifically listed herein or in the engineering withstand the test pressure.
design.
4.1.1.7 Regulator and valve essembl:es
4.1.1.3 In the event repairs of additions are fabricated independently of the piping system in
made following the pressure test, the affected which they are to be installed may be tested with
piping shall be retested, except that in the case of inert gas at the time of fabrication.
minor repairs or additions retest may be omitted.
when precautionary measures are taken to 4.1.2 Test medium
assure sound construction.
4.1.2.1 Except as provided in 4.1.2.2, the test
4.1.1.4 Because it is sometimes necessary to medium shall be air or inert gas (e.g. niitlogSrI,
divide a piping system into test sections and carbon dioxide). OXYGEN SHALL ~EVEP~ E1E~’
.install test heads, connecting piping, and other USED.
necessary appurtenances for testing. it is not
required that the tie-in sections of pipe be 4.1.2.2 Fuel gas may be used in pipIng systems
pressure tested. Tie-in connections, however. operating at pressures of 3.5 kPa (gauge) [0.5
shall be tested with soap solution after gas has psig] or less.
been introudced and the pressure has been
increased sufficiently to give some indications 4.1 .3 Test preparation
should leaks exist. (See ‘Caution’ following
4.1.5.2). 4.1.3.1 Whenever possible. pipe jeints.

50
MS 930: 1986

including welds, shall be left uninsulated and kPa (0.1 psi). The source of pressure shall be
exposed for examination during the test. If the isolated before the pressure tests are made.
pipe end joints have been previously tested in
accordance with this Code, they may be 4.1 .4.2 The test pressure to be used shall be no
insulated, covered or concealed. less than 1 1/2 times the proposed maximum work-
ing pressure, but not less than 20 kPa (gauge)
4.1.3.2 Expansion joints shall be provided with [3 psig], irrespective of design pressure. When
temçorary restraints, if required. for the the test pressure exceeds 860 kPa (gauge) [125
additional thrust load under test. psig~.the test pressure shall not exceed a value
which produces a hoop stress in the piping
4.1.3.3 Equipment which is not to be included greater than 50% of the specified minimum yield
in the test shall be either disconnected from the
strength of the pipe.
piping or isolated by blanks, blind flanges or caps.
Flanged joints at which blinds are inserted to
4.1.4.3 Systems for undiluted liquefied
blank off other equipment during the test need
petroleum gases shall withstand the pressuretest
not be tested.
in accordance with 4.1.4.2 or. for systems
operating at a pressure of 3.5 kPa (gauge) [0.5
4.1.3.4 When the piping system is connected
psig] or less when appliances are connected to
to equipment or components designed for
the piping system. shall withstand a pressure of
operating pressures of less than the test pressure.
not less than 250 mm nor more than 355 mm
such equipment and their individual shutoff
valves shall be isolated from the piping system by water column for a period of not less than 1 0
minutes without showing any drop in pressure.
disconnecting them and capping the outlet(s).
The source of pressure shall be isolated before
4.1.3.5 When the piping system is connected the pressure tests are made.
to equipment or components designed for
operating pressures equal to or greater than the 4,1.4.4 Test duration shall be not less than one-
test pressure, such equipment shall be isolated half hour for each 15 cubic metres of pipe volume
from the piping system by closing their individual or fraction thereof. When testing a system having
manual shutoff valve(s). a volume less than 0.3 cubic metre or a system in
a single-family dwelling, the test duration maybe
4.1.3.6 All testing of piping systems shall be reduced to 10 minutes. For piping systems
done with due regard for the safety of employees having a volume of more than 680 cubic metres.
and the public during the test. Bulkheads, the duration of the test need not exceed 24 hours.
anchorage and bracing suitably designed to
resist test pressures shall be installed if 4.1.5 Detection of leaks and defects
necessary. Prior to testing, the interior of the pipe
shall be cleared of all foreign material. 4.1.5.1 The piping system shall withstand the
test pressure specified without showing any
4.1.4 Test pressure evidence of leakage or other defects. Any
reduction of test pressures as indicated by
4.1.4.1 Pressure shall be measured with a pressure gauges shall be deemed to indicate the
manometer or an equivalent device so calibrated presence of a leak unless such reduction can be
as to be read in increments of not greater than 0.5 readily attributed to some other cause.

51
MS 930: 1986

4.1.5.2 The leakage shall be located by means determined to be free of leakage and purged in
of an approved combustible gas detector, soap accordance with 4.3.3.
and water, or an equivalent nonflammable
solution, as applicable. Matches, candles, open
flames, or other methods which could provide a 4.3 Purging
source of ignition shall not be used.
4.3.1 The processes of voiding a gas pipe line
CAUTION: Since some leak test solutions, of fuel gas and repl~cingthe fuel gas with air, or
including soapand water, maycause corrosion or charging a gas pipe line that is full of air with fuel
stress cracking, the piping shall be rinsed with gas. require that~a significant amount of
water after testing. unless it has been determined combustible mixture not be developed within the
the leak test solution is noncorrosive. pipe line or released within a confined space.

When leakage or other defects are located. the 4.3.2 Removalfromservice.When gas piping is
affected portion of the piping system shall be to be opened for servicing, addition or
repaired or replaced and retested. (See 4.1 .1 .3). modification, the section to be worked on shall be
turned off from the gas supply at the nearest
4.1.6 Test records. Records shall be made of convenient point, and the line pressure vented to
inspection and all tests performed. These records the outdoors.
shall indicate which portions of the piping system
conform to this Code or were pressure tested. If this section exceeds the lengths shown in table
3. the remaining gas shall be displaced with an
inert gas.
4.2 Leakage check after gas turn on

4.2.1 Before turning gas on. Before gas is Table 3. Length of gas line requiring purging
for servicing or modification
turned into a system of new gas piping, or back
into an existing system after being shut off, the
Nominal pipe size Minimum length of pipinç~
entire system shall be checked to determine that requiring purging
mm (inches) m
there are no open fittings or ends and that all
valves at outlets and equipment are closed.
65(2½) 15
80(3) 9
4.2.2 Check for leakage. Immediately after 100(4) 4.5
turning on the gas. the piping system shall be 150(6) 3
checked to ascertain that no gas is escaping. (See 200 (8) or larger Any length

appendix D for suggested method).

If leakage is indicated, the gas supply shall be


shut off until the necessary repairs have been 4.3.3 Placing in operation. When piping full of
made. (See appendix E for suggested emergency air is placed in operation. the air in the piping
procedures for gas leakages). shall be displaced with fuel gas. provided the
piping does not exceed the length shown in table
4.2.3 Placing equipment in operation. Gas 4. The air can be safely displaced with fuel gas
utilization equipment may be placed in operation provided that a moderately rapid and continuous
after the piping system has been tested and flow of fuel gas is introduced atone end of the line

52
MS 930:1986

and air is vented out at the otherend.Thefuel gas of piping systems being purged shall not
flow should be continued without interruption discharge into confined spaces or areas where
until the vented gas is free of air. The point of there are resources of ignition unless precautions
discharge shall not be left unattended during are taken to perform this operation in a safe
purging. The vent shall then be closed. manner by ventilation of the space. control of
purging rate, and elimination of all hazardous
If the piping exceedsthe lengths shown in table 4, conditions.
the air in the piping shall be displaced with an
inert gas. and the inert gas shall then be displaced 4.3.5 Placing equipment in operation. After the
with fuel gas. piping has been placed in operation, all
equipment shall be purged and then placed in
4.3.4 Discharge of purgedgases. The open end operation, as necessary.

Table 4. Length of piping requiring purging


before placing in operation

Nominal pipe size. Minimum length of piping


requiring purging
mm (inches) m

80(3) 9
10014) 4.5

150(6) 3
200 (8) or larger Any length

53
MS 930: 1986

SECTION FIVE: EQUIPMENT INSTALLATION

5.1 General connection with the gas supply. effective means


such as a back pressure regulator and relief valve
5.1.1 Appliances, accessories and equipment shall be provided to prevent air or oxygen from
to be ‘approved’. Gas appliances. accessories. passing back into the gas piping. The serving gas
and gas utilization equipmentshall be ‘approved’. supplier shall be consulted for details. When
oxygen is used, see NFPA 51. ‘Standard for the
Acceptance of unlisted gas utilization equipment design and installation of oxygen-fuel gas
and accessories shall be on the basis of a sound systems for welding and cutting.’
engineering evaluation. In such cases, the
equipment shall be safe and suitable for the 5.1 .6 Protection of gas equipment from fumes
proposed service and be recommended for the or gases other than products of combination.
service by the manufacturer. When corrosive or flammable process fumes are
present, suitable means for their safe disposal
5.1.2 Assignment and coordination of gas shall be provided. Such fumes include, among
equipment design. construction and main- others, carbon monoxide. hydrogen sulphide.
tenance. Because industrial gas applications are ammonia, chlorine and halogenated hydro-
so varied in nature, many agencies are jointly carbons.
involved with their safe and satisfactory use. See
appendix B for suggested guidelines and check NOTE 11. Halogenated hydrocarbons are particulariy Inlurlous and

list. corrosive after contact with flames or hot surfaces.

5.1.3 Type of gas(es). It shall be determined 5.1.7 Building structural members


whether the gas utilization equipment has been
5.1.7.1 Structural members of a building shall
designed for use with the gas to which it will be
not pass through gas utilization equipment
connected. No attempt shall be made to convert
having an operating temperature in excess of
the equipment from the gas specified on the
2 60°C.
rating plate for use with a different gas without
consulting the serving gas supplier or the
equipment manufacturer for complete instruc- 5.1.7.2 Structural members passing through
gas utilization equipment. having an operating
tions.
temperature of 260°C or less shall be of non-
5.1 .4 Safety shutoff devices for unlistedLP-gas combustible material. Building columns. girders.
equipment used indoors. Unlisted gas utilization beams or trusses shall not be included within
equipment for use with undiluted liquefied equipment. unless appropriate insulation and
petroleum gases and installed indoors, shall be ventilation are provided to avoid all deterioration
equipped with safety shutoff devices of the in strength. and linear expansion of the building
complete shutoff type. structure in either a vertical or horizontal
direction.
5.1 .5Use of air or oxygen under pressure.
When air or oxygen under pressure is used in 5.17.3 Gas utilization equipment shall he

54
MS 930 : 1986

furnished either with load distributing bases or floor assemblies having a fire resistance rating of
with a sufficient number of adequate supports to not less than 2 hours. Openings in walls or
prevent damage to either building structure or partitions separating equipment rooms from
Aquipment. motor vehicle repair or parking areas shall be
restricted to those necessary for ducts and shall
5.1.7.4 At the locations selected for installation be located not less than 2.5 m above the floor;
of gas utilization equipment, the dynamic and openings for ducts shall be protected with
static load carrying capacities of the building approved, automatic fire doors or dampers. Air
structure shall be checked to determine if they are for combustion shall be obtained from outside
adequate to carry the additional loads. The the building.
equipment shall be adequately supported and
shall be connected to the piping so as not to exert 5.1.9.3 Gas utilization equipment may be
undue stress on the connections. installed in a repair workshop without the
provisions noted in 5.1.9.2 when there is no
5.1.8 Flarrimable vapours. Gas appliances shall dispensing or transferring of liquefied petroleum
not be installed in any location where flammable gas or class I or II flammable liquids (as defined in
vapours are likely to be present. unless the MS 761. ‘Code of Practice for the storage and
design. operation and installation are such to handling of flammable and combustible liquids).
eliminate the probable ignition of the flammable provided all burner and burner ignition devices
vapours. Gas utilization equipment installed in are located not less than 450 mm above the floor.
compliance with 5.1 9. shall be considered to the equipment is protected so that it is not suhlect
comply with the intent of this provision. to physical damage by a moving vehicle, and
continuous mechanical ventilation is supplied Cl
the rate of 0.23 cubic metre per minute per
5.1.9 Installation in comrriercial jarages
sq usre metre of floor area. The equipment and the
5.1.9.1 Except as noted in 5.1 9.2. gas ventiating system shall be interlocked so the
utilization equipment in an enclosed basement or equipment will not operate unless the ventilating
system is in operation.
underground parking structure shall be installed
so that all burner and burner ignition devices are
5.1.10 Gas equipment physical protection.
located not less than 450 mm above the floor, or
When it is necessary to locate gas utilization
so that the equipment is enclosed bya partition
not less than 450 mm high. provided the parking equipment close to a passageway travelled by
trucks or cranes, suitable guard rails or bumper
structure is continuously ventilated by a
plates shall be installed to protect the equipment
mechanical system capable of providing a
from damage.
minimum of six air changes per hour. Such
equipment shall be located or protected so that It
is not subject to physical damage by a moving 5.1.11 Venting of flue gases. Gas utilization
equipment shall be vented in accordance with the
vehicle.
provisions of section 7: Venting of equipment.
5.1.9.2 Except as noted in 5.1.9.3, gas
utilization equipment in a repair workshop shall 5.1.12 Extra device orattachment. No device or
be installed in a detached building or room, attachment shall be installed on any gas
separated from the motor vehicle repair or utilization equipment which may in any way
parking area by walls or partitions and floors or impair the combustion of gas.

55
MS 930 1986

5.1.13 Adequate capacity of piping. When 5.1.16.4 Under no circumstances shall a


connecting additional gas utilization equipment regulator be vented to the gas utilization
to a gas piping system, the existing piping shall be equipment flue or exhaust system.
checked to determine if it has adequate capacity
(see 2.4). If inadequate, the existing system shall 5.1.16.5 In the case of vents entering the
be enlarged as necessary or separate gas piping combustion chamber, the vent shall be located so
of adequate capacity shall be run from the point that the escaping gas will be readily ignited by the
of delivery to the equipment. pilot flame and the heat liberated thereby will not
adversely affect the normal operation of the
5.1 .14 Avoid strain on gas piping. Gas safety shutoff system. The terminus of the vent
utilization equipment shall be adequately shall be securely held in a fixed position relative to
supported and so connected to the piping as not the pilot flame. For manufactured gas. the need
to exert undue strain on the connections. for a flame arrester in the vent piping shall be
determined.
5.1.15 Gas appliance pressure regulator.
When the gas supply pressure is higher than that 5.1.17 Combination of equipment. Any
atwhich the gas utilization equipment is designed combination of gas utilization equiprrtrrit.
to .operate or varies beyond the design pressure attachments or devices used together in any
limits of the equipment, a gas appliance pressure manner shall comply with the standards whicii
regulator shall be installed. apply to the individual equipment.

5.1.16 Venting of gas appliance pressure


5.1 .18 Installation instructions. The i nstal
regulators agency shall conform to the equipim.~r5:
manufacturer’s specific recommendations in
5.1.16.1 Gas appliance pressure regulators
completing an installation that will providc
requiring access to the atmosphere for
satisfactory performance and serviceability.
successful operation shall be equipped with vent
installing agency shall also leave
piping loading outdoors or, if the regulatorvent is
manufacturer’s installation, operating ai~d
an integral part of the equipment, into the
maintenance instructions in a location on the
combustion chamber adjacent to a constantly
premises where they will be readily available fr:
burning pilot, unless constructed or equipped
reference and guidance of the authority havi;h
with a vent limiting means to limit the escape of
jurisdiction, servicemen and the owner or
gas from the vent opening in the event of
operator,
diaphragm failure.

5.1.16.2 Vent limiting means shall be


.
5.1.19 Protection of outdoor equipment. (~sr
employed on listed gas appliance pressure utilization equipment not listed for outdoor
installation but installed outdoors shall be
regulators only.
provided with protection to the deg.ree that 1
5.1.16.3 In the case of vents leading outdoors. environment requires. Equipment listed fo:
means shall be employed to prevent water from outdoor installation may be installed without
entering this piping and also to prevent stoppage protection in accordance with the provisions of
of it by insects and foreign matter. their listing. (See 5.2.1).

56
MS 930:1986

5.2 Accessibility and clearance dilution of flue gases from within the building.
They do not apply to (a) direct vent equipment
5.2.1 Accessibilityforservice. All gas utilization
which is constructed and installed so that all air
equipment shall be located with respect to for combustion is obtained from the outside
building construction and other equipment so as atmosphere and all flue gases are discharged to
to permit access to the gas utilization equipment, the outside atmosphere, or (b) enclosed furnaces
Sufficient clearance shall be maintained to permit which incorporate an integral total enclosure and
cleaning of heating surfaces; the replacement of use only outside air for combustion and dilution
filters, blowers, motors, burners, controls, and of flue gases.
vent connections: the lubrication of moving parts
where necessary; the adjustment and cleaning of 5.3.1.2 Equipment shall be installed in a
burners and pilots: and, the properfunctioning of location in which the facilities for ventilation
explosion vents, if provided. For attic installation permit satisfactory combustion of gas, proper
the passageway and servicing area adjacent to venting and the maintenance of ambient
the equipment shall be floored. temperature at safe limits under normal
conditions of use. Equipment shall be located so
as not to interfere with proper circulation of air.
5.2.2 Clearance to combustible materials. Gas When normal infiltration does not provide the
utilization equipment and their vent connectors necessary air, outside air shall be introduced.
shall be installed with clearances from
combustible matedal so that their operation will 5.3.1.3 In addition to air needed for
not create a hazard to persons or property. co m bust ion, process air shall be provided as
required for: cooling of equipment or material,
Minimum clearances between combustible walls controlling dew point, heating, drying. oxidation
and the back and sides of various conventional or dilution, safety exhaust, odour control, and air
types of equipment and their vent connectors are for compressors.
specified in section 6: Installation of specific
equipment, and section 7: V~ntingof ~quipment. 5.3.1.4 In addition to air needed for
(Reference may also be~made to NFPA: 89M, combustion, air shall be supplied for ventilation,
‘Manual on clearances for heat producing including all aiç required for comfort and proper
appliances’). working conditions for personnel.

Equipment shall not be installed on carpeting, 5.3.1.5 While all forms of building
unless the equipment is listed for such construction cannot be covered in detail, air for
installation. combustion. ventilation and dilution offluegases
for gas utilization equipment vented by natural
draft normally may be obtained by application of
5.3 Air for combustion and ventilation one of the methods covered in 5.3.3 and 5.3.4.

5.3.1 General 5.3.2 Equipment located in unconfined spaces.


In unconfined spaces in buildings infiltration
5.3.1.1 The provisions of 5.3 apply to gas normally is adequate to provide air for
utilization equipment installed in buildings and combustion, ventilation and dilution of flue
which require air for combustion, ventilation and gases.

57
MS 930 : 1986

5.3.3 Equipment located in confined spaces 5.3.3.2 All air from outdoors. The confined
space shall be provided with two permanent
5.3.3.1 All air from inside t,he building. The openings, one commencing within 300 mm of
confined space shall be provided with two the top and one commencing within 300 mm of
permanent openings communicating directly the bottom of the enclosure. The openings shall
with an additional room(s) ofsufficientvolumeso communicate directly. or by ducts, with the
that the combined volume of all spaces meets the outdoors or spaces (crawl or attic) that freely
criteria for an unconfined space. The total input of communicate with the outdoors.
all gas utilization equipment installed in the
combined space shall be considered in making (a) When directly communicating with the
this determination. Each opening shall have a outdoors, each opening shall have a minimum
minimum free area of 6 cm2 per 1000 k.J per hour free area of 1.5 cm2 per 1000 kJ per hour (1
(1 square inch per 1.000 Btu per hour) of the total square inch per 4,000 Btu per hour) of total input
input rating of all gas utilization equipment in the rating of all equipment in the enclosure. (See fig.
confined space, but not less than 645 cm2 (100 2).
square inches). One opening shall be within 300
mm of the top and one within 300 mm of the
bottom of the enclosure (See fig. 1).

.Chimney or gas vent

Ventilation for
unheated crawl space

NOTE 13. The inlet and outlet air openings shall each have a free areaof
2 0
not less than 1.5cm per 1000 0 per hour (one square inch per4.00
Btu per hourl of thetotal input rating of all equipmentintheenclosure.

Figure 2. Equipment located in confined


2
NOTE 12. Each opening shall have a free area of not less than 6cm per
spaces; all air from outdoors Inlet air -

1000 kJ per hour lone square inch per 1.000 Btu per hourl of the total from ventilated crawl space and outlet
input rating of all equipment in the enclosure, but not less than 645 ~ir to ventilated attic (See 5.3,3.2)
2
cm 1100 square inchesl.

Figure 1. Equipment located in confined


(b) When communicating with the outdoors
spaces; all air from inside the building
through vertical ducts, each opening shall have a
(See 5.3.3.1)
minimum free area of 1.5 cm2 per 1000 kJ per

58
MS 930: 1986

hour (1 square inch per 4.000 Btu per hour) of 5.3.5 Louvers and grilles. In calculating free
toal input rating of all equipment intheenclosure. area in 5.3.3. consideration shall be given to the
(See fig. 3). blocking effect of louvers, grilles or screens
protecting openings. Screens used shall not be
(c) When communicating with the outdoors smaller than 6mm mesh. lfthefreeareathrougha
through horizontal ducts, each opening shall design of louver or grille is know. it should be
have a minimum free area of 3cm2 per 1000 kJ used in calculating the size opening required to
per hour (1 square inch per 2,000 Btu per hour) provide the free area specified. If the design and
of total input rating of all equipment in the free area is not known, it may be assumed that
enclosure. (See fig. 4). wood louvers will have 20% to 25% free area and
metal louvers and grilles will have 60% to 75%
(d) When ducts are used, they shall be of the free area. Louvers and grilles shall be fixed in the
same cross-sectional area as the free area of the open position or interlocked with the equipment
openings to which they connect. The minimum so that they are opened automatically during
dimension of rectangular air ducts shall be not equipment operation.
less than 75 mm.

5.3.4 Specially engineered installations. The


requirements of 5.3.3 shall not necessarily
govern when special engineering, approved by
the authority having jurisdiction, provides an
adequate supply of air for combustion,
ventilation. and dilution of flue gases.
Outlet’air duct

~e~ter
Ventilation louvers’
end of attic) = fHeater Inlet air duct

HLOJ

NOTE 1 5. Each air duct opening shah have a free area of not less than
2
3cm per 1000 Id per hour (one square inch per 2.000 Stu per hourl
of the total input rating of all equipment in the enclosure’.

Figure 4. Equipment located in confined


spaces; all air from outdoors (See 5.3.3.2)

NOTE 14. The inlet and outiet air openings shall each have a free area of
2
not less than 1.5cm per 1000 Id per hourlone squareinch per4,000
Btu per hourl of the total input rating of all equipmentinthe enclosure.
‘If the equipment room is iocated against an outside wall and the air
openings communicate directly with the outdoors, each opening Shall
2
Figure 3. Equipment located in confined have a free area of not less than 1.5cm per 1000 kJ per hour lone

spaces; all air from outdoors through ventilated square inch per 4.000 Btu per hourl of the total input rating of all
equipment in the enclosure.
attics (see 5.3.3.2)

59
MS 930: 986

5.3.6 Special conditions created by 5.4.2.3 All equipment requiring an external


mechanical exhausting. Operation of exhaust source of electrical power for its operation shall
fans, ventilation systems. power burners, induced be provided wi~h an accessible electrical
draft systems. or clothes dryers. may create disconnet means near the equipment, which will
conditions requiring special attention to avoid completely deenergize the equipment, and a
unsatisfactory operation of installed gas 240-volt ac grounding type convenience outlet
utilization equipment. on the roof adjacent to the equipment. The
convenience outlet shall be on the supply side of
the disconnect switch.
5.4 Equipment on roofs
5.4.2.4 When water stands on the roof at the
5.4.1 General equipment or in the passageways to the
equipment, or when the roof is of a design having
5.4.1.1 Gas utilization equipment on roofs shall
a water seal, a suitable platform or walkway or
be designed or enclosed so as to withstand
both shall be provided above the water line. Such
climatic conditions in the area in which they are platform(s) or walkway(s) shall be located
installed. If enclosures are provided, each
adjacent to the equipment and control panels so
enclosure shall permit easy entry and movement. that the equipment can be safely serviced when
shall be of reasonable height, and shall have at
water stands on the roof.
least 750 mm clearance between the entire
service access panel(s) of the equipment and the
5.4.3 Access to equipment on roofs
wall of the enclosure.
5.4.3.1 Gas utilization equipment located on
5.4.1.2 Roofs on which equipment is to be
roofs or other elevated locations shall be
installed shall be capable of supporting the
accessible.
additional load or shall be reinforced to support
the additional load.
5.4.3.2 Buildings of more than 4.5 m in height
5.4.1.3 All access locks, screws and bolts shall shall have an inside means of access to the roof.
be of corrosion-resistant material.
5.4,3.3 The inside means of access shall be a
5.4.2 Installation of equipment on roofs permanent. or fold-away, inside stairway or
ladder, terminating in an enclosure, scuttle or
5.4.2.1 Gas utilization equipment shall be trap door. Such scuttles or trap doors shall be at
installed in accordance with its listing and the least 600 mm by 600 mm in size, and shall open
manufacturer’s installation instructions. easilyand safely underallconditions. and shall be
constructed so as to permit access from the roof
5.4.2.2 Equipment shall be installed on a well- side unless deliberately locked on the inside.
drained surface of the roof. At least 2 m clearance
shall be available between any part of the At least 2 m clearance shall be available between
equipment and the edge of a roof or similar the access opening and the edge of the roof or
hazard, or rigidly fixed rails or guards at least 1 m similar hazard. or rigidly fixed rails or guards at
in height shall be provided on the exposed side least 1 m in height shall be provided on the
except that parapets or other building structure at exposed side except that parapets or other
least 1 m in height maybe utilized in lieu of rails or building structure at least 1 m in height may
guards~ be utilized in lieu of guards or rails.

60
MS 930:1986

5.4.3.4. Proper permanent lighting shall be continuous movement. Repeated bending.


provided at the roof access. The switch for such flexing or vibration shall be avoided. When
lighting shall be located inside the building near moving equipment. bending of a connector shall
the access means leading to the roof. be held to a minimum.

5.4.4 Additional provisions. Also see


Aluminium-alloy tubing and connectors shall be
provisions of 5.1.19, 5.2.1 and 7.14.3.
coated to protect against external corrosion
where they are in contact with masonry, plaster or
insulation or are subject to repeated wettings by
5.5 Equipment connections to building piping such liquids as water (except rain water),
detergents or sewage. Aluminium-alloy tubing
5.5.1 Connecting gas equipment. Gas shall not be used in exterior locations.
utilization equipment shall be connected by one
of the following: 5.5.2 Use of gas hose connectors. Listed gas
hose connectors shall be used as follows:
(a) Rigid pipe.
(a) Indoor. Indoor gas hose connectors may be
(b) Semi-rigid tubing extensions of a tubing used with laboratory, shop or ironing equipment
piping system. that requires mobilityduring operation. Ashutoff
valve shall be installed where the connector is
(c) Listed connectors that are completely in the attached to the building piping. The connector
same room as the equipment. shall be of minimum length butshall not exceed 2
m. The connector shall not be concealed and
(d) Semi-rigid tubing in lengths up to 2 m that shall not extend from one room to another non
are completely in the same room as the pass through wall partitions. ceilings or floors.
equipment. When acceptable to the authority
having jurisdiction, greater lengths may be used (b) Outdoor. Outdoor gas hose connectors may
and need not be connected to an outlet in the be used to connect portable outdoor gas-fired
same room as the equipment. equipment. A shutoff valve or a listed quick-
disconnect device shall be installed where the
(e) Listed gas hose connectors in accordance connector is attached to the supply piping and in
with 5.5.2. such a manner to prevent the accumulation of
water or foreign matter. This connection shall
(f) Gas-fired commercial cooking equipment only be made in the outdoor area where the
listed for use with casters or otherwise subject to equipment is to be used.
movement for cleaning, and other large and
heavy gas utilization equipment that may be 5.5.3 Connection of portable and mobile
moved, shall be connected by a listed appliance industrial gas equipment
connector complying with the ANSI Z21 .69,
‘Standard for connectors for movable gas 5.5.3.1 Portable industrial gas utilization
app1ian ces’. equipment or equipment requiring mobility or
subject to vibration may be connected to the
The co nnector or tubing shall be insta lIed so as to building gas piping system by the use of flexible
be protected against-physical and thermal hose suitable and safe for the conditions under
damage. Connectors are not designed for which it may be used.

61
MS 930:1986

5.5.3.2 Industrial gas utilization equipment plugged or capped shall be installed as close to
requiring mobility may be connected to the rigid the inlet of the equipment as practical (seefig. 5).
piping by the use of swivel joints or couplings Illuminating appliances and outdoor grills need
which are suitableforthe service required. Where not be so installed.
swivel joints or couplings are used, only the
minimum number required shall be installed.

5.5.3.3 Industrial gas utilization equipment 5.6 Electrical


subject to vibration may be connected to the
building piping system by the use of all metal 5.6.1 Electrical connections. Electrical con-
nections between gas utilization equipment and
flexible connectors suitable for the service
the building wiring, including the grounding of
required.
the equipment. shall conform to the requirements
5.5.3.4 Where flexible connections are used, of the Electricity Regulations 1 951 (Revised
they shall be of the minimum practical length and 1977).
shall not extend from one room to another nor
5.6.2 Electric ignition and control devices.
pass throug.h any walls, partitions, ceilings or
Electrical ignition, burner control and electrical
floors. Flexible connections shall not be used in
any concealed location. They shall be protected vent damper devices shall not permit unsafe
operation of the gas utilization equipment in the
against physical or thermal damage and shall be
event of electrical power interruption or when the
provided with gas shutoff valves in readily
power is restored.
accessible locations in rigid piping upstream
from the flexible connections.

5.5.4 Equipment shutoff valves and con-


nections. Any gas utilization equipment con-
nected to a piping system shall have an
accessible, approved manual shutoff valve
installed upstream of any connector and within 2
Tee
m of the equipment it serves. A union or flanged
connection shall be provided downstream from
this valve to permit removal of controls. Nipple

5.5.5 Quick-disconnect devices. Gas utilization ‘Cap


equipment connectors may be connected to the
building piping by means of a listed quick-
disconnect device, and when installed indoors, a
manual shutoff valve shall be installed upstream
of the quick-disconnect device. Figure 5. A method of installir~a trap

5.5.6 Sediment trap. If a sediment trap is not


incorporated as a part of the gas utilization 5.6.3 Electrical circuit. The electrical circuit
equipment and if dirt orotherforeign material is a employed for operating the automatic main gas-
problem, a tee fitting with the bottom outlet control valve, automatic pilot, room temperature

62
MS 930: 1986

thermostat, limit control or other electrical 5.7 Room temperature thermostats


devices used with the gas utilization equipment
shall be in accordance with the wining diagrams 5.7.1 Locations. Room temperature thermo-
supplied with the equipment. stats shall be installed in accordance with the
manufacturer’s instructions.
5.6.4 Continuous power. All gas utilization
equipment using electrical controls shall have the 5.7.2 Drafts. Any hole in the plaster or panel
controls connected into a permanently live through which the wires pass from the thermostat
electric circuit, i.e. one that is not controlled by a to the gas utilization equipment being controlled
light switch. Central heating equipment shall be shall be sealed so as to prevent drafts from
provided with a separate electrical circuit. affecting the thermostat.

63
MS 930: 1986

SECTION SIX : INSTALLATION OF SPECIFIC EQUIPMENT

6.1 General (a) Air conditioning equipment listed for


installation at lesser clearances than specified in
This section is primarily applicable to non- table 5 may be installed in accordance with its
industrial type gas utilization equipment and listing and the manufacturer’s instructions.
installations and, unless specifically indicated.
does not apply to industrial type equipment (b) Air conditioning equipment listed for
installations. Listed gas utilization equipment installation at greater clearances than specified
shall be installed in accordance with their listing in table 5 shall be installed in accordance with its
and the manufacturer’s instructions, or as listing and the manufacturer’s instructions unless
elsewhere specified in this section. Unlisted protected as specified in (c).
equipment ~hall be installed as specified in this
section as applicable to the equipment. (c) Air conditioning equipment installed in
rooms large in comparison with the size of the
For additional information concerning particular equipment may be installed with reduced
gas equipment and accessories, including clearances to combustile material provided the
industrial types, reference can be made to the combustible materi~l or the equipment is
standards listed in appendix A. protected as described in table 6.

6.2.3.2 Air conditioning equipment installed in


6.2 A~rconditioning equipment spaces such as alcoves and closets shall be
specifically listed for such installation and
6.2.1 Independent gas piping. Gas piping installed in accordance with the terms of listing.
serving heating gas utilization equipment may The installation clearances for air conditioning
also serve cooling equipment when heating and equipment in rooms not large in comparison with
cooling equipment cannot be operated the size of equipment shall be as specified in the
simultaneously. (See 2.4). listing, regardless of whether the enclosure is of
combustible or noncombustible material, and
6.2.2 Connection of gas engine-powered air shall not be reduced by the protection methods
conditioners. To protect against the effects of described in table 6.
normal vibration in.service. gas engines shall not
be rigidly connected to’ the gas supply piping. 6.2.3.3 Unlisted air conditioning equipment
shall be installed with clearances from
6.2.3 Clearances for indoor installation combustible material of not less than 450 mm
above the equipment and at sides, front and rear,
6.2.3.1 Listed air conditioning equipment and 230 mm from projecting flue box or draft
installed in rooms which are large in comparison hood.
with the size of the equipment shall be installed
with clearances not less than specified in line I of 6.2.3.4 When the plenum for an air conditioner
table 5 except as provided in (a). (b) and (c) below. which includes provisions for heating air is

64
MS 930 : 1986

adjacent to combustible material, the clearance 6.2.6 Refrigeration coils. (See 6.3.7 and 6.3.8).
shall be measured to the surface of the plaster or
other noncombustible finish when the clearance 6.2.7 Switches in electrical supply line. Means
specified is 50 mm or less. for interrupting the electrical supply to the air
conditioning equipment and to its associated
6.2.3.5 The clearance to this equipment shall cooling tower (if supplied and installed in a
not interfere with combustion air, draft hood location remote from the air conditioner) shall be
clearance and relief. and accessibility for provided within sight of and not over 1 5 m from
servicing. (See 5.2.1, 5.3 and 7.10.8.). the air conditioner and cooling tower.

6.2.4 Erection and mounting. Air conditioning


equipment shall be erected in accordance with
the manufacturer’s instructions. Unless the
6.3 Central heating boilers and furnaces
equipment is listed for installation on a
combustible surface such as a floor or roof, or 6.3.1 Clearance
unless the surface is protected in an approved
manner according to the requirement of the 6.3.1.1 Central heating boilers and furnaces
Uniform Building By-Laws, it shall be installed on installed in rooms large in comparison with the
a surface of noncombustible construction with size of the equipment. shall be installed with
noncom bustible material and surface finish and clearances not less than specified in table 5
with no combustible material against the except as provided in (a) and (b) below.
underside thereof.
(a) Central heating furnaces and boilers listed
6.2.5 Plenum chambers and air ducts. A for installation at lesser clearances than specified
plenum chamber supplied as a part of air, in table S may be installed in acordancewith their
conditioning equipment shall be installed in listing and the manufacturer’s instructions.
accordance with the manufacturer’s instructions.
When a plenum chamber is not supplied with the (b) Central heating furnaces and boilers
equipment, any fabrication and installation installed in rooms large in comparison with the
instructions provided by the manufacturer shall size of the equipment may be installed with
be followed. The method of connecting supply reduced clearances to combustible material
and return ducts shallfacilitate propercirculation provided the combustible material or the
of air. (Reference may be made to NFPA 90A. equipment is protected as described in table 6.
‘Standard for the installation of air conditioning
and ventilating systems’, or NFPA 90B, ‘Standard 6.3.1.2 Central heating furnaces and boilers
for the installation of warm air heating and air installed in spaces such as alcoves and closets
conditioning systems’). shall be specifically listed for such installation
and installed in accordance with the terms of
When the air conditioner is installed within a listing. The installation clearances for furnaces
room not large in comparison with the size of the and boilers in rooms not large in comparison with
equipment, the air circulated by the equipment the size of the equipment shall be as specified in
shall be handled by ducts which are sealed to the the listing, regardless of whether the enclosure is
casing of the equipment and which separate the of combustible or noncombustible material., and
circulating air from the combustion and shall not be reduced by the protection methods
ventilation air. described in table 6.

65
MS 930: 1986

6.3.1.3 When the plenum is adjacent to plaster against the underside thereof or on fire-resistive
on metal lath or noncombustible material slabs or arches having no combustible material
attached to combustible material, the clearance against the underside thereof, unless listed for
shall be measured to the surface of the plaster or installation on a combustible floor or the floor is
other noncombustible finish when the clearance protected in an approved manner according to
specified is 50 mm or less. the requirements of the Uniform Building ii~iy~
Laws.
6.3.1.4 The clearance to this equipment shall
not interfere with combustion air, draft hood 6.3.3 Temperature orpressure limiting devices.
clearance and relief, and accessibility for Steam and hot water boilers respectively shall be
servicing. (See 5.2.1. 5.3 and 7.10.8). provided with approved automatic limiting
devices for shutting down the burner(s) to
6.3.2 Erection and mounting. A central heating prevent boiler steam pressure or boiler water
boiler or furnace shall be erected in accordance temperature from exceeding the maximum
with the manufacturer’s instructions and shall be allowable working pressure or temperature.
installed on a floor of noncombustible
construction’.with noncombustible flooring and Safety limit controls shall not he used a~
surface finish and with no combustible material operating controls.

Construction using combustible material,


plastered or unpiastered

Gas equipment
or vent connector

A equals the clearance with no protection specified in tables 5 and 9 and in the
sections applying to various types of equipment.

B equals the reduced clearance permitted in accordance with table 6. The


protection applied to the construction using combustible material shall extend far
enough in each direction to make C equal to A.

Figure 6. Extent of protection necessary to reduce clearances


from gas equipment or vent connectors

66
MS930: 1986

Table 5. Clearances to combustible material for furnaces and


boilers installed in rooms which are large in comparison
with size of equipment, except as provided in 6.3.1.1 (See note 24)

Minimum clearance. mm

Above and Jacket Front Projecting Veat


aides of sides (see flue box connector
bonnet or and note or draft (see
plenum rear 16) hood note 17)

I. Ustedautomaticaliyfired, 50 150 450 150 150


forced air or gravity (See notes Isee note
system, with 120°C 18 and 19) 25)
temperature limit control.

ii. unlisted automatically tired, 150 150 450 450 450


forced air or gravity system, Isee note (see note lsee note
equipped with temperature 20) 211 211
limit control which cannot
be set higher than 120°C.

Ill. usted automatically fired 150 150 450 150 150


heating boilers; Steam (see note Isee note
boilers operating at not 22) ~ 25)
over 103 kPa (15 psi) gauge
pressure and hot water
boilers operating at not in
excess of 1 20°C.

IV. Unlisted automatically fired 150 150 450 450 450


heating boilers; Steam (see note (see note
boilers operating at not
(see note 211 21)
over 103 kPa (15 psi) 221
gauge pressure and hot
wal9r boilers operating at
not in excess of 120°C.

V. Central heating boilers and 450 450 450 450 450


furnaces, other than above. (see note (see note Isee note
23) 211 21)

NOTE 16. Front ciearance shall be sufficient for servicing the burner and furnace or boiler,

NOTE 17. The vent connector clearance does not apply to listed type B gas vents.
t
NOTE 18. This clearance may be reduced o 25mm for a listed forced air or gravity furnace equipped with:

hal a limit control that cannot be set higher than 93°c. or

ibi a marking to indicate that the outlet air temperature cannot exceed 93°c.

NOTE IS. clearance from suppiy ducts within 1 m of the pienum shah not be lens than that specified from the bonnet or
plenum. No clearance is necessary beyond thin distance.

NOTE 20. crearanceirom supply ducts within 2 m of the plenum shall not be less than 15mm. No clearance is necessary
beyond this distance.

NOTE 21. For unlisted gas i.r.zation equipmentequipped with an approved draft hood. this clearance may be reduced to
230 mm.

NOTE 22. The clearance is above top of boiler.

NOTE 23. clearance from supply ducts shall not be less than 450mm out tot m from the bonnet or plenum, not lessthan
150 mm from 1 m to 2 m. and not less than 25 mm beyond 2 m.

NOTE 24. Rooms which are large in comparisonwith the size ofthe equipmentare rooms having a volume equal toat least
12 times the total volume of an air conditioning apphance or furnace and at least 16 tImes the total volume of a boiler or
water heater. Total volume of an appliance is determined from exterior dimensions and is to include fan compartments and
burner vestibules, when used. When the actual ceiling height of a room is greater than 2.S m. the volume ofa room shall be
figured on the basis of a ceiling height of 2.5 m.

NOTE 25. These clearances shall apply unless the listing ofan appliance specifies different clearances. inwhich casethe
listed clearances shall apply.

67
MS 930: 1986

Table 6. Clearances (mm) with specified forms of protection*

Type of protection Where the required ctearice with no protection Is:


applied to the combus- —~

tibia material unless ,

othe,wie specified and ‘ 1 m 450 mm 300 mm 230mm 150 mm


covering all surfaces
within the distance —

specified as the required Sides Vent Sides Vent Sides Vent Sides Vestt
clearance with no pro- and con- and con- and con- and Uc~’t”
tection. (see fig. 8). Above rear nector Above rear nector Above rear nector. Above rear ~
Thicknesses are mini.
mum.

(a) 7 mm insulating
miiIboard~spaced
out 25 mmt 750 450 750 380 230 300 230 150 150 75 50 ‘/~

(b) 0.310 mm sheet


metal on 7 mm insu-
lating millboard 600 450 600 300 230 300 230 150 100 75 50 ~0
(c) 0.310 mm sheet
metal spaced out
25mmt 450 300 450 230 150 230 150 100 100 50 50 i.~b
(d) 0.310 mm sheet
metal on 3 mm insu-
lating millboard”
spaced out 25 mmt 450 300 450 230 150 230 150 100 100 50 50 50
(a) 7 mm insulating
miliboard” on .

25 mm mineral wool
bats reinforced with
mesh or equivalent 450 300 450 150 150 150 100 100 100 50 50 L
(f)’0.588 mm sheet ,
metal on 25 mm
mineral wool bats
reinforced with wire
or equivalent 450 300 300 100 75 75 50 50 50 50 50 L~
(g) 7 mm insulating ,
millboard” 1000 1000 1000 450 450 450 300 300 230 100 100 1O~J

‘All clearance shall be measured from the outer surface ofthe equivalent to thecombustibie material disregarding anyintervening protection applied to tiiecomi~:~”r~
material.

‘~Afactory fabricated board formed with noncombustible materials, normally fibres.

tSpacers shall be of noncornbustible material.

68
MS 930: 1986

6.3.4 Low water cutoff. Steam boilers shall be 6.3.6.4 When a furnace is installed so. that
provided with an automatic means to shut off the supply ducts carry air circulated by thefurnace to
fuel supply to the burner(s) if the boilerwater level areas outside the space containing the furnace.
drops to the lowest safe water line. the return air shall also be handled by a duct(s)
sealed to the furnace casing and terminating
6.3.5. Steam safety and pressure relief valves. outside the space containing the furnace.
Steam and hot water boilers shall be equipped.
respectively, with listed or approved steam safety 6.3.7 Refrigeration coils
or pressure relief valves of appropriate discharge
capacity and conforming to ASME require- 6.3.7.1 ‘A refrigeration coil shall not be
me nts*. installed in conjunction with a forced air furnace
when circulation of cooled air is provided by the
6.3.6 Plenum chambers and air ducts furnace blower, unless the blower has sufficient
capacity to overcome the external static
6.3.6.1 Plenum chambers and air ducts shall resistance imposed by the duct system and
be installed in accordance with NFPA 90A. cooling coil at the air throughout necessary for
‘Standard for the installation of air conditioning heating or cooling, whichever is greater.
and ventilating system’, or NFPA 90B, ‘Standard
for the installation of warm air heating and air 6.3.7.2 Furnaces shall not be located upstream
conditioning system’. from cooling units, unless the cooling unit is
designed or equipped, so as not to develop
6.3.6.2 Aplenumchambersuppliedasapartof excessive temperature or pressure.
a furnace shall be installed in accordancewith the
manufacturer’s instructions. 6.3.7.3 Refrigeration coils shall be installed in
parallel with or on the downstream side of central
6.3.6.3 When a plenum chamber is not furnaces to avoid condensation in the heating
supplied with the furnace, any fabrication and element, unless the furnace has been specifically
installation instructions provided by the listed for downstream installation. With a parallel
manufacturer shall be followed. The method of flow arrangement. the dampers or other means
connecting supply and return ducts shall used to control flow of air shall be sufficiently
facilitate proper circulation of air. (Reference may tight to prevent any circulation of cooted air
be made to NFPA SOA, ‘Standard for the through the furnace.
installation of air conditioning and ventilating
systems’.’ and to NFPA 90B. ‘Standard for the 6.3.7.4 Means shall be provided for disposal of
installation of warm air heating and air condensate and to prevent dripping of
conditioning systems’). condensate on the heating element.,

6.3.8 Cooling units used with heat/hg boilers

6.3.8.1 Boilers, when used in conjunction with


refrigeration systems. shall be installed so that
the chilled medium is piped in parallel with the
For details of requirements on low-pressure heating boiier safety
heating boiler with appropriate values to prevent
devices refer to ASME Boiler and Pressure Vessel Code, 1980 Edition. the chilled medium from entering the heating
Section IV. Heating Boilers.
boiler.

69
MS 930: 1986

6.3.8.2 When hot water heating boilers are 6.4.2.2 Type 2 clothes dryers shall be
connected to heating coils located in air handling exhausted to the outside air.
units where they may be exposed to refrigerated
air circulation, such boiler piping systems shall 6.4.3 Provisions for make-up air
be equipped with flow control valves or other
automatic means to prevent gravity circulation of 6.4.3.1 When a type 1 clothes dryer is
the boiler water during the cooling cycle. exhausted to the outside, consideration shall be
given to provision for make-up air. (See 5.3.6).
Provision for make-up air shall be provided for
6,4 Clothes dryers closet installed type 1 clothes dryers in
accordance with the manufacturer’s installation
6.4.1 Clearance instructions.

6.4.1.1 Listed type 1 clothes dryers shall be 6.4.3.2 Provision for make-up air shall be
installed with a minimum clearance of 1 50 mm provided for type 2 clothes dryers, with a
from adjacent combustible material, except that minimum free area (see 5.3.5) of 1.5 cm2 per
clothes dryers listed ~for installation at lesser 1.000 kJ per hour (one square inch for each
clearances may be installed in accordance with 1.000 Btu per hour) of the total input rating of the
their listing. Type 1 clothes dryers installed in dryer(s) installed.
closets shall be specifically listed for such
installation. 6.4.4 Exhaust ducts for type 7 clothes dryers

6.4.1.2 Listed type 2 clothes dryers shall be 6.4.4.1 A clothes dryer exhaust duct shall not
installed with clearances of not less than shown be connected into any vent connector, gas vent
on the marking plate and in the manufacturer’s chimney, crawl space. attic or other similar
instructions. Type 2 clothes dryers designed and concealed space.
marked ‘For use only in noncombustible
locations’ shall not be installed elsewhere. 6.4.4.2 Ducts for exhausting clothes dryers
shall not be put together with sheet-metal screws
6.4.1.3 Unlisted clothes dryers shall be or other fastening mean which extend into the
installed with clearances to combustible material duct and which would catch lint and reduce the
of not less than 450 mm. Combustible floors efficiency of the exhaust system.
under unlisted clothes dryers shall be protected
in an approved manner according to the 6.4.5 Exhaust ducts for type 2 clothes dryers
requirements of the Uniform Building By-Laws.
6.4.5.1 Exhaust ducts for type 2 clothes dryers
6.4.2 Exhausting to the outside air shall comply with 6.4.4.

6.4.2.1 Type 1 clothes dryers installed in 6.4.5.2 Exhaust ducts for type 2 clothes dryers
closets shall be exhausted to the outside air. and shall be constructed of sheet metal or other
no other fuel-ourning appliance shall be installed noncombustible material. Such ducts shall be
in the same closet. Type 1 clothes dryers shall not equivalent in strength and corrosion resistance to
be installed in bathrooms or bedrooms unless ducts made of galvanized sheet steel not less than
exhausted to the outside air. 0.495 mm thick.

70
_,MS930:1986

6.4.5.3 Type 2 clothes dryers shall be equipped facturer’s instructions. Equipment designed and
or installed with lint controlling means. marked ‘For use only in noncombustible
locations’ shall not be installed elsewhere.
6.4.5.4 Exhaust ducts for type 2 clothes dryers
shall have a clearance of at least 1 50 mm to 6.5.2 Clearance for unlisted equipment
combustible material except as provided in
6.4.5.5. 6.5.2.1 Unlisted floor-mounted commercial
cooking equipment, except as provided in 6.5.2.2
6.4.5.5 Exhaust ducts for type 2 clothes dryers and 6.5.2.3. shall be installed to provide a
may be installed with reduced clearances to clearance to combustible material of not less than
combustible material provided the combustible 450 mm at the sides and rear of the equipment
material is protected as described in table 6. and from the vent connector and not less than
1 .2 m above cooking tops and at the front of the
6.4.5.6 When ducts pass through walls, floors equipment.
or partitions, the space around the duct shall be
sealed with noncombustible material. 6.5.2.2 Unlisted floor-mounted commercial
cooking equipment may be installed in rooms, but
6.4.5.7’ Multiple installations of type 2 clothes not in partially enclosed areas such as alcoves,
dryers shall be made in a manner to prevent with reduced clearances to combustible material.
adverse operation due to back pressures that provided the combustible material or the
might be created in the exhaust systems. equipment is protected as described in table 6.

6.4.6 Multiple family or public use. All clothes 6.5.2.3 Unlisted floor-mounted commercial
dryers installed for multiple family or public use cooking equipment may be installed in rooms, but
shall be equipped with ~pproved safety shutoff not in partially enclosed areas such as alcoves.
devices ‘and shall be installed as specified for a with reduced clearance of 1 50 mm to
type 2 clothes dryer under 6.4.5. combustible material, provided the wall or
combustible material is protected by sheet metal
not less than 0.386 mm thick, fastened with
noncombustible spacers that are spaced at not
6.5 Commercial cooking equipment, floor-
less than 600 mm vertical and horizontal intervals
mounted
to provide a clearance of 40mm from such wall or
material. Such protection shall extend at least
6.5.1 Clearance for listed equipment. Listed
300 mm beyond the back, side. top or any other
floor-mounted commercial cooking equipment.
part of the equipment and the space between the
such as hotel and restaurant ranges. deep fat
sheet metal and walls or combustile material shall
fryers, unit broilers, gas-fired kettles, steam
be open on both sides and top and bottom to
cookers, steam generators and commercial
permit circulation of air.
baking and roasting ovens, shall be installed at
least 1 50 mm from combustible material except
6.5.3 Mounting on combustible floor.
that at least 50 mm clearance shall be maintained
between the flue box or draft hood and 6.5.3.1 Listed floor-mounted commercial
combustible material. Floor-mounted com- cooking equipment that is listed specifically for
mercial cooking equipment listed for installation installation on floors constructed of combustible
at lesser clearances may be installed ~n material may be mounted on combustible floors
accordance with its listing and the manu- in accordance with its listing.

71
MS 930:1986

6.5.3.2 Listed floor-mounted commercial metal not less than 0.495 mm thick. Such
cooking equipment that is designed and marked masonry courses shall be laid with ends unsealed
‘For use only ir~noncombustible locations’ shall and joints matched in such a way as to provide for
be mounted on floors of noncombustible free circulation of air through the masonry.
construction with noncombustible flooring and
surface finish and with no combustible material (d) When the equipment does not have legs at
least 1 00 mm high. it may be mounted on
against the underside thereof, or on non-
combustible floors. provided the floor under the
cornbust~ble slabs or arches having no
combustible material against the underside equipment is protected by two courses of
thereof. Such construction shall in all cases 100 mm hollow clay tile, or equivalent, with
extend not less than 300 mm beyond the courses laid at right angles and with ends
unsealed and joints matches in such a way as to
equipment on all sides.
provide for free circulation of air through such
masonry courses and covered with steel plate not
6.5.3.3 Floor-mounted commercial cooking
less than 5 mm in thickness.
equipment which is not listed for mounting on a
combustible floor shall be mounted in
,
6.5.4 Combustible material adjacent to
accordance with 6.5.3.2 or be mounted in cooking top. Any portion of combustible material
accordance with one of the following: adjacent to a cooking top section of a hotel or
restaurant range, even though listed for close-to-
(a) When the equipment is set on legs which
wall installation, which is not shielded from the
provide not less than 450 mm open space under
wall by a high shelf, warming closet, etc. shall be
the base of the equipment, or where it has no
protected in an approved manner according to
burners and no portion of any oven or broiler
the requirements of the Uniform Building By-
within 450 mm of the floor, it may be mounted on
Laws for a distance of at least 600 mm above the
a combustible floor without special floor surface of the cooking top.
protection. provided there is at least one sheet
metal baffle between the burner and the floor. 6.5.5 For use with casters. Floor-mounted
equipment with casters shall be listed for such
(b) When the equipment is set on legs which
construction and shall be installed in accordance
provide not less than 200 mm open space under
with their listing and the accompanying
the base of the equipment, it may be mounted on
instructions for limiting the movement of the
combustible floors provided the floor under the
equipment to prevent strain on the connection.
equipment is protected with not less than 1 0 mm
insulating millboard covered with sheet metal not 6.5.6 Install Level. Floor-mounted commercial
less than 0.495 mm thick. The above specified cooking equipment shall be installed level on a
floor protection shall extend not less than firm foundation.
1 50 mm beyond the equipment on all sides.
6.5.7 Ventilation. Adequate means shall he
(c) When the equipment is set on legs which provided to properly ventilate the space in which
provide not less than 100 mm under the base of commercial cooking equipment is installed to
the equipment, it may be mounted on permit proper combustion of the gas. When
combustible floors, provided the floor under the exhaust fans are used for ventilation, special
equipment is protected with hollow masonry not precautions may be necessary to avoid inter
less than 100 mm in thickness covered with sheet ference with the operation of the equipment.

72
MS 930: 1986

6.6 Commercial counter appliances least 7 mm thick~overedwith sheet metal not less
than 0.310 mm thick. or with equivalent
6.6.1 Vertical clearance. A vertical distance of protection.
not less than 1 .2 mm shall be provided between
the top of all commercial hot plates and griddles
and combustible material. 6.7 Conversion burners

6.6.2 Clearance for listed appliances. Listed 6.7.1 installation of conversion burners shall
commercial counter appliances such as hot conform to ANSI Z2 1 .8, ‘Standard for installation
plates and griddles. food and dish warmers, and of domestic gas conversion burners’.
coffee brewers and urns, when installed on
combustible surfaces, shall be set on their own
bases or legs and shall be installed with a 6.8 Hot plates and laundry stoves
mininum horizontal clearance of 1 50 mm from
combustible material except that at least a 50 mm 6.8.1 Listed domestic hot plates and laundry
clearance shall be maintained between the flue stoves installed on combustible surfaces shall be
box or draft hood and combustible material. set on their own legs or bases. They shall be
Commercial counter appliances listed for installed with minimum horizontal clearances of
installation at lesse’r clearances may be installed 1 50 mm from combustible material.
in accordance with their listing and the
manufacturer’s instructions. 6.8.2 Unlisted domestic hot plates and laundry
stoves shall be installed with horizontal
6.6.3 Clearance for unlisted appliances. clearances to combustible material of not less
Unlisted commercial hot plates and griddles shall than 300 mm. Combustible surfaces under
be installed with a hor~izontalclearance from unlisted domestic hot plates and laundry stoves
combustible material of not less than 450 mm. shall be protected in an approved manner
Unlisted gas commercial counter applicances according to the requirements of the Uniform
such as coffee brewers and urns, waffle bakers Building By-Laws.
and hot water immersion sterilizers shall be
installed with a horizontal clearance from 6.8.3 The vertical distance between tops of all
combustible material of not less than 300 mm. domestic hot plates and laundry stoves and
Gas commercial counter appliances may be combustible material shall be at least 750 mm.
installed with reduced clearances to combustible
material provided the combustible material is
protected as described in table 6. Unlisted food 6.9 Household cooking appliances
and dish warmers shall be installed with a
horizontal clearance from combustile material of 6.9.1 Floor-mounted units
not less than 1 50 mm.
6.9.1.1 Clearance from combustible material.
6.6.4 Mounting of unlisted appliances. Un- The clearances specified below shall not interfere
listed commercial counter appliances shall not be with combustion air, accessibility for operation
set on combustible material unless they have legs and servicing.
which provide not less than 1 00 mm of open
space below the burners, and the combustible (a) ‘Listed floor-mounted household cooking
surface is protected with insulating millboard at appliances, except as noted in (b) and (c). when

73
MS 930:1986

installed on combustible floors shall be set on combustible material or metal cabinet, and the
‘their own bases or legs and shall be installed in hood is at least as wide as the appliance is and is
accordance with their listing and the manu- centred over the appliance.
facturers instructions.
6.9.1.3 Install level. Cooking appliances shall
(b) Listed household cooking appliances with be installed so that the cooking top or oven racks
listed gas room heater sections shall be installed are level.
so that the warm air discharge side shall have a
minimum clearance of 450 mm from adjacent 6.9.2 Built-in units
combustible material. A minimum clearance of
900 mm shall be provided between the top of the 6.9.2.1 Installation. Listed built-in household
heater section and the bottom of cabinets. cooking appliances shall be installed in
accordance with their listing and the manu-
(c) Household cooking appliances which facturer’s instructions. Listed built-in household
include a solid or liquid fuel burning section shall cooking appliances may be installed in
be spaced from combustible material and combustible material unless otherwise marked.
otherwise installed in accordance with the
standards applying to the supplementary fuels The installation shall not interfere with
section of the appliance. combustion air, accessibility for operation and
servicing.
(d) Unlisted floor-mounted household cooking
appliances shall be installed with at least a Unlisted built-in household cooking appliances
1 50 mm clearance at the back and sides at shall not be installed in. or adjacent’ to.
combustible material. Combustible floors under combustible material.
unlisted appliances shall be protected in an
approved manner according to the requirements 6.9.2.2 Vertical clearance. Built-in top (or
of the Uniform Building By-Laws. surface) cooking appliances shall have a vertical
clearance above the cooking top of not less than
6.9.1 .2 Vertical clearance above cooking top. 750 mm to combustible material or metal
Household cooking appliances shall have a cabinets, except the clearance may be reduced to
vertical clearance above the cooking top of not not less than 600 mm follows:
less than 750 mm to combustible material or
metal cabinets, except the clearance may be (a) the underside of the combustible material or
reduced to not less than 600 mm as follows: metal cabinet above the cooking top is protected
with not less than 7 mm insulating millboard
(a) the underside of the combustible material or covered with sheet metal not less than 0.31 0 mm
metal cabinet above the cooking top is protected thick, or
with not less than 7 mm insulating millboard
covered with sheet:~metal not less than
. (b) a metal ventilating hood of sheet metal not
‘0.310mm thick, or less than 0.31 0 mm thick is installed above the
cooking top with a clearance of not less than
(b) a metal ventilating hood of sheet metal not 7 mm between the hood and the underside of the
less than 0.310 mm is installed above the combustible material or metal cabinet, and the
cooking ‘top with a clearance of not less than hood is at least as wide as the appliance is and is
7 mm between the hood and the underside of the centred over the appliance.

74
MS 930: 1986

6.9.2.3 Horizontal clearance. The minimum 6.10.2.2 Open-flame type


horizontal distance from the centre of the burner
head(s) of a listed top (or surface) cooking (a) Unlisted open-flame illuminating appliances
appliance to vertical combustible walls extending installed outdoors shall have clearances from
above the top panel shall be not less than that combustible material not less than that specified
distance specified by the permanent marking on in table 7. The distance from ground level to the
the appliance. base of the burner shall be at least 2 m when
installed within 0.6 m of walkways. Lesser
6.9.2.4 Install level. Built-in household cooking clearances may be used when acceptable to the
appliances shall be installed so that the cooking authority having jurisdiction.
Lop, broiler pan or oven racks are level.
(b) Unlisted open-flame illuminating appliances
installed outdoors shall be equipped with a
6.10 Illuminating appliances limiting orifice or other limiting devices whlchwlll
maintain a flame height consistent with the.
6.10.1 Clearances for listed appliances. Listed clearance from combustible material, as given in
illuminating appliances shall be nstalled in table 7.
accordance with their listing and the
manufacturer’s instructions. (ci Appliances designed for flame heights in
excess of 750 mm may be installed if acceptable
6.10.2 Clearances for unlisted appliances to the authority having jurisdiction’. Such
appliances shall be equipped with a safety shutoff
6.10.2.1 Enclosed type device or automatic ignition.

(a) Unlisted enclosed illuminating appliances (dl Unlisted open-flame illuminating appliances
installed outdoors shall be installed with installed indoors shall have clearances from
clearances in any direction from combustible combustible material acceptable to the authority
material of not less than 300 mm. having jurisdiction.

(b) Unlisted enclosed illuminating appliances 6.10.3 Mounting on buildings. Illuminating


installed indoors shall be installed with appliances designed for wall or ceiling mounting
clearances in any direction from combustible shall be securely attached to substantial
material of not less than 450 mm. structures in such a manner that they are not
dependent on the gas piping for support.
Table 7. Clearances to combustible material
for unlisted open-flame illuminating appliances 6.10.4 Mounting on posts.Illuminating
appliances designed for post mounting shall be
Flame height Minimum clearance from securely and rigidly attached to a post.
above burner combustible material, m
head, mm Horizontal Vertical
Posts shall be rigidly mounted. The strength and
300 0.6 1.8 rigidity of posts greaterthan 1 m in height shall be
450 0.9 2.4 at least equivalent to that of a 65 mm diameter
600 0.9 3.0
post constructed of 1 .625 mm thick steel or a
750 1.2 3.6
25 mm (1 inch) schedule 40 steel pipe. Posts 1 m

75
MS 930: 1986

or less in heightshall not be smallerthan a 20mm during loading need not comply with this
(3/4 inch) schedule 40 steel pipe or equivalent. paragraph.

Drain openings should be provided nearthe base. 6.12.1.3 Unlisted incinerators shall be in-
of posts when there is a possibility of water stalled with clearances to combustible material of
collecting inside them. not less than 900 mm at the sides, top and back
and not less than 1.2 mat the front. but in no case
6.10.5 Gas appliance pressure regulators. shall the clearance above a charging door be less
When a gas appliance pressure regulator is not than 1 .2 m. Unlisted wall mounted incinerators
supplied with an illuminating appliance and the shall be installed on a noncombustible wall
service line is not equipped with a service communicating directly with a chimney.
pressure regulator. an appliance pressure
regulators shall be installed in the line to the 6.12.1.4 Domestic type incinerators may be
illuminating appliance. For multiple installations, installed with reduced clearances to combustible
one regulator of adequate capacity may be used material in rooms, provided the combustible
to serve a number of illuminating appliances. material is protected as described in table 6. In
partially enclosed areas, such as alcoves.
clearance shall not be so reduced.
6.1 1 Incinerators, commercial-industrial
6.12.1.5 Whenadomestictypeincineratorthat
Commercial-industrial type incinerators shall be is refractory lined or insulated with heat
constructed and installed in accordance with insulating material is encased in common brick
NFPA No. 82. ‘Standard on incinerators, waste not less than 1 00 mm in thickness, the clearances
and linen handling systems and equipment’. may be reduced to 1 50 mm at the sides and rear,
and clearance at the top may be reduced to 600
and clearance at the top may be reduced to
6.12 Incinerators, domestic 600 mm provided that the construction using
combustible material above the charging door
6.12.1 Clearance and within 1 .2 m is protected with sheet metal not
6.12.1.1 Listed incinerators shall be installed less than 0.310 mm thick spaced Out 25 mm. or
in accordance with their listing and the equivalent protection.
manufacturer’s instructions, provided that in any
case the clearance shall be sufficient to afford 6.12.2 Mounting
ready accessibility or firing, clean-out and
necessary servicing. 6.12.2.1 Listed incinerators specially listed for
installation on combustible floors may be so
6.12.1.2 The clearance to combustible installed.
material above a charging door shall be not less
than 1 .2 m. The clearance may be reduced to 6.12.2.2 Unlisted incinerators, except as
600 mm provided the combustible material is provided in 6.1 2.2.3 and 6.1 2.2.4. shall be
protected with sheet metal not less than mounted on the ground or on floors of
0.310 mm thick spaced out 25 mm on noncombustible construction with noncom-
noncombustible spacers, or equivalent pro- bustible flooring or surface finish and with no
tection. Such protection shall extend 450 mm combustible material against the underside
beyond all sides of the charging door opening. thereof. or on noncombustible slabs or arches
Listed incinerators designed to retain the flame having no combustible material against the

76
‘MS930: 1986

underside thereof. Such construction shall 6.12.4 Venting. Incinerators shall be vented in
extend not less than 300 mm beyond the accordance with 7.3, 7.4, 7.6 and 7.9.
incinerator base on all sides. except at the front or
side where ashes are removed where it shall
extend not less than 450 mm beyond the
6.13 Infrared heaters
i n ci n e rator.

6.13.1 Support. Suspended type infrared


6.12.2.3 Unlisted incinerators may be
heaters shall be safely and adequately fixed in
mounted on floors other than as specified in
position independent of gas and electric supply
6.1 2.2.2. provided the incinerator is so arranged
lines. Hangers and brackets shall be of
that flame or hot gases do not come in contact
noncombustible material.
with its base and, further, provided the floor
under the incinerator is protected with hollow Heaters subject to vibration shall be provided
masonry not less than 100 mm thick, covered with vibration isolating hangers.
with sheet metal not less than 0.495 mm thick.
Such masonry course shall be laid with ends 6.13.2 Clearance
unsealed and joints matched in such a way as to
provide a’ free circulation of air from side to side 6.13.2.1 Listed heaters shall be installed with
through the masonry. The floor for 450 mm clearances from combustible material in
beyond the front of the incinerator or side where accordance with their listing and the manu-
ashes are removed and 300 mm beyond all other facturer’s instructions.
sides of the incinerator ~hall be protected with
not less than 7 mm insulating millboard covered 6.13.2.2 Unlisted heaters shall be installed in
with sheet metal not less than 0.49 5 mm thick or accordance with clearances from combustible
with equivalent protection. material acceptable to the authority having
jurisdiction.
6.12.2.4 Unlisted incinerators which are set on
legs that provide not less than 1 00 mm open 6.13.2.3 In locations used for the storage of
space under the base of the incinerator may be combustible materials, signs shall be posted to
mounted on floors other than as specified in specify the maximum permissible stacking height
6.1 2.2.3. provided the incinerator is such that to maintain required clearances from the heater
flame or hot gases do not come in contactwith its to the combustibles.
base and, further, provided the floor under the
incinerator is protected with not less than 7 mm 6.13.3 Combustion and ventilation air
insulating millboard covered with sheet metal not
less than 0.49 5 mm thick. The above specified 6.13.3.1 Where unvented infrared heaters are
used. natural or mechanical means shall be
floor protection shall extend not less than
provided to supply and exhaust at least
450 mm beyond the front of the incinerator or
0.1 cubic metre per minute per 1.000 kJ per hour
side where ashes are removed and 300 mm
(4 cubic feet per minute per 1 .000 Btu per hour)
beyond all other sides of the incinerator.
input of installed heaters.
6.12.3 Draft hood prohibited. Draft hoods shall
not be installed in the vent connector of an 6.13.3.2 Exhaust openings for removing flue
incinerator. products shall be above the level of the heaters.

77
MS 930: 1986

6.14 Open top broiler units 6.16 Pool heaters

6.14.1 Listed units. Listed open top broiler 6.16.1 Location. A pool heater shall be located
units shall be installed in accordance with their or protected so as to minimize accidental contact
listing and the manufacturer’s instructions. of hot surfaces by persons.

6.16.2 Clearance
6.14.2 Unlisted units. Unlisted open top broiler
units shall be installed in accordance with the
6.16.2.1 In no case shall the clearances be
manufacturer’s instruction, but shall not be
such as to interfere with combustion air, draft
installed in combustible material.
hood or vent terminal clearance and relief, and
accessibility for servicing.
6.14.3 Protection above domestic units.
Domestic open top broiler units shall be provided
6.16.2.2 A listed pool heater shall be installed
with a metal ventilating hood ‘not less than
in accordance with its listing and the
0.310 mm thick with a clearance of not less than
manufacturer’s instructions.
7 mm between the hood and the underside of
combustible material or metal cabinets. A 6.16.2.3 An unlisted pool heater shall be
clearance of at least 600 mm shall be maintained installed with a minimum clearance of 300 mm
between the cooking top and the combustible on all sides and the rear. A combustible floor
material or metal cabinet, and the hood shall be at under an unlisted pool heater shall be protected
least as wide as the open top broiler unit is and be in an approved manner according to the
centred over the unit. requirements of the Uniform Building By-Laws.

6.14.4 Commercial units. Commercial open 6.1 6.3 Temperature or pressure limiting
top broiler units shall be provided with ventilation devices
in accordance with NFPA No. 96, Standard for
the installation of equipment for the removal of 6.16.3.1 An unlisted pool heater shall be
smoke and grease-laden vapours from provided with overtemperature protection or
commercial cooking equipment’. overtemperature and overpressure protection by
means of an approved device(s).

6.16.3.2 When a pool heater is provided with


6.15 Outdoor cooking appliances
overtemperature protection only, and is installed
with any device in the discharge line of theheater
6.15.1 Listed units. Listed outdoor cooking
that can restrict the flow of water from the heater
appliances shall be installed in accordance with
their listing and the manufacturer’s instructions. to the pool (such as a check valve, shutoff valve,
therapeutic pool valving, flow nozzles. etc.) a
6.15.2 Unlisted units. Unlisted outdoor pressure relief valve shall be installed either in the
cooking appliances shall be installed outdoors heater or between the heater and the restrictive
with clearances to combustible material of not device.
less than 900 mm at the sides and back and not
less than 1 .2 m at the front. In no case shall the 6.16.4 Bypass valves. If an integral bypass
appliance be located under overhead com- system is not provided as a partof the pool heater,
bustible construction. a bypass line and’valve shall be installed between

78
MS 930: 1986

the inlet and outlet piping for use in adjusting the 6.18.3 Clearance. A room heater shall be
flow of water through the heater. placed so as not to cause a hazard to walls, floors,
curtains. furniture, doors wi~enopen, etc. and to
6.1 6.5 Venting. A pool heater listed for outdoor the free movements of persons within the room.
installation shall be installed with the venting Heaters designed and marked ‘For use in
means supplied by the manufacturer and in noncombustible fireplace only’, shall not be
accordance with the manufacturer’s instructions. installed elsewhere. Listed room heaters shall be
(See 7.7 and 7.14). installed in accordance with their listings and the
manufacturer’s instructions. In no case shall the
clearances be such as to interfere with
6.17 Refrigerators
combustion air and accessibility. (See 5.2.1 and
5.3).
6.17.1 Clearance.
Refrigerators shall be
provided with adequate clearancesfor ventilation
at the top and back. They shall be installed in Unlisted room heaters shall be installed with
accordance with the manufacturer’s instructions. clearances from combustible material not less
If such instructions are not available, at least than the following:
50 mm shall be provided between the back of the
refrigerator and the wall and at least 300 mm (a) Circulating type. Room heaters having an
above the top. outer jacket surrounding the combustion
chamber, arranged with openings at top and
6.17.2 Venting or ventilating kits approved for bottom so that air circulates between the inner
the use with a refrigerator. If an accessory kit is and outer jacket. and without openings in the
used for conveying air for burner combustion or outer jacket to permit direct radiation, shall have
unit cooling to the refrig’~ratorfromareas outside clearance at sides and rear of not less than
the room in which it is located, or for conveying 300 mm.
combustion products diluted with air containing
waste heat from the refrigerator to areas outside (b) Radiating type. Room heaters other than
the room in which it is located, the kit shall be those described above as of circulating type shall
installed in accordance with the refrigerator have clearance at sides and rear of not less than
manufacturer’s instructions. 450 mm; except that heaters which make use of
metal, asbestos or ceramic material to direct
radiation to the front of the heater shall have a
6.18 Room heaters
clearance of 900 mm in front. and if constructed
with a double back of metal or ceramic may be
6.1 8.1 Installations in sleeping quarters.
installed with a clearance of 450 mm atsides and
Unvented room heaters shall not be installed in
300 mm at rear. Combustible floors under
sleeping quarters.
unlisted room heaters shall be protected in an
NOTE 26. it is recommended that space heating appiiances instalied approved manner according to the requirements
in all sleeping quarters or rooms generally kept closed be of the direct
of the Uniform Building By-Laws.
vent type (see 6.22).

6.18.2 Installations in institutions. Room 6.18.4 Wall-type room heaters. Wall-type room
heaters shall not be installed in institutions such heaters shall not be installed in or attached to
as homes for the aged. sanitariums, convalescent walls of combustible material unless listed for
homes, orphanages. etc. such installation.

79
MS 930: 1986

6.19 Sauna heaters 6.19.2.5 Panels, grilles and access doors


which must be removed for normal servicing
6.19.1 Location and protection operations. shall not be attached to the building.

6.19.1.1 A sauna heater shall be so located as 6.19.2.6 A sauna heater of other than the direct
to minimize the possibility of accidental contact vent type shall be installed generally in
by a person in the room. accordance with fig. 7. If the combustion air inle’t
and the draft hood are in a dressing room
6.19.1,2 A sauna heater shall be protected adjacent to the sauna room, there shall be
from accidental contact by a guard or barrier of provisions to physically prevent blocking the
material having a low coefficient of thermal combustible air inlet and the draft hood inlet, and
conductivity. Wood is satisfactory for this to prevent physical contact with the draft hood
application. The guard shall have no substantial and vent assembly, or warning notices shall be
effect on- the transfer of heat from the heater to posted to avoid such contact. Anywarning notice
the room. shall be easily readable, shall contrast with its
background, and the wording shall be in letters
6.19.2 Installation of heater.
not less than 5 mm high.
6.19.2.1 A listed sauna heatershall be installed
6.19.3 Connection. The provisions of 5.5. shall
in accordance with its listing and the manu-
be observed except that when access to controls
facturer’s instructions.
is from an adjacent room, connections shall be
made in that area. -
6.19.2.2 An unlisted sauna heater shall be
installed in accordance with the following:
6.19.4 Combustion and ventilation air
(a) The heater shall be installed on noncom-
bustible flooring or on flooring which has been 6.19.4.1 Combustion air shall not be taken
equivalently protected in an approved manner from inside the sauna room.
according to the requirements of the Uniform
Building By-Laws. 6.19.4.2 Adequate combustion and ventilation
air for a heater not of the direct vent type shall be
(b) The heater shall be installed in compliance provided to the area in which the combustion air
with the manufacturer’s instructions except that inlet and draft hood are located by suitable means
clearances to the sides, back and top of the heater (see 5.3).
shall be not less than 900 mm.
6.19.5 Means for heat or exposure limitation
6.19.2.3 An unlisted sauna heater shall not be
installed in or attached to combustible material. 6.19.5.1 A sauna heater shall be equipped with
a thermostat which will limit room temperature to
6.19.2.4 A direct vent sauna heater shall be 90°C. If the thermostat is not an integral part ot
installed with the vent/air intake terminal in the the heater, the heat sensing element shall .be
outside atmosphere. The thickness of the wall on located within 1 50 mm of the ceiling. If the heat.
which the heater is mounted shall be within the sensing element is a capillary tube and bulb, the
range of wall thicknesses marked on the heater assembly shall be attached to the wall or other
and covered in the manufacturer’s installation support, and shall be protected against physical
instructions. damage.

80
MS 930: 1986

6.19.5.2 A timer, if provided to control main 6.19.6.2 The following notice on permanent
burner operation, shall have a maximum marking material shall be mechanically attached
operating time of 1 hour. The control for the timer to the sauna room on the outside:
shall be located outside the sauna room.
‘Warning: Do not exceed 30 minutes in sauna.
6.19.6 Provisions for sauna room equipped Excessive exposure can be harmful to health. Any
with a gas-fired sauna heater person with poor health should consult a
physician before using sauna’.
6.19.6.1 A ventilation opening into the sauna
room shall be provided. This shall be not less than This marking shall contrast with its background
100 mm by 200 mm opening near the top of the and the wording shall be in letters not less than
door into the sauna room. 5 mm high.

Draft /
/ partition

Vent Thimble

access Sauna heater

Combustion
air inlet

Floor

Figure 7. Typical sauna heater installation

81
MS 930: 1986

6.20 Stationary gas engines the flue gases are vented horizontally. the
.

1 50 mm clearance shall be measured fromn the


6.20.1 The installation of gas engines shall draft hood or vent instead of the rear ~vallof unit
conform with NFPA No. 37. ‘Standard for the heater.
installation and use of stationary combustion
engines and gas turbines’ (b) A unit heater listed for reduced clearances
shall be installed in accordance with its listing
and the manufacturer’s instructions.

6.21 Unit heaters (c) Floor-mounted type unit heaters may be


installed on combustible floors if listed for such
6.21.1 Support. Suspended type unit heaters installation.
shall be safely and adequately supported with due
consideration given to their weight and vibration (d) Combustible floors under unlisted floor~
characteristics. Hangers and brackets shall be of mounted unit heaters shall be protected in an
noncombustible material. approved manner according to the requirements
of the Uniform Building By-Laws.
6.21.2 Clearance
(e) Clearances for servicing shall be in
6.21.2.1 Suspended type unit heaters accordance with the manufacturer’s recom-
mendations contained in the installation
(a) A listed unit heater shall be installed with instructions.
clearances from combustible material of not less
than 450 mm at the sides, 300 mm at the bottom 6.21.3 Combustion and circulating air. Ade~
and 1 50 mm above the top when the unit heater quate combustion and circulating air shall be
has an internal draft hood, or 25 mm above the provided (see 5.3).
top of the sloping side of a vertical draft hood.
6.21.4 Ductwork. A unit heater shall not be
(b) A unit heater listed for reduced clearances attached to a warm air duct system unless listed
shall be installed in accordance with its listing and marked for such installation.
and the manufacturer’s instructions.
6.21 .5 Installation in commercial garages. Unit
(c) Unlisted unit heaters shall be installed with heaters installed in garages for more than 3
clearances to combustible material of not less motor vehicles or in aircraft hangars shall be of a
than 450 mm. listed type and shall be installed in accordance
with 5.1.9.
(d) Clearances for servicing shall be in
accordance with the manufacturer’s recom-
mendations contained in the installation 6.22 WaIl furnaces
instructions.
6.22.1 Installation
6.21.2.2 Floor-mounted type unit heaters.
6.22.1.1 A listed wall furnace shall be installed’
(a) A listed unit heater shall be installed with in accordance with its listing and the manufac-
clearances from combustible material at the back turer’s instructions. They may be installed in or
and one side only of not less than 1 50 mm. When attached to conribustible material.

82
MS 930:1986

6.22.1.2 Unlisted wall furnaces shall not be spacers furnished with the gas vent. Fire stop
installed in or attached to combustible material. spacers shall be installed at each subsequent
ceiling or floor level penetrated by the vent. (See
6.22.1.3 Vented wall furnaces connected to a fig. 8 for type B-W gas vent installation).
type B-W gas vent system listed only for single
storey shall be installed only in single storey
buildings or the top storey of multistorey 6.22.1.4 Direct vent wall furnaces shall be
buildings. Vented wall furnaces connected to a installed with the vent/air intake terminal in the
type B-W gas vent system listed for installation in outside atmosphere. The thickness of the walls on
multistorey buildings may be installed in single which the furnace is mounted shall be within the
storey or multistorey buildings. Type B-W gas range of wall thickness marked on the furnace
vents shall be attached directly to a solid header and covered in the manufacturer’s installation
plate which serves as a fire stop at that point and instructions.
which may be an integral part of the vented wall
furnace. The stud space in which the vented wall 6.22.1.5 Panels, grilles and access doors
furnace is installed shall be ventilated at the first which must be removed for normal servicing
ceiling level by installation of the ceiling plate operations shall not be attached to the building.

Installation of B-W gas vent


for each subsequent ceiling or floor
level of multistorey buildings. Firestop spacers supplied by manufacturer
/
~

of B-W gas vent.

/ ,, Plate cut away to provide


~ passage of B-W gas vent.

— Nail firestop spacer securely.

Installation of B-W gas vent


for one storey building or for
first floor or multistorey buildings
Ceiling plate spacers to centre
B-W gas vent in stud space-nail securely at
both ends.

Plate cut away for full width of


stud space to provide ventilation.

Studs on 16 inch centres

Sheet metal screw base plate to header

Use manufacturer’s method of


fastening pipe to base plate
Header plate of vented wall furnace
(Also acts as firestop)

Figure 8. Installation of type B-W gas vents for


vented wall furnaces

83
MS 930:1986

6.22.2 Location. Wall furnaces shall be located 6.23.4 Connections. Water heaters shall be
so as not to cause a hazard to walls, floors, connected in a manner to permit observation
curtains, furniture or doors. Wall furnaces maintenance and servicing.
installed between bathrooms and adjoining
rooms shall not circulate air from bathrooms to 6.23.5 Pressure limiting devices. A water
other parts of the building. ‘heater installation shall be provided with over-
pressure protection by means of an approved
device constructed, listed and installed in
6.22.3 Combustion and circulating air. Ade-
accordance with approved standards for such
quate combustion and circulating air shall be
devices.
provided (see 5.3).

6.23.6 Temperature limiting devices. An


automatic storage-type water heater installation
6.23 Water heaters or a hot water stor~gevessel installation shall be
provided with overtemperature protection by
6.23.1 Prohibited installations. Water heaters, means of approved device constructed. listed and
with the exception of those having direct-vent installed in accordance with approved standards
systems, shall not be installed in bathrooms, for such devices.
bedrooms or any occupied rooms normally kept
closed. 6.23.7 Temperature. pressure and vacuum
relief devices. The installation of temperature.
Single-faucet automatic instantaneous water pressure and vacuum relief devices or
heaters, as permitted under 7.1.2 in addition to combinations thereof, and automatic gas shutoff
the above, shall not be installed in kitchen devices shall be in accordance with approved
sections of light housekeeping rooms or rooms standards for such devices.
used by transients.
6.23.8 Automatic instantaneous type. The
6.23.2 Location. Water heaters of other than water supply to any automatic instantaneous
the direct vent type shall be located as close as water heater shall be such as to provide sufficient
practicable to the chimney or gas vent. pressure to properly operate the water actuated
control valve when drawing hot water from a
6.23.3 Clearance faucet on the top floor.

6.23.3.1 In no case shall the clearances be 6.23.9 Circulating or tank types


such as to interfere with combustion air, draft
hood clearance and relief, and accessibility for 6.23.9.1 Connection to boiler or tank. The
servicing. Listed water heaters shall be installed method of connecting the circulating water
in accordance with their listing and the manu- heater to the tank shall provide proper circulation
facturer’s instructions. of water through the heater and permit a safe and
useful temperature of water to be drawn from the
6.23.3.2 Unlisted water heaters shall be
.
tank. (See fig. 9).
installed with a clearance of 300 mm on all sides
and rear. Combustible floors under unlisted water 6.23.9.2 Size of water circulating piping. The
heaters shall be protected in an approved manner size of the water circulating piping, in general.
according to the requirements of the Uniform shall conform with the size of the water
Building By-Laws. connections of the heater.

84
MS 930 : 1986

6.23.9.3 Sediment drain. A suitable watervalve ceptable to the authority having jurisdiction shall
or cock, through which sediment may be drawn be provided to prevent siphoning in any boiler or
off or the tank emptied, shall be installed at the tank to which any circulating water heater is
bottom of the tank. attached. A cold water tube with a hole near the
top is commonly accepted for this purpose. (See
6.23.9.4 Anti-siphoning devices. Means ac- fig. 9).

Cold water
Anti-siphon opening

Limit control

Vent con~iector
Drain

Gas inlet

Figure 9. Suggested location for anti-siphon opening in cold water inlet

85
MS 930: 1986

SECTION SEVEN: VENTING OF EQUIPMENT

7.1 Specification for venting (k)~ Specialized equipment of limited input such
as laboratory burners or gas lights.
7.1.1 Connection to venting systems. Except
as noted in 7.1.2, 7.1.3 and 7.1.4, all gas 7.1.3 Ventilatinghoods. Ventilating hoods and
utilization equipment shall be connected to exhaust systems may be used to vent gas
venting systems. utilization equipment installed in commnercial
appllcatlons”and to vent industrial equipment.
7.1.2 Equipment not required to be vented particularly when the process itself requires fume
disposal.
(a) Listed ranges.
7.1.4 WeII-ventilatedspaces. When located in
(b) Built-in domestic cooking units listed and
a large and well-ventilated space, industrial gas
marked for o~tionaIventing.
utilization equipment may be operated by
discharging the flue gases directly into the space.
(c) Listed hot plates and listed laundry stoves.

(d) Listed type 1 clothes dryers (see 6.4.4).


7.2 Minimum safe performance
(e)~ A single listed booster type (automatic
instantaneous) water heater when designed and 7.2.1 Adequate draft
used solely for the sanitizing rinse requirements
of a National Sanitation foundation Class 1. 2 or 3 7.2.1.1 A venting system shall bedes~gri~d
~,nd
dishwashing machine, provided that the input, is constructed so as to develop a positR’e lb”.
limited to 52.700 kJ (50.000 Btu) per hour, the adequate to remove flue gases to the uu’isidn
storage capacity is limited to 50 litres and the atmosphere.
heater is installed, with the draft hood in place
and unaltered. in a commercial kitchen having a
mechanical exhaust system. When installed in
this manner. the draft hood outlet shall not be less ‘When any or all of this equipment is instalied so ihat the aggregate
inpui rating exceeds 745 kJ per hour per cubic metre (20 Etu per hour
than 900 mm vertically and 1 50 mm horizontally
per cubic foot) of room or space in which it is instalied. one or more
from any surface other than the heater. shail be provided with venting systems or other approved means for
removing the vent gases to the outside atmosphere so that the
aggregate input rating of the remaining unvented equipment does not
(fY Listed refrigerators. exceed the 745 kJ per hour per cubic metre (20 Stu per hour percubic
fäot) figure. When the room or space in which the equipment is
instaiied is directly connected to another room or space by a doorway.
(g)~ Counter appliances.
archway or other opening of comparabie size which cannot be closed.
the volume of such adiacent room or space may be included in the
(h) Room heaters listed for unvented use (see calculations,

6.18.1 and 6.18.2). -

V~lnformationon the construction and installation of ventilating hoods

(j)~ Otherequipment I’istedfor unvented use and may be obtained from NFPA No, 96. ‘Standard for the instaHation of
equipment for the removal of smoke and grease-laden vapolirs from
not provided with flue collars. commercial cooking equipment’.

86
MS 930: ‘1986

7.2.1.2 A venting system serving gas utilization (b) Equipment which may be converted to the
equipment requiring draft for proper operation use of solid or liquid fuels.
shall be designed and installed to develop
adequate draft so as to satisfy the draft (c) Combination gas - and oil - burning
requirements of the equipment in accordance equipment.
with the manufacturer’s instructions.
(d) Equipment listed for usewith chimneys only.
7.2.2 Design and construction. Gas utilization
equipment required to be vented shall be (e) Unlisted equipment.
connected to a venting system, except as 7.3.3 Type B gas vents. Listed gas utilization
provided in 7.14. The venting system shall be equipment equipped with draft hoods and other
designed and constructed in accordance with equipment listed for use with type B gas vents
one of the following methods: may be connected to type B vents, except (a) as
provided in 7.3.2, 7.3.4 and 7.3.7, and (b)
(a) Natural draft provisions of 7.3 through 7.9. commercial cooking equipment listed as not
suitable for connection to type B gas vent.
(b) Natural draft systems designed in accor-
dance with approved engineering methods and 7.3.4 Type B-Wgas vents. Type B-W gas vents
installed in accordance with the plans and shall be used with listed vented wall furnaces
specifications of that design. when the furnace is so listed. Also see 6.28.

(C) Special venting arrangements of 7.1 4. 7.3.5 Single wall metal pipe. Single-wall metal
pipe may be used in accordance with 7.6 for
7.2.3 Circulating air ducts and plenums. No venting the following:
portion of a venting sy~emshall extend into or
pass through any circulating air duct or plenum. (a) Domestic-type and low-heat gas utilization
equipment equipped with draft hoods, except as
provided in 7.3.2 and 7.3.4.
7.3 Type of venting system to be used
(b) Incinerators used outdoors such as in open
sheds, breezeways, or carports as provided in
7.3.1 Venting systems are intended for venting
7.6.3.3.
flue gases at zero or negative pressures unless
the venting system is made so as to prevent the
7.3.6 Type L vents. Type L vents may be used
leakage of vent gases into a building. (See
for venting gas utilization equipment listed for
17.14.3.2).
use with type L vents and equipment listed as
suitable for use with type B gas vents.
7.3.2 Chimneys. Chimneys shall be used for
venting the following types of gas utilization 7.3.7 Special venting arrangements
equipment:
(a) Direct vent equipment. (See 7.14.1)
(a) Incinerators, except as provided in 7.3.5(b)
and 7.14.2. (b) Equipment with integral vent. (See 7.14.2)

87
MS 930:1986

(c) Mechanical draft systems. (See 7.1 4.3) and 44 in appendix G.~As an alternate method of
sizing an individual chimney venting system fora
(d) Ventilating hoods and exhaust systems. (See single appliance only. the effective areas of the
7.14.4). vent connector and chimney flue shall be not less
than the area of the appliance draft hood or flue
outlet. As an alternate method for sizing a
chimney connected to more than one appliance,
7.4 Masonry, metal and factory-built
the effective area of the chimney flue shall be not
chimneys
less than the area of the largest vent connector
plus 50% of the area of additional draft hood or
7.4.1 Listing or construction
flue outlets.
7.4.1.1 Factory-built chimneys shall be
installed in accordance with their listing and the 7.4.3.2 When an incinerator is vented by a
manufacturer’s instructions. chimney serving other gas utilization equipment.
the gas input to the incinerator need not be
7.4.1.2 Mansonry or metal chimneys shall be included in calculating chimney size provided the
built and installed in accordancewith the Uniform chimney flue diameter is not less than 25 mm
Building By-Laws or NFPA No. 211, ‘Standard for larger in equivalent d iameter than the diameter of
chimneys, fireplaces and vents’. the incinerator flue outlet.

7.4.2 Termination 7.4.4 Inspection of chimneys

7.4.2.1 A chimney for domestic-type or low- 7.4.4.1 Before connecting a vent connector to
heat gas utilization equipment shall extend at a chimney. the chimney passageway shall be
least 1 m above the highest pointwhere it passes examined to ascertain that it is clear and free of
through a roof of a building and at least 600 mm obstructions.
higher than any portion of a building within a
7.4.4.2 Cleanouts shall be examined to deter
horizontal distance of 3 m. (See fig. 10).
mine they will remain tightly closed when not in
7.4.2.2 A chimney for medium-heat equipment use.
shall extend at least 3 m higher than any portion
of any building within 7.5 m. 7.4.4.3 When inspection reveals that an
existing chimney is not safe for the intended
7.4.2.3 A chimney shall extend at least 1.5 m application, it shall be rebuilt to conform to the
above the highest connected equipment draft Uniform Building By-Laws or NFPA No. 211,
hood outlet or flue collar. ‘Standard for chimneys, fireplaces and vents,’
lined or relined with a suitable liner, or replaced
7.4.3 Size of chimneys with a vent or chimney suitable for the equipment
to be attached.
7.4.3.1 Excapt as noted in 7.14 or 7.4.3.2, the
effective area of a chimney venting system shall
~Reference may aiso be made to the chapter on chimneys. gas vents
be in accordance with approved engineering
and firepiace systems of the Equipment volume of the ASHRAE
methods. Reference may be made to tables 41 Hand book.

88
MS 930: 1986

7.4.5 Chimney serving equipment burning at least 1.5 m in vertical height above the highest
other fuels. See 7.9.4. connected equipment draft hood or flue collar.

7.4.6 Support of chimneys. All portions of 7.5.2.4 A type B-W vent shall termigate at least
chimneys shall be supported for the design and 3.7 m in vertical height above the bo~tomof the
weight of the materials employed. Listed factory- wall furna~ce.
built chimneys shall be supported and spaced in
accordance with their listings and the manu- 7.5.2.5 A vent extending through an exterior
wall shall not terminate adjacent to the wall or
facturer’s instructions.
below caves or parapets, except as provided in
7.14.1 and 7.14.3.

7.5 Type B, type B-W and type L vents.


7.5.3 Size of gas vents. Except as provided in
7.5.1 Application 7.14, vents shall be sized and constructed in
accordancewith approved engineering methods.
7.5.1.1 Type B, type B-W and type Lvents shall Reference may be made to tables 39 through 44
be installed in accordance with the terms of their in appendix G depending on the construction of
listings and the manufacturer’s instructions. the vent.~As an alternate method for sizing an
individual vent for single appliance only. the
7.5.1 .2 Type B. type B-W and type L vents may effective area of the vent connector and vent shall
be used for single o’r multiple storey installation if be not less than the area of the appliance draft
so listed. hood outlet. As an alternate method for sizing a
vent connected to more than one appliance, the
effective area of the vent shall be not less than the
7.5.1.3 A type B-W vent shall have a listed
area of the largest vent connector plus 50% of the
capacity not less than that of the listed vented
areas of additional draft hood outlets.
wall furnace to which it is connected.

7.5.4 Vents serving equipment on more than


7.5.1.4 A vent passing through a roof shall
one floor. A single or common type B or type L
extend through the roof flashing. roofjack or roof
vent is permissible in multistorey installations to
thimble.
vent gas utilization equipment located on more
7.5.2 Vent termination than one floor level provided the venting system is
designed and installed in accordance with
7.5.2.1 A vent shall terminate above the roof approved engineering practices.
surface with a listed cap or listed roof assembly in
accordance with the terms of their respective 7.5.5 Support of vents. Vents shall be sup-
listings and the manufacturer’s instructions. ported and spaced in accordance with their
except as provided in 7.14. listings and the manufacturer’s instructions.

7.5.2.2 Aventmaybe donnected toachimney


terminating in accordance with 7.4.2.
‘Reference may also be made to the chapter on chimneys, gas vents
and firepiace systems of ihe Equipment Volume of the ASHRAE
7.5.2.3 A type B or a type L vent shall terminate Handbook.

89
MS 930:,1986

Table 8. Clearances for connectors (note 27)

Minimum distance from combustible material

Equipment Listed type B Listed type L


gas vent vent Single-wall Factory built
material material metal pipe chimney sections

Listed equipment with draft


hoods and equipment listed
for use with type B gas vents as listed as listed 150 mm as listed

Residential boilers and


furnaces with listed gas
conversion burner and with
draft hood 150mm 150 mm 230 mm as listed

Residential appliances
listed for use with type
L vents not permitted as listed 230 mm as listed

Domestic incinerators not permitted 230 mm 450 mm as listed

Unlisted residential app-


liances with draft hood not permitted 150 mm 230 mm as listed

Residential and lowheat


equipment other than
those above not permitted 230 mm 450 mm as listed

Medium-heat equipment not permitted not permitted 900 mm as listed

NOTE 27. These clearances shall apply unless the listing of an appiiance specifies.

7.5.6 Marking. In those localities where solid less than 0.864 mm thick, or other approved
and liquid fuels are used extensively. vents shall noncombustible corrosion-resistant material.
be plainly and permanently identified by a label
attached to the wall or ceiling at a point where the 7.6.2 Termination
vent connector enters the vent. The label shall
read: 7.6.2.1 Single-wall metal pipe shall terminate
at least 1 .5 m in vertical height above the highest
‘This gas vent is for appliances which burn gas. connected equipment draft hood outlet or flue
Do not connect to incinerators or solid or liquid collar.
fuel-burning appliances.’
7.6.2.2 Single-wall metal pipe shall extend at
The authority having jurisdiction shall determine least 600 mm above the highest point where it
whether their area constitutes such a locality, passes through a roof of a building and at least
600 mm higher than any portion of a building
within a horizontal distance of 3 m. (See fig. 10).
7,6 Single-wall metal pipe
7.6.2.3 An approved cap which does not
7.6.1 Construction. Single-wall metal pipe obstruct the pipe outlet shall be attached to the
shall be constructed of galvanized sheet steel not terminus of a single-wall metal pipe.

90
SOOmm
mm.
metal

pipe, 1 m mm.

No height above parapet


required when distance
from walls or parapet
is more than 3 m

wall or parapet

3m or less Height above any


roof surface

_Li within 3 m

ridge
600mmmirt.
i
i
7
,Jl
chimney or metal pipe,
m mm.
ridge
horizontally

metal pipe,

A. Termination 3 m or less from ridge, wall or parapet


B. Termination more than 3 m from ridge, wall or parapet

CD

0:

Figure 10. Typical termination locations ~orchimneys and metal pipes serving CD
CD
tiasWential-type and low-heat equipment
MS 930: 1986

7.6.3 Installation with equipment permitted by and constructed in accordance with approved
7.3.5. engineering methods. Reference may be made to
tables 40 and 43 in appendix G. As an alternate
7.6.3.1 Single-wall metal pipe shall be used method for sizing an individual pipe for a singlo
only for run’s directly from the space in which the appliance only, the effective area of the
gas utilization equipment is located through the connector and the pipe shall not be loss thai’i the
roof or exterior wall to the outer air. A pipe area of the appliance draft hood outlet. As an
passing through a roof shall extend without alternate method of sizing a pipe connected to
interruption through roof flashing, roof jacket or more than one appliance, the effective area ofthe
roof thimble. pipe shall be not less than the area of the largest
connector plus 50% of the area of additional drafi
7.6.3.2 Single-wall metal pipe shall not hood, outlets.
originate in any unoccupied attic or concealed
space and shall not pass through any attic, inside
wall or concealed space. or through anyfloor. For 7.6.4.2 Any shaped single-wall metal pipe may
the installation of a single-wall metal pipe be used, provided its equivalent effective area is
through an exterior combustible wall, see equal to the effective area of the round pipe for
which it is substituted and provided. tlie
7.9.14.2.
minimum internal dimension of the pipe is not
7.6.3.3 Single-wall metal pipe used for venting less than 50 mm.
an incinerator shall be exposed and readily
examinable for its full lenth and suitable 7.6.4.3 The vent cap or a roof assembly shall
clearances maintained. have a venting capacity not less than that of the
pipe to which it is attached.
7.6.3.4 Minimum clearances from single-wall
metal pipe to combustible material shall be in 7.6.5 Support of single-wall metal pipe. All
accordance with table 8. The clearance from portions of single-wall metal pipe shall be
single-wall metol pipe to combustible material supported for the design and weight of the
may be reduced when the combustible material is material employed.
protected as specified for vent connectors in
table 6. 7.6.6 Marking. Single-wall metal pipe shall
comply with the marking provisions of 7.5.6.
7.6.3.5 When a single-wall metal pipe passes
thrOugh a roof constructed of combustible
material, a noncombustible, nonventilating
thimble shall be used at the point of passage. The 7.7 Venting system location
thimble shall extend at least 450 mm above and
1 50 mm below the roof with the annular space 7.7.1 Aventing system shall terminate at least
open at the bottom and closed onlyatthetop. The 1 m above any forced air inlet located within 3 m.
thimble shall be sized in accordance with
7.9.1 4.2. 7.7.2 The venting system of other than a direct
vent appliance shall terminate at least 1.2 m.
7.6.4 Size of single-wall metal pipe below, 1 .2 m horizontally from or 300 mm above
any door, window or gravity air inlet into any
7.6.4.1 Single-wall metal pipe shall be sized building.

92
MS 930: 1986

7.7.3 The vent terminal of a direct vent (b) Appliances not installed in attics. Vent
appliance with an input of 52.700 kJ (50.000 connectors for listed gas appliances having draft
Btu) per hour or less shall be located at least hoods and for appliances having draft hoods and
230 mm from any opening through which vent equipped with listed coversion burners, which
gases could enter a building, and such an are not installed in attics, shall be of type B or type
appliance with an input over 52.700 kJ (60,000 L vent material or metal pipe having resistance to
Btu) per hour shall require a 300 mm vent heat and corrosion not less than that of
termination clearance. The bottom of the vent galvanized sheet steel or aluminium not less than
termina1 and the air intake shall.be located at least 0.406 mm thick,
300 mm above ground level.
Vent connectors for combination gas— and oil-
burning appliances, residential incinerators and
7.8 Outside vents and chimneys appliances other than those noted in (a). and
which are not installed in attics, shall be of type L
7.8.1 Condensate drain. When local ex- vent material, factory-built chimney section or
perience indicates that condensate may be a steel pipe having resistance to heat and corrosion
problem. provision shall be made to drain off the not less than that of galvanized steel specified in
condensate. table 9.

Table 9. Minimum thickness for galvanized


7.9 Vent connectors steel vent connectors for low-heat appliances

7.9.1 When required. A vent connector shall Diameter of Minimum thickness,


be used to connect gas utilization equipmentto a connector, mm mm

gas vent, chimney or’~single-walI metal pipe, less than 150 0.483
except when the gas vent, chimney or single-wall 150 to less than 250 0.584
metal pipe is directly connected to the equip- 250 to 300 inclusive 0.737
350 to 400 inclusive 0.864
ment. over 400 1.422

7.9.2 Materials
7.9.2.3 A vent connector for low-heat equip-
7.9.2.1 A vent connector shall be made of ment shall be a factory built chimney section or
noncombustible corrosion-resistant material steel pipe having resistance to heat and corrosion
capable of withstanding the vent gas temperature equivalent to that for the appropriate galvanized
produced by the gas utilization equipment and of pipe as specified in table 9. Factory-builtchimney
sufficient thickness to withstand physical sections shall be joined together in accordance
damage. with the chimney manufacturer’s instructions.

7.9.2.2 Vent connectors for residential-type 7.9.2.4 Vent connectors for medium-heat
appliances shall comply with the following: equipment and commercial and industrial
incinerators shall be constructed of factory-built
(a) Appliances installed in attics. Vent con- medium-heat chimney sections or steel of a
nectors for listed gas appliances having draft thickness not less than specified in table 1 0. and
hoods and appliances listed for use with type B shall comply with the following:
vents, which are installed in attics. shall be of type
B or type L vent material. (a) A steel vent connector for equipment with a

93
I MS930:1986

flue gas temperature in excess of 540°C. 7.9.3.2 For a single appliance having more
measured at the entrance to the connector, shall than one draft hood outlet, the manifold shall be
be lined with medium duty fire brick (MS 327, constructed according to the instructions of the
‘Specification for refractory bricks’) appliance manufacturer. If there are no
instructions, the manifold shall be designed and
(b) The lining shall be at least 65mm thick for a constructed in accordance with approved
vent connector Naving a diameter or greatest engineering practices. As a secoMd alternate, the
cross-section dimension of 450 mm or less. effective area of the manifold shall equal the
combined areas of the draft hood outlets.
(c) The lining shall be at least 11 5 mm thick laid
on the 11 5 mm bed for a vent connector having a
diameter or greatest cross-section dimension 7.9.3.3 When two or more gas appliances are
greater than 450 mm. connected to a common vent or chimney, the
effective area of each vent connector shall be in
(d) Factory-built chimney sections. if employed. accordance with approved engineering
shall be joined together in accordance with the practices. Reference may be made to tables 42
chimney manufacturer’s instructions. through 44 in appendix G. As an alternate
method, each. vent connector shall have art
effective area not less than the area of the draft
7.9.3 Size of vent connector
hood outlet of the appliance to which it is
7.9,3.1 A vent connector for gas utilization connected.
equipment with a single draft hood shall be sized
and constructed in accordance with approved 7.9.3.4 When two or more gas appliances are
vented through a common vent connector or
engineering practices. Reference may be made to
manifold, the common vent connector or
tables39through4l inappendixGdependingon
the construction of the connector. As an manifold shall be located at the highest level
alternate method the effective area of the consistent with available headroom or clearance
to combustible material. The effective area of the
connector shall be not less than the area of the
draft hood outlet. common vent connector or manifold and all
junction fittings shall be not less than the area of
Table 10. Minimum thickness for steel vent the largest vent connector plus 50% of the areas
connectors for medium heat equipment and of additional draft hood outlets.
commercial and industrial incinerators
7.9.3.5 When the size of a,vent connector is
Vent connector SIZO Minimum increased to overcome installation limitations
thickness,
Diameter. mm Area, cm
2—
mm and obtain connector capacity equal to the
equipment input. the size increase shall be made
upto 350
at the equipment draft hood outlet.
upto9.6 1.346
over 350 to 400 9.6 to 12.6 1.702
over 400 to 450 12.6 to 16.0 2.362 7.9.3.6 The effective area of the vent con~
over 450 Larger than 16.0 3.124 nector, when connected to one or more

Aeference may also be made to the chapter on chimneys. gas vents Reference may also be made to the chapter on chimneys, gas vents
and fireplace systems of the Equipment Volume of the ASHRAE and fireplace systems of the Equipment Volume of the ASHRAE
Handbook. Handbook.

94
MS 930:1986 -

appliances requiring draft for operation. shall be except vent connectors of listed type B or type L
obtained by the application of approved vent material which shall be assembled in
engineering practices to perform as specified in accordance with the manufacturer’s instructions.
7.2.1. Joints between sections of connector piping shall
be fastened by sheet-metal screws or other
7.9.4 Two or more appliances connected to a approved means.
single vent
7.9.8 Slope. A vent connector shall be
7.9.4.1 Gas utilization equipment shall not be installed without any dips or sags and shall slope
connected to a chimney flue serving a separate upward at least 20 mm per metre.
appliance designed to burn solid fuel.
7.9.9 Length of vent connector
7.9.4.2 Gas utilization equipment and equip-
ment burning liquid fuel may be connected to one 7.9.9.1 A vent connector shall be as short as
chimney flue through separate openings or may possible and the gas utilization equipment
be connected through a single opening if joined located as close as practicable to the chimney or
by a suitable fitting located as close as practicalto vent.
the chimney. If two or’ more openings are
provided into one chimney flue. they shall be at
7.9.9.2 Except when part of a designed venting
different levels. If the gas utilization equipment is system, the horizontal run of an uninsulated vent
automatically controlled it shall be equipped
,
connector to a natural draft chimney or vent
with safety shutoff’ device.
serving a single appliance shall not be more than
75% of the height of the vertical portion of the
7.9.4.3 When two or more vent connectors
chimney or vent above the connector.
enter a common gas ver’,~,chimney flue or single-
wall metal pipe. the smaller connector shall enter
7.9.9.3 Exceptwhen part of a designed venting
at the highest level consistent with the available system. the horizontal run of an insulated vent
headroom or clearance to combustible material.
connector to a natural draft c’himney or vent
serving a single gas or liquid fuel-fired appliance
7.9.5 Clearance. Minimum clearances from
shall not be more than 100% of the height of the
vent connectors to combustible material shall be
vertical portion of the chimney or vent above the
in accordance with table 8. except that the
connector.
clearance between a vent connector and com-
bustible material may be reduced when the 7.9.10 Support. A vent connector shall be
combustible material is protected as specified for
supported for the design and weight of the
vent connectors in table 6. material employed to maintain clearances and
prevent physical damage and separation of joints.
7.9.6 Avoid unnecessary bends. A vent con-
nector shall be installed so as to avoid turns or 7.9.11 Location. When the vent connector
other construction features which create used for gas utilization equipment having a draft
excessive resistance to flow of vent gases. hood must be located in or pass through a crawl
space or other area which may be cold. that
7.9.7 Joints. Vent connectors shall be firmly portion of the vent connector shall be of listed
attached to draft hood outlets or flue collars by double-wall type B or type L vent material or
sheet-metal screws or other approved means, material having equivalent insulation qualities.

95
MS 930:1986

7.9.12 Chimney connection. In entering a residential and low-heat equipment, 300 mm


passageway in a masonry or metal chimney, the larger in diameter than the vent connector.
vent connector shall be installed above the
extreme bottom to avoid stoppage. A thimble or In lieu of thimble protection. all combustible
slip joint may be used to facilitate removal of the material in the wall may be cut awayfromthevent
connector. The connector shall be firmly attached connector a sufficient distance to provide the
to or inserted into the thimble or slip joint to specified clearance from such vent connector to
prevent the connector from falling out. Means combustible material. Any material used to close
shall be employed which will prevent the up such opening shall be noncom bustible.
connector from entering so far as to restrict the
space between its end and the opposite wall of 7.9.14.3 Except as provided in 7.9.14.1, vent
the chimney. connectors made of listed type B or type L vent
material and serving listed equipment with draft
7.9.13 Inspection. The entire length of a vent hoods and other equipment listed for type B vents
connector shall be readily accessible for m~pa’ss through walls or partitions constructed
inspection, cleaning and replacement. of combustible material if the connectors are
installed with not less than the listed clearance to
7.9.14 Passage through ceilings, floors or combustible material.
wa//s
7.9.14.4 Vent connectors for medium-heat
7.9.14.1 A vent connector shall not pass equipment shall not pass through walls or
through any ceiling, floor, fire wall or fire partitions constructed of combustible material.
partition. Asingle-wall metal pipe connector shall
not pass through any interior wall.

7.9.14.2 A vent connector made of a single- 7.10 Draft hoods and draft controls
wall metal pipe shall not pass through a
combustible exterior wall unless guarded at the 7.10.1 Equipment requiring draft hoods.
point of passage byaventilated metalthimble not Vented gas utilization equipment shall be installed
smaller than the following: with draft hoods except dual oven type corn-
bination ranges. incinerators, direct vent
(a) For listed gas utilization equipment equipment. equipment requiring chimney draft
equipped with draft hoods and equipment listed for operation, single firebox boilers equipped
for use with type B vents. 100 mm larger in with conversion burners with inputs greater than
diameter than thevent connector. When there is a 422,000 kJ (40,000 Stu) per hour, equipment
run of not less than 1 .8 m of vent connector in the equipped with blast. power or pressure burners
open between the draft hood outlet and the which are not listed for use with draft hoods. and
thimble, the thimble may be 50 mm larger in equipment designed for forced venting.
diameter than the vent connector.
7.10,2 Installation
(b) For unlisted equipment having draft hoods,
1 50 mm larger in diameter than the vent 7.10.2.1 Except as noted in 7.10.2.2. a draft
coo rector. hood supplied with or forming a part of listed
vented gas utilization equipment shall be
(C) ~For domestic incinerators and all other installed without alteration. exactly as furnished

96
MS 930 : 1986

and specified by the equipment manufacturer. If a accordance with the instructions accompanying
draft hood is not supplied by the equipment the incinerator.
manufacturer when one is required, a draft hood
shall be installed. be of a listed or approved type 7.10.6 Install in same room. A draft hood or a
and. in the absence of other instructions, be of the barometric draft regulator shaII~einstalled in the
same size as the equipment flue collar. When a same room or enclosure as the equipment in such
draft hood is required with a conversion burner, it a manner as to prevent any difference in pressure
shall be of a listed or approved type. between the hood or regulator and the com-
bustion air supply.
7.10.2.2 If it is determined that a draft hood of
special design is needed or preferable for a
particular installation. the advice of the gas 7.10.7 Positioning. A draft hood or draft
utilization equipment manufacturer and the regulator shall be installed in the position for
approval of the authority having jurisdiction shall which it was designed with reference to the
be secured. horizontal and vertical planes and shall be
located so that the relief opening is not
7.10.2.3 For suggested general dimensions of obstructed by any part of the gas ut’lzaton
draft hoods, see figs. 11. 1 2 and 1 3. equipment or adjacent construction. The equip-
ment and its draft hood shall be located so that
7.10.3 Draft control devices. When a draft the relief opening is accessible for checking vent
control device is part of the gas utilization operation.
equipment or is supplied by the equipment
manufacturer, it shall be installed without 7.10.8 Clearance. A draft hood shall be
alteration in accordance with the manufacturer’s located so its relief opening is not less than 1 50
instructions. ‘In the absence of manufacturer’s mm from any surface except that of the gas
instructions, the device shall be attached to the
utilization equipment it serves and the venting
flue collar of the equipment or as near to the system to which the draft hood.is connected.
equipment as conditions permit. When a greater or lesser clearance is indicated on
the equipment label, the clearance shall not be
7.10.4 Additional devices. Gas utilization
less than that specified on the label. These
equipment (except incinerators) requiring
clearances shall not be reduced.
controlled chimney draft may be equipped with a
listed double acting barometric draft regulator. A
device which will automatically shut off gas to the
burner in the event of sustained backdraft is 7.11 Manually operated dampers
recommended if such backdraft might adversely
affect burner operation or if flue gas spillage 7.11.1 A manually operated damper shall not
might introduce a hazard. be placed in the vent connector from any gas
utilization equipment. except in a connector
7.10.5 Incinerator draft regulator. A listed gas- serving a listed gas-fired incinerator when
fired incinerator may be equipped with a listed recommended by the incinerator manufacturer
single acting barometric draft regulator when and installed in accordance with the instructions
recommended by the incinerator manufacturer. accompanying the incinerator. Fixed baffles are
This draft regulator shall be installed in not classified as manually operated dampers.

97
MS 930:1986

H
I ~,,
D
+ / -T
Ti,
H__

___IM
\i
-I
A

Table of dimensions
(mm)

A B C D E F G H I J K L M

76 140 178 18 96 64 112 76 38 58 38 81 18


102 183 241 25 127 89 153 102 51 76 51 114 25
127 239 274 38 135 102 203 127 58 89 61 124 23
152 292 305 48 142 114 249 152 64 102 68 135 20
178 343 353 58 163 135 295 178 74 117 79 157 23
203 394 401 68 180 153 340 203 81 135 89 178 25
229 445 445 79 196 170 386 229 89 147 102 196 25
254 500 478 91 200 185 437 254 96 157 109 211 25
279 564 526 109 213 203 498 279 104 168 117 241 38
305 627 564 127 221 216 559 305 112 178 127 259 43

NOTE 28. This is only one design of a vertical hood and should not be construed as the only
design that may be used. A hood of any other design which will comply with ANSI Z21.1 2.
‘Standard for draft hoods, should be satisfactory within the limits of performance specified.

Figure 11. Suggested general dimensions for a vertical draft


hood

98
MS 930: 1986

Table of dimensions
(mm)

A B C D E F G H I J K L

76 152 127 251 38 64 40 89 95 35 64 121


102 203 171 296 51 86 54 118 127 48 86 121
127 254 213 337 64 107 65 149 158 60 107 121
152 305 254 381 76 127 79 178 191 73 127 121
178 356 298 425 89 149 94 206 222 86 149 121
203 406 341 467 102 170 105 239 254 98 170 121
229 457 381 511 114 191 120 267 285 112 191 121
254 508 426 553 127 213 130 296 318 124 213 121
279 559 468 598 140 234 145 324 350 137 234 121
305 610 508 641 152 254 158 356 381 149 254 121

NOTE 29. This is onlyone design for a horizontal hood and should not be construed
as the only design that may be used. A hood of any other design which will complywith
ANSI Z21 .12, ‘Standard for draft hoods’, should be satisfactory within the limits of
performance specified’.

Figure 12. Suggested general dimensions for a horizontal


draft hood
MS 930:1986

Table of dimensions
(mm)

A B C 0 E F G H I

76 102 108 102 13 13 19 51 32


102 127 140 127 13 13 25 68 41
127 152 171 152 13 13 32 84 51
152 178 203 178 13 13 44 102 60
178 203 235 203 13 13 44 120 70
203 229 267 229 13 13 51 135 79
229 254 298 254 13 13 57 152 89
254 279 331 279 13 13 64 170 98
279 305 362 305 13 13 70 186 108
305 331 394 331 13 13 76 203 118

NOTE 30. This is only one design of a horizontal to vertical hood


and should not be construed as the onlydesign that may be used. A
hood of any other design which will comply with ANSI z21,12.
‘Standard for draft hoods’, should be satisfactory within the limits
of performance specified.

Figure 13. Suggested general dimensions


for a horizontal to vertical draft hood

100
MS 930:1986

7.12 Automatically operated vent dampers 7.14.3 Mechanical draft systems

7.12.1 An automatically operated vent damper 7.14.3.1 Gas utilization equipment, except
shall be of a listed type. Also see 9.3. incinerators, requiring venting may also be
vented by means of mechanical draft systems of
either forced or induced draft design.
7.13 Obstructions
7.14.3.2 Forced draft systems and all portions
7.13.1 Except as noted below, a device which of induced draft systems under positive pressure
will retard the flow of vent gases shall not be during operation shall be designed and installed
installed in a vent connector. chimney or vent. so as to prevent leakage of vent gases into a
building..
7.13.2 Draft regulators and safety controls; (a)
specifically listed for installation in venting 7.14.3.3 Vent connectors serving equipment
systems and installed in accordance with the vented by natural draft shall not be connected
terms of their listing, and (b) designed and into any portion of mechanical draft systems
installed in accordance with approved operating under positive pressure.
engineering methods and approved by the
authority having jurisdiction. 7.14.3.4 When a mechanical draft system is
employed, provision shall be made to prevent the
7.13.3 Listed automatically operated vent flow of gas to the main burners when the draft
dampers installed ir~accordancewith the terms of system is not performing so as to satisfy the
their listing. operating requirements of the equipmentfor safe
performance.
7.13.4 Approved economizers, heat reclaimers
and recuperators installed in venting systems of 7.14.3.5 The exit terminals of mechanical draft
equipment not required to be equipped with draft systems shall be not less than 2 rn above ground
hoods provided performance in accordance with level when located adjacent to public walkways
7.2.1 is obtained. and shall be located as specified in 7.7.1 and
7.7.2.

7.14 Special venting arrangements


7.14.4 Ventilating hoods and exhaust systems.
7.14.; Direct vent equipment. Listed direct
vent gas utilization equipment shall be con- 7.14.4.1 Ventilating hoods and exhaust
sidered properly vented when installed in systems may be used to vent gas utilization
accordance with the terms of its listing, the equipment installed in commercial applications.
manufacturer’s instructions and 7.7.3.

7.14.2 Equipment with integral vents. Gas


utilization equipment incorporating integral
venting means shall be considered properly
vented when installed in accordance with its information on the construction and installation of ventilating hoods
may be obtained from NFPA NO. 96. Standard for the installation of
listing, the manufacturer’s instructions and 7.7.1 equipment for the removal of smoke and grease-laden vapOurS from
and 7.7.2. commercial cooking equipment’,

101
MS 930:1986

7.14.4.2 When automatically operated gas interlp,eked so as to permit the equipment firing
utilization equipment is vented through a only when the damper is open to a positiorì to
ventilating hood or exhaust system equipped with
properly vent the equi~mentand when the power
a damper or with a power means of exhaust, the
gas utilization equipment control system shall be means of exhaust is in operation.

102
MS 930 :1986

SECTION EIGHT: PROCEDURES TO BE FOLLOWED TO PLACE EQUIPMENT IN


OPERATION

8.1 Adjusting the burner input regulator is provided). Consult the serving gas
supplier.
8.1.1 Burner input. Each burner shall be
adjusted to its proper input in accordance with
the manufacturer’s instructions. Overheating of 8.2 Primary air adjustment
burners is prohibited.
8.2.1 The primary air for injection (Bunsen)
8.1.2 High altitude. Ratings of gas utilization type burners shall be adjusted for proper flame
equipment are based on sea level operation and characteristics in accordance with the menu-
need not be changed for operation at elevations facturer’s instructions. Normally, the primary air
up to 600 metres. For operation at elevations adjustment should first be set to give a soft blue
above 600 metres and, in the absence of specific flame having luminous tips and then increased to
recommendations fromthe local authority having a point where the yellow tips just disappear. If the
jurisdiction, equipment ratings shall be reduced burner cannot be adjusted as above, consult the
at the rate of 4 per cent for each 300 metres manufacturer or serving gas supplier. After
above sea level before selecting appropriately setting the primary air. the adjustment means
sized equipment. shall be secured in position.

8.1 .3 Checking burner input

8.1.3.1 Checking burner input using a’ meter. 8.3 Safety shutoff devices
To check the kJ (Btu) input rate, the test hand on
8.3.1 When a safety shutoff device is provided.
the meter should be timed for at least one
it shall be checked for proper operation and
revolution and the input determined from this
adjustment in accordance with the manu-
timing.
facturer’s instructions. If the device does not
function properly to turn off the gas supply in the
8.1.3.2 Checking burner input not using a
meter. The fixed orifice size for each burner may event of pilot outage. it shall be properly serviced
or replaced with new equipment.
be determined in accordance with table 35 for
utility gases and table 36 for undiluted liquefied
petroleum gases in appendix F.
8.4 Automatic ignition
8.1 .4 Adjusting input. The input rate shall be
adjusted to the proper rate by changing a fixed 8.4.1 Gas utilization equipment supplied with
orifice size, changing the adjustment of an means for automatic ignition shall be checked for
adjustable orifice, or by readjustment of the gas proper operation. If necessary. proper adjust-
pressure regulator outlet pressure (when a ments shall be made.

103
MS 930: 1986

8.5 Protective devices extinguish this flame. If the combustion products


are escaping from the relief opening of the draft
8.5.1 All protective devices furnished with the hood, the equipment shall not be operated until
gas utilization equipment. such ~s a limit control, proper adjustments or repairs are made to
fan control to blower, temperature and pressure provide adequate draft through the chimney or
relief valve, low water cutoff device, manual gas vent.
operating features, etc. shall be checked for
proper operation.

8.7 Operating instructions

8.6 Checking the draft 8.7.1 Operating instructions shall be furnished


and shall be left in a prominent position near the
8.6.1 Vent connected gas utilization equipment equipment for the use of the consumer.
shall be operated for several minutes and
checked to see that the combustion products are
going up the cnimney, or gas vent, properly by 8.8 Notification of completion
passing a hg hted match or taper around the edge
of the relief opening’ of the draft hood. If the 8.8.1 When regulations so require. the serving
chimney or gas vent is drawing properly. the gas supplier or the authority having jurisdiction
match flame will be drawn into the draft hood.If shall be notified that the installation has been
not, the combustion products will tend to completed.

104
MS 930:1986

SECTION NINE: MODIFICATION TO EXISTING APPLIANCE INSTALLATIONS FOR THE


PURPOSE OF FUEL CONSERVATION

9.1 Safety inspection

9.1 .1 Prior to attempting any modification, a safety inspection of the existing appliance
installation shall be performed by a qualified agency performing the modification. See appendix H
for a recommended procedure for such a safety inspection.

9.2 Reduction of vent connector size

9.2.1 If an existing vent connector is determined to be oversized for the input rate c’ the
connected appliance, it may be resized in accordance with 7.9.3.

9.3 Automatic vent damper device installation

9.3.1 A listed automatic vent damper device may be installed on an existing appliance installatior
provided the appliance is listed and equipped with a draft hood and provided the device is installed
by a qualified agency (see 1 .4) in accordance with the terms of its listing. The name of the installer
and date of installation shall be marked on a label affixed to the damper device. For recommended
procedures for installing automatic vent damper devices on existing appliance installations, see
appendices J, K and L.

105
MS 930:1986

Appendix A

List of reference standards (note 31)

NOTE 31. users of this code are advised against attempting direct ANSI/ASTM A539 Standard specification for
application of these standards without carefully observing the Code’s electric resistance-welded coiled steel tubing for
reference to that standard. Reference shouid be made to the
appropriate authority having jurisdiction before using any of these gas and fuel oil lines
standards for the purpose of this Code.

A2. COPPER AND BRASS PIPE AND TUBING


Al. IRON AND STEEL PIPE AND TUBING ANSI/ASTM B88 Standard ‘specification for
seamless copper water tube
MS 862 Welded and seamless carbon steel
pipes for general pressure purposes ANSI/ASTM B280 Standard specification for
seamless copper tube for air-conditioning and
MS 863 Welded and seamless steel pipes (6
refrigeration field service
mm -150 mm). screwed-type

ANSI A21.52 Standard for ductile iron pipe,


centrifugally cast, in metal molds or sand-lined A3. ALUMINIUM PIPE AND TUBING
molds for gas -

ANSI/ASTM B210 Standard specification for


ANSI B36.10 Standard for welded and seam- aluminium alloy drawn seamless tubes
less wrought steel pipe
ANSI/ASTM B241 Standard specification for
ANSI/ASTM A53 Standard specification for aluminium alloy seamless pipe and seamless
black and hot-dipped, zinc coated welded and extruded tube
seamless steel pipe

ANSI/ASTM A106 Standard specification for


A4. PLASTIC PIPE, TUBING AND FITTiNGS
seamless carbon steel pipe for high-temperature
service ASTM 02513 Specification for thermoplastic

ANSI/ASTM Al 20 Standard specification for gas pressure pipe, tubing and fittings
black and hot-dipped zinc-coated (galvanized) ASTM 02517 Specification for reinforced
welded and seamless steel pipe for ordinary uses epoxy resin gas pressure pipe and fittings

ANSI/ASTM A254 Standard specification for


copper brazed steel tubing
A5. FLANGES
ASTM A377 Specification for gray iron and
ductile iron pressure pipe ANSI B 1 6.1 Standard for cast iron pipe flanges

106
MS 930: ‘1986

and flanged fittings. class 25, 1 25, 250 and 800 ANSI Z2 1.6 and addenda. Z2 1 .6a and Z2 1 .6b
Domestic gas-fired incinerators
ANSI B1 6.5. Standard for steel pipe flanges and
flanged fittings. including ratings for class 1 50, ANSI Z2 1 .9 and addenda. Z2 1 .Sa Domestic gas
300, 400, 600, 900, 1 500 and 2500 hot plates and laundry stoves

ANSI B16.20 Standard for ring-joint gaskets ANSI Z2l.10.1 and addenda, Z21.10.la and
and grooves for steel pipe flanges Z21.10.lb Gas water heaters. volume I. auto-
matic storage type water heaters with inputs of
ANSI/AWWA Clii Standard for rubber gasket 75,000 Btu per hour or less
joints for ductile iron and gray iron pressure
ANSI Z21.10.3 and addenda, Z21.l0.3a and
fittings
Z21.l0.3b Gas water heaters volume Ill, cir-
MSS SP 6 Standard finishes for contactfaces of c’ulating tank, instantaneous and large automatic
pipe flanges and connecting end flanges of valves storage type water heaters
and fittings
ANSI Z21.i1.i and addenda, Z21.11 la and
Z2 1 .11 .1 b Gas-fired room heaters, volume I,
vented room heaters
A6. PIPE THREAD ANSI Z21.l 1.2 and addenda, Z21.l i.2a Gas-
fired room heaters, volume II, unvented room
ANSI B2.1 Standard for pipe threads (except
heaters
dryseal)
ANSI Z2 1 .1 3 and addenda, Z2 1.1 3a and
Z2 1 .1 3b Gas-fired low-pressure steam and hot
A7. PIPE HANGERS AND SUPPORTS water boilers
ANSI Z21.19 and addenda. Z21.19a Refri-
ANSI/MSS SP 58 Standard practice for pipe
hangers and supports materials, design and
- gerators using gas fuel
manufacture
ANSI Z21.40.i and addenda, Z21.40.ia Gas-
fired absorption summer air conditioning
appliances
A8. EQUIPMENT
ANSI Z21.42 and addenda, Z21.42a Gas-fired
ANSI Z21 and addenda, Z21.ia Household illuminating appliances
cooking gas appliances
ANSI Z21.44 and addenda. Z21.44a and
ANSI Z21.5.l and addenda. Z21.5.la Gas Z21.44b Gas-fired gravity and fan type direct
clothes dryers, volume 1, type 1 clothes dryers vent wall furnaces

ANSI Z21.5.2 Gas clothes dryers. volume II, ANSI Z21.47 and addenda Z21.47a Gas-fired
type 2 clothes dryers central furnaces (except ‘direct vent and,
separated combustion system central furnaces)
•Manufacturers Standardization Society of the valve and Fittings
industry. 1815 North Fort Myer Drive, Arlington virginia 22209. ANSI Z21 .48 and addenda. Z21 .48a Gas-fired

1:07
MS 930:1986

gravity and fan type floor furnaces A9. ACCESSORIES

ANSI Z21 .49 and addenda, Z21 .49a Gas-fired ANSI Z2i .2 Gas hose connectors for portable
gravity and fan type vented wall rurnaces in.door gas-fired appliances

ANSI Z21.55 and addenda. Z21.55a Gas-fired ANSI Z21.12 and addenda. Z2i.12a Draft
sauna heaters hoods

ANSI Z2i .56 Gas-fired swimming pool heaters ANSI Z2l .15 Manually operated gas valves

ANSI Z21.57 and addenda. Z21.57a Re- ANSIZ21.17 Domesticgasconversionburners


creation vehicle cooking gas appliances
ANSI Z21 .18 Gas appliances pressure re-
ANSI Z21.58 and addenda. Z2i.58a Outdoor gulators
cooking gas appliances
ANSI Z2i.20 and addenda, Z21.20a, Auto-
ANSI Z2i .64 and addenda, Z21 .64a Direct matic gas ignition systems and components
vent central furnaces
ANSI Z21.21 and addenda. Z2i.21a. Auto-
ANSI Z83.10 and addenda.Z83.i0a Separated matic valves for gas appliances
combustion system central furnaces
ANSI Z21.22 Relief valves and automatic gas
ANSI Z83.4 Direct gas-fired make-up air shutoff devices for hot water supply systems
heaters
ANSI Z21.23 and addenda, Z21.23a and
ANSI Z83.6 and addenda, Z83.6a and Z83.6b Z21 .23b Gas appliance thermostats
Gas-fired infrared heaters
ANSI Z2i.24 and addenda. Z2i.24a and
ANSI Z83.8 and addenda. Z83.8a and Z83.8b Z21 .24b Metal connectors for gas appliances
Gas-fired unit heaters
ANSI Z21 .35 Gas filters on appliances
ANSI Z83.9 and addenda. Z83.9a Gas-fired
duct furnaces ‘ ANSI Z2i .41 Quick-disconnect devices for use
with gas fuel
ANSI Z83.1 1 Hotel and restaurant gas ranges
and unit broilers ANSI Z21 .45 Flexible connectors of other
than all-metal construction for gas appliances
ANSI Z83.l 2 Commercial gas baking and
roasting ovens ANSI Z2i .54 Gas hose connectors for portable
outdoor gas-fired appliances
ANSI Z83. 1 3 Hotel and restaurant gas deep fat
fryers ANSI Z2i.66 Electrically operated automatic
vent damper devices for use with gas-fired
ANSI Z83.14 Gas counter appliances appliances

ANSI Z83.1 5 Gas-fired kettles, steam cookers ANSI Z2i .69 Connectors for movable gas
and steam generators appliances,

108
MS 930: 1986

ANS1/UL 144 PressureregulatingvalvesforLP- use of stationary combustion engines and gas


Gas turbines

NFPA No. 51 Standard for the design and


installation of oxygen-fuel gas systems for
AlO. TESTING welding and cutting

ANSI/ASTM D2385 Testforhydrogensulphide NFPA No. 68 Guide for explosion venting


and mercaptan sulphur in natural gas (Cadmium
sulphate-lodometric titration method) NFPA No. 82 Standard on incinerators, waste
and linen handling systems and equipment
ANSI/ASTM D2420 Test for-hydrogen sulphide
in liquefied petroleum (LP) gases (Lead acetate NFPA No. 89M Manual on clearances for heat
method) pFoducing appliances

NFPA No. 90A Standard for the installation of


air conditioning and ventilation systems
All. APPLICATION CODES
NFPA No. 90B Standard for the installation of
MS 761 Code of Practice for the storage and warm air heating and air conditioning systems
handling of flammable and combustible liquids
NFPA No. 96 Standard for the installation of
MS 830 Code of Practice for the storage, equipment for the removal of smoke and grease-
handling and transportation of liquefied petro- laden vapours from commercial cooking
leum gases equipment

NFPA No. 70 National electrical code NFPA No. 211 Standard for chimneys, fire-
places and vents
ASME Boiler and pressure vessel code
Section IV: Heating boilers ANSI Z21.8 Standard for the installation of
domestic gas conversion burners

A12. REGULATIONS
A14. EQUIVALENT STANDARDS
Street. Drainage and Building Act. 1974 (Act
133) Uniform Building By-Laws A14.1 Any equivalent British Standards
Australian Standards, iiapanese Industrial
Electricity Regulations 1 975 (Revised 1 977) Standards. German Standards (DIN) and Inter-
national Standards acceptable to the appropriate
authority having jurisdiction may be used in place
A13. MISCELLANEOUS of the standards referred to in this Code. A list of
some equivalent standards is given in A14.2 to
MS 327 Refractory bricks A14.7 (It should be noted that this list is not
meant to be exhaustive for the purpose of this
NFPA No. 37 Standard for the installation and Code).

109
MS930:1986 I

A14.2 Iron and steel pipe and tubing low alloy steel for supply purposes. process plant
and tanks
BS 534 Steel pipes, fittings and specials for
water, gas and sewage ‘ DIN 1 629 Seamless tubes in unalloyed steel for
supply purposes, process plant and’ tanks
BS 1 387 Steel tubes and tubulars suitable for
screwing to BS 21 pipe threads DIN 2440 Steeltubes.mediumtypesuitablefor
screwing
BS 3601 Steel pipes and tubes for pressure
purposes: DIN 1 71 75 Seamless tubes in unalloyed steel
Carbon steel with specified room temperature and alloy steel for high temperature services
properties
ISO 65 Carbon steel tubes suitablefor screwing
BS 3602 Steel pipes and tubes for pressure in accordance with ISO 7/1
purposes:
Carbon and carbon manganese steel with ISO 559 Welded or seamless steel tubes for
specified elevated temperature properties ‘ water, sewage and gas

AS 1074 Steel tubes and tubulars threaded or ISO 4200 Plain and steel tubes. welded and
suitable for threading with pipe threads of seamless General tables of dimensions and
-

Whitworth form
masses
AS 1751 Copper brazed steel tubing
A14.3 Copper and brass pipe and tubing’
AS 1835 Seamless steel tubes for pressure
purposes BS 2871 : Part 1 Copper tubes for water, gas
and sanitation
AS 1836 Welded steel tubes for pressure
purposes AS 1 432 Copper tubes for water, gas and
sanitation
AS 2280 Centrifugally cast ductile iron
pressure pipes JIS H3300 Copper and copper alloy seamless
pipes and tubes
AS 2544 Grey iror’~pressure pipes and fittings
DIN 1 754 Copper tubes. seamless drawn
JIS G3452 Carbon steel pipes for ordinary
piping DIN 1786 Copper pipes for fluid and gas
distribution with soldered capillary type joints,
JIS G3454 Carbon steel pipes for pressure seamless drawn
service
DIN 17171 Tubes of copper and wrought
JIS G3456 Carbon steel pipes for high tempe- copper alloys
rature service
ISO 274 Copper tubes of circular section -

DIN 1626 Welded steel pipe in unalloyed and dimensions

110
MS 930; 1986

A14.4 Aluminium pipe and tubing JIS B2202 Dimensions for pipe flange facing

AS 1 867 Wrought aluminium and aluminium JIS B2203 Tolerances for pipe flanges
alloy drawn tubes for general engineering
purposes JIS B221 0-B221 7 Basic dimensionslof ferrous
materials pipe flanges
DIN 1 795 Aluminium tubes (highest grade
aluminium. high grade aluminium and JIS B2404 Spiral-wound gaskets for pipe
aluminium wrought alloys), seamless drawn flanges

DIN 9107 Aluminium tubes (highest grade DIN 2500 Flanges. general information, survey
aluminium, high grade aluminium and
DIN 2501-2504 Flanges, companion
aluminium wrought alloys), extruded.
dimensions
dimensions
DIN 2519 Steelflanges. technical conditions of
A14.5 Plastic pipe, tubing and fittings delivery

AS 1667 Polyethylene pipes and fittings forgas DIN 2532 Cast iron flanges, nominal pressure
10
recirculation

JIS K6774 Polyethylene pipes for the supply of DIN 2533 Cast iron flanges. nominal pressure
16
gaseous fuels

DIN 2693 Sealing rings for flanges with groove.


JIS K6775 Polyethylene pipe-fittings for the
nominal pressures from 10 to 40
supply of gaseous fuels
DIN 2697 Grooved 0-rings and seals for
flanged joints, nominal pressures 64 to 400
A14.6 Flanges

BS 1 560: Part 2 Steel pipe flanges and flanged A14.7 Pipe thread
fittings (nominal sizes 1/2 in to 24 in) for the
petroleum industry. metric dimensions BS 21 Pipe threads for tubes and fittings where
pressure-tight joints are made on the threads
BS 3381 Metallic spiral wound gaskets for use
with flanges to B5 1 560 :Parts 1 and 2 AS 1 722 Pipe threads of Whitworth form
Part 1: Sealing pipe threads
.BS 4504 Flanges and bolting for pipe. valves Part 2: Fastening pipe threads
and fittings, metric series
JIS B0203 Taper pipe threads
AS 21 29 Flanges and bolting for pipes, valves
and fittings DIN 3858 Whitworth pipe thread

ISO 7/1 Pipe threads where pressure-tight


JIS B2201 Pressure ratings for ferrous material
pipe flanges joints are made on the threads Part 1:
-

Designation. dimensions and tolerances

ill
MS930; 1986

Appendix B

Coordination of gas utilization equipment design,


construction and maintenance

Bi. COORDINATION (a) Design and construction of all gas equip-


ment or assemblies shipped from its plant.

B1.1 Because industrial gas applications are so (b) Design and construction of all gas
varied in nature. many agencies are jointly equipment fabricated, erected or assembled by
involved with their safe and satisfactory use. Prior the gas equipment manufacturer or builder in the
to installation, the specific assignments should field.
be agreed upon by the parties concerned. A (c) A statement of the maximum hourly kJ (Btu)
typical. but not mandatory. delineation of input, type of gas and design pressure range.
assignments is given in Bi .2 through B1 .5. and a
detailed check list is given in clause B2. (d) Written installation and operating
instructions for the user
B1.2 Person or agency planning an installation
of gas equipment shall: B1.5 The person or agency making and the
person or agency authorizing the installation of
(a) Verify the adequacy of the gas supply, gas equipment (purchaser) shall jointly:
volume, pressure and meter location.
(a) Select, erect or assemble gas equipment,
(b) Determine suitability of gas for the process. components or designs purchased or developed
by that person or agency.
(c) Notify gas suopliersof significant changes in
requirements. (b) Assure conformance to codes, ordinances
or regulations applicable to the installation.
B1.3 Upon request, the gas supplier furnishes
the user complete information on: (c) Provide adequate means of disposal of
products of combustion.
(a) Combustion characteristics and physical’or
chemical properties such as specific gravity. (d) Initially operate the gas equipment in a safe
heating value, pressure and the approximate manner.
analysis of the gas.

(b) Conditions under which an adequate supply


B2. GAS EQUIPMENT DESIGN AND CON-
of gas at suitable pressure can be brought to the
STRUCTION CHECK LIST
site.
(c) Continuity of the gas supply.
B2.1 The basic design and installation should
consider:
B1.4 The gas equipment manufacturer or
builder provides:
(a) Suitability of equipment for process

112
MS930: 1986

requirements. material in fittings should not be selected nor


used until the following factors have been
(b) Adequate structural strength and stability. considered:

(c) Reasonable life expectation. (a) Correct size to handle required volume
(consideration of pressure drop in controls and
(d) Conformance to existing safety standards. manifolds is particularly important in low
pressure systems).
(e) Adequate combustion space and venting.
(b) Material specifications suitable for
(f) Means for observation and inspection of pressures and temperatures encountered.
combustion.
(c) Adequate supports and protection against
physical damage.
B2.2 Materials of construction used, other than
pipe. fittings and valves, should provide
(d) Tight assembly and thorough leak inspec-
reasonable life expectancy for the service
tion.
intended and be capable of satisfactorily with-
standing:
(e) Use of sufficient’ unions and flanges. wriere
permitted. for convenient field replacement or
(a) Operating temperatures.
repair.
(b) Chemical action.
(f) Arrangement of piping to provide accessibi’
(C) Thermal shock. hity for equipment adjustments and freedom from
thermal damage.
(d) Load stresses.
B2.5 Information concerning the charac-
B2.3 Combustion systems should be selected teristics of the gas and electricity’available at the
for the characteristics of the available gas so that point of utilization should be specific and
they will operate properly at the elevation at point complete. Gas controls and electrical, equipment
of use and produce: should be selected to conform to these charac-
teristics which include:
(a) Proper heat distribution.
(a) Gas characteristics: heat content, pressure.
(b) Adequate operating temperature range. specific gravity and approximate analysis.

(c) Suitable flame geometry. (b) Electrical characteristics: voltages, number


of phases and frequencies for both control and
(d) Flame stability.
power circuits.

(e) Operating flexibility.


(c) Location of electrical equipment and wiring
to avoid thermal damage and excessive con-
(f) Desired heating chamber atmosphere.
centrations of dust, dirt or foreign material.
B2.4 Pipe, fittings and valves shall conform to
(d) Requirements of applicable electrical codes
applicable standards. Piping, bushings and

113
I MS930:1986

and standards. maintenance of gas equipment. Special types of


equipment demand special attention.
B2.6 Temperature controls. if used, should be
carefully selected considering: B3.2 Burners and pilots should be kept clean
and in proper operating condition. Burner
(a) Range and type of instruments and sensing refractory parts should be examined at frequent
elements. regular intervals to assure good condition.

(b) Ty.pe of control action.


B3.3 When automatic flame safeguards are
(c) Suitability for service required. used, a complete shutdown and restart should be
made at frequent intervals to check the com-
(d) Correlation of control instruments with ponents for proper operation.
operating equipment.
B3.4 Other safeguard equipment
B2.7 In enclosed chambers. the accumulation
of gas-air or solvent ai~mixtures which may be B3.4.1 Accessory safeguard equipment, such
as manual reset valves with pressure or vacuum
accidentally ignited constitutes a potential
switches, high temperature limit switches. draft
hazard to life and property. For this reason.
controls, shutoff valves, air flow switches, door
consideration shall be given to the selection and
switches and gas valves, should be operated at
installation of suitable protective equipment. The
frequent regular intervals to insure proper
selection of a satisfactory protective system and
functioning. If inoperative, they should be
components not otherwise covered by existing
repaired or replaced promptly.
codes or standards should be based on the
requirements of each individual installation after
B3.4.2 When fire checks are installed in gas-air
consultation with the various interested parties.
mixture piping to prevent flashbacks from
including user, designer insurance company and
travelling further upstream, the pressure loss
local authorities having jurisdiction. Some of the
across the fire checksi should be measured at
factors and considerations involved in the
regular intervals. When excessive pressure loss is
selection of protective equipment are:
found, screens should be removed and cleaned.
Water type backfire checks should be inspected
(a) Feasibility of its installation.
at frequent regular intervals and ‘liquid’ level
(.b) Its adaptability to process and control maintained.
requirements.
B3.4.3 All safety shutoff valve~ should be
(c) Conformance to existing standards. checked for leakage and proper operation at
ordinances, requirements and other regulations frequent regular intervals.
which apply. (See appendix A for listing of
standards and specifications). B3.5 Auxiliary devices

B3.5.1 A necessary part of the gas equipment


maintenance should be the proper maintenance
B3. MAINTENANCE OF GAS EQUIPMENT
of auxiliary devices. Maintenance instructions as
B3.1 These recommendations are prepared for supplied by the manufacturers of these devices

114
MS 930: 1986

should be followed. maintenance should be the proper maintenance


of the gas piping system. It is recommended that
B3.5.2 Gas combustion equipment, including gas piping be inspected and tested for leakage at
blowers, mechanical mixers, control valves. regular intervals in accordancewith provisions of
temperature control instruments, air valves and 4.1 .5. Air piping should be kept internally cleanto
air filters, should be kept clean and should be prevent accumulation of dust, lint and grease in
examined at frequent regular intervals. air jets and valves. Where conditions warrant.
filters should be installed at the intake to thefans.
B3.5.3 Necessary repairs and replacements
should be made promptly.
B3.8 Stand-by or substitute fuel equipment and
B3.6 Regulator and zero governor vents and systems for gas equipment should be kept in
impulse or control piping and tubing should be good operating conditions and tested perio-
kept clear. Regulator valves which operate di cal ly.
improperly should be cleaned, repaired ‘or
replaced promptly.
B3.9 An adequate supply of repair partc should
be maintained.
B3.7 A necessary part of the gas equipment

115
MS 930: 1986

Appendix C

Sizing and capacity of gas piping

Cl. GENERAL engineering practices acceptable to the authority


having jurisdiction.
Cl.1 The units expressed herein for the
computation of sizing and capacities of gas
piping are in the imperial units. The computation C2. NFPA NO. 54 METHOD
capacity formulae and the derived tables
currently published and used for gas piping C2.1 lntheNFPAno. 54 methódforthe sizing of
installation are in the imperial units, and pipe in the gas piping system design installation.
consequently for convenience of pipe desig,n the following factors shall be considered:
applications the imperial units are retained, at (a) Allowable loss in pressure from point of
least for some interim period of time. delivery to equipment.

C1.2 Two different pipe sizing methods that (b) Maximum gas demand.
have been used widely are familiarized in this
appendix. They are: (c) Length of piping and number of fittings.

(a) NFPA no. 54 method. (d) Specific gravity of the gas.

(b) Clifford method. (e) Diversity factor.

The NFPA no. 54 method is noted for its C2.2 Description of tables
simplicity. Given the length of pipe and the
maximum load, the required pipe size is read C2.2.1 The quantity of gas to be provided at
directly from the appropriate table. Com- each outlet should be determined, whenever
paratively the Clifford method may not be simple possible. directly from the manufacturer’s Btu
but offers the advantage of flexibility. The piping input rating of the equipment which will be
system layout using the Clifford method can be installed. In case the ratings of the equipment to
notated with actual pressure drops and pipe be installed are not known, table 11 shows the
sizes, which ultimately may prove useful when approximate consumption of average appliances
making adjustments for possible future loads. of certain types in Stu per hour.

Cl .3 For any gas piping system, for special gas To obtain the cubic feet per hour of gas required.
utilization equipment or for conditions other than divide the total Btu input of all equipment by the
those covered by the two methods in C1.2, such average Btu heating value per cubic foot of the
as in cases of longer runs, greater gas demands gas. The average Btu per cubic foot of the gas in
or greater pressure drops, the size of each gas the area of the installation may be obtained from
piping system should be determined by standard the serving gas supplier.

116
MS 930:1986

C2.2.2 Capacities for gas at low pressures (0.5 appliance to be attached to the piping system.
psig or less) in cubic feet perhourof 0.60 specific When tables 1 3 through 1 6 are to be used to
gravity gas for different sizes and lengths are select the piping size, calculate the gas demand in
shown in tables 13 and ‘14 for iron pipe or terms of cubic feet per hour for each piping
equivalent rigid pipe and in tables 1 5 and 1 6 for system outlet. When tables 26’ or 27 are to be
semi-rigid tubing. Tables 13 and 1 5 are based used to select the piping size, calculate the gas
upon a pressure drop of 0.3 inch water column, demand in terms of thousands of Btu per hourfor
whereas tables 14 and 1 6 are based upon a each piping system outlet.
pressure drop of 0.5 inch water column. In using
these tables no additional allowance is necessary C2.3.2 When the piping system is for use with
for an ordinary number of fittings. other than undiluted liquefied petroleum gases.
determine the design system pressure. the
C2.2.3 Capacities in thousands of Btu per hour allowable loss in pressure (pressure drop), and
of undiluted liquefied pertoleum gases based on the specific gravity of the gas to be used in the
a pressure drop of 0.5 inch water column for piping system.
different sizes and lengths are shown in table 26
for iron pipe or equivalent rigid pipe and in table C2.3.3 Measure the length of piping ~r’ the
27 for semi-rigid tubing. In using these tables, no point of delivery to the most remote outlet in the
additional allowance is necessary for an ordinary building.
number of fittings.
C23.4 In the appropriate capacity table, select
C2.2.4 Gas piping systems that are to be the column showing the measured length, or the
supplied with gas of a specific gravity of 0.70 or next longer length is the table does not give the
less can be sized directly from tables 1 3 through exact length. This is the only length used in
1 6. unless the authority having jurisdiction detemining the size of any section of gas piping. If
specifies that a gravity factor be applied. When the gravity factor is to be applied, the values in the
the specific gravity of the gas is greater than 0.70. selected column of the table are multiplied by the
the gravity factor shall be applied. appropriate rr~ultiplierfrom table 25.

Application of the gravity factor converts the Capacities may also be determined by using the
figures given in tables 1 3 through 1 6 to capa- following formulae:
cities with another gas of different specific
gravity. Such application is accomplished by (a) High pressure (1.5 psig and above):
multiplying the capacities given in tables 13
through 1 6 by the multipliers shown in table 25.
In case the exact specific gravity does not appear Q

18l6J

2
D5(P12_P2 ).Y
Cr.fba.L
in the table, choose the next higher value specific
gravity shown. p22)y1O.541
= 2237 D2~623[(P1Cr.L

]
C2.3 Use of capacity tables. To determine the
size of each section of gas piping in a system
within the range of the capacity tables, proceed
as follows: ~Forfurther details on the formulae, refer to ‘Polyflo fiow computer,’
B.C. Shebeke. 1974. available from Polyfio Computer Company.
8ox 501 26. Dallas, Texas 75250.
C2.3.1 Determine the gas demand of each

117
MS 930: 1986

(b) LowPressure (less than 1.5 psig): Z is the viscosity of gas. centipoise (0.01 2
for natural gas. 0.008 for propane),
I D5.~H or given as 1488~i:
o = 187.3 1
,J Cr.fba.L
i~ is the viscosity, pounds per second ft:

= 23 1 3 D2’623 ( ~ H
Cr.L /
0.541 fba is the base friction factor for air at 60°F
(CF = 1);
where, L is the length of pipe, ft;

~ H is the pressure drop, in. water column


0 is the rate. cu ft per hr at 60°F and 30 in. (27.7”H20 = 1 psi);
mercury column:
fb
D is the inside diameter of pipe, in; CF is the factor CF and given as ( fb
fb is the base friction factor for any fluid
Pt is the upstream pressure, psia: at a given temperature, °F.

P2 is the downstream pressure. psia; C2.3.5 Use this vertical column to locate ALL
gas demand figures for this particular system of
Y is the superexpansibility factor~ = 1/ piping.
supercompressibility factor;
C2.3.6 Starting at the most remote outlet, find
Cr is the factor for viscosity, density and in the vertical column just selected the gas
Z .152
temperature. and given 0.00354 ST(-~.) demand for that outlet. If the exact figure of
demand is not shown, choose the next larger
figure below in the column.
S is the specific gravity of gas at 60°F
and 30 in. mercurycolumn;
C2.3.7 Opposite this demand figure, in the first
column at the left, will be found the correctsize of
T is the absolute temperature, °F. or given as
gas piping.
+ 460

t is the temperature, °F: C2.3.8 Proceed in.a similar manner for each
outlet and each section of gas piping. For each
section of piping determine thetotal gas demand
supplied by that section.

C2.4 Example ,of piping system design

C2.4.l Determine the required pipe size of


each section and outlet of the piping system
‘FOr values for natural gas, refer to ‘Manual for determination of
supercompressibility factors for natural gas.’ availablefrom American shown in fig. 1 4. with a designated pressure drop
Gas ~ssociation. 1515 Wilson Boulevard. Arlington, Virginia 22209. of 0.50 inch water column. Gas to be used has
For iaiues for liquefied petroleum gases. refer to ‘Engineering data
0.65 specific gravity and a heating value of 1 .000
booJ,’ available from Gas Processors Association. 1812 First Place.
Tulsa, Oklahoma 74102. Btu per cubic foot.

118
MS 930:1986 -

Furnace
Outlet 0. 136,000 8tu per hr.

20’
OutletA 30 Gal. automatic
water heater
Section 2
30,000 Btu per hr.
Section 3 Section 1 10’
20’ 10 10’

}5.
Outlet B Gas refrigerator
}15 3,000 Btu per hr.

Point of delivery
Outlet C Range
75,000 Btu per hr.

Figure 14. Example of pipe sizing using NFPA method no. 54

C2.4.2 Solution Table 11. Approximate gas input for


typical appliances
(a) Maximum gas demand for outlet A:
Input
Appliance Btu per hour
Consumption Irating plate input, or table 1 1 necessaryl = (Approx.)
Btu of gas

30.000 Stu per hour rating 30 cubic feet per hour Range, free standing, domestic 65,000
1.000 Btu per cubic foot (or 30 cfhl Built-in oven or broiler unit, domestic 25,000
Built-in top unit, domestic 40,000
Water heater, automatic storage
Maximum gas demand for outlet B: 30 to 40 gal, tank 45,000

Water heater, automatic storage


Consumption 3.000.
________ = _3cfh 50 gal. tank 55,000
Btu of gas 1.000
Water heater, automatic instantaneous
(2 gal. per minute 142,800
Maximum gas demand for outlet C: Capacity
(4 gal. per minute 285,000
Consumption = 7 5.000 75 cfh (6 gal, per minute 428,400
Btu of gas 1 .000 Water heater, domestic, circulating
or side-arm 35,000
Refrigerator 3,000
Maximum gas demand for outlet D.
Clothes dryer, type 1 (domestic) 35,000
Consumption = 136,000 136 cfh’
Gas light 2.500
Btu of gas 1,000
Incinerator, domestic 35,000

(b) The length of pipe from the point of delivery


to the most remote outlet (A) is 60 feet. This is the NOTE 32. For specific appliances or appliances not shown
above. the input should be determined from the manu-
only distance used. facturer’s rating.
(Continued on page 127)

119
-5
Table 12. Equivalent lengths, in feet of straight pipe, of bends, fittings and valves
0 C’)
The equivalent lengths in feet shown in table 1 2 have been computed on a basis ihat the inside diameter corresponds io that of schedule 40 lstandard weight) steel pipe
0
which is close enough for most purposes involving other schedules of pipe. Where a more specilic solution for equivalent iengih is desired, this may be made by
-5
multiplying the aclual inside diameter of the pipe in inches by n/I 2. or the actual inside diameter in feel by n. N can be read from the table heading. The equivalent length
values can be used wiih reasonable accuracyfor copper or brass fillingsand bends. For copper or brass valves. however, theequivalent length of pipe should be taken as
45 per cent longer than the values in the table which are for steel pipe, Resistance per foot of copper or brass pipe is less than that of steel.

Screwed fittings tHeta 34) 90° weiding elbows end amooth bonds (Note 361 Mitre elbow mo, of m’itrasl Welding tees Vslves
(Note 361 (screwed, flanged, or weidedf
180° ctoae
45° 90° return Tee R/d R/d Rid R/d Rid R/d 1-45° 1-60° 1-90° 2-90° 3-90° Forged Mitre Gets Globe Angie Swing
oil eli bends I =1½ 2 4 = 6 8 (Note 36( ~ ‘ check

k factor = 0.42 0.90 2.00 1.80 0.48 0.36 0.27 0.21 0.27 0.36 0.45 O.90 1.80 0.60 0.46 1.35 1.80 0.21 10 6.0 2.5

L/d’ redo (Note 371 14 30 67 60 16 12 9 7 9 12 15 30 60. 20 15 45 60 7 333 167 83

Inside

Z d~m~er
c~ E~ 17~

L = equ’reaient length in feet of scheduied 40 Istandard wsightl straight pipe iNote 39) L = equivalent length in feeI of eched ute 40 Istandard weight) straight pipe (Note 39)

0.78 1.55 3.10 1.04 0.78 2.33 3.10 0.36 17.3 8.65 4.32
½ 0.622 0.73 1.65 3.47 3.10 0.83 0.62 0.47 0.36 0.47 0.62 1.03 2.06 4.12 1.37 1.03 3.09 4.12 0.48 22.9 11.4 5.72
‘4 0.624 0.96 2.06 4.60 4.12 1.10 0.82 0.62 0.48 0.62 082 1.31 262 5.24 1.75 1.31 3.93 5.24 0.61 29.1 14.6 7.27
1 1.049 1.22 2.62 582 5.24 1.40 1.05 0.79 0.61 0.79 105 1.72 3.45 6.90 2.30 1.72 5.17 690 081 38.3 19.1 9.58
Fl, 1.380 1.61 3.45 7.86 6.90 1.84 1.38 1.03 0.81 1.03 1.38 2.01 4.02 8.04 ‘168 2.01 6.04 8.04 0.94 44.7 22.4 11.2
1½ 1.610 1.88 4.02 895 8.04 2.14 1.81 1.21 0.94 1.21 1 61
2.58 5.17 10.3 3.45 2.58 7.75 10.3 1.21 57.4 28.7 14.4
2 2.067 2.41 5.17 11.5 10.3 2.76 2.07 1.55 1.21 1.55 2.07 3.08 6.16 12.3 4.11 3.08 9.25 12.3 1.44 68.5 34.3 17.1
2½ 2.469 2.88 6.16 1’3.7 12.3 3.29 2.47 1.85 1.44 1.86 2.47
3.84 7.67 15.3 5.11 3.84 11.5 15.3 1.79 85.2 42.6 21.3
3 3068 3.58 7.67 17.1 15.3 ‘ 4.09 3.07 2.30 1.79 2.3 307 5.04 10.1 20.2 6.71 5.04 15.1 20.2 2.35 112 56.0 28.0
4 4.026 4.70 10.1 224 20.2 5.37 4.03 3.02 2.35 30 403 6.30 t2.6 25.~ 840 6.30 18.9 25.2 2.94 140 70.0 35.0
5 5.047 5.88 12.6 28.0 25.2 6.72 5.05 3.78 2.94 3.7 5.05
7.58 15.2 30.4 10.1 7.58 22.8 30.4 1.54 168 84.1 42.1
6 6.065 7.07 15.2 33.8 30.4 8,09 6.07 4.55 3.54 4.5 6.07 9.97 20.0 40.0 13.3 9.97 29.9 40.0 4.65 222 111 5.5
8 7.981 9.31 20.0 44.6 40.0 10.6 7.98 5.98 465 5.9 7.98 12.5 25.0 50.0 16.7 12.5 37.6 50.0 5.85 278 139 69.5
10 10.02 11.7 25.0 55.7 50.0 13.3 10.0 751 5.85 7.61 10.0 14.9 298 596 19.9 14.9 44.8 59.6 6.96 332 166 83.0
12 11.94 13.9 29.8 66.3 596 15.9 11.9 6.95 6.96 8.9 11.9 16.4 32.8 65.6 21.9 16.4 49.2 65.6 7.65 364 182 91.0
14 13.13 15.3 32.8 730 65.6 17,5 13.1 9.85 7.65 9.8~13.1
15.8 37.5 75.0 25.0 18.8 56.2 75.0 8.75 417 208 104
16 15.06 17.5 37.5 83.5 75.0 20.0 15.0 11.2 8.75 11.2 15.0 21.1 42.1 84.2 28.1 21.1 63.2 84.2 9.85 469 234 117
18 16.88 19.7 42.1 93.8 84.2 225 16.9 12.7 9.85 12.7 18.9 23.5 47.0 94.0 314 23.5 70.6 94.0 11.0 522 261 131
20 18.81 22.0 47.0 105 94.0 25.1 18.8 14.1 11.0 14.1 18.8 28.3 566 113 37.8 28.3 85.0 113 13.2 629 314 157
24 22.63 26.4 56.6 126 113 30.2 22.6 17.0 13.2 17.0 22.6

NOTE 37. Equivalent resistance in number of diameters of straight pipe computed for a value of
NOTE 33. Values for welded fittings are for conditions where bore is not obstructed by weld
— 0.007 5 from the relation n — k/4f.
spatter or backing rings. If appreciably obstructed, use values for ‘Screwed fittings’.
NOTE 38. For condition 0) minimum resistance where the centre-line length of each mitre is
NOTE 34. Flanged fittings have three-fourths the resistance of screwed elbows and tees.
between d and 2/2 d.
NOTE 35. Tabular figures give the extra resistance due to curvature alone to which should be
NOTE 39. For pipe having other inside diameiers; the equivalent resistance may be computed
added the full length of travel.
from the above n values.
NOTE 36. Small size socket-welding fittings are equivalent to mitre elbows and mitre tees.

I’
MS 930:1986

Table 13, Maximum capacity of pipe in cubic feet of gas per hour for gas pressures of
0.5 psig or less and a pressure drop of 0.3 inch water column
(Based on a 0.60 specific gravity gas)

Nominal Internal Length of pipe, feet


iron pipe diameter.
size, inches 10 20 30 40 50 80 70 80 90 100 125 160 175 200
inches
1/4 .364 32 22 18 15 14 12 ii 11 10 9 8 8 7 6
.493 72 49 , 40 34 30 27 25 23 22 21 18 17 15 14
Vs .622 132 92 73 63 56 50 46 43 40 38 34 31 28 26
¾ .824 276 190 152 ISO 115 105 96 90 84 79 72 64 59 55
1 1.049 520 350 285 245 215 195 180 170 160 150 130 120 110 100
P14 1.380 1,050 730 590 500 440 400 370 350 320 305 275 250 225 210
11/i 1.610 1,600 1,100 890 760 670 610 560 530 490 460 410 380 350 320
2 2.067 3,050 2,100 1,650 1,450 1,270 1,150 1,050 990 930 870 780 710 650 610
2½ 2.469 4,000 3,300 2,700 2,300 2,003 1,850 1,700 1,600 1,500 1,400 1.250 1,130 1.050 980
3 3.068 8,500 5,900 4,700 4,100 3,600 3,250 3,000 2,800 2,600 2,500 2.200 2,000 1,850 1,700
4 4.026 17,500 12,000 9,700 8,300 7,400 6,800 6,200 5,800 5,400 5;100 4.500 4,100 3,800 3,500

Table 14. Maximum capacity of pipe in cubic feet of gas per hour for gas pressures of
0.5 psig or less and a pressure drop of 0.5 inch water column
(Based on a 0.60 specific gravity gas)

Internal Length of pipe. feet


size, diameter,
inches c~ 10 20 30 40 50 60 70 80 90 100 125 150 175 200
1/4 .364 43 29 24 20 18 16 15 14 13 12 11 10 9’ 8
¾ .493 95 65 52 45 40 36 33 31 29 27 24 22 20 19
½ ~ .622 175 120 97 82 73 66 61 57 53 50 44 40 37 35
¾ 824 360 250 200 170 151 138 125 118 110 103 93 84 77 72
1 1.049 680 465 375 320 285 260 240 220 205 195. 175 160 145 135
1¼ 1.380 1,400 950 770 660 580 530 490 460 430 400 360 325 300 230
1½ 1.610 2,100 1,460 1,180 990 900 810 750 690 650 620 550 500 460 430
2 2.067 3,950 2,750 2,200 1,900 1,680 1,520 1,400 1,300 1,220 1,150 1,020 950 850 800
2½ 2.469 6,300 4,350 3,520 3,000 2,650 2,400 2,250 2.050 1,950 1,850 1,650 1,500 1,370 1,280
3 3.068 11,000 7,700 6,250 5,300 4,750 4,300 3.900 3,700 3,250
3,450 2,950 2,650 2.450 2.280
4 4.026 23.000 15,800 12,800 10,900 9,700 8,800 8,100 7,500 7,200 6.700 6.000 5,500 5,000 4.600

Table 15. Maximum capacity of semi-rigid tubing in cubic


feet of gas per hour for gas pressures of 0.5 psig or less
and a pressure drop of 0.3 inch water column
(Based on a 0.60 specific gravity gas)

Outside Length of tubing. feet


diameter. —

inch 10 20 30 40 50 60 70 80 90 100 125 150 175 200

¾ 20 14 11 10 9 8 7 7 6 6 5 S 4 4
½ 42 29 23 20 13 16 15 14 13 12 ~ 10 ~ $
¾ 84 59 47 40 36 33 30 23 26 25 fl 20 18 17
¾ 150 3 33 .7~ 63 57 52 49 46 43 33 35 32 30
~‘k 212 146 117 100 ‘89 81 74 69 65 61 54 49 43 42

121
MS 930 : 1986

Table 16. Maximum capacity of semi-rigid tubing. in’ cubic


feet of gas per hour ‘for gas pressures of 0.5 psig or less
and a pressure drop of 0.5 inch water column
(Based on a 0.60 specific gravity gas)
Outside Length of tubing. feet
diameter,
inch 10 20 30 40 50 60 70 80 90 100 125 150 175 200

¾ 27 18 15 13 11 10 9 9 8 3 7 6 6 5
1/3 56 38 31 26 23 21 19 18 17 16 14 13 12 11
¾ 113 78 62 53 47 43 39 37 34 33 29 26 24 22
¾ 197 136 109 93 83 75 69 64 60 57 50 46 42 3~
¾ 280 193 155 132 117 106 98 91 85 31 71 65 60 35

Table 17. Pipe sizing table for pressures under 1 pound approximate capacity of pipes of
different diameters and lengths in cubic feet per hour with pressure drop of 0.3 inch water
column and 0.6 specific gravity
Pipe size of
Internal. Total equivalent length of pipe in feet
schedule 40
diameter
standard pipe
(inches) (inches) 50 100 150 200 250 300 400 500 1000 1500 2000’

1.00 1.049 215 148 119 102 90 82 70 62’ 43 34 29


1.25 . 1.380 442 304 244 209 185 168 143 127 87 70 60
1.50 1.610 662 455 366 313 277 251 215 . 191 131 105 90
2.00 . 2.067 1275 877 704 602 534 484 414 367 252 203 173
2.50 2.469 2033 1397 1122 960 851 771 660 585 402 323 276
3.00 - 3068 3594 2470 1983 1698 1505 1363 1167 1034 711 571 488
3.50 3.548 5262 3616 2904 2485 2203 1996 1708 1514 1041 836 715
4.00 4.026 7330 5038 4046 3462 3069 2780 2380 2109 1450 1164 996
5.00 5.047 13261 9114 7319 6264 5552 5030 4305 3816 2623 2106 1802
6.00 6.065 21472 14758 11851 10143 8990 8145 6971 6178 4246 3410 2919
8.00 7.981 44118 30322 24350 20840 18470 16735 14323 12694 8725 7006 5997
10.00 10.020 80130 55073 44225 37851 33547 30396 26015 23056 15847 12725 10891
12.00 11.938 126855- 87187 70014- 59923 53109 48120 41185 36501 25087 20146 17242

Table 18. Pipe sizing table for pressures under 1 pound approximate capacity of pipes’ of
.

different diameters and lengths in cubic feet per hour with pressure drop of 0.5 inch water
column and 0.6 specific gravity
Pipe size of Internal Total equivalent length of pipe in feet
scheduled 40 diameter
standard pipe
(inches) (inches) 50 100 150 200 250 300 400 500 1000 1500 2000

1.00 1.049 284 195 157 134 119 108 92 82 56 45 39


1.25 1.380 583 400 322 275 244 221 189 168 115 93 79
1.50 1.610 873 600 482 412 366 331 283 251 173 139 119
2.00 2.067 1681 1156 928 794 704 638 546 484 333 267 229
2.50 2.469 2680 1842 1479 1266 1122 1017 870 771 530 426 364
3.00 3.068 4738 3256 2615 2238 1983 1797 1538 1363 937 752 644
3.50 3.548 6937 4767 3828 3277 2904 2631 2252 1996 1372 1102 943
4.00 4.026 9663 6641 5333 4565 4046 3866 3137 2780 1911 1535 1313
5.00 5.047 17482 12015 9649 8258 7319 6632 5676 5030 3457 2776 2376
6.00 6.065 28308 19456 15624 13372 11851 10738 9190 8145 5598 4496 3848
8.00 7.981 58161 39974 32100 27474 24350 22062 18883 16735 11502 9237 7905
10.00 ‘ 10.020 105636 72603 58303 49900 44225 40071 34296 30396 20891 16776 14358
12.00 11.938 167236 114940 92301 78998 70014 63438 54295 48120 33073 26559 22731

122
MS 930: 1986

Table 19. Piping sizing table for 1 pound pressure capacity of pipes of different diameters
and lengths in cubic feet per hour for an initial pressure of 1 .0 psig with a 10 per cant
pressure drop and a gas of 0.6 specific gravity

Internal - Total equivalent length of pipe in feet


St anap
d d i pe diameter
(inches) 50 100 150 200 250 300 400 600 1000 1600 2000

1.00 1.049 717 493 396 338 300 272 233 206 142 114 97
1.25 1.380 1471 1011 812 695 616 558 478 423 291 234 200
1.50 1.610 2204 1515 1217 1041 923 836 716 634 436 350 300
2.00 2.067 4245 2918 2343 2005 1777 1610 1378 1222 840 674 ‘ 577
2.50 2.469 6766 4651 3735 3196 2833 2567 2197 1947 1338 1075 920
3.00 3.068 11962 8221 - 6602 5650 5008 4538 3884 3442 2366 1900 1626
3.50 3.548 17514 12037 9666 8273 7332 6644 5686 5039 3464 2781 2381
4.00 4.026 24398 16769 13466 11525 10214 9255 7921 7020 4825 3875 3316
5.00 5.047 44140 30337 24362 20851 18479 16744 14330 12701 8729 7010 6000
6.00 6.065 71473 49123 39447 33762 29923 27112 23204 20566 14135 11351 9715
8.00 7.981 146849 100929 81049 69368 61479 55705 47676 42254 29041 23321 19960
10.00 10.020 266718 183314 147207 125990 111663 101175 86592 76745 52747 42357 36252
12.00 11.938 422248 290209 233048 199459 176777 160172 137087 121498 83505 67057 57392

Table 20. Pipe sizing table for 2 pounds pressure capacity of pipes of different diameters and
lengths in cubic feet per hour for an initial pressure of 2.0 psig with a 10 per cent pressure
drop and a gas of 0.6 specific gravity
Pipe size of Internal Total equivalent length of pipe in feet
schedule 40 diameter
standard pipe
(inches) (inches) 50 100 150 200 250 300 400 500 1000 1500 2000

1.00 1.049 1112 764 614 525 466 422 361 320 220 177 151
1.25 1.380 2283 1569 1260 1079 956 866 741 657 452 363 310
1.50 1.610 3421 2351 1888 1616 1432 1298 1111 984 677 543 465
2.00 2.067 6589 4528 3636 3112 2758 2499 2139 1896 1303 1046 896
2.50 2.469 10501 7217 5796 4961 4396 3983 3409 3022 2077 1668 1427
3.00 3.068 18564 12759 10246 8769 7772 7042 6027 5342 3671 2948 2523
3.50 3.548 27181 18681 15002 12840 11379 10311 8825 7821 5375 4317 3694
4.00 4.026 37865 26025 20899 17887 15853 14364 12293 10895 -7488 6013 5147
5.00 5.047 68504 47082 37809 32359 28680 25986 22240 19711 13547 10879 9311
6.00 6.065 110924 76237 61221 52397 464,39 42077 36012 31917 21936 17616 15077
8.00 7.981 227906 156638 125786 107657 95414 86452 73992 65578 45071 36194 30917
10.00 10.020 413937 284497 228461 195533 173297 .157020 134389 119106 81861 65737 56263
12.00 11.938 655315 450394 361682 309553 274351 248582 212754 188560 129596 104070 89071

Table 21. Pipe sizing table for 5 pounds pressure capacity of pipes of different diameters
and lengths in cubic feet per hour for an initial pressure of 5.0 psig with a 10 per cent
pressure drop and a gas of 0.6 specific gravity
Pipe size of
schedule 40 Internal Total equivalent length of pipe in feet
diameter
standard pipe . -

(inches) (inches) 50 100 150 200 250 300 400 500 1000 1500 2000

1.00 1.049 1989 1367 1098 940 833 755 646 572 393 316 270
125 1.380 4084 2807 2254 1929 1710 1549 1326 1175 808 649 555
1.50 1.610 6120 4206 33714 2891 2552 2321 1987 1761 1210 972 832
2.00 2.067 11786 8101 6505 5557 4934 4471 3827 3391 2331 1872 1602
2.50 2.469 - 18785 12911 10368 8874 7865 7126 6099 5405 3715 2983 2553
3.00 3.068 33209 22824 18329 15687 13903 12597 10782 9556 6568 5274 4514
3.50 3.548 48623 33418 264436 22968 20356 18444 15786 13991 9616 7722 6609
4,00 4.026 67736 46555 37385 31997 28358 25694 21991 19490 13396 10757 9207
5.00 5.047 122544 84224 67635 57887 51304 46485 39785 35261 24235 19461, 16656
6.00 6.065 198427 136378 109516 93732 83073 75270 64421 57095 39241 31512 26970
8.00 7.981 407692 280204 225014 192583 170683 154651 132361 117309 80626 54745 55414
10.0,0 10.020 740477 508926 408686 349782 310005 280887 240403 213065 146438 117595 100646
12.00 11.938 1172269 805694 647001 553749 490777 444680 380588 337309 231830 186168 159336

123
MS 930: 1986

Table 22. Pipe sizing table for 10 pounds pressure capacity of pipes of different diameters
and lengths in cubic feet per hour for an initial pressure of 10.0 psig with a 10 per cent
pressure drop and a gas of 0.6 specific gravity
Pipe size of Internal Total equivalent length of pipe in feet
schedule 40 diameter
standard pipe (in hes)
(inches) c 50 100 150 200 250 300 400 500 1000 1500 2000

1.00 1.049 3259 2240 1798 1539 1364 1236 1058 938 644 517 443
1.25 1.380 6690 4598 3692 3160 2801 2538 2172 1925 1323 1062 909
1.50 1.610 10024 6889 5532 4735 4197 3802 3254 2884 1982 1592 1362
- 2.00 2.067 19305 13268 10655 9119 8082 7323 6268- 5555 3818 3066 2624
2.50 2.469 30769 21148 16982 14535 12882 11672 9990 8854 6085 4886 4182
3.00 3.068 54395 37385 30022 25695 22773 20634 17660 15652 10757 8638 7393
3.50 3.548 79642 54737 43956 37621 33343 30211 25857 22916 15750 12648 10825
4.00 4.026 110948 76254 61235 52409 46449 42086 36020 31924 21941 17620 15080
5.00 5.047 200720 137954 110782 94815 84033 76140 65166 57755 39695 31876 27282
6.00 6.065 325013 223379 179382 153527 136068 123288 105518 93519 64275 51615 44176
8.00 7.981 667777 458959 368561 315440 279569 253310 216800 192146 132061 106050 90765
10.00 10.020 1212861 833593 669404 572924 507772 460078 393767 348988 239858 192614 164853
12.00 11.938 1920112 1319682 1059751 907010 803866 728361 623383 552493 379725 - 304933 260983

Table 23. Pipe sizing table for 20 pounds pressure capacity of pipes of different diameters
and lengths in cubic feet per hour for an initial pressure of 20.0 psig with a 10 per cent
pressure drop and a gas of 0.6 specific gravity

Internal Total equivalent length of pipe in feet


standard pipe diameter
(inches) (inches) so ioo 150 200 250 300 400 500 1000 1500 2000

1.00 1.049 5674 3900 - .3132 2680 2375 2152 1842 1633 1122 - 901 771
1.25 1.380 11649 8006 6429 5503 4877 4419 3782 3352 2304 1850 1583
1.50 1.610 17454 11996 9633 8245 7307 6621 5667 5022 3452 2772 2372
2.00 2.067 33615 23103 18553 15879 14073 12751 10913 9672 6648 5338 4569
2.50 2.469 53577 36823 29570 25308 22430 20323 17394 15416 10595 8509 7282
3.00 3.068 94714 65097 52275 44741 39653 35928 30750 27253 18731 15042 12874
3.50 3.548 138676 95311 76538 65507 58058 52604 45023 39903 27425 22023 18849
4.00 4.026 193187 132777 106624 91257 80879 73282 62720 55538 38205 30680 26258
5.00 5.047 349503 240211 192898 165096 146322 132578 113470 100566 69118 55505 47505
6.00 6.065 565926 388958 312347 267329 236928 214674 183733 162840 111919 89875 76921
8.00 7.981 1162762 799160 641754 549258 486797 441074 377502 334573 229950 184658 158043
10.00 10.020 2111887 1451488 1165596 997600 884154 801108 685645 607674 417651 335388 287049
12.00 11.938 3343383 2297888 1845285 1579326 1399727 1268254 1085462 962025 661194 530962 454435

Table 24. Pipe sizing table for 50 pounds pressure capacity of pipes of different diameters
and lengths in cubic feet per hour for an initial pressure of 50.0 psig with a 10 per cent
pressure drop and a gas of 0.6 specific gravity
Pine size of .

s chedule 40 diameter
Internal Total equivalent length of pipe in feet
standard pipe
(inches) (inches) 50 100 150 200 250 300 400 500 1000 1500 2000

1.00 1.049 12993 8930 7171 6138 5440 4929 4218 3739 2570 2063 1766
1.25 1.380 26676 18335 14723 12601 11168 10119 8661 7676 5276 4236 3626
1.50 1.610 39970 27471 22060 18881 16733 15162 12976 11501 7904 6348 5433
2.00 2.067 76977 52906 42485 36362 32227 29200 24991 22149 15223 12225 10463
2.50 2.469 122690 84324 67715 57955 51365 46540 39832 35303 24263 19484 16676
3.00 3.068 216893 149070 119708 102455 90804 82275 70417 62409 42893 34445 29480
3.50 3.548 317564 218260 - 175271 150009 132950 120463 103100 91376 62802 50432 43164
4.00 4.026 442393 304054 244166 208975 185211 167814 143627 127294 87489 70256 60130
5.00 5.047 800352 550077 441732 378065 335072 303600 259842 230293 158279 127104 108784
6.00 6.065 1295955 890703 715266 612175 542559 491598 420744 372898 256291 205810 176147
8.00 7.981 2662693 1830054 1469598 1257785 1114752 1010046 864469 766163 526579 422862 361915
10.00 10.020 4836161 3323866 2669182 2284474 2024687 1834514 1570106 1391556 956409 768030 657334
12.00 11.938 7656252 5262099 4225651 3616611 3205335 2904266 2485676 2203009 1514115 1215888 1040643

124
MS 930:1986

Table 25. Multipliers to be used with tables 13


through 24 when the specific gravity of the gas
is other than 0.60
Specific Specific
gravity Multiplier gravity Multiplier

.35 1.31 1.00 .78


40 1.23 1.10 .74
.45 1.16 1.20 .71
.50 1.10 1.30 .68
.55 1.04 1.40 .66
.60 1.00 1.50 .63
.65 .96 1.60 .61
.70 .93 1.70 .59
.75 .90 1.80 .58
.80 .87 1.90 .56
.85 .84 ZOO .55
.90 .82 2.10 .54

Table 26. Maximum capacity of pipe in thousands of Btu


per hour of undiluted liquefied petroleum gases
(at 11 inches water columninlet pressure)
(Based on a pressure drop of 0.5 inch water column)
Nominal
iron. pipe Length of pipe. feet

i~~S 10 20 30 40 50 60 70 80 90 100 125 150

½ 275 189 152 129 114 103 96 89 83 78 69 63


¾ 567 39 315 267 237 217 196 185 173 162 146 132
1 1071 732 590 504 448 409 378 346 322 307 275 252
1¼ 2205 1496 1212 1039 913 834 771 724 677 630 567 511
1½ 3307 2299 1858 1559 1417 1275 1181 1086 1023 976 866 787
2 6221 4331 3465 2992 2646 2394 2205. 20471921 1811 1606 149€

Table 27. Maximum capacity of semi-rigid tubing in


thousands of Btu per hour of undiluted liquefied
petroleum gases
(at 11 inches water column inlet pressure)
(Based on a pressure drop of 0.5 inches water column)

Outside Length of tubing. feet


diameter,
inch 10 20 30 40 50 60 70 80 90 100

39 26 21 19
½ 92 62 50 41 37 35 31 29 27 26
199 131 107 90 79 72 67 62 59 55
¾ 329 216 181 145 131 121 112 104 95 90
501 346 277 233 198 187 164 155 146 138

125
MS 930:1986

Table 28. LP-Gas low pressure pipe sizing table

l.n~h Allowable pressure drop in pipe line


lOft. .01 .02 .03 .04 .05 .06 .07 .08 .09 .10 .12 .13 .15 .17 .20 .25 .30 .40 .50 .60
15’ .01 .03 .04 .06 .07 .09 .10 .11 .13 .15 .18 .20 .22 .25 .30 .37 .45 .60 .75 .90
20 .02 .04 .06 .08 .10 .12 .13 .15 .17 .20 .24 .27 .30 .33 .40 .50 .60 .80 1.00 1.20
25 .02 .05 .07 .10 .12 .15 .16 .19 .21 .25 .30 .36 .37 .41 .50 .62 .75 1.00
30 .03 .06 .09 ‘.12 .15 .18 .20 .23 .26 .30 .36 .40 .45 .50 .60 .75 .90 1.20
35 .03 .07 .10 .14 .17 .21 .23 .26 .30 .35 .42 .46 .52 .58 .70 .87 1.05
40 .04 .08 .12 .16 .20 .24 .27 .30 .34 .40 .48 .53 .60 .67 .80 1.00
45 .04 .09 .13 .18 .22 .27 .30 .34 .38 .45 .54 .60 .67 .75 .90 1.13
50 .05 .10 .15 .20 .25 .30 .33 .38 .43 .50 .60 .67 .75 .83 1.00
55 .05 .11 .16 .22 .27 .33 .36 .41 .47 .55 .66 .73 .82 .91 1.10
60 .06 .12 .18 .24 .30 .36 .40 .45 .51 .60 .72 .80 .90 1.00
70 .07 .14 .21 .28 .35 .42 .47 .52 .60 .70 .84 .93 1.05 -

80 .08 .16 .24 .32 .40 .48 .53 .60 .69 .80 .96 1.07
90 .09 .18 .27 .36 .45 .54 .60 .67 .77 .90 .08
100 .10 .20 .30 .40 .50 .60 .67 .75 .86 1.00

size Gas flow -thousands of Btu

3/80D 8 12 14 16 18 20 21 22 24 26 28 30 31 33 36 40 45 51 57 63
1/20D 19 27 33 38 42 46 50 53 56 60 66 69 74 78 86 95 104 121 135 147
5/800 36 50 62 71 79 87 94 100 106 113 124 130 139 146 159 178 193 222 251 275
3/400 53 78 94 109 123 134 141 149 159 172 190 197 212 227 243 272 298 342 382 420
1/4K 8 12 14 16 18 20 21 22 24 26 28 30 31 33 36 40 45 51 57 63
3/8K 15 22 27 31 34 37 40 42 45 49 52 56 60 63 68 77 84 97 108 120
1/2K 30 43 53 61 68 75 78 84 89 96 105 111 118 124 135 152 165 192 215 233
5/8K 52 73 90 104 115 126 133 143 153 164 178 187 203 210 230 259 283 325 363 400
3/4 K 72 102 125 145 162 177 183 197 213 230 252 262 280 293 320 360 392 452 510 S60
1K 150 208 256 300 333 365 380 410 440 471 520 543 584 610 670 745 820 940 1050 1145
1/4L 8 12 15 17 19 21 22 ‘ 23 . 24 27 29 30 33 35 38 42 46 53 59 65
318L 18 26 31 36 41 45 47 50 S4 58 64 67 71 76 82 92 100 115 129 142
1/2L 33 47 57 66 74 80 86 90 96 105 115 120 129 136 148 165 180 209 232 256
5/8L 55 78 94 109 123 134 141 149 159 172 190 197 212 227 243 272 298 342 382 420
3/4L 82 116 143 165 184 201 212 224 240 261 287 300 320 340 369 413 451 523 584 640
1L 160 228 277 320 358 390 411 435 462 505 557 584 623 660 720 800 877 1015 1130 1240
3/811’S 20 28 35 40 45 49 52 55 59 63 69 73 78 81
109 126 142 154.89 99
1/2IPS 37 52 64 73 82 90 94 101 127 133 142 148 163 183 198 232 257 281
108 115
3/4 11’S 78 110 136 157 175 192 202 215 232
250 273 284 305 317 350 390 430 490 555 605
1 11’S 148 208 253 293 330 360 373 404 435 465 510 536 575 600 660 730 810 930 1040 1135
1-1/411’S 297 420 515 600 670 725 765 820 885 955 1040 1090 1170 1220 1350 1510 1635 1890 2110 2300
1-1/21PS 445 635 775 900 1000 1090 1130 1225 1310 1420 1560 1640 1740 1850 2015 2275 2480 2850 3180 3480
2 11’S 850 1200 1460 1700 1880 2080 2180 2300 2470 2680 2940 3080 3300 3500 3800 4230 4620 5370 6000 6580

Table 29. Equivalent length of pipe for


various fittings

Pipe 90 deg. elI 45 deg. -eli Tee-side


outlet Tee-straight
through
size, in.

¾ 0.50 ft 0.40 ft 2.50 ft 0.25 ft


½ 0.85 ft 0.75 ft 3.00 ft 0.40 ft
¾ 1.30 ft 1.00 ft 4.00 ft 0.60 ft
1 1.60 ft 1.25 ft 5.25 ft 0.75 ft

1-¼ 2.60ft 1.60ft 7.OOft 1.OOft


1-½ 3.30ft 1.90ft 8.OOft 1.30ft
2 5.00 ft 2.40 ft 10.40 ft 1.70 ft
2-½ 6.00 ft 3.00 ft 12.50 ft 2.20 ft
3 9.00 ft 3.50 ft 15.00 ft 2.75 ft

126
MS 930: 1986

(c) Using the column marked 60 feet in table 14. made for a 280 ft line with an allowable pressure
drop of 0.6 in. w.c.
Outlet A, supplying 30 cfh, requires ~/8 in. pipe.
4) 280 ft 0.6 in. w.c.
Outlet B. supplying 3 cfh. requires ¼ in. pipe. 70 ft 0.15 in. w.c.

Section 1 supplying outlets A and B, or 33 cfh. The pipe line would be properly sized if the length
requires 3/~ in. pipe. is considered to be 70 ft and the allowable
pressure drop 0.1 5 in. w.c.
Outlet C. supplying 75 cfh. requires 3/4 in. pipe.
To the actual length of pipe as measured there
Sectibn 2~supplying outlets A. B and C, or 1 08 must be added a suitable allowance to offset the
cfh requires 3/4 in. pipe. pressure loss due to fittings. For the average
installation with up to four fittings in a given
Outlet D. supplying 1 36 cfh. requires 3/4 in. pipe. section of line the following allowances have
proven satisfactory:
Section 3. supplying outlets A, B. C and D, or 244
cfh requires 1 in. pipe. a 90° elI 5 ft
a 450 elI 2.5 ft
(d) If the gravity factor (see C2.2.4 under a tee, side outlet 5 ft
description of tables) is applied to this example. a tee, straight through no allowance
the values in the column marked 60 feet of table
14 would be multiplied by the multiplier 0.96 If the derived pipe length totals some odd number
from table 25 and the resulting cubic feet not found in the table, then the nearest figure for
per hour ~aIues would be used to size the piping. pipe length is used. This procedure over-
estimates the allowance for fittings and thereby
introduces a conservative element in the sizing
operation. It is believed, however, that overall
C3. THE ‘CLIFFORD METHOD’ results are better when the number of fittings is
taken into consideration. If an unusual number of

C3.1 Pipe sizing low pressure lines. Five fittings is involved, suitable allowance for length
factors are involved in Clifford method of sizing may be made by using table 29. ‘Equivalent
low pressure lines, all of which are included in lengths of pipe for various fittings’.
table 28. ‘LP-Gas low pressure pipe sizing
table’.The following sub-clauses explain how the C3.1.2 Allowable pressure drop. The upper
table is used. portion of the pipe sizing table is given over to
pressure drops ranging from 0.01 in. to 1 in. w.c.
C3.1 .1 Pipe length. Pipe lengths from 1 0 ft to or slightly more. This range of pressure drops
1 OOft are listed in the left-hand column of the makes the table quite flexible and allows for
upper portion-of table 28. For lengths over 1 OOft appropriate selection. It is recommended that a
the actual length, plus the allowance for fittings, maximum of 0.6 in w.c. pressure drop be
and the allowable pressure drop are both divided considered. For an installation involving one
by a convenient number that will bring the pipe appliance there is but a single pipe line with no
length within the range of thetable. The following branches to consider. In such cases the allowable
calculation shows how this adjustment would be pressure drop to be used will be 0.6 in. w.c.

127
MS 930: 1986

Branch lines complicate the sizing problem as allowable pressure drops have been included in
each one must be sized separately. and the sizing the drawing. fig. 1
5 adjacent to the figures for
based on a suitable allowance for pressure drop. pipe length. In a more complicated piping system.
These steps will show how allowable pressure one can double check by proceeding from each of
drops are assigned to the various lines in a given the appliances and adding up the pressure drops
installation: on each of the lines to the regulator outlet. In each
case the total should be 0.6 in w.c.
Step 1. Consideration is given first to the main
line and branch leading to the appliance with the C3.1 .3 Load or demand. The next step in sizing
greatest input. Referring to fig. 1 5, this will be the piping system is to calculate the load it must
seen to be the floor furnace. Allowable pressure handle. A branch line is sized on the basis of the
drops will be in proportion to the length of the Btu rating of the appliance it serves. The main line
individual lines, therefore these lengths must be must handle the total load, of course, and an
established first. intermediate line will be sized for the appliances it
serves.
Main line, measured length 15 ft
1 900 elI shown 5 ft
Total Forthe installation shown in fig. 1 5. the load is
summerized as follows:
Branch line to floor furnace
measured length 5 ft
Gas range 27,000 Btu
tee, side outlet 5 ft 3 top burners @
Total lOft 9000 Btu 20.000
1 oven burner 1 6,000
Pipe length from furnace to the
pressure regulator 30 ft 1 broiler burner 63,000 Btu
Water heater 30.000
It is obvious in this case that the main line is two- Floor furnace 80.000
thirds of the tot~Ilength involved and that two-
thirds of the allowable pressure drop of 0.6 in. Total load 1 73.000 Btu
w.c. is 0.4 in. Since this may not be obvious in
other situations, the arithmetic is spelled out in
detail.
P~Water heater
20 ft (length of main line) t\ ) 30,000 Btu
x 0.6 in. = 0.4 in.
30 ft (total length)
Gas range
63,000 Btu
1 0 ft (length branch line) ~ 0.6 in. = 0.2 in.
30 ft (total length) ,15-ft lOftB
0.2”
_________________ lOft
0.4” 0.2”
5ft
Step 2. Since the total allowable pressure drop o 0.2”
from the regulator outlet to each of the
appliances is 0.6 in. w.c., and 0.4 in. w.c. has E
_______
‘~FIoorfurnace
80, 000 Btu

been alloted to the main line, it is obvious that the


allowable pressure drop for each of the branch Figure 15. Example in sizing the lines of a
lines is 0.6 in. — 0.4 in. or 0.2 in w.c. These domestic installation

128
MS 930: 1986

C3.1.4 Pipe s/ze.Four types of piping material that the actual pressure drop will be less than 0.4
are included in the pipe sizing table (table 28) and in. w.c. since the ¾ in. pipe selected has a
the practitioner will make his selection on the capacity considerably in excess of the require-
basis of company practice. For the illustrated ment. To determine the actual pressure drop in
example the following procedure is outlined: this case proceed to the right from the 3/4 IPS to
Type K tubing will be used up to and including the the figure which represents the actual load to be
½ in. size; for greater capacities standard pipewill handled. The 1 75 is selected and the next step is
be used. This is not intended as a recommended to move vertically upward to the figure opposite
procedure but as a convenient means of the 20 ft. The pressure drop is seen to be 0.1 in.
simplifying the presentation. w.c.

Having established the length of pipe to be used


with the table, the allowable pressure drop and lOft .01 .02 .03 .04 .05 .12 .13 .15 .17 .20
15 .01 .03 .04 .06 .07 .18 .20 .22 .25 .30
the load to be carried, the next step is to select the 20— .02 .04 .06 .00 .1(1 .24 .27 .20 .33 ~. I
pipe size. The sizing of the main line A shown in 25 .02 .05 .07 .10 .12 .30 .36 .37 .41
30 .03 .06 .09 .12 .15 .36 .40 .45 .50 . I
fig. 1 5 will be used as an example. The solution is
shown in a portion of the pipe sizing table 35 .03 .07 .10 .14 .17 .42 .46 .52 .58

reproduced in fig. 1 6. Proceed as follows: 40 .04 .08 .12 .16 .20 .48 .53 .60 .87
45 .04 .09 .13 .18 .22 .54 .60 .67 .75
50 .05 .10 .15 .20 .25 .60 .67 .75 .83 1.
55 .05 .11 .16 .22 .27 .66 .73 .82 .91 1.1
Step 1. Find the pipe length. 20 ft. in the left
hand column of the upper portion of the table. 60 .06 .12 .18 .~4 .30 .72 .80 .90 1.00
Whenever the actual length is not shown, the 70 .07 .14 .21 .28 .35 .84 .93 1.05
80 .08 .16 .24 .32 .40 .96 1.07
nearest length listed may be used. Those who 90 .09 .18 .27 .36 .45 1.08
want to be more conservative may take the next 100 .10 .20 .30 .40 .50

higher figure in the table.


¾ PS 20 28 36 40 45 69 73 78 81
½ PS 37 52 64 73 82 127 133 142 148 1
..~70~110 136 157 17t 273 284 306 317 350,
Step 2. From the point just selected proceed to ‘AlPS
1 PS 148 208 253 293 330 510 536 578 600 660
the right to the figure representing the allowable 1¼IPS 297 420 515 600 670 1040 1090 1170 1220 1360
1½IPS 445 635 775 900 1006 1560 1640 1740 1850!2015
pressure drop. 0.4 in. w.c. in this example. 2 IPS 850 1200 1460 1700 1880 2940 3080 3300 3500 3800

Step 3. From the 0.4 in. pressure drop selected


drop straight down to the lower portion of the Figure 16. Solution showing how line A of
table to the section opposite the type of pipe or fig. 15 is sized with the use of table 28.
tubing to be used. In this example the main line
will carry a load of 1 73.000 Btu. The 1 63 is less The solution to this part of the problem is shown

than the required capacity so the next figure 350 in fig. 1 6.


must be selected.
Continuing with the problem shown in fig. 1 5. the
Step 4. From the 350 just selected, proceed to pipe sizes and actual pressure drops are

the left to 3/4 IPS which is the pipe size required. determined as follows:
Line B. Using 1 5 ft as the length and 0.2 in. as
C3.1,,5 Actual pressure drop. For the more the allowable pressure drop. the table indicates
complicated piping systems it is helpful to than 1/2 in. K tubing will be required for line B.
determine the actual pressure drop for the pipe Working backward it is found that the actual

size selected. In the present example it is obvious pressure drop (for 61.000 Btu) is 0.06 in. w.c.

129
MS 930: 1986

Line C. For the water heater the total length of C3.2 Pipe sizing high pressure lines
pipe is 1 5 ft and the allowable pressure drop 0.2
in.w.c. The table indicates than 1/4 K tubing is right C3.2.1 While a majorityof pipesizing problems
for this line, and since its capacity is the same as involve low pressure lines, there are frequent
the load. the actual pressure drop is 0.2 in. w.c. occasions when high pressure lines are
necessary or advantageous. If an appliance
Line D.Following the same procedure it is found requires gas at a pressure of 10 lb or 1 5 lb for
than 1/2 in. K tubing will be required for line Dwith proper operation. it will have to be supplied by a
an actual pressure drop of 0.07 in. w.c. high pressure gas line. Even with appliances
operating at low pressure, it is better ecoriomy
many times to use two-stage pressure reduction
It is good practice at the completion of a pipe with the first-stage regulator at the container and
sizing project to appraise the results. Minimum the second-stage regulator at or near the point of
sizes can be indicated either on-a drawing or bya use. Furthermore, there is the advantage of better
summary table as in table 30. In the present case pressure regulation.
the line loss at each of the appliances is well
below the maximum allowable of 0.6 in. w.c. The The carrying capacity of a pipeline is 10 times or
only practicable would be to
improvement 15 times greaterwith high pressure gas than with
increase the line to the water heater by one size. low pressure. The increased capacity depends, 9f
but this is not necessary. Considerationshould be course, on the pressure at which the gas is piped
given to oversizing the main line if there is reason and the allowable pressure drop. If an existing low
to believe that additional appliances may be pressure line has become overloaded, its
installed at a later date. However, in this exercise capacity may be increased considerably by
the ¾ in. main line would handle a 350,000 Btu increasing the pressure by only a few pounds. In
load at the allowable pressure drop of 0.4 in: w.c. many such cases it would be less expensive and
It is quite obvious that thi-s extra capacity is in provide better performance to change to two-
excess of the requirements of a domestic stage regulation than to replace the existing low
installation. - - - pressure line with one of adequate size.

The most common problem in high pressure pipe


sizing is the sizing of the intermediate line
Table 30 Solution summary of pipe sizing of a
domestic installation shown in fig. 15 between the-first and second-stage regulators in
a two-stage system. Most of these supply
-

domestic or commercial loads with a single high


Allowable Actual Total line
Load Pipe pressure pressure loss at pressure line of moderate length and capacity.
Line l000s size drop drop applianc~
Btu (in.) (in.) (in.) (in.) For this limited application, table 31 has been
found the simplest and easiest to use. When
using table 31 four steps have to be followed for
3 determining proper sizing of high pressure lines.
A 173 4)PS 0.4 0.1 —

B 63 ½ K 0.2 0.06 0.16


1/4 K
C 30 0.2 0.2 0.30 Step 1. Find the figure representing pipe length
0 80 ½K 0.2 0.07 0.17 in the left hand column of the table. This will be
the measured length plus an allowance for

130
MS 930: 1986

fittings. As with low pressure piping. where only a Table 31. High pressure pipe sizing table
few fittings are involved, five feet can be allowed
for each 900 elI or side outlet of a tee. Pip. cepiciti... 1000. of Stu

length Typ. K tubing St.nd.rd pip. siz.s


Step 2. Decide which of the lines representing ¼ ¼ ‘Is ½ ½ ¾
pipe capacities will be used. An almost unlimited
range of pressures and pressure drops may be A 990 1860 3660 2400 4400 9320
B 460 880 1740 1140 2100 4400
encountered in high pressure pipe sizing. but for C 278 534 1030 688 1240 2660

the usual domestic or commercial installation


A 800 1550 2970 1980 3580 7600
those shown in the key below the table are quite B 374 710 1400 930 1675 3600
C 225 427 840 560 1010 2170
satisfactory. The determining factor to be
considered is the minimum temperature which A 695 1300 2570 1700 3090 6160
8 325 620 1200 795 1460 3100
may- be encountered. Gas will condense to a C 196 370 730 486 880 1885

liquid if too high a pressure is used in cold


5900
weather. If. for example. t.he lowest temperature A
B
624
290
1185
560
2285
1090
1520
720
2775
1300 2740
likely to be encountered in an area is —20°F the B C 174 327 650 427 780 1670

capacities based on a line pressure of 10 Ibwould


A 570 1085 2100 1390 2500 5370
be used. B 268 500 1000 660 1206 2550
C 160 300 600 397 720 1535

A 495 930 1830 1200 2200 4660


Step 3. Having determined the capacities to be B
C
230
139
440
267
870
515
570
344
1050
620
2200
1330
used. A, B. or C. proceed from the figure
representing pipe length to the right to the A 440 830 1635 1090 1960 4160
B 200 390 766 502 925 1980
required capacity in terms of l000s of Btu. The C 123 235 460 310 556 1180

first three columns represent the capacities of


A 400 770 1500 1000 1785 38(X)
type K tubing and the others refer to standard B 188 356 700 463 850 1785
C 113 213 420 282 515 1090
pipe sizes. The type of pipe or tubing to be
selected will be determined by company practice. A 370 710 1380 920 1660 3530
B 170 330 540 428 775 1670
If the exact figure representing the required C 105 198 388 260 464 1000
capacity is not found, the next larger is selected.
A 350 664 1300 870 1570 3350
B 162 310 600 400 730 1540
C 100 187 365 246 4.44 950
Step 4. From the figure representing required
capacity, proceed upward to the size of pipe or A 328 615 1200 820 1470 3130
B 155 292 576 382 697 1485
tubing which should be used. It is good practice C 95 174 343 230 420 900

to consider future loads which may be added and


A 310 590 1160 776 1400 2950
to select the pipe size accordingly. B 145 278 540 360 656 1400
C 90 168 325 219 396 860

Key to selection of int.rm.di.te prsesu,.

C3.2.2 Example. A commercial installation is to A B C


be made in a northern area where the lowest Minimum tern p.rature -10°F -20°c -30°F
temperature to be encountered is—i 50F. The pipe
length is 40 ft and the maximum load is 650,000 Intermediate pressure 15 lb 10 lb 5 lb
Pressure drop 2 lb 0.5 lb 1.25 lb
Btu. Using table 31 determine the required pipe Delivered pressure 13 lb 9.5 lb .75 lb

size for the intermediate high pressure line.

131
MS 930:1986

C3.2.3 Solution 5) 500 ft 600 value of the h


100 ft 120 value of the ‘h’
Step 1. Referring to the key at the bottom of
table .31, it will be noted that for a minimum
temperature of —1 5°F, the B capacities shou~dbe The proper size pipe will be selected if the line is
used.
considered to be 100 ft and the value of ‘h’ 1 20.
Equally good results would be obtained in this
Step~2. Select 40 ft in the left hand column of
the table and use the pipe capacities shown case by dividing by 10.
opposite the letter B.
C3.2.4.2 Value of ‘h’. The letter ‘h’ in the pipe
Step 3. Since the figure 650. representing the sizing formula represents pressure drop, and it is
load in thousands of Btu. does not appear in the at this point that high pressure pipe sizing differs
horizontal line opposite 40 ft B the next higher greatly from low pressure. In sizing low pressure
figure. 870. is selected. lines, the pressure, regardless of the amount of
pressure drop. is approximately atmospheric
Step 4. Moving upward from the 870 just pressure. With high pressure lines, pressures
selected the required pipe size is found to be ½ in. may be two or three times’ the atmospheric
type K tubing. By following the same procedure in pressure and pressure drop may vary from less
the right half of the table, 1/2 in. pipe will be than a pound up to 20 lb or more. In order to
indicated for this installation. reflect this wide range of pressures properly, the
letter representing pressure drop in the formula
for sizing high pressure lines is defined as
C3.2.4 Sizing lines with table 32. For sizing
follows:
high pressure lines involving factors beyond the
scope of the simplified table 31, table 32 is his the difference in the squares of the initial and
recommended. This is set up in the same manner delivered pressures expressed in terms of
as the low pressure pipe sizing table, and it is used absolute pressure.
in substantially the same way. There are a few
major differences, especially in regard to Expressed as a formula this becomes:
pressure drop and these are explained in
2
C3.2.4.1 through C3.2.4.4. h = P12 — P2

C3.2.4.1 Pipe length. The left hand column in or h = (Pi + P2) (Pi — P2)
the upper portion of the table represents the
length of the pipe including any allowance to be
where,
made for fittings. High pressure lines may
sometimes be beyond the limits of the table but Pi is the initial pressure, psia:
adjustment may be made by dividing both the
pipe length and the value of ‘h’ by some P2 is the delivered pressure, psia.
convenient number that will bring the length
within the desired limits. For example, suppose a An example showing how for a given situation the
500 ft high pressure line is to be run under value of ‘h’ is determined is shown in fig. 1 7. To
pressure conditions which indicate the value of simplify the finding of the ‘h’values for avarietyof
‘h’ to be 600. Both can be divided by 5 as follows: pressure conditions, tables 33 and 34 have been

132
MS930: 1986

30 psi (?)24 psig As with any pipe sizing job. the possibility of
9
future load additions should be considered and
(~) -
350 ft I I2.O00.0~0I
~Btu
piping of adequate capacity installed.

Pt P2 P1 30.Op.Ig
30.0 pug 24.0 pug P2 24.0 pug C3.2.4.4 Pipe sizes. Three types of piping
+14.7 +14.7

44.7 psia 38.7 psie (14.7 x 2) 29.4 psi


material are listed in the left hand column of the
‘~44.7 “38.7 I lower portion of the pipe sizing table. It is
1498 (Pt-P2)
assumed that in addition to carrying gas at high
1998—1498=500 500
pressure many of these lines will be placed

Figure 17. Two methods for finding the value underground. For this reason type K tubing.
of ‘h’ for a problem in high pressure pipe sizing standard weight pipe and extra strong pipe have
been included in the table.
prepared. Table 34 covers problems in which the
C3.2.4.5 The following examples will illustrate
initial pressure is given. Opposite the various
the use of table 32 for sizing high pressure lines.
figures for pressure drop in the left handcolumn
are the values of ‘h’ for initial pressures from 5 lb Example. What size extra strong pipe would be
to 50 lb. Whenever a pipeline has more than the required for the. installation shown in fig. 1 7?
required capacity, the actual “alue of ‘h’ will be Determine the actual delivered pressure with the
less. By locating this figure in the proper initial pipe size selected. -

pressure column, the actual pressure drop may


be read or estimated in the pressure drop column. Solution:

In situations where it must be determined what Step 1. Referring to table 33 find the value of ‘h’
initial pressure will be required for a given in the 30 lb initial pressure column opposite 6 lb
delivered pressure, table 34 is used. This may in the pressure drop column. The value is seen to
happen when an additional load is placed on a be 500 as shown in the illustration.
high pressure line and the same delivered
pressure must be maintained. The increase load Step 2. Since the 350 length of pipe is beyond
results in a new value of ‘h’ and the new figure is the range of the pipe sizing table this is adjusted
found in the proper delivered pressure column of as follows:
the table. Opposite this figure will be the actual
pressure drop. This pressure drop added to the 1 0) 350 ft value of ‘h’ 500
delivered pressure will indicate the required 35ft value of ‘ft 50
initial pressure. When the actual figures are not
found in the tables, careful estimates may be used Step 3. Entering pipe sizing table 32 at 35 ft
with satisfactor.y results. Examples involving both proceed to the right to find 50. the value of ‘h’.
tables 33 and 34 will be given, following further Since this number does not appear in the table.
explanation of the pipe sizing table. 49 will be selected.

C3.2.4.3 Gas load. Referring again to table 32. Step 4. Follow down the column in which the 49
the lower portion represents gas flow in was found to the section opposite the extra strong
thousands of Btu. This is the maximum load the pipe sizes. The load in 1 000s of Btu is 2000 and
pipeline is expected to carry and is the sum of the since this figure is not found in the table, the next
Btu inputs of the various appliances to be served. figure. 2488, is selected.

133
Table 32. High pressure pipe sizing table .
(n.
(0
(5)

Pipe length Values of ‘h’ . 0


(0
03
10 1 2 3 4 5 6 7 8 9 10 12 14 16 18 20
15 1.5 3 4.5 6 7.5 9 10.5 12 13.5 15 18 21 24 27 30
20 2 4 6 8 10 12 14 16 18 20 24 28 32 36 40
25 2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 30 35 40 45 50
30 3 6 9 12 15 18 21 24 27 30 36 42 46 54 60

35 3.5 7 10.5 14 17.5 21 24.5 28 1.5 35 42 49 56 63 70


4-0 4 8 12 16 20 24 28 32 36 40 48 56 64 72 80
45 4.5 9 13.5 18 22.5 27 31.5 36 40.5 45 54 63 72 81 90
50 5 10 15 20 25 30 35 40 45 50 60 70 80 90 100
55 5.5 11 16.5 22 27.5 33 38.5 44 49.5 55 66 77 88 99 110

60 6 12 18 24 30 36 42 48 54 60 72 84 96 108 120
70 7 14 21 28 35 42 49 56 63 70 84 98 112 126 140
80 8 16 24 32 40 48 56 64 72 80 96 112 128 144 160
90 9 18 27 36 45 54 63 72 81 90 108 126 144 162 180
100 10 20 30 40 50 60 70 80 90 100 120 140 160 180 200

Pipe size Gas load (l000s of Btu)

3
/eK 172 244 299 344 385 421 455 487 516 545 596 644 688 731 770
½K 339 480 587 678 758 831 898 959 1017 1073 1175 1270 1358 1440 1518
577 816 1000 1155 1290 1412 1528 1630 1732 1825 2000 2160 2310 2452 2582
~,4K 806 1140 1396 1610 1800 1973 2133 2277 2420 2547 2790 3015 3221 3420 3600
IK 1660 2350 2876 3320 3713 4060 4390 4693 4980 5250 5750 6330 6640 7050 7425

½IPS 409 578 708 818 915 1003 1082 1158 1227 1293 1415 1530 1637 1738 1830
3
/SIPS 875 1238 1516 1750 1958 2141 2316 2474 2625 2766 3030 3275 3500 3715 3915
lIPS 1642 2321 .2840 3280 3670 4020 4346 4642 4952 5191 5680 6148 6565 6975 7348
1% (PS 3344 4730 5785 6684 7475 8185 8850 9450 10036 10593 11580 12520 13380 14200 14950
1½(PS 5040 7122 8720 10080 11280 12330 13325 14235 15116 15920 17430 18850 20156 21380 22520
2 PS 9510 13450 16450 19000 21240 23250 25150 26850 28530 30077 32900 35600 38000 40360 42500

½XS 297 420 515 594 665 728 786 840 892 940 1030 1112 1189 1262 1330
~,4XS 665 940 1152 1330 1488 1630 1760 1880 1997 2103 2300 2488 2660 2824 2975
1 xs 1322 1870 2292 2644 2958 3218 3500 3740 3970 4183 4575 4950 5284 5616 5916
I’AxS 2706 3830 4684 5417 6050 6627 7162 7652 8125 8563 9367 10122 10820 11500 12110
1½XS 4254 6018 7366 8510 9520 10415 11265 12030 12790 13460 14720 15920 17000 18075 19030
2XS 8000 11300 13850 16000 17890 19580 21160 22600 24000 25286 27670 29940 32000 34930 35760
MS 930:1986

Step 5. Going to the left from the figure 2488


just selected it is noted that ¾ in. XS pipe will be 1 1 Delivered
2,000,000 1.3 pressure
required for this installation. ‘Btu 10
.a~.~!~t!_LII]
20 ft .. psig
®~Li 200 ft
Step 6. To find the actual value of ‘h’ proceed to Initial L4 3,001J,~IJ~
the right from the 3/4 in. XS pipe to the figure pressure
2Oft Btu
15 psi ~
closest to the actual load which is 2000 thousand 9

Btu. The figure 1 997 is selected. Moving directly 1 .500,000


Stu
upward to the line opposite 35 ft. the value of’h’ is
seen to be 31 .5. Since the value of’h’was divided Figure 18. A high pressure pipe sizing
by 1 0 in the beginning, it is now necessary to problem involving branch lines
multiply by 10 to getthetruevalue: 31.5 x 10 =
31 5. the actual value of ‘h’ for this problem. C3.2.5.2 Solution:

Step 1. The maximum allowable pressure drop


Step 7. To find the actual pressure drop with the
between the high pressure regulator outlet and
3/4 in. XS pipe refer to table 33 and Iookfor3l 5 in
the several appliances is 5 lb. An arbitrary
the 30 lb initial pressure column. Selecting the
decision must be made as to how this will be
next larger figure. 342, it will be noted that this is
apportioned and for this problem it is suggested
opposite a pressure drop of 4 lb.
that 3 lb be allotted-to the main line and 2 lb for
each of the branches. On this basis the delivered
Step 8. The actual.delivered pressure is found as
pressure for the main line will be 12 lb and this
follows:
will then be the initial pressure for the branch
Initial pressure 30 lb lines.
Actual pressure drop 4 lb
Step 2. Referring to table 33 in the 15 lb initial
Actual delivered pressure 26 lb pressure column itwill be seen that thevalue of’h’
for a 3 lb pressure drop is- 1 69. For each of the
C3.2.5 Problems involving branch lines. branch lines the initial pressure is 1 2 and the
Whenever a high pressure installation involves pressure drop 2 lb. For this pressure drop and
two or more appliances the piping system is 1 0— and 1 5— lb initial pressures the values for ‘h’
broken down into component parts as follows: are 95 and 11 5, a difference of 20. One can
estimate that for 1 2 lb initial pressure ‘h’ would be
The main supply line slightly over 100. By actual calculation, it comes.
An intermediate line if one is used out 103.
Lines to the individual appliances
Step 3. To size the main line the following
A piping layout such as shown in fig. 18 is factors are to be considered.
handled in much the same way as a low pressure
installation: the problem is broken down into
individual lines each of which is sized separately. Pipe length 200 ft
Valve of ‘h’ 1 69
C3.2.5.1 Example. Determine the proper pipe Load 6500 thousand Btu
sizes for the high pressure piping system shown
in fig. 1 8. Since 200 ft is not shown in the pipe sizing table.

135
MS 930: 1986

it is necessary to make an adjustment such as the Trial and error may be required with some
following: problems, but with this one it would seem best to
divide the value of ‘h’ by 4 and the load by the
2) 200 ft value of ‘h’ 1 69 square root of 4 which is 2. as follows:
100 ft value of ‘ft 85
4) Value of ‘h’ 1 03
Value of ‘h’ 26 -
Opposite 1 00 ft in table 32 the values 80 and 90
are found for ‘h’. Since 85 is half way between, 2) Load 3000 thousand Btu
one can follow down between the two lines to the Load 1 500 thousand Btu
standard pipe section. The indicated pipe size is
11/4 IPS. In case it should be desirable later to The problem can now be solved on the basis of
know the actual value of ‘h’. find 6500 in the the following factors:
horizontal line opposite 1V4IPS: 6684 is selected.
Proceeding upward to the 100-ft line it is seen
that the actual value of h’ appears to be 40. Since Pipe length 25 ft
both the pipe length and the value of ‘h’ were Value of ‘h’ 26
divided by two. it is necessary nowto multiply by2 Load 500 thousand Btu
to get the true value of ‘h’ for the pipe size
Using the table as already explained, it is seen that
selected.
3/4IPS should be specified for line 2. The chart
shows 7.5 as the value of ‘h’ but this must be
Step 4. For sizing line 2 these factors are multiplied by 4, since the allowable figure was
involved: - - divided- by 4. This makes the actual value of’h’ for
this line to be 30.
Pipe length 25 ft
Value of ‘h’ 103 Step 5. Line 3 is solved in the same manner, the
Load 3000 thousand Btu following factors being used with the pipe sizing
table:
Referring to the pipe sizing table, it will be seen
Pipe length (2 ells) 30 ft
that opposite 25 ft the values of ‘h’ go only to 50.
Value of ‘h’ 26
Whatever adjustment may be made with these
Load 1 000 thousand Btu
figures. this problem would still be beyond the
capacity ofthe table. In such a situation the length
These are the results: Pipe size ½IPS. actualvalue
is left at 25 ft and adjustment is made by changing
of ‘h’ 72.
the value of ‘h’ and the load. How this is done is
explained in the box below: Step 6. Sizing Iine4follows the same procedure
and comes out to be 1/2 IPS with 40 as thevalueof
To adjust the values of ‘h’ and the gas loud to bring a high
pressure pipe sizing problem within the limit, of the pipe
sizing table:

Multiply or 2 3 4 5 6 7 8 9 10 C3.2.6 High pressure pipe sizing chart. The


divide ‘h’ by
high pressure pipe sizing chart. fig. 1 9 is included
Multiply or 1.41 1.73 2 2.24 2.45 2.65 2.83 3 3.16 for the benefit of those who are familiar with this
divide load by
method of pipe sizing. With some problems

136
MS 930: 1986

beyond the range of capacity of the pipe sizing these are involved in a pipe sizing problem the
table, the chart may be more convenient to use load, either in cubic feet or Btu. must be divided
than making the necessary adjustments in by 1 0 before going to scale 4. This is illustrated in
connection with the table. When using the chart, the following example.
it is necessary to align certain points and this
must be done with the page as flat as possible. It C3.2.6.1 Example. Find the proper size of
has been found convenient to use either a standard weight pipe for a 1000 ft linewhich isto
transparent straightedge or a black thread. The carry a load of 10,000,000 Btuh. The initial
various scales on the chart are numbered in the pressure is 20 lb and the pressure drop is limited
order of their use in solving a pipe sizing problem. to 3 lb.

Scale 1 includes the values of ‘h’ from 10 to C3.2.6.2 Solution


2000. It will be noted that between 100 and 200
on this scale there are 1 0 divisions, each ofwhich Step 1. Referring to table 33, find thevalue of’h’
has a value of 1 0. For an ‘h’ value of 11 5 the point which for this problem is 1 99. Align this point of
to select would be one and one-half spaces below scale 1 with 1000 o~scale 2 extending the thread
the figure 100. Between 40 and 50. for example. or straightedge on to line 3.
there are only 5 divisions, each of which would
count 2. Thus 46 on this scale would be 3 spaces Step 2. Align the point just established on line 3
with 10.000 on the right side of scale 4 and
below the figure 40.
extend the line on to scale 5. It will be found that
Scale 2 represents the length of pipe from 10 ft this line does not intersect scale 5 and that no
to 5000 ft and from 1 mile to 10 miles which is pipe size can be read.
considerably beyond the range of the pipe sizing
table.
Step 3. Divide the 1 0.000 thousand Btu load by
Scale 4 shows the gas flow for which a pipe line 1 0 and repeat step 2 using 1000 as the load.
is to be sized. Figures on the left side of the scale Reading the left side of scale 5 it will be noted that
represent cubic feet while those at the right are the line comes between 11/2 in. and 2 in. pipe. The
thousands of Btuh. 2 in. size will be adequate for this installation.

Scale 5 includes pipe sizes from ½ in. to 3 in. Step 4. To find the actual pressure dropwith the
The points on the heavy vertical line representing pipe size selected, the above procedure is
the various pipe sizes are designated by the reversed, beginning with the point on scale 5
letters STD or XS or in the case of copper tubing representing 2 in. standard weight pipe, and
by the letters K and L. going through 1000 on scale 4. Intersection is
made on scale 1 atapointslightlymorethan 110.
It will be noted that the larger pipe sizes from 11/2 Reference to table 33, indicates that the actual
in. to 3 in. are on the left side of scale 5. Whenever pressure drop will be between 11/2 lb and 2 lb.

137
MS 930:1986

Table 33. Values of ~h’for high pressure pipe sizing

Initial pressure - psig


Pressure
drop-psi 5 - 10 15
-

20 25 30 35 40 J 45 50

0.1 4 5 6 7 8 9
J- 10 11
I
12 13
0.5 19 24 29 34 39 44 49 54 59 64

1 38 48 58 68 78 88 98 108 118 128


2 75 95 115 135 155 175 195 215 235 255
3 109 139 169 199 229 259 289 319 349 379
4 142 182 222 262 302 342 382 422 462 502
5 222 272 322 372 422 472 522 572 622

6 260 320 380 440 500 560 620 680 740


7 297 367 437 507 577 647 - 717 787 857
8 331 411 491 571 651 731 811 891 971
9 364 454 544 634 724 814 904 994 1084
10 494 594 694 794 894 994 1094 1194

12 569 689 809 929 1049 1169 1289 1409


14 776 916 1056 I 1196 1336 1476 1616
16 854 1014 1174 1334 1494 1654 1814
18 1105 1285 I 1465 1645 1825 2005
20 1186 1388j 1588 178811988 2188

Table 34. Values of ‘h’ for high pressure pipe sizing

Delivered pressure - psig


Pressure
drop-psi 5 10 15 20 25 30 35 35 40 50

0.1 4 5 6 7 8 9 10 11 12 13
0.5 20 25 30 35 40 45 50 55 60 65

1 40 50 60 70 80 90 100 120 130


2 83 103 123 143 163 183 203 223 243 263
3 127 157 187 217 247 277 307 337 367 397
4 174 214 254 294 334 274 414 454 494 534
5 222 272 322 372 422 472 522 572 622 672

6 27. 332 392 452 512 572 632 692 752 812
7 325 395 465 535 605 675 745 815 885 955
8 379 459 539 619 699 779 859 939 1019 1099
9 436 526 616 706 796 886 976 1066 1156 1246
10 494 594 694 794 894 994 1094 1194 1294 1394

12 617 737 857 977 1097 1217 1337 1457 1577 1697
14 748 888 1028 1168 1308 1448 1588 1728 1828 2008
16 886 1046 1206 1366 1526 1686 1846 2006 2166 2326
18 1033 1213 1393 1573 1753 1933 2113 2293 2473 2653
20 1188 1388 1588 1788 1988 2188 2388 2588 2788 2988

138
MS 930: ‘1986

- 30,000
10,000-
9,000-~
10— 8,000~S 20.000
7,000-:
6,000:
5,000 10
20 4,000~-10,O00
STDr x5 20
30°1J.~:8,000 30
30 :
~7,000 40
6,000 50
40 2.000 - - 5,000 60
- 80
50 —4,000 100
STD 60
3.000 200
8 1,000. 00
90 900—
x5 100 — 8O0~ 2,000 400
—500
— 600
600 800
500 1000
200 400~ 1,000
2” .STD - ~-900 2000
x5 300— ~ —3000
300 - = -700 4000
- F 600 —.~5000
400 200500 Miles

500— -—400 ‘2
600 :: 3
700 300 4
1½” 800 100 5
x5 900: 9O~.
1000 80- 200 8
70- 10
60 Pipe length
Feet - miles
(1) 50Ø

2000 40~ 100


Pipe size Values of ‘h’ Cu. ft. ~8tu’s—10O0’s
Gas flow

Figure 19. High pressure pipe sizing chart

139
MS 930 : 1986

Appendix D

Suggested method for checking for leakage

Dl. USEOFLIGHTS burner, the meter is defective and the gas should
be shut off and the serving gas supplier notified.
D1.1 Artificial illumination used in connection
with a search for gas leakage shall be restricted to
battery-operated flashlights (preferably of the
safety type) or approved safety lamps. In D3. CHECKING FOR LEAKAGE NOT USING A
searching for leaks, electric switches should not METER
be operated. If electric lights are already turned
on, they should not be turned off. D3.1 This can be done in two ways: (a) by
attaching to an appliance orifice a manometer or
equivalent device calibrated so that it can be read
D2. CHECKING FOR LEAKAGE USING THE GAS in increments of not more than 2 per cent of
METER operating system pressure. and momentarily
turning on the gas supply and observing the
D2.1 Immediately prior to the test it should be gauging device for pressure drop with the gas
determined that the meter is in operating supply shut off. No discernible drop in pressure
condition and has not been bypassed. shall occur during a period of 3 minutes; or (b) by
inserting a pressure gauge between the container
Checking for leakage can be done by carefully gas shutoff valve and the first regulator in the
watching the test dial of the meter to determine system, admitting full container pressure to the
whether gas is passing through the meter. To system and then closing the container shutoff
assist in observing any movement of the test valve. An appliance valve shall then be opened
hand, wet a small piece of paper and paste its momentarily dropping the pressure in the system
edge directly over the centre line of the hand as between the first regulator and the container
soon as the gas is turned on. Allow 5 minutesfor a shutoff valve 70 kPa (gauge). The system shall
1 50 mm dial and proportionately longer for a then be allowed-to stand for 10 minutes without
larger dial in checking for gas flow. This showing an increase or a decrease in the pressure
observation should be made with thetest hand on gauge reading.
the upstroke.

In case careful observation of the test hand for a D4. WHEN LEAKAGE IS INDICATED
sufficient length of time reveals no movement, the
piping shall be purged and a small gas burner D4.1 If the meter test hand moves, or a pressure
turned on and lighted and the hand of thetestdial drop on the gauge is noted, all equipment or
again observed. If the dial hand moves (as it outlets supplied through the system shall be
should), it will show that the meter is operating examined to see if they are shut off and do not
properly. If the test hand does not move or leak. If they are found tight there is a leak in the
register flow of gas through the meterto the small piping system.

140
MS 930:1986

Appendix E

Suggested emergency procedure for gas leaks

El. When an investigation discloses a concentration of gas inside of a building, it is


suggested the following immediate actions be taken:

El.l Clear the room, building or area of all occupants.

El .2 Ventilate the affected portion of the building by opening windows and doors.

E1.3 Use every practical means to eliminate sources of ignition.Take precautions to


prevent smoking, striking matches, operating electrical switches or devices. opening
furnace doors, etc. If possible, cut off all electric circuits at a remote source to
eliminate operation of automatic switches in the dangerous area. Safety flashlights
designed for use in hazardous atmospheres are recommended for use in such
emergencies.

El .4 Shut off the supply of gas to the areas involved.

El .5 Investigate other buildings in the immediate area to determine the presence of


escaping gas therein.

E1.6 Notify all personnel in the area and the gas supplier from a telephone remote
from the area of the leak.

141
MS 930: 1986

Appendix F

Flow of gas through fixed orifices

Fl. USE OF ORIFICE TABLES with the manufacturer’s rated input.

F1.1 General Fl .3 To select correct orifice size for rated


burner input
The units given in the appendix are wholly in the
imperial system. The conversion of the imperial The selection of a fixed orifice size for any rated
data to the metric units would create discrepancy, burner input is affected by many variables.
inconsistency and loss of accuracy of the including orifice coefficient. and it is
physical constant values, which in this instance recommended that the appliance manufacturer
have been measured or assessed from actual be consulted for that purpose. When correct
operational performance of the gas utilization orifice size cannot be readily determined. the
equipment. The imperial units have therefore orifice flow rates, as stated in the tables in this
been retained for practical reasons. until such appendix, maybe used to select a fixed orifice size
time when actual data irithe metric units could be with a flow rate to approximately equal the
compiled. required rated burner input.

Fl .2 To check burner input in accordance with For gases of the specific gravity and pressure
8.1.3.2 conditions stipulated at elevations under
2.000 feet, table 35 (in cubic feet per hour) or
Check gauge size of burner orifice and determine table 36 (in Btu per hour) may be used directly.
flow rate at sea level from table 35. utility gases
(cubic fe-et hour), or from table 36. LP-gases (Btu When the specific gravity of the gas is other than
per hour). When the specific gravity of the utility 0.6. select the multiplier from table 37 for the
gas is other than 0.6. select the multiplier from utility gas served and divide the rated burner
table 37 for the specific gravity of the utility gas input by the selected factor to determine
served and apply to the flow rate as determined equivalent input at a specific gravity of 0.60 and
from table 35. When altitude is above 2,000 feet. then select orifice size as directed above.
first select equivalent orifice size at sea level
using table 38 and then determine flow rate from When the appliance is located at an altitude of
table 35’or table 36 a~ iirected above. 2.000 feet or above, first use the manufacturer’s
rated input at sea level to select orifice size as
Having determined flow rate (as adjusted for directed above, then use table 38 to select the
specific gravity and/or altitude when equivalent orifice size for use at the higher
necessary). check the burner input at sea level altitude.

142
MS 930: 1986

Table 35. Utility gases


(Cubic feet per hour at sea level)

Specific gravity = 0.60 Orifice coefficient = 0.90

Orifice Pressure at orifice, inches water column


or drill
size 3 3.5 4 5 6 7 8 9 10

80 .48 .52 .55 .63 .69 .73 .79 .83 .88


79 .55 .59 .64 .72 .80 .84 .90 .97 1.01
78 .70 .76 .78 .88 .97 1.04 1.10 1.17 1.24
77 .88 .95 .99 1.11 1.23 1.31 1.38 1.47 1.55
76 1.05 1.13 1.21 1.37 1.52 1.61 1.72 1.83 1.92
75 1.16 1.25 1.34 1.52 1.64 1.79 1.91 2.04 2.14
74 1.33 1.44 1.55 1.74 1.91 2.05 2.18 2.32 2.44
73 1.51 1.63 1.76 1.99 2.17 2.32 2.48 2.64 2.78
72 1.64 1.77 1.90 2.15 2.40 2.52 2.69 2.86 3.00
71 1.82 1.97 2.06 2.33 2.54 2.73 2.91 3.11 3.26
70 2.06 2.22 2.39 2.70 2.97 3.16 3.38 3.59 3.78
69 2.25 2.43 2.61 2.96 3.23 3.47 3.68 3.94 4.14
68 2.52 2.72 2.93 3.26 3.58 3.88 4.14 4.41 4.64
67 2.69 2.91 3.12 3.52 3.87 4.13 4.41 4.69 4.94
66 2.86 3.09 3.32 3.75 4.11 4.39 4.68 4.98 5.24
65 3.14 3.39 3.72 4.28 4.62 4.84 5.16 5.50 5.78
64 3.41 3.68 4.14 4.48 4.91 5.23 5.59 5.95 6.26
63 3.63 3.92 4.19 4.75 5.19 5.55 5.92 6.30 6.63
62 3.78 4.08 4.39 4.96 5.42 5.81 6.20 6.59 6.94
61 4.02 4.34 4.66 5.27 5.77 6.15 6.57 7.00 7.37
60 4.21 4.55 4.89 5.52 5.95 6.47 6.91 7.35 7.74
59 4.41 4.76 5.11 5.78 6.35 6.78 7.25 7.71 8.11
58 4.66 5.03 5.39 6.10 6.68 7.13 7.62 8.11 8.53
57 4.84 5.23 5.63 6.36 6.96 7.44 7.94 8.46 8.90
56 5.68 6.13 6.58 7.35 8.03 8.73 9.32 9.92 10.44
55 7.11 7.68 8.22 9.30 10.18 10.85 11.59 12.34 12.98
54 7.95 8.59 9.23 10.45 11.39 12.25 13.08 13.93 14.65
53 9.30 10.04 10.80 12.20 13.32 14.29 15.27 16.25 17.09
52 10.61 11.46 12.31 13.86 15.26 16.34 17.44 18.57 19.53
51 11.82 12.77 13.69 15.47 16.97 18.16 19.40 20.64 21.71
50 12.89 13.92 14.94 16.86 18.48 19.77 21.12 22.48 23.65
49 14.07 15.20 16.28 18.37 20.20 21.60 23.06 24.56 25.83
48 15.15 16.36 17.62 19.88 21.81 23.31 24.90 26.51 27.89
47 16.22 17.52 18.80 21.27 23.21 24.93 26.62 28.34 29.81
46 17.19 18.57 19.98 22.57 24.72 26.43 28.23 30.05 31.61
45 17.73 19.15 20.52 23.10 25.36 27.18 29.03 30.90 32.51
44 19.45 21.01 22.57 25.57 27.93 29.87 31.89 33.96 35.72
43 20.73 22.39 24.18 27.29 29.87 32.02 34.19 36.41 38.30
42 23.10 24.95 26.50 29.50 32.50 35.24 37.63 40.07 42.14
41 24.06 25.98 28.15 31.69 34.81 37.17 39.70 42.27 44.46
40 25.03 27.03 29.23 33.09 36.20 38.79 41.42 44.10 46.38
39 26.11 28.20 30.20 34.05 37.38 39.97 42.68 45.44 47.80
38 27.08 29.25 31.38 35.46 38.89 41.58 44.40 47.27 49.73
37 28.36 30.63 32.99 37.07 40.83 43.62 46.59 49.60 52.17
36 29.76 32.14 34.59 39.11 42.76 45.77 48.88 52.04 54.74
35 32.36 34.95 36.86 41.68 45.66 48.78 52.10 55.46 58.34
34 32.45 35.05 37.50 42.44 46.52 49.75 53.12 56.55 59.49
33 33.41 36.08 38.79 43.83 48.03 51.46 54.96 58.62 61.55

143
MS 930:1986

Table 35. Utility gases (Continued)

Specific gravity -~• 0.60 Orifice coefficient = 0.90 -

Orifice Pressure at orifice, inches water column


or drill
size 3.5 4 5 6 7 10
8
9
32 35.46 38.30 40.94 46.52 50.82 54.26 57.95 61.70 64.89
31 37.82 40.85 43.83 49.64 54.36 58.01 61.96 65.97 69.39
30 43.40 46.87 50.39 57.05 62.09 66.72 71.22 75.86 79.80
29 48.45 52.33 56.19 63.61 69.62 74.45 79.52 84.66 89.04
28 51.78 55.92 59.50 67.00 - 73.50 79.50 84.92 90.39 95.09
27 54.47 58.83 63.17 71.55 78.32 83.59 89.27 95.04 99.97
26 - 56.73 61.27 65.86 74.57 81.65 87.24 93.17 99.19 104.57
25 58.87 63.58- 68.22 77.14 84.67 90.36 96.50 102.74 108.07
24 60.81 65.67 70.58 79.83 87.56 93.47 99.83 106.28 - 111.79
23 62.10 67.07 72.20 81.65 89.39 94.55 100.98 107.49 113.47
22 64.89 70.08 75.21 85.10 93.25 99.60 106.39 113.24 119.12
21 66.51 71.14 77.14 87.35 95.63 102.29 109.24 116.29 122.33
20 68.22 73.68 79.08 89.49 97.99 104.75 111.87 119.10 125.28
19 72.20 77.98 83.69 94.76 103.89 110.67 118.55 125.82 132.36
18 75.53 81.57 87.56 97.50 108.52 116.03 123.92 131.93 138.78
17 78.54 84.82 91.10 103.14 112.81 120.33 128.52 136.82 143.91
16 82.19 88.77 95.40 107.98 118.18 126.78 135.39 144.15 151.63
15 85.20 92.02 98.84 111.74 122.48 131.07 139.98 149.03 156.77
14 87.10 94.40 100.78 114.21 124.44 133.22 142.28 151.47 159.33
13 89.92 97.11 104.32 118.18 128.93 138.60 148.02 157.58 165.76
12 93.90 101.41 108.52 123.56 135.37 143.97 153.75 163.69 172.13
11 - 95.94 103.62 111.31 126.02 137.52 147.20 157.20 167.36 176.03
10 98.30 106.16 114.21 129.25 141.82 151.20 161.81 172.26 181.13
9 100.99 109.07 117.11 132.58 145.05 154.71 165.23 175.91 185.03
8 103.89 112.20 120.65 136.44 149.33 160.08 170.96 182.00 191.44
7 105.93 114.40 123.01 139.23 152.56 163.31 174.38 185.68 195.30
6 109.15 117.88 126.78 142.88 156.83 167.51 178.88 190.46 200.36
5 111.08 119.97 128.93 145.79 160.08 170.82 182.48 194.22 204.30
4 114.75 123.93 133.22 150.41 164.36 176.18 188.16 200.25 210.71
3 118.25 128.79 137.52 156.26 170.78 182.64 195.08 207.66 218.44
2 128.48 138.76 148.61 168.64 184.79 197.66 211.05 224.74 235.58
1 136.35 147.26 158.25 179.33 194.63 209.48 223.65 238.16 250.54

NOTE 40. For utility gases of another specific gravity, select multiplier from table 38. For altitudes above 2.000 feet. firstseiectthe
equivalent orifice size at sea level from table 38.

144
MS 930: 1986

Table 36. LP-gases


(Btu per hour at sea level)

Butane or
Orifice or Propane butane-propane
drill size mixtures

.008 500 554


.009 641 709
.010 791 875
.011 951 1,053
.012 1,130 L250
80 1 ,.430 1,590
79 1,655 1,830
78 2,015 2,230
77 2,545 2,815
76 3,140 3,480
75 3,465 3,840
74 3,985 4,410
73 4,525 5,010
72 4,920 5,450
71 5,320 5,900
70 6,180 6,830
69 6,710 7,430
68 7,560 8,370
67 8,040 8,910
66 8,550 9,470
65 9430 10,670
64 10,200 11,300
63 10,800 11,900
62 11,360 12,530
61 11,930 13,280
60 12,570 13,840
59 13,220 14430
58 13,8.40 15,300
57 14,550 16,090
56 16,990 18,790
55 21,200 23,510
54 23,850 26,300
53 27,790 30,830
52 31,730 35,100
51 35,330 39,400
50 38,500 42,800
49 41,850 45,350
48 45,450 50,300
47 48,400 53,550
46 51,500 57,000
45 52,900 58,500
44 58,050 64.350
43 62,200 69,000
42 68,700 76,200
41 72,450 80,200
40 75,400 83,500
39 77,850 86,200
38 81,000 89,550
37 85,000 94,000
36 89,200 98,800
35 95,000 105,300
34 97,000 107,200
33 101,000 111,900
32 105,800 117,000
31 113,200 125,400
30 129,700 143400
29 145,700 163,400
28 154,700 171400
27 163,100 180,000
26 169,900 187,900
25 175,500 194400

145
MS 930:1986

Table 36. LP-gases (Contd.)


Butane or
Orifice or - butane-propane
Propane
drill size mixtures

24 181,700 201400
23 186,800 206,400
22 193,500 214.500
21 198,600 220,200
20 203,700 225,000
19 217,100 241,900
18 225,600 249,800

NOTE 41. Propane and butane data

Propane Butane
Btu per cubic foot = 2.500 3.175
Specific gravity = 1.53 2.00
Pressure at orifice, inches water column = 11 11
Orifice coefficient = 0.9 0.9
For altitudes above 2.000 feet. first select the equivalent orifice size at sea level from
table 38.

- - Table 37. Multipliers for utility gases of another


specific gravity

Specific gravity Multiplier Specific gravity Multiplier

0.45 L155 0.95 0.795


0.50 1.095 1.00 0.775
0.55 1.045 1.05 0.756
0.60 1.000 1.10 0.739
0.65 0.961 1.15 0.722
0.70 0.926 1.20 0.707
0.75 0.894 1.25 0.693
0.80 0.866 1.30 0.679
0.85 0.840 1~35 0.667
0.90 0.817 1.40 0.655

146
MS 930:1986

Table 38. Equivalent orifice sizes at high altitudes


(Includes 4% input reduction for each 1,000 feet)

Orifice size required at other elevations


Ofl~Ce
. .
size at
sea level 2000 3000’ 4000 5000 6000 7000 8000 9000 10000

2 2 3 3 4 S 7 8 10
2 3 3 4 5 6 7 9 10 12
3 4 5 7 8 9 10 12 13 15
.4 6 7 12 13 14 16
8 9 11
5 7 8 9 10 12 13 14 15 17
6 8 9 10 11 12 13 14 16 17
7 9 10 11 12 13 14 15 16 18
8 10 11 12 13 13 15 16 17 18
9 11 12 12 13 14 16 17 18 19
10 12 13 13 14 15 16 17 18 19
11 13 13 14 15 16 17 18 19 20
12 13 14 15 16 17 17 18 19 20
13 15 15 16 17 18 18 19 20 22
14 16 16 17 18 18 19 20 21 23
15 16 17 17 18 19 20 20 22 24
16 17 18 18 19 20 22 23 25
17 18 19 19 20 21 22 23 24 26
18 19 19 20 21 22 23 24 26 27
19 20 20 21 22 -23 25 26 27 28
20 22 22 23 24 25 26 27 28 29
21 23 23 24 25 26 27 28 28 29
22 23 24 25 26 27 27 28 29 29
23 25 25 26 27 27 28 29 29 30
24 25 26 27 27 28 28 29 29 30
25 26 27 27 28 28 29 29 30 30
26 27 28 28 28 29 29 30 30 30
27 28 28 29 29 29 30 30 30 31
28 29 29 29 30 30 30 30 31 31
29 29 30 30 30 30 31 31 31 32
30 30 31 31 31 31 32 32 33 35
31 32 32 32 35 36 37 38
33 34
32 33 34 35 35 36 36 37 38 40
33 35 35 36 36 37 38 38 40 41
34 35 36 36 37 37 38 39 40 42
35 36 36 37 37 38 39 40 41 42
36 37 38 38 39 40 41 41 42 43
37 38 39 39 ~40 41 42 42 43 43
38 39 40 41 41 42 42 43 43 44
39 40 41 41 42 42 43 43 44 44
40 41 42 42 42 43 43 44 44 45
41 42 42 42 43 43 44 44 45 46
42 42 43 43 43 44 44 45 46 47
43 44 44 44 45 45 46 47 47 48
44 45 45 45 46 47 47 48 48 49
45 46 47 47 47 48 48 49 49 50
46 47 47 47 48 48 49 49 50 50

147
MS 930:1986

Table 38. Equivalent orifice sizes at high altitudes


(Includes 4% input reduction for each 1,000 feet)
(Contd.)

Orifice Orifice size required at other elevations


size at
sea level 2000 3000 4000 [ 5000 6000 7000 8000 9000 10000

47 48 48 49 49 49 50 50 51 51
48 49 49 49 50 50 50 51 51 52
- 49 50 50 so 51 51 51 52 52 52
50 51 51 51 51 52 52 52 ~3 53
51 51 52 52 52 52 53 53 53 54
52 52 53 53 53 53- 53 54 54 54
53 54 54 54 54 54 54 55 55 55
54 54 55 55 55 55 55 56 56 56
55 55 55 55 56 56 56 56 56 57
56 56 56 57 57 57 58 59 59 60
57 58 59 59 60 60 61 62 63 63
59 60 60 61 62 62 63 64
58
59 60 61 - 61 62 62 63 64 64 65
60 61 61 62 63 63 64 64 65 65
61 62 62 63 63 64 65 65 66 66
62 63 63 64 64 65 65 o6 67
63 64 64 65 65 65 66 66 67 68
64 65 65 65 66 66 66 67 67 68
65 65 66 66 66 67 67 68 68 69
66 67 67 68 68 68 69 69 69 70
67 68 68 68 69 69 69 70 70 70
68 68 69 69 69 70 70 70 71 71
69 70 70 70 70 71 71 71 72 72
70 70 71 71 71 71 72 72 73 73
71 72 72 72 73 73 73 74 74 74
72 73 73 73 73 74 74 74 74 75
73 73 74 74 74 74 75 75 75 76
74 74 75 75 75 75 76 76 76 76
75 75 76 76 76 76 77 77 77 77
76 76 76 77 77 77 77 77 77 77
77 77 77 77 78 78 78 78 78 78
78 78 78 78 79 79 79 79 80 80
79 79 80 80 80 80 .013 .012 .012 .012
80 80 .013 .013 .013 .012 .012 .012 .012 .011

148
MS 930:1986

Appendix G

Sizing of venting systems serving appliance equipped with

draft hoods and appliance listed for use with type B vents

VENT CAP

Figure 20. Double wall or asbestos Figure 21. Masonry chimney


cement type B vents or single-wall serving a single appliance
metal vents serving a single (See table 41)
appliance (See tables 39 and 40)

NOTE 42. Single appliance vents. (See tables 39. 40 and 41)

(a) For single-wall metal pipe, use table 40. -

(b) If the vent size determined from the tables is less than the size of the draft hood, the smallersized vent may
be used as long as the vent height H’ is at least 10 feet.

Id Vents for draft hoods 12 inches in diameter or less should not be reduced more than one size (12 inches to
10 inches is a one-size reduction). For larger fuel-gas burning equipment, reductions of more than two
sizes (24 inches to 20 inches is a two-size reduction) are not recommended.

(d) Regardless of the vent size shown, do not connect any 4-inch draft hoods to 3-inch vents.

(e) ZerofO) lateral ‘L’ applies only to a straight vertical vent attached to a top outlet draft hood.

(f( Use sea level input rating when calculating vent size for high altitude installation.

(g) Designation NR’ in tables 39. 40 and 41 indicates not recommended.

(h) Number followed by an asterisk)’) in tables 40 and 41 indicates the possibility ofcontinuous condensation.
depending on locality. Consult local serving gas supplier and/or local codes.

149
MS 930:1986

Table 39. Capacity of type B double-wall vents with type B double-wall connectors
serving a single appliance
- (See fig. 20 and note 42) -

Vent diameter, D
Height Lateral
H L 3” 4” 5” 6” 7” 8” 10” 12” 14” 16” 18” 20” 22” - 24”
Maximum appliance input rating in thousands of Btu per hour

0 46 86 141 205 285 370 570 850 1170 1530 1960 2430 2950 3520
6’ 2’
6’ 36
32 67
61 105
100 157
149 217
205 285
273 455
435 650
630 890
870 1170
1150 1489
1470 1850
1820 2220
2210 2670
2650
12’ 28 55 91 137 190 255 406 610 840 1110 1430 1795 2180 2600
0 50 94 155 235 320 415 660 970 1320 1740 2220 2750 3360 4010
8’ 2’ 40 75 120 180 247 322 515 745 1020 1340 1700 2110 2560 3050
8’ 35 66 109 165 227 303 490 720 1000 1320 1670 2070 2530 3030
16’ 28 58 96 148 206 281 458 685 950 1260 1600 2035 2470 2960
0 53 100 166 255 345 450 720 1060 1450 1925 2450 3050 3710 4450
10’ 2’ 42 81 129 195 273 355 560 850 1130 1480 1890 2340 2840 3390
10’ 36 70 115 175 245 330 525 795 1080 1430 1840 2280 2780 3340
20’ NR 60 100 154 217 300 486 735 1030 1360 1780 2230 2720 3250

0 - 58 112 187 285 390 525 840 1240 1720 2270 2900 3620 U1O 5300
15’ 2’ -48 93 150 225 316 414 675 985 1,350 1770 2260 2800 3410 4080
~5’ 37 76 128 198 275 373 610 905 1250 1675 2150 2700 3300 3980
30’ NR 60 107 169 243 328 553 8.45 11~0 1550 2050 2620 3210 3840
0 61 119 202 307 430 575 930 1350 1900 2520 3250 4060 4980 6000
2’ 51 100 166 249 346 470 755 1100 1520 2000 2570 3200 3910 4700
20’ 10’ 44 89 150 228 321 4-43 710 10.45 1460 1940 2500 3130 3830 4600
20’ 35 78 134 206 295 410 665 990 1390 1880 2430 3050 3760 4550
30’ NR 68 120 186 273 380 626 945 1270 1700 2330 2980 3650 4390
0 64 128 220 336 475 650 1060 1550 2170 2920 3770 4750 5850 7060
2’ 56 112 185 280 394 535 865 1310 1800 2380 3050 3810 4650 5600
30 20’ NR 90 154 237 343 473 784 1185 1650 2200 2870 3650 4480 5310
40’ NR NR NR 200 298 415 705 1075 1520 2060 - 2700 3480 4270 5140
0 66 132 228 353 500 685 1140 1730 2400 3230 4180 5270 6500 7860
2’ 59 118 198 298 420 579 960 1420 2000 2660 3420 4300 5260 6320
40 20’ NR 96 167 261 377 516 860 1310 1830 2460 3200 4050 5000 6070
40’ NR NR NR 223 333 460 785 1205 1710 2310 3020 3840 4780 5820
0 NR 136 236 373 535 730 1250 1920 2700 3650 4740 6000 7380 9000
2’ NR 125 213 330 470 650 1060 1605 2250 3020 3920 4960 6130 7400
60 30’ NR NR 170 275 397 555 930 1440 2050 2780 3640 4700 5730 7000
60’ NR NR NR NR 334 475 830 1285 1870 2560 3380 4330 5420 6600
0 NR NR 239 384 550 755 1290 2020 2880 3900 5100 6450 8000 9750
2’ NR NR 217 350 495 683 1145 1740 2460 3320 4310 5450 6740 8200
80 40’ NR NR NR 275 404 570 980 1515 2180 2980 3920 5000 6270 7650
80’ NR NR NR NR NR NR 850 1420 2000 2750 3640 4680 5850 7200
0 NR NR NR 400 560 770 1310 2050 2950 4050 5300 6700 8600 10300
~, 2’ NR NR NR 375 510 700 1170 1820 2550 3500 4600 5800 7200 8800
50’ NR NR Ng NR .405 575 1000 1550 2250 3100 4050 5300 6600 8100
100’ NR NR NR NR NR NR 870 1430 2050 2850 3750 4900 6100 7500

150
Table 40. Capacity of single-wall metal pipe or type B Table 41. Capacity of masonry chimneys and single-wall
asbestos cement vents serving a single appliance vent connectors serving a single appliance
(See fig. 21 and note 42) (See fig. 21, table 45 and note 42)
Vent diameter, D Single-wall vent connector diameter, D

To be used with chimney areas not less than


I-bight Latera! ~“ ~“ 5” 6” 7” 8” 10” 12” those at bottom

Maximum appliance input rating in thousands of Height Lateral 3” 4” 5” 6” 7” 8” 10” 12”


Stu per hour H L
Maximum appliance input rating in thousands of
Stu per hour -
0 39 70 116 170 232 312 500 750
6’ 2’ 31 55 94 141 194 260 415 620
5’ 28 51 88 128 177 242 390 600 2’ 28 52 86 130 180 247 400 580
6 5’ 25* 48 81 - 118 16-4 230 375 560
0 42 76 126 185 252 340 542 815
2’ 32 61 102 154 210 284 451 680
5’ 29 56 95 141 194 26-4 430 548 2’ 29 55 93 145 197 265 4-45 650
10’ 24* 49 86 131 180 250 406 625 8’ 5’ 26’ 51 87 133 182 246 422 638
10’ 22* 44’ 79 123 169 233 400 598
0 -45 84 138 202 279 372 606 912
2’ 35 67 111 168 233 311 505 760 2’ 31 61 102 161 220 297 490 722
10’ 5’ 32 61 104 153 215 289 480 724 10’ 5’ 28’ 56 95 147 203 276 465 710
10’ 27* 54 94 143 200 274 455 700 10’ 24’ 49’ 86 137 189 261 441 665
15’ NP 46* 84 130 186 258 .432 666 15’ NP 42* 79’ 125 175 246 421 634

o 49 91 151 223 312 420 684 1040 2’ 35’ 67 113 178 249 - 335 560 840
2’ 39 72 122 186 260 350 570 865 5’ 32’ 61 106 163 230 312 531 825
5’ 35* 67 110 170 240 325 540 825 15’ 10’ 27’ 54’ 96 151 214 294 504 774
10’ 30’ 58’ 103 158 223 308 514 795 15’ NR 46’ 87’ 138 198 278 481 738
15’ NR 50* 93’ 144 207 291 488 760 20’ NP NP 73* 128’ 184 261 459 706
20’ NR NP 82* 132* 195 273 466 726
2’ 38’ 73 123 200 273 374 625 950
0 53’ 101 163 252 342 470 770 1190 5’ 35’ 67’ 115 183 252 348 594 930
2’ 42* 80 136 210 286 392 641 990 20’ 10’ NR 59’ 105’ 170 235 330 562 875
5’ 38’ 74* 123 192 264 364 610 945 15’ NR NR 95’ 156 217 311 536 835
10’ 32* 65* 115* 178 246 345 571 910 20’ NR NP 80’ 144’ 202 292 510 800
15’ NP 55’ 104* 163 228 326 550 870
2’ 41’ 81’ 136 215 302 420 715 1110
20’ -NP NR 91* 149* 214* 306 525 832
5’ NP 75’ 127’ 196 279 391 680 1090
0 56’ 108* 183 276 384 529 878 1370 10’ NP 66’ 113’ 182’ 260 370 64-4 1020
2’ 44’ 84’ 148* 230 320 441 730 1140 15’ NP NP 105* 168’ 240’ 349 615 975
5’ NR 78* 137* 210 296 410 694 1080 20’ NR NR 88’ 155’ 223’ 327 585 932
30’ 10’ NR 68* 125* 196* 274 388 656 1050 30’ NP NP NR NR 182’ 281’ 54-4 865
15’ NR NP 113* 177* 258* 366 625 1000
20’ NP NR 99’ 163* 240* 344 596 960 2’ NP 91’ 160’ 250’ 35(3* 475 810 1240
30’ NR NP NP NR 192* 295* 540 890 5’ NR NR 149’ .228’ 321* 4.42 770 1220
10’ NR NR 136’ 212’ 301’ 420’ 728 1140 ci)
0 NR 120* 210* 310* 443’ 590 980 1550 15’ NR NR 124’ )95* 278* 395’ 695 1090 (0
2’ NR 95* 171* 260’ 370* 492 820 1290 20’ NP NP NP 180’ 258’ 370* 660’ 1040 (A)
5’ NR NP 159* 234* 342* 474 780 1230 30’ NP NP NP NP NR 318’ 610’ 970 0
50’ 10’ NP NP 146* 221* 318* 456* 730 1190
15’ NP NR NP 200* 292* 407’ 705 1130 Minimum internal
(0
-‘a 20’ NP NP NP 185* 276* 384* 670’ 1080 area of chimney, A 19 28 38 50 63 95 132 03
01 30’ NR NP NP NP 222* 33Q* 605’ 1010 - square inches C)
-a
MS 930: 1986

Total vent height “H”


Total vent height “H”

Figure 22. Double-wall or


asbestos cement type B vents Figure 23. Masonry chimney
or single-wall metal vents serving two or more appliances
serving two or more (See table 44)
appliances (See table 42 and 43)

NOTE 43. Multiple appliance vents. (See tables 42. 43 and 44.)

(a) For single-wall metal pipe connectors, use table 43.

(b) Maximum vent connector length: 1½ feet for every inch of connector diameter. Greater lengths require
increase in size, rise or total vent height. to obtain full capacity.

Ic) Each 90-degree turn in excess of the first two reduces the connector capacity by 10 per cent.

(dl Each 90-degree turn in the common vent reduces capacity by 10 per cent.

)e) Where possible, locate vent closer to or directly over smaller appliance connector. - -

)f) Connectors must be equal to or larger than draft hood outlets.

(g) If both connectors are same size, common vent must be at least one size larger, regardless of tabulated
capacity.

(h) Common vent must be equal to or larger than largest connector..

(I) Interconnection fittings must be same size as common vent.

1k) Use sea level input rating when calculating vent size for high altitude installation.

(ml Designation NA’ in tables 42. 43 and 44 indicates not recommended.

Table 42. Capacity of type B double-wall vents with type B


double-wall connectors serving two or more appliances
Vent connector capacity (See fig. 22 and note 43)
Common vent diameier
Total vent - . -

height 3” I 4” 5” 6~’ 7” 8” 10” 12”I 14”I 16” 18” 20” 22” 24”
H
Combined appliance input rating in thousands of Btu per hour

6’ — 65 103 147 200 260 410 588 815 1065 13-45 1660 1970 2390
8’ — 73 114 163 223 290 465 652 - 912 1190 1510 1860 2200 2680
10’ — 79 124 178 242 315 495 712 995 1300 1645 2030 2400 2920
15’ — 91 14.4 206 280 365 565 825 1158 1510 1910 2360 2790 3400
20’ — 102 160 229 310 405 640 916 1290 1690 2140 2640 3120 3800
30’ — 118 185 266 360 470 740 1025 1525 1990 2520 3110 3680 4480
40’ — 131 203 295 405 525 820 1180 1715 2240 2830 3500 4150 5050
60’ — NP 224 324 440 575 900 1380 2010 2620 3320 4100 4850 5900
80’ — NP NP 344 468 610 955 1540 2250 2930 3710 4590 5420 6600
~00’ — NR NP NP 479 625 975 1670 2450 3200 4050 5000 5920 7200

152
Table 42. Capacity of type B double-wall vents with type B
double-wall connectors serving two or more appliances
(See fig. 22 and note 43)

Vent connector capacity

Total Vent connector diameter, 0


vent Connector - -

height rise ~“ ~“ 6” 7” 8” 10” 12” 14” 16” 18”


~“ 20” 122” 24”
Maximum appliance input-rating in thousands of Btu per hour

1’ 26 46 72 10.4 142 185 289 416 - 577 755 955 1180 1425 1700
6’ 2’ 31 55 86 124 168 220 345 496 653 853 1080 1335 1610 1920
3’ 35 62 96 139 - 189 248 386 - 556 740 967 1225 1510 1830 2180

1’ 27 48 76 109 148 194 303 439 601 805 1015 1255 1520 1810
8’ 2’ 32 57 90 129 175 230 358 516 696 910 1150 1420 1720 2050
3’ 36 64 101 145 198 258 402 580 790 1030 1305 1610 1950 2320

1’ 28 50 78 113 154 200 314 452 642 840 1060 1310 1585 1890
10’ 2’ 33 59 93 134 182 238 372 536 730 955 1205 1490 1800 2150
3’ 37 67 10.4 150 205 268 417 600 827 1080 1370 1690 2040 2430
1’ 30 53 83 120 163 214 333 480 697 910 1150 1420 1720 20.50
15’ 2’ 35 63 99 142 193 253 394 568 790 1030 1305 1610 1950 2320
3’ 40 71 111 160 218 286 444 640 898 1175 1485 1835 2220 2640
1’ 31 56 87 125 171 224 347 500 740 965 1225 1510 ‘1830 2190
20’ 2’ 37 66 104 149 202 265 414 596 840 1095 1385 1710 2070 - 2470
3’ 42 74 116 168 228 300 466 672 952 1245 1575 1945 2350 2800
1’ 33 59 93 134 182 238 372 536 805 1050 1330 1645 1990 2370
30’ 2’ 39 70 110 158 215 282 439 632 910 1190 1500 1855 2240 2670
3’ 44 79 124 178 242 317 494 712 1035 1350 1710 2110 2550 3040
1’ 35 62 97 140 190 248 389 560 850 1110 1405 1735 2100 2500
40’ 2’ 41 73 115 166 225 295 461 665 964 1260 1590 1965 2380 2830
3’ 46 83 129 187 253 331 520 748 1100 1435 1820 2240 2710 3230

60’ ~ 1’ 37 66 104 150 20-4 266 417 600 926 1210 - 1530 1890 2280 2720
2’ 44 - 79 123 178 242 316 494 712 1050 1370 1740 2150 2590 3090 (1)
3’ 50 89 138 200 272 355 555 800 1198 1565 1980 2450 2960 3520 (0
(A)

,(0
.‘a 03
U’ C)
MS 930:1986

Gi. GENERAL column to 1 5-feet and read across 2-foot


connector rise ‘R’ line. Note 5-inch vent size
The units expressed herein for the data tables and shows 99,000 Btu per hour or less than furnace
computation of sizing of venting systems are in input. However, with 20-foot total height read
the imperial unIts. The data obtained in the across 2-foot connector rise line. Note 5-inch
imperial units are operational data values, and vent size shows 1 04.000 Btu per hour. Since
consequently for convenience of computation of 1 8-foot height is 3/5 of difference between 1 5—
sizing venting systems the imperial units would and 20— foot heights. take difference between
be used, until such time when metric data 99,000 and 104,000 or 5,000 and add 3/5 of
becomes available, this to 15-foot figure of 99.000. 99,000

+ ,5” Common vent


145,000 total
18” input

- Figure 24. Example of multiple vent-design


using table 42 double-wall type B vent

G2. EXAMPLE + 3,000 = 102.000 which is maximum inputfor


1 8-foot total vent height. Therefore a 5-inch
Connect a 45,000 Btu water heater with a 1-foot connector would be the correct size for the
connector rise ‘R’ and a 100,000 Btu furnace with furnace, providing the furnace had a 5-inch or
a 2-feet, connector rise’R’to acommonventwith smaller draft hood outlet,
a minimum total vent height ‘H’ of 18 feet.
G2.3 Common vent size. Total input to
G2.1 Water heater vent connector size. Using common vent is 1 45.000 Btu. Note that for
table 42, read down total vent height ‘H’ column 1 5-foot total vent height ‘H’ maximum Btu for
to 1 5-feet and read across 1 -foot connector rise 5-inch vent is 1 44,000. For 20-foot total vent
‘R’ line to Btu rating equal to or higher than water height ‘H’ maximum Btu for 5-inch vent is
heater input rating. This figureshows 53,000 Btu 1 60.000.
and is in the column for 4-inch connector. Since
this is in excess of the water heater Input it is not Therefore for 1 8-foot total vent height maximum
necessary to find the maximum input for an allowable -input would be 3/5 of difference
1 8-foot minimum total vent height. Use a 4-inch between 144,000 and 160.000 = 3/5 X

con nector. 16.000 or 9.600; 144,000 + 9,600 =


1 53,600 which is greater than total input to
G2.2 Furnace vent connector size. Under vent common vent, Therefore common vent can be
connector tables read down total vent height ‘H’ 5-inch-diameter pipe.

154
Table 43. Capacity of a single-wall metal pipe of type B Table 44. Capacity of a masonry chimney and single-wall vent
asbestos cement vent serving two or more appliances connectors serving two or more appliances
(See fig. 22 and note 43) (See fig. 23, note 43 and table 45)

Vent connector capacity Single-wall connector capacity

Vent connector diameter, 0 Vent connector diameter, D

Total vent Rise


Total vent Connector 3” 4” 5” 6” 7” 8” height connector 3” 4” 5” 6” ~ 8”
height rise ‘H’ ‘R’
H R
Maximum appliance input rating in thousands Maximum appliance input rating in
of Btu per hour thousands of Btu per hour

1’ 21 40 68 102 146 205 1’ 21 39 66 100 140 200


6’-8’ 2’ 28 53 86 124 178 235 6’-V 2’ 28 52 84 123 172 231
3’ 34 61 98 147 204 275 3’ 34 61 97 142 202 269

1’ 23 44 77 117 179 240 1’ 23 43 73 112 171 225


15’ 2’ 30 56 - 92 134 194 265 15’ 2’ 30 54 88 132 189 256
3’ 35 64 102 155 216 298 3’ 34 63 101 151 213 289

1’ 25 49 8-4 129 190 270 I’ 24 47 80 124 183 250


2’ 31 58 97 145 211 295 31 57 93 142 205 282
. up 2’ -

36 68 107 164 232 321 p 35 65 105 160 229 312

Common vent capacity Common chimney capacity

Minimum internal area of chimney,


‘A’ square inches
Common vent diameter To~~~gv~efflt
Total vent 19 28 38 50 78 113
height 4” 5” 6” 7” 8” 10” 12”
‘H Combined appliance input rating in Combined appliance input rating in
thousands of Btu per hour thousands of Btu per hour

6’ 48 78 111 155 205 320 HR 6’ 45 71 102 142 245 HR Cr)


8’ 55 89 128 175 234 365 505 8’ 52 61 118 162 277 405 (0
10’ 59 95 136 190 250 395 560 10’ 56 89 129 175 300 450 ‘(A)
0
15’ 7) 115 168 228 305 480 690 15’ 66 105 150 210 360 540
20’ 80 129 186 260 340 550 790 20’ 74 120 170 240 415 6.40 (0
30’ HR 147 215 300 400 650 940 30’ NR 135 195 275 490 740 03
01 50’ HR NP NR 360 - 490 810 1190 50’ HR HR NP 325 60O 910 C)
01
MS 930:1986

Table 45. Masonry chimney liner dimensions with circular


equivalents

Nominal Inside dimensions Inside diameter Equivalent


liner size of liner in or equivalent area square
inches inches diameter inches inches

4x8 21/2x6Y2 4 12.2


5 19.6
6 28.3
7 38.3
3
8x8 634x6 / 7.4 42.7
4
8 50.3
1
8x12 6’/2x10 /2 9 63.6
10 78.5

12 x 12 934 x 93/4 10.4 83.3


11 95
12 x 16 ‘ 9’/~x 13’/2 11.8 107.5
12 113.0
14 153.9
16 x 16 131/4 x 131/4 14.5 162.9
15 176.7
16 x 20 13 x 17 16.2 206.1
18 2544
20 x 20 1634 x 163/4 18.2 2602
20 314.1
20 x 24 16’/2 x 20’/2 20.1 314.2
22 380.1
24 x 24 20¼ x 20¼ 22.1 380.1
- 24 452.3
24 x 28 20~/4x 24¼ 24.1 456.2 ,

28 x 28 2411+ X 241/4 26.4 543.3


27 572.5
30 x 30 25~ x 25~ 27.9 607
2 2
30 706.8
30 x 36 25’/2 x 31’/2 30.9 749.9
33 855.3
36 x 36 - 31’/2 x 31’/2 344 929.4
36 1017.9

NOTE 44. When liner sizes differ dimensionally from those shown in table 45. equivalentdiameters
may be determined from published tables for square and rectangular ducts of equivalent carrying
capacity or by other engineering methods.

156
MS 930: 1986

Appendix H

Recommended procedure for safety inspection of an existing


-appliance installation

Hi. The following procedure is intended as a H2.3 Shut off all gas to the appliance and shut
guide to aid in determining that an appliance is off any other fuel-gas burning appliance within
properly installed and is in a safe condition for the same room. Use the shutoff valve in the supply
continuing use. line to each appliance.

This procedure is predicated on central furnace H2.4 Inspect burners and crossovers for
and -boiler installations, and it should be blockage and corrosion.
recognized that generalized procedure cannot
anticipate all situations. Accordingly. in some H2.5 Applicable only to furnaces. Inspect heat
cases deviation from this procedure may be exchanger for cracks, openings. or excessive
necessary to determine safe operation of the corrosion.
equipment:
H2.6 Applicable only to boilers. Inspect for
(a) This procedure should be performed prior to evidence of water or combustion product leaks.
any attempt at modification of the appliance or of
the installation, H2.7 Insofar as is practical, close all building
doors and windows and all doors between the
(b). If it is determined there is a condition which space in which the appliance is located and other
could result in unsafe operation, the appliance spaces of the building. Turn on clothes dryers.
should be shut off and the owner advised of the Turn on any exhaust fans, such as range hoods
unsafe condition, and bathroom exhausts, so they will operate at
maximum speed. Close fireplace dampers. If.
after completing requirements of H2.7 through
H2. The following steps should be followed in H2.1 2 it is believed sufficient combustion air ~s
making the safety inspection: not available, refer to 5.3 of this Code for
guidance.
H2.i Conduct a gas leakage test of the
appliance piping and control system downstream H2.8 Place in operation the appliance being
of the shutoff valve in the supply line to the inspected. Follow the lighting instructions. Adjust
appliance. (See 5.5,4). thermostat so appliance will operate cont-
thermostat so appliance will operate con-
H2.2 Visually inspect the venting system for tinously.
proper size and horizontal pitch and determine
there is no blockage or restriction, leakage. H2.9 Determine that the pilot(s) is burning -

corrosion, and other deficiencies which could properly and that main burner ignition is
cause an unsafe condition. satisfactory by interrupting and reestablishing

157
MS 930:1986

the electrical supply to the appliance in any H2.13 Repeat H2.1O and H2.1 1 on the
convenient manner. Test the pilot safety device to appliance being inspected.
determine it is operating properly by
extinguishing the pilot burner(s) when the main H2.’14 Return doors, windows, exhaust fans.
burner(s) is off and determining, after 3 minutes, fireplace dampers, and any other fuel-gas
that the main burner gas does notfiowupon a call burning appliance to their previous conditionsfor
for heat. use.

H2.1O (a) Visually determine that main burner H2. 15 Applicable only to furnaces. C heck both
gas is burning properly: i.e. no floating, lifting or the limit control and the fan-control for proper
flashback. Adjust the primary air shutter(s) as operation. Limit control operation can be
required. checked by blocking the circulating air inlet or
temporarily disconnecting the electrical supplyto
(a) If appliance is equipped with high and ow the blower motor and determining that the limit
flame controlling or flame modulation, check for control acts to shut off the main burner gas.
proper main burner operation at low flame.
H2.16 Applicable only to boilers -

H2.11 Test for spillage at the draft hood relief


opening after 5 minutes of main burner (a) Determine that the water pumps are in
operation. Use a draft gauge. flame of a match or operating condition.

candle, or smoke from a cigarette. cigar. or pipe.


(b) Test low water cutoffs, automatic feed
H2.12 Turn on all other fuel-gas burning controls, pressure and temperature limit
appliances within the same room so that will controls, and relief valves in accordance with the
operate at their full inputs. Follow lighting manufacturer’s recommendations to determine
instructions for each appliance. they are in operating condition.

158
MS 930:1986

Appendix J
Recommended procedure for installing electrically operated
automatic vent damper devices on existing appliances

Ji. This procedure is intended as a guide to aid J2.4 Make certain wiring connections are tight
in safely installing an electrically operated and wires are positioned and secured so they will
automatic vent damper device on an existing not be able to contact high temperature
appliance. - locations.

This procedure is based on the assumption that


J2.5 When an additional automatic valve has
the history of the specific appliance has been one
been incorporated or an existing gas control
of safe and satisfactory operation.
replaced, conduct a gas leakage test of the
appliance piping and control system downstream
This procedure is predicated on central furnace.
of the shutoff valve in the supply line to the
boiler and water heater installations, and it
appliance.
should be recognized that generalized
procedures cannot anticipate all situations.
Accordingly, in sOme cases deviation from this J2.6 Visually inspect the modified venting
procedure may be necessary to determine safe system for proper horizontal pitch.
operation of the equipment.
J2.7 Check that the damper operates properly
and is properly sequenced with the appliance
J2-. The following steps should be followed in operating controls so that it opens when there is a
making the modifications: call for heat and closes when the appliance is in a
standby condition.
J2.1 Perform a safety inspection of the existing
appliance installation. See appendix H for a NOTE 45. If a boiler gas valve is sequenced by the aquastat.
determine that the damper opens prior to the opening of the gas valve.
recommended procedure for such a safety
inspection.
J2.8 Determine the amperage draw of the gas
J2.2 Shut off all gas and electricity to the control circuit and damper device.
appliance. To shut off gas use the shutoff valve in
the supply line to the appliance. (a) Check appliance transformer for adequate
capacity.
J2,3 Install the damper device in strict
accordance with the manufacturer’s installation (b) Check heat anticipator in comfort
instructions. Make certain the device is not thermostat to determine it is properly adjusted.
located in that portion of the venting system
which serves any appliance other than the one for J2.9 Sequence the appliance through at least
which ~hedamper is installed. three normal operating cycles.

159
MS 930:1986

J2.1O Insofar as is practical, close all building extinguishing the pilot burner(s) when the main
doors and windows and all doors between the burner(s) is off and determining, after 3 minutes,
space in which the appliance is located and other that the main burner gas does not flow upon a call
spaces of the building. Turn on clothes dr’~ers. for heat.
Turn on any exhaust fans, such as range hoods
and bathroom exhausts, so they will operate at J2. 15 Applicable only to furnaces. C heck both
maximum speed. Close fireplace dampers. the limit control and the fan control for proper
operation. Limit control operation can be
J2.1 1 Place appliance in operation. Follow the checked by blocking the circulating air inlet or
lighting instructions. Adjust thermostat
- so
temporarily disconnecting the electrical supplyto
appliance will operate continuously. the blower motor and determining that the limit
control acts to shut off the main burner gas.
J2.12 Test for spillage at the draft hood relief
opening after 5 minutes of main burner
operation. Use a draft gauge, flame of a match or J2.16 Applicable only to boilers -

candle, or smoke from a cigarette, cigar, or pipe.


(a) Determine that the water pumps are in
J2.13 (a) Visually determine that main burner operating condition.
gas is burning properly: i.e. no floating, lifting, or
fIashback~.Adjust the primary air shutter(s) as (b) Test low water cutoffs, automatic feed
required. controls, pressure and temperature limitcontrols
and relief valves in accordance with the
(b) If appliance is equipped with high and low manufacturer’s recommendations to determine
flame controlling or flame modulation, check for they are in operating condition.
proper main burner operation at low flame.
J2.17 Label the damper device (see 9.3) with
J2.14 Determine that the pilot(s) is burning
information as to:
properly and that main burner ignition is
satisfactory by interrupting and reestablishing (a) Name of qualified agency responsible for
the electrical supply to the appliance in any damper installation.
convenient manner. Test the pilot safety device to
determine it is operating properly by (b) Date of installation.

160
MS 930: 1986

Appendix K

Recommended procedure for installing mechanically actuated


automalic vent damper devices on existing appliances

K1. This procedure is intended as a guideto aid K2.4 Make certain wiring and mechanical
in safely installing a mechanically actuated connections are tight and wires are positioned
automatic vent damper device on an existing and secured so they will not be able to contact
appliance, high temperature locations. -

This procedure is based on the assumption that


K2.5 When an additional automatic valve has
the history of the specific appliance has been one
been incorporated or an existing gas control
of safe and satisfactory operation. -

replaced, conduct a gas leakage test of the


appliance piping and control system downstream
This procedure is predicated on central furnace,
of the shutoff valve in the supply line to the
boiler and water heater installations, and it
appliance.
should be recognized that generalized
procedures cannot anticipate all situations.
Accordingly. in some cases deviation from this K2.6 Visually lnspecL the modified venting
procedure may be necessary to determine safe system for proper horizontal pitch.
operation of the equipment.
K2.7 Check that the damper operates properly
and is properly sequenced with the appliance
K2. The following steps shoLld be followed in operatingóontrolssothatitopenswhenthereisa
making the modifications: call for heat and closes when the appliance is in a
standby condition.
K2. 1 Perform a safety inspection of the existing
appliance installation. See appendix H for a NOTE 46. If a boiler gas valve is sequenced by the aquastat.
recommended procedure for such a safety determine that the damper opens prior to the opening of the gasvalve.

inspection.
K2.8 Determine the amperage draw of the gas
K2.2 Shut off all gas and electricity to the control circuit and damper device.
appliance. To shut off gas use the shutoff valve in
the supply line to the appliance. (a) Check appliance transformer for adequate
cclty.
K2.3 Install the damper device in strict
accordance with the manufacturer’s installation (b) Check heat
anticipator in comfort
instructions. Make certain the device is not thermostat to determine it is properly adjusted.
located in that portion of the venting system
which serves any appliance other than the one for
K2.9 Sequence the appliance through at least
which the damper is installed.
three normal operating cycles.

161
MS 930 : 1986

K210 Insofar as is practical, close all building determine it is operating properly by


doors and windows and all doors between the extinguishing the pilot burner(s) when the main
space in which the appliance is located and other burner(s) is off and determining, after 3 minutes,
spaces of the building. Turn on clothes dryers. that the main burner gas does notflow upon a call
Turn on any exhaust fans, such as range hoods for heat.
and bathroom exhausts, so they will operate at
maximum speed. Close fireplace dampers. K2. 15 Applicable only to furnaces. Check both
the limit control and the fan control for proper
K2.11 Place appliance in operation. Follow the ~operation. Limit control operation can be
lighting instructions. Adjust thermostat so checked by blocking the circulating air inlet or
appliance will operate continuously. temporarily disconnecting the electrical supply to
the, blower motor and determining that the limit
K2.12 Test for spillage at the draft hood relief control acts to shut off the main burner gas.
opening after 5 minutes of main burner
operation. Use a draft gauge, flame of a match or K2.16 Applicable only to boilers
candle, or smoke from a cigarette. cigar. or pipe.
(a) Determine that the water pumps are in
K2.13 (a) Visually determine that main burner operating condition.
gas is burning properly: i.e. no floating. lifting, or
flashback.’ Adjust the primary air shutter(s) as (b) Test low water ‘cutoffs, automatic feed
required. controls. pressure and temperature limit controls
and relief valves in accordance with the
(b) If appliance is equipped with high and low manufacturer’s recommendations to determine
flame controlling or flame modulation, check for they are in operating condition.
pr,oper main burner operation at low flame.
K2.17 Label the damper device (see 9.3) with
1(2,14 Determine that the pilot(s) is burning information as to:
properly and that main burner ignition is
satisfactory by interrupting and reestablishing (a) Name of qualified agency responsible for
the electrical supply to the appliance in any damper installation.
convenient manner. Test the pilot safety device to (b) Date of installation.

162
MS 930:1986

Appendix L

- Recommended procedure for installing thermally actuated


automatic vent damper devices on existing appliances

Li. This procedure is intended as a guide to aid L2.4 Make certain wiring connections are tight
in safely installing a thermally actuated automatic and wires are positioned and secured so they will
ve,nt damper device on an existing appliance. not be able to contact high temperature
locations.
This procedure is based on the assumption that
the history of the specific appliance has been one L2.5 When an additional automatic valve has
of safe and satisfactory operation. been inco~poratedor an existing gas control
replaced, a gas leakage test of the appliance
This procedure is predicated on central furnace. piping and control system downstream of the
boiler and water heater installations, and it shutoff valve in the supply line to the appliance.
should be recognized that generalized
procedures cannot anticipate all situations. L2.6 Visually inspect the modified venting
Accordingly, in some cases deviation from this system for proper horizontal pitch.
procedure may be necessary to determine safe
operation of the equipment. L2.7 Check the installation to determine there is
no physical obstruction or deformation which
could impair damper operation.

L2.8 Determine the amperage draw of the gas


L2. The following steps should be followed in
control circuit and damper device.
making the modifications:
(a) Check appliance transformer for adequate
L2.1 Perform a safety inspection of the existIng
capacity.
appliance installation. See appendix H for a
recommended procedure for such a safety (b) Check heat anticipator in comfort
inspection. thermostat to determine it is properly adjusted.

L2.2 Shut off all gas and electricity to the L2.9 Sequence the appliance through at least
appliance. To shut off gas use the shutoff valve in three normal operating cycles.
the supply line to the appliance.
L2.10 Insofar as is practical. close all building
L2.3 Install the damper device in strict doors and windows and all doors between the
accordance with the manufacturer’s installation space in which the appliance is located and other
instructions. Make certain the device is not spaces of the building. Turn on clothes dryers.
located in that portion of the venting system Turn on any exhaust fans, such as range hoods
which serves any appliance other than the onefor and bathroom exhausts, so they will operate at
which the damper is installed. maximum speed. Close fireplace dampers.

163
MS 930: 1986

L2..1 1 Place appliance in operation. Follow the L2.14 Determine that the pilot(s) is burning
lighting instructions. Adjust thermostat so properly and that main burner ignition is ~
appliance will operate continuously. satisfactory by interrupting and reestablishing
the electrical supply to the appliance in any
L2.12 Test for spillage at the draft hood relief convenient manner. Test the pilot safety device to
opening after 5 minutes of main burner determine it is operating properly by
operation: Use a draft gauge, flame of a match or extinguishing the pilot burner(s) when the main
candle, or smoke from a cigarette. cigar, or pipe. burner(s) is off and determining, after 3 minu~s,
that the main burner gas does not flow upon ~
L2.13 (a) Visually determine that main burner for heat.
gas is burning properly: i.e. no floating, lifting, or
flashback. Adjust the primary air shutter(s) as L2.15 Label the damper device (see 9.3) with
required. information as to:

(a) Name of qualified agency responsible for


(b) If appliance is equipped with high and low
damper installation.
flame controlling or flame modulation, check for
proper main burner operation at low flame. (b) Date of installation.

164

4
TANDA-TANDA STANDARD SIRIM
Tanda-tanda Standard SIRIM seperti yang tertera di bawah adalah tanda-tanda pengesahan
dagangan berdaftar. Tanda-tanda ini hanya boleh digunakan oleh mereka yang dilesenkan
di bawah skim tanda pengesahan yang dijalankan oleh SIRIM mengikut nombor Standard
Malaysia yang berkaitan. Kewujudan tanda-tanda ini pada atau berkaitan dengan sesuatu
barangan adalah sebagai jaminan bahawa barangan tersebut telah dikeluarkan melalui satu
sistem penyeliaan, kawalan dan ujian, yang dijalankan semasa pengeluaran. Ini termasuk
pemeriksaan berkala kerja-kerja pengeluaran menurut skim tanda pengesahan SIRIM yang
dibentuk untuk menentukan bahawa barangan tersebut menepati Standard Malaysia.

Keterangan-keterangan lanjut mengenai syarat-syarat lesen boleh didapati dari:

Ketua Pengarah
Institut Standard dan Penyelidikan Perindustrian Malaysia
Persiaran Dato’ Menteri, Seksyen 2, Peti Surat 7035
40911 Shah Alam
Selangor Darul Ehsan

SIRIM STANDARD MARKS


The SIRIM standard marks shown above are registered certification trade marks. They may
be used only by those licensed under the certification marking scheme operated by SIRIM
and in conjunction with relevant Malaysian Standard number. The presence of these Marks
on or relation to a product is assurance that the goods have been produced under a system
of supervision, control and testing, operated during production, and including periodical
inspection of the producer’s works in accordance with the certification marking scheme of
SIRIM designed to ensure compliance with a Malaysian Standard.

Further particulars of the terms of license may be obtained from:

Director-General
Standards and Industrial Research Institute of Malaysia
Persiaran Dato’ Menteri, Section 2. P.O.Box 7035
40911 Shah Alam
Selangor Darul Ehsan

3
MS ISO/TR 9007 : 1993
INSTITUT STANDARD DAN PENYELIDIKAN PERINDUSTRIAN MALAYSIA

Institut Standard dan Penyelidikan Perindustrian Malaysia (SIRIM) telah ditubuhkan hasil dari cantuman Institut
Piawaian Malaysia (SIM) dengan Institut Negara bagi Penyelidikan Sains dan Perusahaan (NISIR) di bawah
Undang-Undang Malaysia Akta 157 pada 16hb. September 1975:Akta Institut Standard dan Penyelidikan
Perindustrian Malaysia (Perbadanan) 1975. Institut ini diletakhak dengan kuasa untuk memamju dan
menjalankan penyelidikan perindustrian dan untuk menyedia dan memajukan standard-standard bagi barangan-
barangan, proses-proses, amalan-amalan dan perkhidmatan-perkhidmatan; dan bagi mengadakan peruntukan
bagi perkara-perkara yang bersampingan atau berkaitan dengan maksud-maksud itu.

Satu daripada tugas-tugas Institut ini adalah menyediakan Standard-Standard Malaysia dalam bentuk
penentuan-penentuan bagi bahan-bahan, keluaran-keluaran, kaedah-kaedah ujian, kod-kod amalan yang
sempurna dan selamat, sistem penamaan dan lain-lain. Standard-Standard Malaysia disediakan oleh
jawatankuasa-jawatankuasa perwakilan yang menyelaras keupayaan pengilang dan kecekapan pengeluaran
dengan kehendak-kehendak yang munasabah dari pengguna. Ia menuju ke arah mencapai kesesuaian bagi
maksud, memudahkan pengeluaran dan pengedaran, kebolehsalingtukaran gantian dan pelbagai pilihan yang
mencukupi tanpa pembaziran.

Standard-Standard Malaysia disediakan hanya setelah penyiasatan yang lengkap menujukkan bahawa sesuatu
projek itu disahkan sebagai yang dikehendaki dan berpadanan dengan usaha yang terlibat. Hasil ini berasaskan
persetujuan sukarela dan memberi pertimbangan kepada kepentingan pengeluar dan pengguna. Standard-
Standard Malaysia adalah sukarela kecuali is dimestikan oleh badan-badan berkuasa melalui peraturan-
peraturan, undang-undang persekutuan dan tempatan atau cara-cara lain yang sepertinya.

Institut ini beroperasi semata-mata berasaskan tanpa keuntungan. Ia adalah satu badan yang menerima bantuan
kewangan dari Kerajaan, kumpulan wang dari bayaran keahlian, hasil dari jualan Standard-Standard dan
terbitan-terbitan lain, bayaran-bayaran ujian dan bayaran-bayaran lesen untuk mengguna Tanda Pengesahan
SIRIM dan kegiatan-kegiatan lain yang berhubung dengan Penstandardan, Penyelidikan Perindustrian dan
Khidmat Perunding.

STANDARDS AND INDUSTRIAL RESEARCH INSTITUTE OF MALAYSIA

The Standard and Industrial research Institute of Malaysia (SIRIM) is established with the merger of the
Standards Institution of Malaysia (SIM) and the National Institute for Scientific and Industrial Research (NISIR)
th
under the Laws of Malaysia Act 157 on 16 . September 1975: Standards and Industrial Research Institute of
Malaysia (Incorporation) Act 1975. The Institute is vested with the power to provide for the promotion and
undertaking of industrial research and for the preparation and promotion of standards for commodities,
processes, practices and services; and to provide for matters incidental to or connected with those purposes.

One of the functions of the Institute is to prepare Malaysian Standards in the form of specifications for materials
and products, methods of testing, codes of sound and safe practice, nomenclature, etc. Malaysian Standards are
prepared by representative committees which co-ordinate manufacturing capacity and production efficiency with
the user’s reasonable needs. They seek to achieve fitness for purpose, simplified production and distribution
replacement interchangeability, and adequate variety of choice without wasteful diversify.

Malaysian Standards are prepared only after a full enquiry has shown that the project is endorsed as a desirable
one and worth the effort involved. The work is based on voluntary agreement, and recognition of the community
of interest of producer and consumer. The use of Malaysian Standards is voluntary except in so far as they are
made mandatory by statutory authorities by means of regulations, federal and local by-laws or any other similar
ways.

The Institute operates entirely on a non-profits basis. It is a grant aided body receiving financial aid from the
Government, funds from membership subscriptions and proceeds from sales of Standards and other
publications, fees and licence fees for the use of SIRIM Certification Mark and other activities associated with
Standardization, Industrial Research and Consultancy Services.

You might also like