You are on page 1of 9

THE DOGBONE

CONNECTION: PART II
Selectively trimming a portion of a beam allows
connection strength to exceed beam strength without
the need to develop a stronger connection
By Michael D. Engelhardt, case, however, the connection is
Ted Winneberger, Andrew J. made stronger than the beam
Zekany and Timothy J. not by increasing the strength of
Potyraj the connection, but rather by
decreasing the strength of the

S
INCE THE 1994 NORTHRIDGE beam. The dogbone can be
EARTHQUAKE, INTENSIVE viewed as a ductile fuse. It forces
RESEARCH AND TESTING yielding to occur within the
EFFORTS have been underway to reduced section of the beam, an
find better methods to design area that can sustain large
and construct seismic resistant inelastic strains. At the same
steel moment connections. A Figure 1: Typical “dogbones” time, the dogbone acts as a fuse,
wide variety of solutions have limiting stress at the less ductile
been proposed over the last two region near the face of the col-
years, many of which have ated states of triaxial tension, umn. Previous work has been
shown greatly improved perfor- etc. The reinforcement reduces conducted on the constant cut
mance in the laboratory com- stress levels within this vulnera- and tapered cut dogbone shapes
pared to the previous “Pre- ble region near the column face, shown in Figure 1. In the case of
Northridge” connection. The and forces the large stresses and the tapered cut, the taper is
overall goal in the development inelastic strains further into the intended to follow the moment
of new connections is to provide beam. Reinforcing the connec- diagram in order to promote uni-
highly ductile response, reliable tion, however, increases its cost. form yielding over the full length
performance, and economy. Further, if excessive reinforce- of the dogbone.
Many of the new moment con- ment is used, new problems can At first glance, it may seem
nections combine improvements be created resulting from the counterintuitive that removing a
in welding with some type of need for very large welds with portion of a structure actually
reinforcement at the connection high shrinkage, and higher improves the performance of the
(cover plates, ribs, haunches, degrees of restraint and triaxial structure. In the case of the dog-
side plates, etc.). The purpose of tension. bone, however, this is exactly the
the reinforcement, in the most An alternative to reinforcing a case! The dogbone results in only
general terms, is to provide a moment connection that provides a small reduction in lateral
connection that is stronger than benefits similar to reinforce- strength and stiffness of a frame
the beam. A strong earthquake ment, but may avoid some of the but can provide a large increase
would be expected to develop disadvantages, is the “dogbone” in ductility, the key to survival of
plastic hinges at the beam ends moment connection. A distin- a structure in a strong earth-
in a traditional fully restrained guishing feature of the dogbone, quake. Trading a small amount
(FR) moment frame. The rein- also known as the Reduced of strength in return for a large
forcement is intended to force Beam Section (RBS) connection, amount of ductility represents
the plastic hinge away from the is that portions of the beam an excellent bargain for earth-
face of the column, where prema- flange are trimmed away in the quake resistant design.
ture fractures can occur due to region adjacent to the beam-to- The size of moment frame
potential weld defects, stress column connection (Figure 1). beams is normally controlled by
concentrations at weld access Various shape cutouts are possi- code-mandated drift limitations
holes, stress concentrations due ble. The result is similar to rein- rather than by code strength
to column flange bending, high forcement, i.e., the connection is requirements. The dogbone gen-
levels of restraint and the associ- stronger than the beam. In this erally results in only a slight

Modern Steel Construction / August 1996


E I N
S M C DE S
I S I G
decrease in frame stiffness.
Consequently, in many practical
cases, the use of the dogbone will
likely not necessitate a change of
beam size in order to meet code
strength and stiffness require-
ments.
A significant amount of
research and full scale testing
has already been done on the
dogbone concept. An article by
Nestor R. Iwankiw, P.E., and
Charles J. Carter in the April
1996 Modern Steel Construction
summarized some of the recent
testing. Early work was conduct-
ed by S.J. Chen and C.H. Yeh in
Taiwan, and by A. Plumier in
Figure 2 (above): Typical floor
Belgium. More recently, addi-
framing plan
tional work has been conducted
by AISC at Smith-Emery
Figure 3 (left): 3D view of lateral
Company in Los Angeles, and by
framing members
Ove-Arup & Partners working
with the University of California
at San Diego. This previous
research, conducted on either
constant cut or tapered cut dog-
bones (Figure 1) has shown very
promising performance. Typ-
ically, large plastic rotations
have been obtained. In a few
cases, fractures developed during
testing, either at the beam
flange to column connection or
within the dogbone, but only
after large levels of plastic rota-
tion were achieved.
Based on the earlier laborato-
ry successes of the dogbone, this
concept was recently applied to a steel moment frames as its pri- and typical office space. The
25-story steel office building in mary lateral force resisting sys- office space is designed for maxi-
Salt Lake City. In applying this tem. W&W Steel Company of mum flexibility and is pro-
concept, some further refine- Oklahoma City was responsible grammed to be an open space
ments were made to the dogbone for detailing, fabricating and plan layout, requiring 43-ft.-4-in.
approach and verified by full erecting the building’s 7,900 tons spans for the floor framing.
scale laboratory testing. The of structural steel. The floor framing was
remainder of this article The typical floor of the build- designed using composite steel
describes this building project, ing is triangular shaped in plan beams with 3 1/4-in. lightweight
and the associated connection (Figure 2). The plan measures concrete slabs over 3-in. compos-
testing program 302-ft. along the long face and ite deck. The AISC Load and
121-ft. along the width. A promi- Resistance Factor Design
AMERICAN STORES COMPANY nent feature of the plan is an Specification (LRFD) was uti-
HEADQUARTERS enclosed atrium on the west side lized in the design of the beams
When the American Stores of the building. The atrium con- and columns. ASTM A572 Gr. 50
Company and Howa sists of a series of individual steel was used for all members.
Construction Company decided four-story and two-story open The primary frames are locat-
to build the new American spaces that stack above each ed around the building perimeter
Stores Headquarters Building in other throughout the height of and around the elevator cores. A
Salt Lake City, HKS Inc. of the building. Surrounding the three dimensional perspective
Dallas designed a 25 story, atriums are the elevator cores illustration of the lateral fram-
650,000-sq.-ft. structure with and lobbies, conference rooms ing members is shown in Figure

Modern Steel Construction / August 1996


A test program with five
Table 1: Description of Test Specimens & Results large-scale specimens was
Spec. Column Beam Dogbone Plastic Comments undertaken to evaluate suitabili-
Type Rotation ty of the dogbone for use in the
DB1 W14x426 W36x160 Constant Cut 0.020 rad. Fracture at dogbone 2,000 moment connections of the
DB2 W14x426 W36x150 Radius Cut 0.030 rad. No conn. failure
American Stores Company
headquarters building. The spec-
DB3 W14x426 W36x170 Radius Cut 0.038 rad. No conn. failure
imens, designated DB1 to DB5
DB4 W14x426 W36x194 Radius Cut 0.037 rad. No. conn. failure are outlined in Table 1. The con-
DB5 W14x257 W30x148 Radius Cut 0.040 rad. No conn. failure; cept adopted for these specimens
signif. column panel was to combine the dogbone cut
zone participation in the beam, together with a
high quality welded beam-to-col-
umn connection at the face of the
Table 2: Beam Tensile Properties column. Both welding and design
improvements were incorporated
Spec. Beam Yield Stress (ksi) Tensile Strength (ksi)
into the beam-to-column connec-
Flange Web Flange Web tion to provide significantly
DB1 W36x160 54.7 53.5 75.6 79.2 improved capabilities compared
DB2 W36x150 41.4 47.1 58.7 61.8 to the Pre-Northridge type con-
DB3 W36x170 58.0 58.5 73.0 76.7 nection. With these improved
DB4 W36x194 38.5 43.6 58.6 59.8 connection capabilities, together
DB5 W30x148 46.6 48.5 64.5 65.4 with a reduced demand on the
connection due to the presence of
3. W36 and W40 frame column umn. This, in turn, increases the dogbone, the hope was for a
sizes were utilized to control stress levels at the face of the seismic resistant moment con-
drift. The building design called column, and negates some the nection system capable of devel-
for 1,000 moment resisting beneficial effects of forcing the oping large plastic rotations
frame beams, ranging in size plastic hinge away from the col- under severe cyclic loading con-
from W27x114 to W36x210. umn. ditions.
Located in UBC Seismic Zone Considering the options, the For the beam-to-column con-
3, earthquake safety was an dogbone emerged as the most nection at the face of the column,
important design concern for this cost effective solution for this each of the five specimens used
building. The design and con- project. Although the dogbone essentially the same detail. A
struction team was faced with already had a good track record typical detail is illustrated in
the challenge of developing a in earlier testing, Andy Zekany Figure 4. An all-welded connec-
moment resisting connection of HKS requested additional tion was used, in which the beam
that would perform as intended testing using representative W36 flanges and beam web were con-
by the UBC for a Special beams. These tests would permit nected to the column flange
Moment Resisting Frame. evaluation of details specific to using complete joint penetration
Working together with The this project, and help build confi- groove welds. It was believed
University of Texas at Austin, dence in the connection. that the welded web connection,
HKS and W&W Steel explored Remarkably, the decision was although somewhat more costly
several options, including rein- made to embark upon this test than a more conventional bolted
forced connections, bolted con- program after construction on web connection, would provide a
nections, and the dogbone con- the American Stores Company higher level of ductility. The
nection. Connection design was Headquarters had already begun welded web connection can
somewhat complicated by the on an extremely fast track sched- transfer significant moment
very short 17-ft. clear spans on ule. Stuart King with American from the beam to the column,
many of the building’s moment Stores and Rick Howa of Howa thereby reducing demands on
frame girders since connection Construction required the most the beam flange welds. The rela-
concepts that move the plastic effective and economical moment tively thin shear tab provided at
hinge away from the face of the connection available for seismic- the beam web connection serves
column are more difficult to resistant steel framing. Their to support the beam during erec-
implement on short spans. The consistent direction in meeting tion and also acts as backing for
high moment gradients associat- this goal and their support of the the beam web groove weld.
ed with short spans cause a large engineers’ recommendations led Testing done since the
amplification of moment from to the test program. Northridge Earthquake has
the point of plastic hinge forma- raised questions on previous
tion back to the face of the col- TEST PROGRAM design criteria for continuity
plates in seismic resistant

Modern Steel Construction / August 1996


E I N
S M C DE S
I S I G
moment connections. For this based on AWS D1.1-94, Specimen DB1 showed excellent
project, the decision was made to Structural Welding Code - Steel. performance in the initial inelas-
provide continuity plates at all Items emphasized for in process tic cycles. However, a fracture
connections, with the thickness inspection included checking the developed within the dogbone at
chosen to be comparable to the joint fit-up, preheat, and enforc- the end of the flat portion of the
beam flange thickness. For the ing the Welding Procedure cutout that was closest to the
test specimens, beam flange Specification (WPS) for the pro- face of the column. A stress con-
thickness ranged from 0.94 to ject. Ultrasonic testing was done centration resulting from the
1.26 in. One-in. thick continuity for the complete joint penetra- change of cross-section at this
plates were used for all speci- tion groove welds, with accep- point apparently contributed to
mens. tance criteria based on Table 8.2 this fracture. Despite this frac-
Welding at the beam-to-col- of AWS D1.1-94. ture, the specimen still sus-
umn connection was accom- The member sizes used for the tained 0.02 radian of plastic
plished by self-shielded flux- test specimens are listed in rotation. Further, there were no
cored arc welding process using Table 1. Each of the test speci- signs of distress anywhere with-
an electrode with a minimum men columns were A572 Gr. 50 in the beam-to-column connec-
specified Charpy V-Notch tough- steel. Four of the specimens used tion at the face of the column.
ness of 20 ft.-lbs. at -20 degrees W14x426 columns, taken from Although the first test did not
F. For the beam flange groove three different heats of steel. For meet full performance expecta-
welds, properly oriented weld the beam sections used in the tions, the results were still
runoff tabs were used, and then tests, mill certificates were not encouraging. It appeared that
removed after completion of the available. Tensile coupon tests achievement of the higher per-
weld. At the bottom flange were run on the beam sections, formance goal might be possible
groove weld, the backing bar was and the results are shown in by changing the shape or dimen-
removed, and a reinforcing fillet Table 2. Actual beam flange sions of the dogbone cutout to
weld was placed at the root of yield stresses varied from 38.5 reduce stress concentrations
the weld joint. Removing the ksi to 58 ksi. Consequently, a within this region. In order to
backing bar permits visual wide range of beam strengths provide a cutout region with
inspection of the weld root, mini- were represented in the test minimum stress concentrations
mizing the chance of undetected specimens. Member sizes in and one that would still be eco-
root defects, and eliminating any Specimens DB1 to DB4 were nomical to fabricate, the concept
possible notch effects of the selected to force virtually all of of a circular radius-cut dogbone
backing bar. the inelastic deformations into was suggested by Ted
The top flange backing bar the beam. Specimen DB5 was Winneberger of W&W Steel Co.
was left in place. There were sev- sized to encourage shear yielding This ultimately proved success-
eral reasons for this. First, root of the column panel zone, in ful in the testing program.
defects are less likely at the top order to evaluate its effects on The remaining four test speci-
flange since neither the groove the dogbone connection. mens were all constructed with a
weld nor the ultrasonic testing of radius-cut dogbone. Figure 5
the groove weld is interrupted by TEST RESULTS shows the shape and dimensions.
the beam web, as they are at the Testing was conducted at The The same all-welded beam-to-
bottom flange. Further, removal University of Texas Ferguson column connection described ear-
of the top flange backing bar is Laboratory. All tests were con- lier was used. A typical speci-
more difficult and costly than at ducted on single cantilever type men, DB4, is shown in Figure 4.
the bottom flange, since the arc- specimens, with cyclic loads Each of the four radius-cut
gouging must be done through applied to the tip of the beam fol- dogbone specimens (DB2 to DB5)
the weld access hole. lowing the loading protocol of showed excellent performance.
Consequently, for this project ATC-24. The goal of the test pro- The plastic rotations developed
the top backing bar was left in gram was to develop plastic rota- by each specimen at the end of
place. However, a continuous fil- tions of at least 0.03 radian, as the test are listed in Table 1. In
let weld was provided between suggested by the SAC Interim each case, testing was stopped as
the backing bar and the column Guidelines. a result of limitations in the test
flange (see Figure 4). From a The first specimen, DB1, com- equipment, rather than because
theoretical perspective, this fillet bined the all-welded connection of specimen failure. Conse-
weld reduces the potential notch described above with a constant quently, the specimens would
effect of a left in place backing cut dogbone (Figure 1(a)). have likely developed larger
bar. Previous successful tests had plastic rotations had the testing
For welding quality control, been run on both constant cut been continued.
both in-process inspection and and tapered cut dogbones. The At large plastic rotations, the
ultrasonic testing were specified. constant cut was elected for this beams of the test specimens typi-
Inspection and testing were first test. During testing, cally exhibited considerable

Modern Steel Construction / August 1996


twist that accompanied local
flange and web buckling in the
beam. This resulted in a gradual
reduction in flexural strength.
Testing was stopped in each case
to avoid damage to the test
equipment from this twisting. It
should be noted however that
the twisting experienced by
these dogbone specimens was no
more severe, and perhaps some-
what less severe, than reinforced
connections previously tested at
The University of Texas.
At the point at which testing
was stopped, no fractures had
developed within the dogbone
region for any of the radius-cut
specimens. Further no failures
occurred at the beam-to-column
connections. The connection on
Specimen DB3 showed small
cracks near the weld access holes
that developed during the cycles
at 0.02 radian. These small
cracks, however, did not grow
during the remainder of the test
and had no impact on the
response of the specimen. For
the remaining specimens, the
weld access holes were enlarged
and were provided with a
smoother transition to the beam
flange. The small cracks
observed in DB3 were not
observed in the remaining speci-
mens.
Figure 6 shows photos of
Specimen DB4 during testing.
Figure 6(a) is a view looking
down at the top beam flange at a
plastic rotation of 0.012 radian.
The darkened regions are areas
where the whitewash coating
has flaked off, providing a quali-
tative indication of where yield-
ing has occurred. This photo
Figure 4 (top): Test specimen DB4 shows yielding concentrated
within the dogbone region of the
Figure 5 (above): Radius cut dogbones beam, and indicates the connec-
tion was performing as intended.
Figure 6(b) shows the specimen
at plastic rotation of 0.022 radi-
an. Finally, Figure 6(c) shows
the specimen at a plastic rota-
tion of 0.037 radian, the point at
which testing was stopped.
As noted earlier, at large plas-
tic rotations the specimens
exhibited flange and web local
buckling within the plastic hinge

Modern Steel Construction / August 1996


E I N
S M C DE S
I S I G
Table 3: Cost Comparisons
Connection Type Relative
Cost
Pre-Northridge welded
flange-bolted web 1.00
Radius-cut dogbone 1.71
Constant or tapered
cut dogbone 2.18
Cover plate 2.50
Flange ribs 2.91
Bottom haunch 3.01
Proprietary side plates 3.76
Side plates 3.96
Top & bottom haunch 4.00
Column tree 6.38

region. Flange buckling is visible


in Figure 6(c). Such local buck-
ling has been observed in many
tests on reinforced or other modi-
fied connection concepts.
However, this severe local buck-
ling typically occurs at very large
plastic rotations. Figure 6(b)
shows Specimen DB4 at a plastic
rotation of 0.022 radian. At this
level of demand, the degree of
local buckling is still very slight,
and in fact, is hardly noticeable. Figure 6a (above): View of beam
Analytical studies of steel flange of specimen DB4 at 0.012
moment frame buildings affected rad. plastic rotation (column is at
by the Northridge Earthquake left)
suggest that most buildings
experienced maximum plastic Figure 6b (left): Specimen at
joint rotations on the order of 0.022 rad. plastic rotation
0.005 to 0.00 radian. Under this
level of demand, these test speci- Figure 6c (top): Specimen at end
mens had no visible damage, of test; plastic rotation equals
other than yielding patterns 0.037 rad.
indicated by whitewash flaking.
Such connections would likely
require no repair after experi- deformations of the panel zone number of moment connections
encing this level of demand. had no apparent detrimental in this building, the cost of the
For all test specimens, with effect on the connection, and con- dogbone connection relative to
the exception of DB5, plastic tributed to the ductility of the other options was also a critical
rotations were developed by test specimen. concern.
inelastic deformations in the Based on the successful To address the issue of cost,
beams. Specimen DB5 was results of this testing program, W&W Steel developed cost esti-
designed to permit significant the overall cyclic loading perfor- mates for a number of moment
shear yielding of the column mance of the radius-cut dogbone connection options for this pro-
panel zone. During testing, a connection was judged as excel- ject. The results are shown in
great deal of yielding was in fact lent. Table 3. Relative costs are pro-
observed in the panel zone. vided with respect to the Pre-
Analysis of test data indicates COST COMPARISONS Northridge welded flange-bolted
that of the total plastic rotation The test program indicated web moment connection. Cost
of 0.040 radian developed by that the radius-cut dogbone con- comparisons were based on a
DB5, approximately 25% was nection was capable of providing W36x194 girder of A572 Gr. 50
contributed by the column panel a high level of performance. steel with weld metal toughness
zone. For this specimen, inelastic However, because of the large requirements for all cases except

Modern Steel Construction / August 1996


dimensions as small as possible,
in order to minimize the amplifi-
cation of moment from the hinge
location in the dogbone to the
face of the column. The dimen-
sion “a” must be large enough,
however, to permit stress in the
reduced beam flange to spread
uniformly over the flange width
at the face of the column.
Similarly, dimension “b” should
be large enough to avoid exces-
sive inelastic strains in the dog-
bone. Consequently, the suggest-
ed dimensions above are a
compromise between different
requirements.
The depth of the cut, dimen-
sion “c” in Figure 5 is a critical
dimension for the dogbone. The
following approach was used to
determine this dimension. First,
it was assumed that the maxi-
mum moment that can develop
at midlength of the dogbone was
equal to the plastic moment of
Figure 7: this reduced section, increased
Mechanized by 10 to 15 percent to allow for
plasma arc strain hardening. This moment
cutting of was then projected to the face of
dogbones in the column using a moment gra-
fabrication shop dient based on an assumed point
of inflection at midspan of the
beam. The maximum moment at
the face of the column was then
limited to approximately 90 to
the Pre-Northridge connection. DESIGN AND FABRICATION 100 percent of the plastic
The various connection types CONSIDERATIONS moment of the full cross section
listed in Table 3, other than the In designing the radius-cut of the beam. It was believed that
radius-cut dogbone, are connec- dogbone test specimens, it was the all-welded connection com-
tion options illustrated in the necessary to establish dimen- bined with the welding details
SAC Interim Guidelines. The sions of the dogbone. Key dimen- used in these tests was capable
cost data presented in Table 3 sions are shown in Figure 5, and of sustaining such levels of bend-
were developed for this project, were established based on the ing moment. The reduced beam
and will vary for other projects judgment of the writers. This sections were also checked for
depending upon location, labor judgment relied on these test conformance with flexural
factors, and connection design results, results of previous dog- strength requirements of the
variations. bone tests, and experience with LRFD Specification for all fac-
The cost comparisons for this other connection test programs tored gravity and lateral load
project indicated that the radius- over the last several years. combinations. Following this
cut dogbone was the most eco- Based on this judgment, the dis- basic approach, the depth of cut,
nomical alternative of all the tance “a” from the face of the col- “c,” was chosen. For all of the
options considered. Based on the umn to the start of the dogbone radius-cut specimens, the depth
successful testing program, com- cut was chosen to be approxi- of cut resulted in removing
bined with the favorable econom- mately 50 to 75 percent of the approximately 40 percent of the
ics, the radius-cut dogbone beam flange width. The length of beam flange width.
moment connection was accepted the cut, dimension “b” in Figure The maximum moment devel-
for use on the American Stores 5, was chosen in the range of oped at the face of the column
Company Headquarters about 65 to 85 percent of the can be reduced by increasing the
Building. beam depth. In general, it is depth of cut in the dogbone. The
preferable to keep the “a” and “b” writers view removal of about 50

Modern Steel Construction / August 1996


E I N
S M C DE S
I S I G
percent of the beam flange width
as a maximum practical cut.
Note that for a given depth of
cut, a greater reduction in
moment at the face of the col-
umn is possible in longer span
beams with smaller moment gra-
dients. If further reduction of
stress at the face of the column
is desired, some reinforcement
could be added to the connection,
for example, thin cover plates or
ribs. In these tests, the actual
maximum moments developed at
the face of the column ranged
from 92 percent to 113 percent of
the actual plastic moment of the
beam. These moments were sus-
tained without connection fail-
ure. Consequently, no additional
reinforcement was provided at
the connection. It was felt that
such additional reinforcement
would largely negate the econo-
my of this connection and was
unnecessary.
Once the length of the dog-
bone “b” and depth of cut “c”
have been chosen, the radius of
the cut follows simply from the
geometry of a circular arc, as
indicated by the formula in
Figure 5.
Once the radius-cut dogbone
was accepted for use on the
American Stores Company build-
ing, W&W Steel was faced with
the task of cutting dogbones into
both flanges of both ends of
1,000 moment frame girders.
This required making 8,000 cuts. Figures 8a & 8b: Moment frame during erection
In order to make these cuts as
economically as possible, W&W
devised a mechanized process ing is expected to be completed nection concepts that have
employing plasma arc cutting. in November of 1996. shown good performance in labo-
Figure 7 shows two cuts being ratory cyclic loading tests.
made simultaneously in the fab- CONCLUSIONS Engineers must carefully consid-
rication shop. The mechanized The test program conducted er currently available test data
plasma arc cut left a very high on the radius-cut dogbone con- combined with the economics of
quality surface. The cutting was nection showed excellent perfor- a project when choosing the most
followed by the use of a 3M pad- mance. Together with a number appropriate moment connection
dle wheel grinder. Grinding was of other connection types devised detail. This represents a rapidly
done parallel to the beam flange and tested since the Northridge changing picture in the current
to minimize stress concentra- Earthquake, the dogbone connec- environment of intensive
tions due to grinding marks. tion promises to deliver a much research and testing. Based on
Figure 8 shows views of higher level of ductility and safe- the experiences from this project,
moment frame girders with ty as compared to the “Pre- however, the dogbone connection
radius-cut dogbone moment con- Northridge” moment connection. appears to be one of the more
nections during erection at the Structural engineers can now promising moment connection
construction site in Salt Lake choose from a fairly wide variety concepts capable of delivering
City. The structural steel fram- of seismic resistant moment con- both performance and economy.

Modern Steel Construction / August 1996


Michael D. Engelhardt, is an
Associate Professor of Civil
Engineering, The University of
Texas at Austin, Ted Winne-
berger, is Senior Vice President,
Engineering, W&W Steel
Company, Oklahoma City, OK,
Andrew J. Zekany, is Vice
President, Structural Eng-
ineering, HKS Inc., Dallas, and
Timothy J. Potyraj, is a
Graduate Research Assistant,
The University of Texas at
Austin. The testing program was
financially sponsored by W&W
Steel Co. and the American
Institute of Steel Construction,
Inc. Additional support was pro-
vided through National Science
Foundation Grant Nos. CMS-
9358186 and CMS-9416287. The
writers thank Nestor Iwankiw
and Charlie Carter of AISC, Inc.

Modern Steel Construction / August 1996

You might also like