EL. 0.0 M
NWL 0.5
EL. -0.8 M
Min.WL 0.5
EL. -1.3 M
0.5
EL. -1.8 M Stoplog gate
NWL 0.50
INDUCED DRAFT COOLING TOWER BASIN L = 304 EL. -0.826
Min.WL
0.50 EL. -1.326
4.15
5.37
CW PUMP SUMP
NWL
EL. -0.826
Min.WL 0.0
EL. -1.326
1.36
1.79
2.8979 =B Y = 12.07
A = 14.81
Screen
A = 14.81
2.8979 =B
Y = 12.07
Min.Water Level
Page 2
4.15 =S Pump Sump_CW Stopgate
system
Page 3
Pump Sump_ACW system
PUMP INSTALLATION DIAGRAM ( ALL DIMENSION ARE IN M)
Q = PUMP CAPACITY = 2970 M3/HR
0.7526 =B Y = 3.80
A = 4.56
Screen
A = 4.56
0.7526 =B
Y = 3.80
Min.Water Level
Page 4
1.36 =S Pump Sump_ACWStopgate
system
Page 5
Flow through CW channel to CW & ACW pump sump
For gravity flow in open channel , Mannings Formula has been used
Where, V = Velocity
n = Constant ( assumed for concrete channel)
R = Hydraulic Radius = Area/ Wetted perimeter
=by/(b+2y) (b = width, y = depth)
Ha = Energy Gradient b=
= ha/L, where ha = head difference & L = channel length
Calculation:
Hence, R = 1.14 m
= 3.7534492074 ft
and Ha = 0.0001411528
Therefore, ha = 0.0118568321 m
Inputs:
V = 3.28 ft/s
= 1 m/s
L = 94 m
n = 0.013
b/y = 1.5/1 Hence, b = 1.5 y
Maximum flow of CW & ACW in one CT (Q) = 77000 m3/hr
Hence, R = 1.62 m
= 5.3081787748 ft
and Ha = 8.8920668E-05
Therefore, ha = 0.0083585428 m
Inputs:
V = 3.28 ft/s
= 1 m/s
L = 36 m
n = 0.013
b/y = 1.5/1 Hence, b = 1.5 y
Hence, R = 1.98 m
= 6.5011647308 ft
and Ha = 6.785917E-05
Therefore, ha = 0.0024429301 m
Inputs:
V = 3.28 ft/s
= 1 m/s
L = 60 m
n = 0.013
b/y = 1.5/1 Hence, b = 1.5 y
Hence, R = 2.29 m
= 7.5068984148 ft
and Ha = 5.6016511E-05
Therefore, ha = 0.0033609907 m
ft