You are on page 1of 124

CLIENT:

UTTAR PRADESH EXPRESSWAYS INDUSTRIAL DEVELOPMENT


AUTHORITY (UPEIDA)

AUTHORITY ENGINEER:
In
Joint Venture
with

CONTRACTOR:AFCONS INFRASTRUCTURELIMITED

PROOF CONSULTANT:CONSULTING ENGINEERS GROUP LTD.

PROJECT TITLE:

Detailed Engineering Services for Construction of


6 Lane Greenfield Kannauj to Unnao (Km 172.5 to Km 236.5)
access controlled expressway with service road in State of Uttar Pradesh
on EPC basis (Package IV)

TITLE OF CALCULATIONS :DESIGN OF SUPER STRUCTURE OF FLYOVER AT


CH.216+700

47404700/ST/CAL/SUP-FLY-216+700 No. of Rev.: R0


DOCUMENT/FILE NO:
Sheets: Date: 3/11/2015

APPROVED
FOR APPROVAL OF Client Client
BY
LDS LDS

CONSULTING ENGINEERING SERVICES (INDIA) PVT. LIMITED


Plot No. 184, Platinum Tower, UdyogVihar, Phase – I
Gurgaon – 122016 (Haryana), India
NAME DESIGNATION SIGNATURE

S.SUCHISMITA
MOHAPATRA
DESIGNER

JACOBS-CES

SOUMYA RAY CHECKER

JAYSHREE GHOSE APPROVER


Design of Super structure
at CH 216+700
CONTENT

1. Design Data

2. Calculation of the Geometric Property

3. Loading &Summary of foces

4. Cable Profile

5. Stress Check

6. Anchor Block Design

7. Design of Cross Girder

8 Transverse Analysis
BASIC DESIGN
DATA
Design of PSC Girder 34.35m span For FLYOVER AT CH.216+700

BASIC DESIGN DATA

1 Total width of superstructure Wsup 27.250 m


2 Effective span Leff 34.350 m
3 Clear carriage way Bcw 27.250 m
4 Skew angle Ang 22.000 Deg.
5 Spacing of main girder c/c Spmg 2.900 m
6 Width of crash barier Wkerb 0.500 m
7 Thk of deck slab Df 0.240 m
8 Thk of wearing coat Wc 0.065 m
9 Length of cantilever of deck slab (in trans dir.) Lcan 2.0250 m
10 Cantilever slab thk at fixed end Dcan1 0.400 m
11 Cantilever slab thk at free end Dcan2 0.400 m
12 No of main girder Nomg 9 m
13 Depth of main girder (incl slab) Dmg 2.740 m
14 Width of Flange Wf 0.950 m
15 Depth of Flange Dfl 0.150 m
16 Web thk of main girder ( at center ) bwmc 0.275 m
17 Web thk of main girder ( at support ) bwms 0.710 m
18 Length of extra widening ( varying ) Lwv 1 2.000 m
19 Length of extra widening ( varying ) Lwv 0.000 m
20 Length of extra widening ( uniform ) Lwu 2.000 m
21 Top haunch Thw x Thh 0.338 x 0.075 m
22 Bottom haunch Bhw x Bhh 0.218 x 0.200 m
23 Bottom bulb Bbw x Bbh 0.710 x 0.240 m
24 Area of Beam at center Abc 0.962 m2
25 Area of Beam in between center and support Abcs 1.388 m2
26 Area of Beam at support Abs 1.814 m2
27 No of cross girder (incl. end girders) Nocg 3 m
28 Depth of cross intermedate girder (incl. Slab) Dcg 2.300 m
29 Thk of cross girder (Intermediate) bwcg 0.300 m
30 Thk of cross girder (End) bwcge 0.700 m
32 Grade of concrete Cgrade 50 N/mm2
33 Grade of reinforcement Sgrade 500 N/mm2
34 Clear cover cov 0.040 m
35 Unit weight of concrete wcon 2.500 t/m3
36 Weight of wearing course wwc 0.200 t/m2
37 Weight of crash barrier wrail 1.000 t/m
CALCULATION OF GEOMETRIC
PROPERTIES
SECTION PROPERTY CALCULATION :

1. INNER GIRDER

a. MID SECTION
1450 1450
Individual section
950
Area
961962.5 mm2 240
0.962 m2 150
C.G. of section from bottom 75
1236.665 mm

MOMENT OF INERTIA ABOUT CG = 2500


6.99755E+11 mm4 275
0.700 m4
COMBINED SECTION

AREA= 1657962.5 mm2


1.658 m2 200
C. G OF SECTION FROM BOTTOM= 240
1817.38 mm
MOMENT OF INERTIA ABOUT COMBINED CG 710
1.47586E+12 mm4
1.476 m4
b.SUPPORT SECTION
1450 1450
Individual section
950
Area
1814200 mm2 240
1.814 m2 150
C.G. of section from bottom 27
1275.241 mm

MOMENT OF INERTIA ABOUT CG = 2500


9.76903E+11 mm4 710
0.977 m4
COMBINED SECTION

AREA= 2510200 mm2


2.510 m2 0
C. G OF SECTION FROM BOTTOM= 0
1648.100 mm
MOMENT OF INERTIA ABOUT COMBINED CG 710
1.8899E+12 mm4
1.890 m4
AVRERAGE PROP
AREA= 2.084 m2
CG FROM BOTTOM 1.733 m
MOMENT OF INERTIA = 1.683 m4
SECTION PROPERTY CALCULATION :

2. OUTER GIRDER 0.961963


2.5
a. MID SECTION 1.236665
0.700 1450 2025
Individual section
950

Area 961962.5 mm2 240


0.962 m2 150
C.G. of section from bottom 75
1237 mm

MOMENT OF INERTIA ABOUT CG = 2500


6.99755E+11 mm4 275
0.700 m4
COMBINED SECTION

AREA= 1795962.5 mm2


1.796 m2 200
C. G OF SECTION FROM BOTTOM= 240
1879 mm
MOMENT OF INERTIA ABOUT COMBINED CG 710
1.55859E+12 mm4
1.559 m4

b.SUPPORT SECTION 1450 2025

Individual section 950


Area
1814200 mm2 240
1.814 m2 150
C.G. of section from bottom 27
1275 mm

MOMENT OF INERTIA ABOUT CG = 2500


9.76903E+11 mm4 710 2323
0.977 m4
COMBINED SECTION

AREA= 2648200 mm2


2.648 m2 0
C. G OF SECTION FROM BOTTOM= 0
1699 mm
MOMENT OF INERTIA ABOUT COMBINED CG 2.648 710
2.01412E+12 mm4 2.74
2.014 m4 1.698747
2.014
AVRERAGE PROP
AREA= 2.222 m2
CG FROM BOTTOM 1.789 m
MOMENT OF INERTIA = 1.786 m4
INTERMIDIATE CROSS GIRDER

353 353
Individual section
0
Area
678000 mm2 240
0.678 m2 0
C.G. of section from bottom 0
1130 mm

MOMENT OF INERTIA ABOUT CG = 2260


2.88579E+11 mm4 300
0.289 m4
COMBINED SECTION

AREA= 847440 mm2


0.847 m2 0
C. G OF SECTION FROM BOTTOM= 0
1380 mm
MOMENT OF INERTIA ABOUT COMBINED CG 0
5.01208E+11 mm4
0.501 m4

END CROSS GIRDER 1050


553
Individual section
0
Area
1960000 mm2 240
1.960 m2 0
C.G. of section from bottom 0
1400 mm

MOMENT OF INERTIA ABOUT CG = 2800


1.28053E+12 mm4 700
1.281 m4
COMBINED SECTION

AREA= 2344720 mm2


2.345 m2 0
C. G OF SECTION FROM BOTTOM= 0
1649 mm
MOMENT OF INERTIA ABOUT COMBINED CG 0
2.02539E+12 mm4
2.025 m4
LOADING
Calculation of Dead Load during 1st Stage
STAAD INPUT FILE FOR SELF WEIGHT

STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 07-Jul-15
END JOB INFORMATION
INPUT WIDTH 79
UNIT METER MTON
JOINT COORDINATES
1008 0.0125 0 0; 2008 33.9275 0 0; 2009 16.97 0 0; 2010 1.795 0 0;
2011 3.795 0 0; 2012 32.145 0 0; 2013 30.145 0 0; 2123 7.9969 0 0;
2220 12.7691 0 0; 2221 21.1709 0 0; 2222 25.9431 0 0;
MEMBER INCIDENCES
1 1008 2010; 507 2009 2221; 508 2010 2011; 509 2011 2123; 510 2012 2008;
511 2013 2012; 638 2123 2220; 666 2013 2222; 668 2222 2221; 790 2009 2220;
DEFINE MATERIAL START
ISOTROPIC CONCRETE
E 2.21467e+006
POISSON 0.17
DENSITY 2.5
ALPHA 1e-005
DAMP 0.05
**********
END DEFINE MATERIAL
CONSTANTS
MATERIAL CONCRETE ALL
MEMBER PROPERTY AMERICAN
507 509 638 666 668 790 PRIS AX 0.962 IX 0.001 IY 0.001 IZ 0.7
1 510 PRIS AX 1.814 IX 0.001 IY 0.001 IZ 0.977
508 511 PRIS AX 1.388 IX 0.001 IY 0.001 IZ 0.838
SUPPORTS
1008 2008 PINNED
LOAD 1 LOADTYPE None TITLE DL
SELFWEIGHT Y -1 LIST ALL
PERFORM ANALYSIS
FINISH
Calculation of Dead Load during 2nd Stage & Shuttering Load

B. Inner Girder (2nd Stage)

1 Weight of deck slab =2.9*0.24*2.5 = 1.74 t/m

2 Weight of Inner cross girder =((2.9-0.95)*2.3)*0.3*2.5 = 2.67 t

3 Weight of End cross girder =((2.9-0.95)*2.3) *0.7*2.5 = 6.91 t

B. Outer Girder (2nd Stage)

1 Weight of deck slab =(1.925*0.24+ 1.55*(0.24+0.4)/2) = 2.395 t/m


*2.5
2 Weight of Inner cross girder =((2.9-0.95)*2.3)*0.3*2.5/2 = 1.335 t

3 Weight of End cross girder =((2.9-0.95)*2.3) *0.7*2.5/2 = 3.455 t

(2nd Stage Loading) Inner Girder

6.91 t 0.00 t 2.67 t 0.00 t 6.91 t


8.59 m 8.59 m 8.59 m 8.59 m

1.74t/m

34.35 m
A B

Support reaction at A = 38.13 t

At distance 2 4 8.2 12.97 17.17


Location
Sl. Nr. Item Deff from support Span (L/8) Span Span Span (L/2)
(L/4) (3L/8)
1 BM (t-m) 59.0 111.0 197.5 258.6 279.5
2 SF (t) 27.7 24.3 17.0 8.7 1.3

Calculation of bending moment and shear force (DL) Outer Girder

nd
(2 Stage Loading)

3.46 t 0.00 t 1.33 t 0.00 t 3.46 t


8.59 m 8.59 m 8.59 m 8.59 m

2.40t/m

34.35 m
A B

Support reaction at A = 44.59 t

At distance 2 4 8.2 12.97 17.17


Location
Sl. Nr. Item Deff from support Span (L/8) Span Span Span (L/2)
(L/4) (3L/8)
1 BM (t-m) 77.5 145.4 256.8 332.1 353.2
2 SF (t) 36.3 31.6 21.5 10.1 0.0
Calculation of bending moment and shear force (Shuttering Load) (Inner girder)
Shuttering Load

0.70t/m

34.35 m
A B

Support reaction at A = 11.95 t

At distance 2 4 8.2 12.97 17.17


Location
SL. Deff from support Span (L/8) Span Span Span (L/2)
Item
No. (L/4) (3L/8)

1 BM (t-m) 22.5 42.2 74.6 96.5 102.7


2 SF (t) 10.6 9.2 6.2 2.9 0.0

Calculation of bending moment and shear force (Shuttering Load) (Outer girder)
Shuttering Load

0.83t/m

34.35 m
A B

Support reaction at A = 14.32 t

At distance 2 4 8.2 12.97 17.17


Location
Sl. Nr. Item Span Span
Deff from support Span (L/8) Span (L/2)
(L/4) (3L/8)
1 BM (t-m) 27.0 50.6 89.4 115.6 123.0
2 SF (t) 12.7 11.0 7.5 3.5 0.0

SIDL LOAD CALCULATION

1. Crash barrier 1.0 t/m

2. wearing course 0.2 t/m2


STAAD INPUT FILE FOR SIDL
STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 07-Jul-15
END JOB INFORMATION
INPUT WIDTH 79
UNIT METER MTON
JOINT COORDINATES
8 -1.305 0 0; 9 35.245 0 0; 100 -0.571 0 0; 111 34.511 0 0; 299 -0.938 0 0;
310 34.878 0 0; 1008 -0.205 0 0; 2008 34.145 0 0; 2009 16.97 0 0;
2010 1.795 0 0; 2011 3.795 0 0; 2012 32.145 0 0; 2013 30.145 0 0;
2014 0.9667 0 -2.9; 2015 2.9667 0 -2.9; 2016 -0.1333 0 -2.9;
2017 0.2337 0 -2.9; 2018 35.3167 0 -2.9; 2019 35.6827 0 -2.9;
2020 0.6007 0 -2.9; 2021 36.0497 0 -2.9; 2022 36.4167 0 -2.9;
2023 18.1417 0 -2.9; 2024 31.3167 0 -2.9; 2025 4.9667 0 -2.9;
2026 33.3167 0 -2.9; 2027 2.1384 0 -5.8; 2028 4.1384 0 -5.8;
2029 1.0384 0 -5.8; 2030 1.4054 0 -5.8; 2031 36.4884 0 -5.8;
2032 36.8544 0 -5.8; 2033 1.7724 0 -5.8; 2034 37.2214 0 -5.8;
2035 37.5884 0 -5.8; 2036 19.3134 0 -5.8; 2037 32.4884 0 -5.8;
2038 6.1384 0 -5.8; 2039 34.4884 0 -5.8; 2040 3.3101 0 -8.7;
2041 5.3101 0 -8.7; 2042 2.2101 0 -8.7; 2043 2.5771 0 -8.7;
2044 37.6601 0 -8.7; 2045 38.0261 0 -8.7; 2046 2.9441 0 -8.7;
2047 38.3931 0 -8.7; 2048 38.7601 0 -8.7; 2049 20.4851 0 -8.7;
2050 33.6601 0 -8.7; 2051 7.3101 0 -8.7; 2052 35.6601 0 -8.7;
2053 4.4818 0 -11.6; 2054 6.4818 0 -11.6; 2055 3.3818 0 -11.6;
2056 3.7488 0 -11.6; 2057 38.8318 0 -11.6; 2058 39.1978 0 -11.6;
2059 4.1158 0 -11.6; 2060 39.5648 0 -11.6; 2061 39.9318 0 -11.6;
2062 21.6568 0 -11.6; 2063 34.8318 0 -11.6; 2064 8.4818 0 -11.6;
2065 36.8318 0 -11.6; 2066 5.6535 0 -14.5; 2067 7.6535 0 -14.5;
2068 4.5535 0 -14.5; 2069 4.9205 0 -14.5; 2070 40.0035 0 -14.5;
2071 40.3695 0 -14.5; 2072 5.2875 0 -14.5; 2073 40.7365 0 -14.5;
2074 41.1035 0 -14.5; 2075 22.8285 0 -14.5; 2076 36.0035 0 -14.5;
2077 9.6535 0 -14.5; 2078 38.0035 0 -14.5; 2079 6.8252 0 -17.4;
2080 8.8252 0 -17.4; 2081 5.7252 0 -17.4; 2082 6.0922 0 -17.4;
2083 41.1752 0 -17.4; 2084 41.5412 0 -17.4; 2085 6.4592 0 -17.4;
2086 41.9082 0 -17.4; 2087 42.2752 0 -17.4; 2088 24.0002 0 -17.4;
2089 37.1752 0 -17.4; 2090 10.8252 0 -17.4; 2091 39.1752 0 -17.4;
2092 7.9969 0 -20.3; 2093 9.9969 0 -20.3; 2094 42.3469 0 -20.3;
2095 42.7129 0 -20.3; 2096 43.0799 0 -20.3; 2097 43.4469 0 -20.3;
2098 25.1719 0 -20.3; 2099 38.3469 0 -20.3; 2100 11.9969 0 -20.3;
2101 40.3469 0 -20.3; 2102 9.1686 0 -23.2; 2103 11.1686 0 -23.2;
2104 43.5186 0 -23.2; 2105 43.8846 0 -23.2; 2106 44.2516 0 -23.2;
2107 44.6186 0 -23.2; 2108 26.3436 0 -23.2; 2109 39.5186 0 -23.2;
2110 13.1686 0 -23.2; 2111 41.5186 0 -23.2; 2112 6.8969 0 -20.3;
2113 7.2639 0 -20.3; 2114 7.6309 0 -20.3; 2115 8.0686 0 -23.2;
2116 8.4356 0 -23.2; 2117 8.8026 0 -23.2; 2118 -1.023 0 2.025;
2119 33.327 0 2.025; 2120 9.9866 0 -25.225; 2121 44.3366 0 -25.225;
2122 9.1686 0 0; 2123 7.9969 0 0; 2124 6.8252 0 0; 2125 5.6535 0 0;
2126 4.4818 0 0; 2127 3.3101 0 0; 2128 2.1384 0 0; 2129 0.9667 0 0;
2130 -2.123 0 2.025; 2131 -1.756 0 2.025; 2132 33.693 0 2.025;
2133 -1.389 0 2.025; 2134 34.06 0 2.025; 2135 34.427 0 2.025;
2136 44.7026 0 -25.225; 2137 45.0696 0 -25.225; 2138 45.4366 0 -25.225;
2139 8.8866 0 -25.225; 2140 9.2536 0 -25.225; 2141 9.6206 0 -25.225;
2142 26.3436 0 0; 2143 25.1719 0 0; 2144 24.0002 0 0; 2145 22.8285 0 0;
2146 21.6568 0 0; 2147 20.4851 0 0; 2148 19.3134 0 0; 2149 18.1417 0 0;
2150 18.1417 0 -23.2; 2151 19.3134 0 -23.2; 2152 20.4851 0 -23.2;
2153 21.6568 0 -23.2; 2154 22.8285 0 -23.2; 2155 24.0002 0 -23.2;
2156 25.1719 0 -23.2; 2157 34.145 0 -23.2; 2158 35.3167 0 -23.2;
2159 36.4884 0 -23.2; 2160 37.6601 0 -23.2; 2161 38.8318 0 -23.2;
2162 40.0035 0 -23.2; 2163 41.1752 0 -23.2; 2164 42.3469 0 -23.2;
2165 18.1417 0 -25.225; 2166 19.3134 0 -25.225; 2167 20.4851 0 -25.225;
2168 21.6568 0 -25.225; 2169 22.8285 0 -25.225; 2170 24.0002 0 -25.225;
2171 25.1719 0 -25.225; 2172 26.3436 0 -25.225; 2173 34.145 0 -25.225;
2174 35.3167 0 -25.225; 2175 36.4884 0 -25.225; 2176 37.6601 0 -25.225;
2177 38.8318 0 -25.225; 2178 40.0035 0 -25.225; 2179 41.1752 0 -25.225;
2180 42.3469 0 -25.225; 2181 43.5186 0 -25.225; 2183 18.1417 0 2.025;
2184 19.3134 0 2.025; 2185 20.4851 0 2.025; 2186 21.6568 0 2.025;
2187 22.8285 0 2.025; 2188 24.0002 0 2.025; 2189 25.1719 0 2.025;
2190 26.3436 0 2.025; 2191 16.97 0 -25.225; 2192 16.97 0 2.025;
2193 9.1686 0 2.025; 2194 7.9969 0 2.025; 2195 6.8252 0 2.025;
2196 5.6535 0 2.025; 2197 4.4818 0 2.025; 2198 3.3101 0 2.025;
2199 2.1384 0 2.025; 2200 0.9667 0 2.025; 2201 -0.205 0 2.025;
2203 10.4688 0 0; 2204 11.7691 0 0; 2205 13.0693 0 0; 2206 14.3695 0 0;
2207 15.6698 0 0; 2208 27.6438 0 -23.2; 2209 28.9441 0 -23.2;
2210 30.2443 0 -23.2; 2211 31.5445 0 -23.2; 2212 32.8448 0 -23.2;
2213 10.4688 0 -25.225; 2214 11.7691 0 -25.225; 2215 13.0693 0 -25.225;
2216 14.3695 0 -25.225; 2217 15.6698 0 -25.225; 2218 27.6438 0 0;
2219 28.9441 0 0; 2220 30.2443 0 0; 2221 31.5445 0 0; 2222 32.8448 0 0;
2223 27.6438 0 2.025; 2224 28.9441 0 2.025; 2225 30.2443 0 2.025;
2226 31.5445 0 2.025; 2227 32.8448 0 2.025; 2228 15.6698 0 2.025;
2229 14.3695 0 2.025; 2230 13.0693 0 2.025; 2231 11.7691 0 2.025;
2232 10.4688 0 2.025; 2233 27.6438 0 -25.225; 2234 28.9441 0 -25.225;
2235 30.2443 0 -25.225; 2236 31.5445 0 -25.225; 2237 32.8448 0 -25.225;
2238 2.1384 0 -2.9; 2239 30.2443 0 -2.9; 2240 28.9441 0 -2.9;
2241 27.6438 0 -2.9; 2242 26.3436 0 -2.9; 2243 25.1719 0 -2.9;
2244 24.0002 0 -2.9; 2245 22.8285 0 -2.9; 2246 21.6568 0 -2.9;
2247 20.4851 0 -2.9; 2248 19.3134 0 -2.9; 2249 4.4818 0 -2.9;
2250 3.3101 0 -2.9; 2251 16.97 0 -2.9; 2252 15.6698 0 -2.9;
2253 14.3695 0 -2.9; 2254 13.0693 0 -2.9; 2255 11.7691 0 -2.9;
2256 10.4688 0 -2.9; 2257 9.1686 0 -2.9; 2258 7.9969 0 -2.9;
2259 6.8252 0 -2.9; 2260 5.6535 0 -2.9; 2261 3.3101 0 -5.8;
2262 31.5445 0 -5.8; 2263 30.2443 0 -5.8; 2264 28.9441 0 -5.8;
2265 27.6438 0 -5.8; 2266 26.3436 0 -5.8; 2267 25.1719 0 -5.8;
2268 24.0002 0 -5.8; 2269 22.8285 0 -5.8; 2270 21.6568 0 -5.8;
2271 20.4851 0 -5.8; 2272 5.6535 0 -5.8; 2273 4.4818 0 -5.8;
2274 18.1417 0 -5.8; 2275 16.97 0 -5.8; 2276 15.6698 0 -5.8;
2277 14.3695 0 -5.8; 2278 13.0693 0 -5.8; 2279 11.7691 0 -5.8;
2280 10.4688 0 -5.8; 2281 9.1686 0 -5.8; 2282 7.9969 0 -5.8;
2283 6.8252 0 -5.8; 2284 35.3167 0 -5.8; 2285 34.145 0 -5.8;
2286 32.8448 0 -5.8; 2287 4.4818 0 -8.7; 2288 32.8448 0 -8.7;
2289 31.5445 0 -8.7; 2290 30.2443 0 -8.7; 2291 28.9441 0 -8.7;
2292 27.6438 0 -8.7; 2293 26.3436 0 -8.7; 2294 25.1719 0 -8.7;
2295 24.0002 0 -8.7; 2296 22.8285 0 -8.7; 2297 21.6568 0 -8.7;
2298 6.8252 0 -8.7; 2299 5.6535 0 -8.7; 2300 19.3134 0 -8.7;
2301 18.1417 0 -8.7; 2302 16.97 0 -8.7; 2303 15.6698 0 -8.7;
2304 14.3695 0 -8.7; 2305 13.0693 0 -8.7; 2306 11.7691 0 -8.7;
2307 10.4688 0 -8.7; 2308 9.1686 0 -8.7; 2309 7.9969 0 -8.7;
2310 36.4884 0 -8.7; 2311 35.3167 0 -8.7; 2312 34.145 0 -8.7;
2313 5.6535 0 -11.6; 2314 34.145 0 -11.6; 2315 32.8448 0 -11.6;
2316 31.5445 0 -11.6; 2317 30.2443 0 -11.6; 2318 28.9441 0 -11.6;
2319 27.6438 0 -11.6; 2320 26.3436 0 -11.6; 2321 25.1719 0 -11.6;
2322 24.0002 0 -11.6; 2323 22.8285 0 -11.6; 2324 7.9969 0 -11.6;
2325 6.8252 0 -11.6; 2326 20.4851 0 -11.6; 2327 19.3134 0 -11.6;
2328 18.1417 0 -11.6; 2329 16.97 0 -11.6; 2330 15.6698 0 -11.6;
2331 14.3695 0 -11.6; 2332 13.0693 0 -11.6; 2333 11.7691 0 -11.6;
2334 10.4688 0 -11.6; 2335 9.1686 0 -11.6; 2336 37.6601 0 -11.6;
2337 36.4884 0 -11.6; 2338 35.3167 0 -11.6; 2339 6.8252 0 -14.5;
2340 35.3167 0 -14.5; 2341 34.145 0 -14.5; 2342 32.8448 0 -14.5;
2343 31.5445 0 -14.5; 2344 30.2443 0 -14.5; 2345 28.9441 0 -14.5;
2346 27.6438 0 -14.5; 2347 26.3436 0 -14.5; 2348 25.1719 0 -14.5;
2349 24.0002 0 -14.5; 2350 9.1686 0 -14.5; 2351 7.9969 0 -14.5;
2352 21.6568 0 -14.5; 2353 20.4851 0 -14.5; 2354 19.3134 0 -14.5;
2355 18.1417 0 -14.5; 2356 16.97 0 -14.5; 2357 15.6698 0 -14.5;
2358 14.3695 0 -14.5; 2359 13.0693 0 -14.5; 2360 11.7691 0 -14.5;
2361 10.4688 0 -14.5; 2362 38.8318 0 -14.5; 2363 37.6601 0 -14.5;
2364 36.4884 0 -14.5; 2365 7.9969 0 -17.4; 2366 36.4884 0 -17.4;
2367 35.3167 0 -17.4; 2368 34.145 0 -17.4; 2369 32.8448 0 -17.4;
2370 31.5445 0 -17.4; 2371 30.2443 0 -17.4; 2372 28.9441 0 -17.4;
2373 27.6438 0 -17.4; 2374 26.3436 0 -17.4; 2375 25.1719 0 -17.4;
2376 10.4688 0 -17.4; 2377 9.1686 0 -17.4; 2378 22.8285 0 -17.4;
2379 21.6568 0 -17.4; 2380 20.4851 0 -17.4; 2381 19.3134 0 -17.4;
2382 18.1417 0 -17.4; 2383 16.97 0 -17.4; 2384 15.6698 0 -17.4;
2385 14.3695 0 -17.4; 2386 13.0693 0 -17.4; 2387 11.7691 0 -17.4;
2388 40.0035 0 -17.4; 2389 38.8318 0 -17.4; 2390 37.6601 0 -17.4;
2391 9.1686 0 -20.3; 2392 37.6601 0 -20.3; 2393 36.4884 0 -20.3;
2394 35.3167 0 -20.3; 2395 34.145 0 -20.3; 2396 32.8448 0 -20.3;
2397 31.5445 0 -20.3; 2398 30.2443 0 -20.3; 2399 28.9441 0 -20.3;
2400 27.6438 0 -20.3; 2401 26.3436 0 -20.3; 2402 11.7691 0 -20.3;
2403 10.4688 0 -20.3; 2404 24.0002 0 -20.3; 2405 22.8285 0 -20.3;
2406 21.6568 0 -20.3; 2407 20.4851 0 -20.3; 2408 19.3134 0 -20.3;
2409 18.1417 0 -20.3; 2410 16.97 0 -20.3; 2411 15.6698 0 -20.3;
2412 14.3695 0 -20.3; 2413 13.0693 0 -20.3; 2414 41.1752 0 -20.3;
2415 40.0035 0 -20.3; 2416 38.8318 0 -20.3; 2417 10.4688 0 -23.2;
2418 13.0693 0 -23.2; 2419 11.7691 0 -23.2; 2420 16.97 0 -23.2;
2421 15.6698 0 -23.2; 2422 14.3695 0 -23.2; 2423 34.145 0 -2.9;
2424 32.8448 0 -2.9; 2425 31.5445 0 -2.9; 2426 12.7691 0 0;
2427 13.9408 0 -2.9; 2428 15.1125 0 -5.8; 2429 22.3426 0 -2.9;
2430 21.1709 0 0; 2431 23.5143 0 -5.8; 2432 24.686 0 -8.7;
2433 25.8577 0 -11.6; 2434 27.0294 0 -14.5; 2435 16.2842 0 -8.7;
2436 22.1427 0 -23.2; 2437 17.4559 0 -11.6; 2438 18.6276 0 -14.5;
2439 19.7993 0 -17.4; 2440 20.971 0 -20.3; 2441 28.2011 0 -17.4;
2442 29.3728 0 -20.3; 2443 30.5445 0 -23.2; 2444 10.3403 0 -5.8;
2445 11.512 0 -8.7; 2446 12.6837 0 -11.6; 2447 13.8554 0 -14.5;
2448 15.0271 0 -17.4; 2449 16.1988 0 -20.3; 2450 17.3705 0 -23.2;
2451 32.9733 0 -17.4; 2452 31.8016 0 -14.5; 2453 30.6299 0 -11.6;
2454 29.4582 0 -8.7; 2455 28.2865 0 -5.8; 2456 25.9431 0 0;
2457 27.1148 0 -2.9;
MEMBER INCIDENCES
1 1008 2129; 7 8 299; 8 2008 111; 117 100 1008; 128 111 310; 495 299 100;
506 310 9; 507 2009 2149; 508 2010 2128; 509 2011 2126; 510 2012 2222;
511 2013 2220; 512 2014 2238; 513 2016 2017; 514 2018 2019; 515 2020 2014;
516 2019 2021; 517 2017 2020; 518 2021 2022; 519 2023 2248; 520 2015 2250;
521 2025 2260; 522 2026 2423; 523 2024 2425; 524 2027 2261; 525 2029 2030;
526 2031 2032; 527 2033 2027; 528 2032 2034; 529 2030 2033; 530 2034 2035;
531 2036 2271; 532 2028 2273; 533 2038 2283; 534 2039 2284; 535 2037 2286;
536 2040 2287; 537 2042 2043; 538 2044 2045; 539 2046 2040; 540 2045 2047;
541 2043 2046; 542 2047 2048; 543 2049 2297; 544 2041 2299; 545 2051 2309;
546 2052 2310; 547 2050 2312; 548 2053 2313; 549 2055 2056; 550 2057 2058;
551 2059 2053; 552 2058 2060; 553 2056 2059; 554 2060 2061; 555 2062 2323;
556 2054 2325; 557 2064 2335; 558 2065 2336; 559 2063 2338; 560 2066 2339;
561 2068 2069; 562 2070 2071; 563 2072 2066; 564 2071 2073; 565 2069 2072;
566 2073 2074; 567 2075 2349; 568 2067 2351; 569 2077 2361; 570 2078 2362;
571 2076 2364; 572 2079 2365; 573 2081 2082; 574 2083 2084; 575 2085 2079;
576 2084 2086; 577 2082 2085; 578 2086 2087; 579 2088 2375; 580 2080 2377;
581 2090 2387; 582 2091 2388; 583 2089 2390; 584 2092 2391; 585 2094 2095;
586 2095 2096; 587 2096 2097; 588 2098 2401; 589 2093 2403; 590 2100 2413;
591 2101 2414; 592 2099 2416; 593 2102 2417; 594 2104 2105; 595 2105 2106;
596 2106 2107; 597 2108 2208; 598 2103 2419; 599 2110 2422; 600 2111 2164;
601 2109 2162; 602 2112 2113; 603 2114 2092; 604 2113 2114; 605 2115 2116;
606 2117 2102; 607 2116 2117; 608 2102 2092; 609 2092 2079; 610 2079 2066;
611 2066 2053; 612 2053 2040; 613 2040 2027; 614 2027 2014; 615 2014 1008;
616 2104 2094; 617 2094 2083; 618 2083 2070; 619 2070 2057; 620 2057 2044;
621 2044 2031; 622 2031 2018; 623 2018 2008; 624 2108 2098; 625 2098 2088;
626 2088 2075; 627 2075 2062; 628 2062 2049; 629 2049 2036; 630 2036 2023;
631 2023 2009; 632 2120 2102; 633 1008 2118; 634 2121 2104; 635 2008 2119;
636 2118 2201; 637 2120 2213; 638 2122 2203; 639 2102 2391; 640 2123 2122;
641 2092 2365; 642 2124 2123; 643 2079 2339; 644 2125 2124; 645 2066 2313;
646 2126 2125; 647 2053 2287; 648 2127 2011; 649 2040 2261; 650 2128 2127;
651 2027 2238; 652 2129 2010; 653 2014 2129; 654 2130 2131; 655 2119 2132;
656 2133 2118; 657 2132 2134; 658 2131 2133; 659 2134 2135; 660 2121 2136;
661 2136 2137; 662 2137 2138; 663 2139 2140; 664 2141 2120; 665 2140 2141;
666 2142 2218; 667 2108 2401; 668 2143 2456; 669 2098 2375; 670 2144 2143;
671 2088 2349; 672 2145 2144; 673 2075 2323; 674 2146 2145; 675 2062 2297;
676 2147 2430; 677 2049 2271; 678 2148 2147; 679 2036 2248; 680 2149 2148;
681 2023 2149; 682 2150 2151; 683 2023 2274; 684 2151 2152; 685 2036 2300;
686 2152 2153; 687 2049 2326; 688 2153 2436; 689 2062 2352; 690 2154 2155;
691 2075 2378; 692 2155 2156; 693 2088 2404; 694 2156 2108; 695 2098 2156;
696 2157 2158; 697 2008 2423; 698 2158 2159; 699 2018 2284; 700 2159 2160;
701 2031 2310; 702 2160 2161; 703 2044 2336; 704 2161 2109; 705 2057 2362;
706 2162 2163; 707 2070 2388; 708 2163 2111; 709 2083 2414; 710 2164 2104;
711 2094 2164; 712 2165 2166; 713 2150 2165; 714 2166 2167; 715 2151 2166;
716 2167 2168; 717 2152 2167; 718 2168 2169; 719 2153 2168; 720 2169 2170;
721 2154 2169; 722 2170 2171; 723 2155 2170; 724 2171 2172; 725 2156 2171;
726 2172 2233; 727 2108 2172; 728 2173 2174; 729 2157 2173; 730 2174 2175;
731 2158 2174; 732 2175 2176; 733 2159 2175; 734 2176 2177; 735 2160 2176;
736 2177 2178; 737 2161 2177; 738 2178 2179; 739 2162 2178; 740 2179 2180;
741 2163 2179; 742 2180 2181; 743 2164 2180; 744 2181 2121; 745 2104 2181;
746 2008 2222; 748 2183 2184; 749 2149 2183; 750 2184 2185; 751 2148 2184;
752 2185 2186; 753 2147 2185; 754 2186 2187; 755 2146 2186; 756 2187 2188;
757 2145 2187; 758 2188 2189; 759 2144 2188; 760 2189 2190; 761 2143 2189;
762 2190 2223; 763 2142 2190; 764 2191 2165; 765 2009 2251; 766 2192 2183;
767 2009 2192; 768 2193 2232; 769 2122 2193; 770 2194 2193; 771 2123 2194;
772 2195 2194; 773 2124 2195; 774 2196 2195; 775 2125 2196; 776 2197 2196;
777 2126 2197; 778 2198 2197; 779 2127 2198; 780 2199 2198; 781 2128 2199;
782 2200 2199; 783 2129 2200; 784 2201 2200; 785 1008 2201; 788 2203 2204;
789 2204 2426; 790 2205 2206; 791 2206 2207; 792 2207 2009; 793 2208 2209;
794 2209 2210; 795 2210 2443; 796 2211 2212; 797 2212 2157; 798 2213 2214;
799 2203 2256; 800 2214 2215; 801 2204 2255; 802 2215 2216; 803 2205 2254;
804 2216 2217; 805 2206 2253; 806 2217 2191; 807 2207 2252; 808 2218 2219;
809 2208 2400; 810 2219 2013; 811 2209 2399; 812 2220 2221; 813 2210 2398;
814 2221 2012; 815 2211 2397; 817 2212 2396; 818 2223 2224; 819 2218 2223;
820 2224 2225; 821 2219 2224; 822 2225 2226; 823 2220 2225; 824 2226 2227;
825 2221 2226; 826 2227 2119; 827 2222 2227; 828 2228 2192; 829 2207 2228;
830 2229 2228; 831 2206 2229; 832 2230 2229; 833 2205 2230; 834 2231 2230;
835 2204 2231; 836 2232 2231; 837 2203 2232; 838 2233 2234; 839 2208 2233;
840 2234 2235; 841 2209 2234; 842 2235 2236; 843 2210 2235; 844 2236 2237;
845 2211 2236; 846 2237 2173; 847 2212 2237; 848 2238 2015; 849 2239 2024;
850 2240 2239; 851 2241 2240; 852 2242 2457; 853 2243 2242; 854 2244 2243;
855 2245 2244; 856 2246 2429; 857 2247 2246; 858 2248 2247; 859 2249 2025;
860 2250 2249; 861 2251 2023; 862 2252 2251; 863 2253 2252; 864 2254 2427;
865 2255 2254; 866 2256 2255; 867 2257 2256; 868 2258 2257; 869 2259 2258;
870 2260 2259; 871 2261 2028; 872 2262 2037; 873 2263 2262; 874 2264 2263;
875 2265 2455; 876 2266 2265; 877 2267 2266; 878 2268 2267; 879 2269 2431;
880 2270 2269; 881 2271 2270; 882 2272 2038; 883 2273 2272; 884 2274 2036;
885 2275 2274; 886 2276 2275; 887 2277 2428; 888 2278 2277; 889 2279 2278;
890 2280 2279; 891 2281 2444; 892 2282 2281; 893 2283 2282; 894 2284 2031;
895 2285 2039; 896 2286 2285; 897 2287 2041; 898 2288 2050; 899 2289 2288;
900 2290 2289; 901 2291 2454; 902 2292 2291; 903 2293 2292; 904 2294 2293;
905 2295 2432; 906 2296 2295; 907 2297 2296; 908 2298 2051; 909 2299 2298;
910 2300 2049; 911 2301 2300; 912 2302 2301; 913 2303 2435; 914 2304 2303;
915 2305 2304; 916 2306 2305; 917 2307 2445; 918 2308 2307; 919 2309 2308;
920 2310 2044; 921 2311 2052; 922 2312 2311; 923 2313 2054; 924 2314 2063;
925 2315 2314; 926 2316 2315; 927 2317 2453; 928 2318 2317; 929 2319 2318;
930 2320 2319; 931 2321 2433; 932 2322 2321; 933 2323 2322; 934 2324 2064;
935 2325 2324; 936 2326 2062; 937 2327 2326; 938 2328 2327; 939 2329 2437;
940 2330 2329; 941 2331 2330; 942 2332 2331; 943 2333 2446; 944 2334 2333;
945 2335 2334; 946 2336 2057; 947 2337 2065; 948 2338 2337; 949 2339 2067;
950 2340 2076; 951 2341 2340; 952 2342 2341; 953 2343 2452; 954 2344 2343;
955 2345 2344; 956 2346 2345; 957 2347 2434; 958 2348 2347; 959 2349 2348;
960 2350 2077; 961 2351 2350; 962 2352 2075; 963 2353 2352; 964 2354 2353;
965 2355 2438; 966 2356 2355; 967 2357 2356; 968 2358 2357; 969 2359 2447;
970 2360 2359; 971 2361 2360; 972 2362 2070; 973 2363 2078; 974 2364 2363;
975 2365 2080; 976 2366 2089; 977 2367 2366; 978 2368 2367; 979 2369 2451;
980 2370 2369; 981 2371 2370; 982 2372 2371; 983 2373 2441; 984 2374 2373;
985 2375 2374; 986 2376 2090; 987 2377 2376; 988 2378 2088; 989 2379 2378;
990 2380 2379; 991 2381 2439; 992 2382 2381; 993 2383 2382; 994 2384 2383;
995 2385 2448; 996 2386 2385; 997 2387 2386; 998 2388 2083; 999 2389 2091;
1000 2390 2389; 1001 2391 2093; 1002 2392 2099; 1003 2393 2392; 1004 2394 2393;
1005 2395 2394; 1006 2396 2395; 1007 2397 2396; 1008 2398 2397; 1009 2399 2442;
1010 2400 2399; 1011 2401 2400; 1012 2402 2100; 1013 2403 2402; 1014 2404 2098;
1015 2405 2404; 1016 2406 2405; 1017 2407 2440; 1018 2408 2407; 1019 2409 2408;
1020 2410 2409; 1021 2411 2449; 1022 2412 2411; 1023 2413 2412; 1024 2414 2094;
1025 2415 2101; 1026 2416 2415; 1027 2417 2103; 1028 2418 2110; 1029 2419 2418;
1030 2420 2450; 1031 2421 2420; 1032 2422 2421; 1033 2257 2122; 1034 2281 2257;
1035 2308 2281; 1036 2335 2308; 1037 2350 2335; 1038 2377 2350; 1039 2391 2377;
1040 2258 2123; 1041 2282 2258; 1042 2309 2282; 1043 2324 2309; 1044 2351 2324;
1045 2365 2351; 1046 2259 2124; 1047 2283 2259; 1048 2298 2283; 1049 2325 2298;
1050 2339 2325; 1051 2260 2125; 1052 2272 2260; 1053 2299 2272; 1054 2313 2299;
1055 2249 2126; 1056 2273 2249; 1057 2287 2273; 1058 2250 2127; 1059 2261 2250;
1060 2238 2128; 1061 2242 2142; 1062 2266 2242; 1063 2293 2266; 1064 2320 2293;
1065 2347 2320; 1066 2374 2347; 1067 2401 2374; 1068 2243 2143; 1069 2267 2243;
1070 2294 2267; 1071 2321 2294; 1072 2348 2321; 1073 2375 2348; 1074 2244 2144;
1075 2268 2244; 1076 2295 2268; 1077 2322 2295; 1078 2349 2322; 1079 2245 2145;
1080 2269 2245; 1081 2296 2269; 1082 2323 2296; 1083 2246 2146; 1084 2270 2246;
1085 2297 2270; 1086 2247 2147; 1087 2271 2247; 1088 2248 2148; 1089 2409 2150;
1090 2382 2409; 1091 2355 2382; 1092 2328 2355; 1093 2301 2328; 1094 2274 2301;
1095 2408 2151; 1096 2381 2408; 1097 2354 2381; 1098 2327 2354; 1099 2300 2327;
1100 2407 2152; 1101 2380 2407; 1102 2353 2380; 1103 2326 2353; 1104 2406 2153;
1105 2379 2406; 1106 2352 2379; 1107 2405 2154; 1108 2378 2405; 1109 2404 2155;
1110 2395 2157; 1111 2368 2395; 1112 2341 2368; 1113 2314 2341; 1114 2312 2314;
1115 2285 2312; 1116 2394 2158; 1117 2367 2394; 1118 2340 2367; 1119 2338 2340;
1120 2311 2338; 1121 2284 2311; 1122 2393 2159; 1123 2366 2393; 1124 2364 2366;
1125 2337 2364; 1126 2310 2337; 1127 2392 2160; 1128 2390 2392; 1129 2363 2390;
1130 2336 2363; 1131 2416 2161; 1132 2389 2416; 1133 2362 2389; 1134 2415 2162;
1135 2388 2415; 1136 2414 2163; 1137 2420 2191; 1138 2410 2420; 1139 2383 2410;
1140 2356 2383; 1141 2329 2356; 1142 2302 2329; 1143 2275 2302; 1144 2251 2275;
1145 2417 2213; 1146 2403 2417; 1147 2376 2403; 1148 2361 2376; 1149 2334 2361;
1150 2307 2334; 1151 2280 2307; 1152 2256 2280; 1153 2419 2214; 1154 2402 2419;
1155 2387 2402; 1156 2360 2387; 1157 2333 2360; 1158 2306 2333; 1159 2279 2306;
1160 2255 2279; 1161 2418 2215; 1162 2413 2418; 1163 2386 2413; 1164 2359 2386;
1165 2332 2359; 1166 2305 2332; 1167 2278 2305; 1168 2254 2278; 1169 2422 2216;
1170 2412 2422; 1171 2385 2412; 1172 2358 2385; 1173 2331 2358; 1174 2304 2331;
1175 2277 2304; 1176 2253 2277; 1177 2421 2217; 1178 2411 2421; 1179 2384 2411;
1180 2357 2384; 1181 2330 2357; 1182 2303 2330; 1183 2276 2303; 1184 2252 2276;
1185 2241 2218; 1186 2265 2241; 1187 2292 2265; 1188 2319 2292; 1189 2346 2319;
1190 2373 2346; 1191 2400 2373; 1192 2240 2219; 1193 2264 2240; 1194 2291 2264;
1195 2318 2291; 1196 2345 2318; 1197 2372 2345; 1198 2399 2372; 1199 2239 2220;
1200 2263 2239; 1201 2290 2263; 1202 2317 2290; 1203 2344 2317; 1204 2371 2344;
1205 2398 2371; 1206 2262 2425; 1207 2289 2262; 1208 2316 2289; 1209 2343 2316;
1210 2370 2343; 1211 2397 2370; 1212 2286 2424; 1213 2288 2286; 1214 2315 2288;
1215 2342 2315; 1216 2369 2342; 1217 2396 2369; 1218 2131 299; 1219 299 2017;
1220 2017 2030; 1221 2030 2043; 1222 2043 2056; 1223 2056 2069; 1224 2069 2082;
1225 2082 2113; 1226 2113 2116; 1227 2116 2140; 1228 2137 2106; 1229 2106 2096;
1230 2096 2086; 1231 2086 2073; 1232 2073 2060; 1233 2060 2047; 1234 2047 2034;
1235 2034 2021; 1236 2021 310; 1237 310 2134; 1238 2423 2018; 1239 2424 2026;
1240 2423 2285; 1241 2424 2222; 1242 2425 2424; 1243 2425 2221; 1244 2426 2205;
1245 2427 2253; 1246 2428 2276; 1247 2429 2245; 1248 2430 2146; 1249 2431 2268;
1250 2432 2294; 1251 2433 2320; 1252 2434 2346; 1253 2435 2302; 1254 2436 2154;
1255 2437 2328; 1256 2438 2354; 1257 2439 2380; 1258 2440 2406; 1259 2441 2372;
1260 2442 2398; 1261 2443 2211; 1262 2444 2280; 1263 2445 2306; 1264 2446 2332;
1265 2447 2358; 1266 2448 2384; 1267 2449 2410; 1268 2450 2150; 1269 2451 2368;
1270 2452 2342; 1271 2453 2316; 1272 2454 2290; 1273 2455 2264; 1274 2456 2142;
1275 2457 2241;
DEFINE MATERIAL START
ISOTROPIC CONCRETE
E 2.21467e+006
POISSON 0.17
DENSITY 2.5
ALPHA 1e-005
DAMP 0.05
**********
ISOTROPIC CONCRETE1
E 2.21467e+006
POISSON 0.17
DENSITY 0
ALPHA 1e-005
DAMP 0.05
END DEFINE MATERIAL
CONSTANTS
MATERIAL CONCRETE MEMB 1 8 117 507 TO 512 514 515 519 TO 524 526 527 -
531 TO 536 538 539 543 TO 548 550 551 555 TO 560 562 563 567 TO 572 574 575 -
579 581 TO 585 588 TO 594 597 TO 601 603 606 608 TO 631 638 640 642 644 646 -
648 650 652 666 668 670 672 674 676 678 680 682 684 686 688 690 692 694 696 -
698 700 702 704 706 708 710 746 788 TO 797 808 810 812 814 848 TO 959 961 -
962 TO 1032 1238 1239 1242 1244 TO 1275
MATERIAL CONCRETE1 MEMB 7 128 495 506 513 516 TO 518 525 528 TO 530 537 540 -
541 TO 542 549 552 TO 554 561 564 TO 566 573 576 TO 578 580 586 587 595 596 -
602 604 605 607 632 TO 637 639 641 643 645 647 649 651 653 TO 665 667 669 -
671 673 675 677 679 681 683 685 687 689 691 693 695 697 699 701 703 705 707 -
709 711 TO 745 748 TO 785 798 TO 807 809 811 813 815 817 TO 847 960 1033 -
1034 TO 1237 1240 1241 1243
MEMBER PROPERTY AMERICAN
519 521 531 533 543 545 555 557 567 569 579 581 588 590 849 TO 858 -
861 TO 870 872 TO 881 884 TO 893 898 TO 907 910 TO 919 924 TO 933 -
936 TO 945 950 TO 959 962 TO 971 976 TO 985 988 TO 997 1002 TO 1011 1014 -
1015 TO 1023 1245 TO 1247 1249 TO 1253 1255 TO 1260 1262 TO 1267 1269 TO 1273 -
1275 PRIS AX 1.658 IX 0.001 IY 0.001 IZ 1.476
MEMBER PROPERTY AMERICAN
512 514 515 522 524 526 527 534 536 538 539 546 548 550 551 558 560 562 563 -
570 572 574 575 582 584 585 591 603 848 871 894 897 920 923 946 949 972 975 -
998 1001 1024 1238 PRIS AX 2.51 IX 0.001 IY 0.001 IZ 1.89
520 523 532 535 544 547 556 559 568 571 583 589 592 859 860 882 883 895 896 -
908 909 921 922 934 935 947 948 961 973 974 986 987 999 1000 1012 1013 1025 -
1026 1239 1242 PRIS AX 2.084 IX 0.001 IY 0.001 IZ 1.683
507 509 597 599 638 640 642 644 646 666 668 670 672 674 676 678 680 682 684 -
686 688 690 692 694 696 698 700 702 704 788 TO 797 808 810 1030 TO 1032 1244 -
1248 1254 1261 1268 1274 PRIS AX 1.796 IX 0.001 IY 0.001 IZ 1.1559
1 8 117 510 593 594 600 606 652 710 746 -
1027 PRIS AX 2.648 IX 0.001 IY 0.001 IZ 2.014
508 511 598 601 648 650 706 708 812 814 1028 -
1029 PRIS AX 2.222 IX 0.001 IY 0.001 IZ 1.786
624 TO 631 PRIS AX 0.847 IX 0.001 IY 0.001 IZ 0.501
608 TO 623 PRIS AX 2.345 IX 0.001 IY 0.001 IZ 2.025
641 643 645 647 649 651 653 669 671 673 675 677 679 681 683 685 687 689 691 -
693 695 699 701 703 705 707 709 711 713 715 717 719 721 723 725 731 733 735 -
737 739 741 743 749 751 753 755 757 759 761 771 773 775 777 779 781 783 1040 -
1041 TO 1060 1068 TO 1109 1116 TO 1136 PRIS YD 0.24 ZD 1.17
580 639 667 697 727 729 763 765 767 769 960 1033 TO 1039 1061 TO 1067 1110 -
1111 TO 1115 1137 TO 1144 1240 PRIS YD 0.24 ZD 1.235
799 801 803 805 807 809 811 813 815 817 819 821 823 825 827 829 831 833 835 -
837 839 841 843 845 847 1145 TO 1217 1241 1243 PRIS YD 0.24 ZD 1.3
745 785 PRIS YD 0.24 ZD 0.79
636 637 654 TO 665 712 714 716 718 720 722 724 726 728 730 732 734 736 738 -
740 742 744 748 750 752 754 756 758 760 762 764 766 768 770 772 774 776 778 -
780 782 784 798 800 802 804 806 818 820 822 824 826 828 830 832 834 836 838 -
840 842 844 846 PRIS AX 0.001 IX 0.001 IY 0.001 IZ 0.001
632 TO 635 PRIS YD 0.4 ZD 0.4
1218 TO 1237 PRIS YD 0.4 ZD 0.4
513 516 TO 518 525 528 TO 530 537 540 TO 542 549 552 TO 554 561 564 TO 566 -
573 576 TO 578 586 587 602 604 PRIS YD 0.4 ZD 2.9
7 128 495 506 595 596 605 607 PRIS YD 0.4 ZD 3.475
SUPPORTS
1008 2008 2014 2018 2027 2031 2040 2044 2053 2057 2066 2070 2079 2083 2092 -
2094 2102 2104 PINNED
LOAD 1 LOADTYPE None TITLE DL
SELFWEIGHT Y -1.02 LIST ALL
LOAD 2 LOADTYPE None TITLE SIDL OTHERS
MEMBER LOAD
636 637 654 TO 665 712 714 716 718 720 722 724 726 728 730 732 734 736 738 -
740 742 744 748 750 752 754 756 758 760 762 764 766 768 770 772 774 776 778 -
780 782 784 798 800 802 804 806 818 820 822 824 826 828 830 832 834 836 838 -
840 842 844 846 UNI GY -1
LOAD 3 LOADTYPE None TITLE SIDL WC
MEMBER LOAD
512 TO 592 602 TO 604 848 TO 1026 1238 1239 1242 1245 TO 1247 1249 TO 1253 -
1255 TO 1260 1262 TO 1267 1269 TO 1273 1275 UNI GY -0.58
1 7 8 117 128 495 506 TO 511 593 TO 601 605 TO 607 638 640 642 644 646 648 -
650 652 666 668 670 672 674 676 678 680 682 684 686 688 690 692 694 696 698 -
700 702 704 706 708 710 746 788 TO 797 808 810 812 814 1027 TO 1032 1244 -
1248 1254 1261 1268 1274 UNI GY -0.595
PERFORM ANALYSIS
FINISH
Summary of Loads

Clear Span= 34.350 m

70R : Impact has been considered while designing the Girder


(As per Cl.211.7 IRC-6,2014)
Impact Percentage: 12.0%
Impact Factor = (1+0.12) = 1.120

Class-A : Impact has been considered while designing T Girder


(As per Cl.211.7 IRC-6,2014)
Impact Factor= = 1.112

Reduction factor for 4 lane load 0.800


BENDING MOMENTS:

OUTER GIRDER {OG1} CRASH BARRIER SIDE


TYPE OF LOADING AT END SPAN
Deff (2m) L/8 (4.0m) L/4 (8.973m) 3L/7 (12.974m) L/2 (17.17m)
KNm KNm KNm KNm KNm

1 LANE 70R WHEEL MOST ECCENTRIC 802.00 1475.00 2395.00 2855.00 2891.00

1 LANE OF 70R TRACK MOST ECCENTRIC 658.00 1211.00 1971.00 2341.00 2358.00

2 LANE CLASS A MOST ECCENTRIC 690.00 1313.00 2245.00 2633.00 2645.00

70R 140.00 280.00 570.00 880.00 1135.00


70R wheel MOST ECC + 70R . AT 7.25 M GAP
70R 802.00 1475.00 2395.00 2855.00 2891.00
TOTAL 898.24 1652.00 2682.40 3340.59 3599.60

INNER GIRDER {IG}


TYPE OF LOADING Deff (2m) L/8 (4.0m) L/4 (8.973m) 3L/7 (12.974m) L/2 (17.17m)
KNm KNm KNm KNm KNm

1 LANE 70R WHEEL PLACED CENTRALLY ON IG 992.00 1695.00 2440.00 2594.00 1814.00

1 LANE 70R WHEEL PLACED(ONE WHEEL) ON IG 865.00 1518.00 2325.00 2522.00 2075.00

70R 975.00 1551.00 2136.00 2233.00 1725.00


1 LANE 70R WHEEL +1 LANE 70R PLACED AT 1.2m
DISTANCE
70R 374.00 574.00 855.00 1096.00 1347.00

70R TRACKED PLACED CENTRALLY ON IG 536.00 1470.00 2123.00 2233.00 1665.00

2-LANE OF CLASS A CENTRALLY PLACED 580.00 1100.00 1865.00 2128.00 1984.00

TOTAL 1206.17 1900.11 2732.80 2975.35 2743.38


SHEAR FORCE :

OUTER GIRDER {OG1} CRASH BARRIER SIDE


TYPE OF LOADING AT END SPAN
Deff (2m) L/8 (4.0m) L/4 (8.973m) 3L/7 (12.974m) L/2 (17.17m)
KN KN KN KN KN

1 LANE 70R WHEEL MOST ECCENTRIC 408.00 354.00 276.00 200.00 241.00

1 LANE OF 70R TRACK MOST ECCENTRIC 333.00 290.00 232.00 170.00 207.00

2 LANE CLASS A MOST ECCENTRIC 336.00 297.00 230.00 145.00 158.00

70R 72.00 70.00 69.00 64.00 75.00


70R wheel MOST ECC +70R wheel . AT 7.25 M
GAP
70R 408.00 354.00 276.00 200.00 241.00

TOTAL 456.96 396.48 309.12 236.11 282.63

INNER GIRDER{IG}
TYPE OF LOADING Deff (2m) L/8 (4.0m) L/4 (8.973m) 3L/7 (12.974m) L/2 (17.17m)
KNm KNm KNm KNm KNm

1 LANE 70R WHEEL PLACED CENTRALLY ON IG 470.00 365.00 242.00 256.00 373.00

1 LANE 70R WHEEL PLACED(ONE WHEEL) ON IG 425.00 348.00 245.00 216.00 305.00

1 LANE 70R WHEEL +70R PLACED AT 1.2m 70R 415.00 300.00 190.00 179.00 263.00
DISTANCE
70R 123.00 91.00 66.50 66.00 95.00

70R TRACKED PLACED CENTRALLY ON IG 402.00 316.00 225.00 265.00 346.00

2-LANE OF CLASS A CENTRALLY PLACED 295.00 251.00 190.00 115.00 176.00

TOTAL 476.00 389.76 274.40 296.13 394.49

SUMMARY OF BENDING MOMENT AND SHEAR FORCE (INNER GIRDER)-IG

Location
SL. No. Item Deff from Span (L/8) Span (L/4) Span Span
support (3L/8) (L/2)
t-m t-m t-m t-m t-m
Bending Moments
1 Stage 1 Loading 76.1 146.0 258.0 334.0 355.0

2 Stage 2 Loading 59.0 111.0 197.5 258.6 279.5

3 Shuttering Load 22.5 42.2 74.6 96.5 102.7

4 SIDL crash barrier ( Moment) 3.8 4.7 20.3 53.8 96.6


From STAAD
5 SIDL W/C ( Moment) 19.7 37.4 66.7 87.5 94.7 Output

6 123.1 193.9 278.9 303.6 279.9


Due to Live Load (Moment)
129.23 203.58 292.80 318.79 293.93
Shear Forces
ton ton ton ton ton
1 Stage 1 Loading 38.6 31.7 21.6 10.1 0.0

2 Stage 2 Loading 27.7 24.3 17.0 8.7 1.3

3 Shuttering Load 10.6 9.2 6.2 2.9 0.0

4 SIDL crash barrier ( Moment) 1.7 2.3 5.7 8.8 10.7


From STAAD
Output

5 SIDL W/C ( Moment) 9.5 8.3 5.7 3.0 0.0

6 47.6 39.0 27.4 29.6 39.4


Due to Live Load (Shear)
49.98 40.92 28.81 31.09 41.42
SUMMARY OF BENDING MOMENT AND SHEAR FORCE (OUTER GIRDER)-OG1

Location
SL. No. Item Deff from Span (L/8) Span (L/4) Span Span
support (3L/8) (L/2)
t-m t-m t-m t-m t-m
Bending Moments
1 Stage 1 Loading 76.1 146.0 258.0 334.0 355.0

2 Stage 2 Loading 77.5 145.4 256.8 332.1 353.2

3 Shuttering Load 27.0 50.6 89.4 115.6 123.0

4 SIDL crash barrier ( Moment) 30.2 53.7 82.3 82.9 60.8

From STAAD
Output
5 SIDL W/C ( Moment) 16.8 31.6 55.1 69.4 71.5

6 89.8 165.2 268.2 334.1 360.0


Due to Live Load (Moment)
94.32 173.46 281.65 350.76 377.96
Shear Forces
ton ton ton ton ton
1 Stage 1 Loading 38.6 31.7 21.6 10.1 0.0

2 Stage 2 Loading 36.3 31.6 21.5 10.1 0.0

3 Shuttering Load 12.7 11.0 7.5 3.5 0.0

4 SIDL(Shear) 13.0 9.0 4.2 4.0 10.1

From STAAD
Output
5 SIDL W/C ( Moment) 8.0 7.0 4.4 1.6 0.9

6 45.7 39.6 30.9 23.6 28.3


Due to Live Load (Shear)
47.98 41.63 32.46 24.79 29.68
Cable Forces outer girder
Cable No 1

Jacking Force 272.187


Symmetrical Cable

X Y Z Slope y Slope z Deviation Length Pfriction Pslip


0 0.400 0.000 -0.078 0.000 272.2 237.7
3 0.167 0.000 -0.078 0.000 0.000 3.009 270.6 239.3
4.2 0.120 0.000 0.000 0.000 0.078 1.201 266.4 243.5
4.5 0.120 0.000 0.000 0.000 0.000 0.300 266.2 243.6
6.3 0.120 -0.060 0.000 -0.067 0.067 1.801 262.3 247.6
7.2 0.120 -0.120 0.000 -0.067 0.000 0.902 261.8 248.1
9 0.120 -0.180 0.000 0.000 0.067 1.801 257.9 251.9
16.8075 0.120 -0.180 0.000 0.000 0.000 7.808 253.9 253.9
16.821
Length of Cable 33.643

Null point 16.82


Pmin 253.9

Pslipleft 254.9216 Xslipleft 14.8250


Pslipright 254.9 Xslipright 18.7900

Cable No 2

Jacking Force 272.187


Symmetrical Cable

X Y Z Slope y Slope z Deviation Length Pfriction Pslip


0 0.800 0.000 -0.084 0.000 272.2 239.8
4.5 0.422 0.000 -0.084 0.000 0.000 4.516 269.7 242.2
6.3 0.271 0.060 -0.084 0.067 0.067 1.807 265.7 246.2
7.2 0.196 0.120 -0.084 0.067 0.000 0.905 265.3 246.7
7.5 0.170 0.138 -0.084 0.056 0.011 0.302 264.6 247.4
8.7 0.120 0.178 0.000 0.011 0.128 1.202 258.3 253.7
9 0.120 0.180 0.000 0.000 0.011 0.300 257.7 254.3
16.8075 0.120 0.180 0.000 0.000 0.000 7.808 253.7 253.7
16.839
Length of Cable 33.678

Null point 16.84


Pmin 253.7

Pslipleft 255.9808 Xslipleft 12.2520


Pslipright 256.0 Xslipright 21.3630
Cable No 3

Jacking Force 272.187


Symmetrical Cable

X Y Z Slope y Slope z Deviation Length Pfriction Pslip


0 1.200 0.000 -0.110 0.000 272.2 246.0
9.2 0.186 0.000 -0.110 0.000 0.000 9.256 267.2 251.0
10.4 0.120 0.000 0.000 0.000 0.110 1.202 261.6 256.6
16.8075 0.120 0.000 0.000 0.000 0.000 6.408 258.3 258.3
16.865
Length of Cable 33.730

Null point 16.87


Pmin 258.3

Pslipleft 259.108 Xslipleft 15.1973


Pslipright 259.1 Xslipright 18.4177

Cable No 4

Jacking Force 186.233


Symmetrical Cable

X Y Z Slope y Slope z Deviation Length Pfriction Pslip


0 1.600 0.000 -0.112 0.000 186.2 169.2
11 0.367 0.000 -0.112 0.000 0.000 11.069 182.2 173.2
12.2 0.300 0.000 0.000 0.000 0.112 1.202 178.3 177.1
16.8075 0.300 0.000 0.000 0.000 0.000 4.608 176.7 176.7
16.878
Length of Cable 33.756

Null point 16.88


Pmin 176.7

Pslipleft 177.6922 Xslipleft 13.8768


Pslipright 247.0 Xslipright 19.7382
Stress Check for Outer Girder
Basic Design Data

Characteristics value of prestressing 0.9

1st stage prestressing 14 day


2nd stage prestressing 28 day
Casting of Deck Slab 28 day
3rd stage prestressing 90 day
Shift of Bearing 90 day
SIDL(Wearing Coat & Crash Barrier) 90 day
Age of deck slab at time of 3rd stage 62 day

Fck 50 Mpa
Modulus of Elasticity (Conc) 14th Day 3.30E+06 t/m2
Modulus of Elasticity (Conc) 28th Day 3.40E+06 t/m2
Modulus of Elasticity (Conc) 28th Day 3.40E+06 t/m2
Modulus of Elasticity (Conc) 90th Day 3.51E+06 t/m2
Modulus of Elasticity (Strands) 1.95E+07 t/m2

Type of cables 19 T13


Area of 1 strand 0.0000987 m2
Area of one cable 1.8753E-03 m2
no of cables stressed in 1st stage 3.68
no of cables stressed in 2nd stage 0.001
no of tendons stressed in 3rd stage 0.00
Jacking Force 0.765 *UTS
No of Sections to be checked 5
Prestressing force per cable (UTS) 355.8 t
Increase Factors for losses
Elastic Shortening loss 1.0
Relaxation loss 1.0
Shrinkage loss 1.0
Creep loss 1.0

Factor for Shrinkage loss


14th day 2.47E-04
28th day 2.25E-04
90th day 1.73E-04
90th day 1.73E-04
90th day 1.73E-04
Infinity 1.73E-04

Factor for Creep Loss


14th day 0.00E+00
28th day 1.60E-04
90th day 2.61E-04
90th day 2.61E-04
90th day 2.61E-04
Infinity 5.45E-04

Factor for Relaxation Loss


1000hr relaxation 2.50%

Total Relaxation Loss at service condition (cl: 6.3.6 IRC 112) = 3 x (1000 hr. value)
Initial force after Friction, slip & ES loss = 898.46 t
Percentage of Initial force = 0.6854 UTS
Relaxation Loss at 1000hr. for low relaxation steel = 2.32 % of initial stress
Relaxation Loss at 1000hr. for low relaxation steel = 5.65 t/Cable
Immediate Loss i.e 1 hr. of stressing (Table 6.3 IRC:112) = 34 % of Total Loss
7 - 28 days Loss = 90 % of Total Loss
28 - 90 days Loss = 100 % of Total Loss
90 - a days Loss = 200 % of Total Loss
Immediate Loss i.e 1 hr. of stressing = 1.92 t/Cable
7 - 28 days Loss = 3.17 t/Cable
28 - 90 days Loss = 0.57 t/Cable
90 - a days Loss = 11.30 t/Cable
Strain due to differential shrinkage and creep 1.00E-04
Reduction factor due to differential creep 0.43
PSC BEAM AND RC SLAB STRUCTURE OF SIMPLY SUPPORTED SPAN
(OUTER GIRDER)
Item Unit 1 2 3 4 5
MEMBER NO
distance of Section from left support m 2.000 4.000 8.973 12.974 17.175

Details of Section property (Individual Beam Section)


Area of the section m2 1.8142 1.3881 0.9620 0.9620 0.9620
Depth of the section m 2.5000 2.5000 2.5000 2.5000 2.5000
CG of section from bottom m 1.2752 1.2560 1.2367 1.2367 1.2367
Moment of Inertia of section m4 0.9769 0.8383 0.6998 0.6998 0.6998

Details of Section property (Composite Section)


Area of the section m2 2.6482 2.2221 1.7960 1.7960 1.7960
Depth of the section m 2.7400 2.7400 2.7400 2.7400 2.7400
CG of section from bottom m 1.6987 1.7889 1.8791 1.8791 1.8791
Moment of Inertia of section m4 2.0141 1.7864 1.5586 1.5586 1.5586

Details of Section property (Composite Section)


Area of the section m2 2.6482 2.2221 1.7960 1.7960 1.7960
Depth of the section m 2.7400 2.7400 2.7400 2.7400 2.7400
CG of section from bottom m 1.6987 1.7889 1.8791 1.8791 1.8791
Moment of Inertia of section m4 2.0141 1.7864 1.5586 1.5586 1.5586

Details of Stage I prestressing after 14 day For Cable 1a/1


Prestressing Force (P1) (Hor) T 237.83 241.35 251.07 253.79 253.92
CG of Tendons from Bottom m 0.27 0.13 0.12 0.12 0.12
Prestressing Force (P1) (Ver) T 18.50 8.86 0.00 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1b/2


Prestressing Force (P1) (Hor) T 239.82 240.90 253.17 255.80 253.66
CG of Tendons from Bottom m 0.66 0.50 0.12 0.12 0.12
Prestressing Force (P1) (Ver) T 20.13 20.22 1.69 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1c/3


Prestressing Force (P1) (Hor) T 245.44 246.52 249.19 257.76 258.28
CG of Tendons from Bottom m 1.02 0.80 0.25 0.12 0.12
Prestressing Force (P1) (Ver) T 27.05 27.17 27.46 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1d/4


Prestressing Force (P1) (Hor) T 168.71 169.45 171.28 177.24 176.66
CG of Tendons from Bottom m 1.42 1.19 0.64 0.30 0.30
Prestressing Force (P1) (Ver) T 18.91 18.99 19.19 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1e/5


Prestressing Force (P1) (Hor) T 0.00 0.00 0.00 0.00 0.00
CG of Tendons from Bottom m 0.00 0.00 0.00 0.00 0.00
Prestressing Force (P1) (Ver) T 0.00 0.00 0.00 0.00 0.00
PSC BEAM AND RC SLAB STRUCTURE OF SIMPLY SUPPORTED SPAN
(OUTER GIRDER)
Item Unit 1 2 3 4 5
MEMBER NO
distance of Section from left support m 2.000 4.000 8.973 12.974 17.175
Details of Stage II prestressing after 28 day For Cable 2a
Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2b


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2c


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2d


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2e


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage III prestressing after 90th day


Prestressing Force (P3) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P3) (Ver) T 0.01 0.01 0.01 0.01 0.01
PSC BEAM AND RC SLAB STRUCTURE OF SIMPLY SUPPORTED SPAN
(OUTER GIRDER)
Item Unit 1 2 3 4 5
MEMBER NO
distance of Section from left support m 2.000 4.000 8.973 12.974 17.175

Dead Load - Ist stage


Moments Tm 76.1 146.0 258.0 334.0 355.0
Shear T 38.6 31.7 21.6 10.1 0.0

Dead Load - Ist stage due to permanent bearing


Moments Tm 86.3 157.0 269.0 344.0 365.0
Shear T 38.6 31.7 21.6 10.1 0.0

Dead Load - Ist stage due to shift of bearing


Moments Tm 10.2 11.0 11.0 10.0 10.0
Shear T 0.0 0.0 0.0 0.0 0.0

Construction load/Shuttering load


Moments Tm 27.0 50.6 89.4 115.6 123.0
shear 12.7 11.0 7.5 3.5 0.0

Dead Load - 2nd stage


Moments Tm 77.5 145.4 256.8 332.1 353.2
Shear T 36.3 31.6 21.5 10.1 0.0

SIDL
Moments Tm 47.0 85.3 137.4 152.3 132.3
Shear T 21.0 16.0 8.6 5.6 11.0

Live Load (Sagging) (max Moment Case & max Positive Shear case)
Moments Tm 94.3 173.5 281.7 350.8 378.0
Shear T 48.0 41.6 32.5 24.8 29.7

Stress due to Temp (Rise) (Eigen stresses)


top of deck slab T/m2 209.37 209.37 207.25 206.99 206.99
top of girder T/m2 -130.13 -130.13 -134.36 -134.57 -134.57
bottom T/m2 158.80 158.80 132.57 132.85 132.85

Stress due to Temp (Fall) (Eigen Stresses)


top of deck slab T/m2 -301.87 -301.87 -316.30 -127.00 -127.00
top of girder T/m2 -90.19 -90.19 -105.27 59.00 59.00
bottom T/m2 -109.29 -109.29 -131.10 -128.00 -128.00
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Details of Section property (Individual Beam Section)

2
Area of the section m 1.8142 1.38808125 0.96196 0.961963 0.9619625
Depth of the section m 2.500 2.500 2.500 2.500 2.500
CG of section from bottom m 1.2752406 1.255953054 1.23667 1.236665 1.236665476
4
Inertia of section m 0.9769032 0.838329327 0.69976 0.699755 0.699755494
3
Top Section Modulus m 0.7976 0.6739 0.5539 0.5539 0.5539
3
Bottom Section Modulus m 0.7661 0.6675 0.5658 0.5658 0.5658

Details of Section property (Composite Section) (62 day old slab)

2
Area of the section m 2.6482 2.22208125 1.79596 1.795963 1.7959625
Depth of the section m 2.740 2.740 2.740 2.740 2.740
CG of section from bottom m 1.6987469 1.788899142 1.87905 1.879051 1.879051379
4
Inertia of section m 2.0141187 1.786355282 1.55859 1.558592 1.558591853
3
Top Section Modulus m 1.9343 1.8782 1.8103 1.8103 1.8103
3
Bottom Section Modulus m 1.1856 0.9986 0.8295 0.8295 0.8295

Details of Section property (Composite Section)

2
Area of the section m 2.6482 2.22208125 1.79596 1.795963 1.7959625
Depth of the section m 2.740 2.740 2.740 2.740 2.740
CG of section from bottom m 1.6987469 1.788899142 1.87905 1.879051 1.879051379
4
Inertia of section m 2.0141187 1.786355282 1.55859 1.558592 1.558591853
3
Top Section Modulus m 1.9343 1.8782 1.8103 1.8103 1.8103
3
Bottom Section Modulus m 1.1856 0.9986 0.8295 0.8295 0.8295

Details of Stage I prestressing


For Cable 1a
No of Tendons of 19T13 1.00 1.00 1.00 1.00 1.00
Prestressing Force (P1) T 237.83 241.35 251.07 253.79 253.92
CG of Tendons from Bottom m 0.2730 0.1304 0.1200 0.1200 0.1200
Eccentricity of Tendons m 1.0023 1.1255 1.1167 1.1167 1.1167
Prestressing Factor (Top) -0.7053 -0.9498 -0.9765 -0.9765 -0.9765
Prestressing Factor (Bottom) 1.8595 2.4066 3.0130 3.0130 3.0130

For Cable 1b
No of Tendons of 19T13 1.00 1.00 1.00 1.00 1.00
Prestressing Force (P1) T 239.82 240.90 253.17 255.80 253.66
CG of Tendons from Bottom m 0.6629 0.4950 0.1203 0.1200 0.1200
Eccentricity of Tendons m 0.6123 0.7609 1.1163 1.1167 1.1167
Prestressing Factor (Top) -0.2165 -0.4088 -0.9759 -0.9765 -0.9765
Prestressing Factor (Bottom) 1.3505 1.8604 3.0124 3.0130 3.0130

For Cable 1c
No of Tendons of 19T13 1.00 1.00 1.00 1.00 1.00
Prestressing Force (P1) T 245.44 246.52 249.19 257.76 258.28
CG of Tendons from Bottom m 1.0200 0.7996 0.2516 0.1200 0.1200
Eccentricity of Tendons m 0.2552 0.4563 0.9851 1.1167 1.1167
Prestressing Factor (Top) 0.2313 0.0433 -0.7389 -0.9765 -0.9765
Prestressing Factor (Bottom) 0.8843 1.4041 2.7805 3.0130 3.0130
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

For Cable 1d
No of Tendons of 19T13 0.68 0.68 0.68 0.68 0.68
Prestressing Force (P1) T 168.71 169.45 171.28 177.24 176.66
CG of Tendons from Bottom m 1.4170 1.1929 0.6355 0.3000 0.3000
Eccentricity of Tendons m -0.1418 0.0631 0.6011 0.9367 0.9367
Prestressing Factor (Top) 0.7289 0.6268 -0.0457 -0.6515 -0.6515
Prestressing Factor (Bottom) 0.3662 0.8150 2.1019 2.6949 2.6949

For Cable 1e
No of Tendons of 19T13 0.00 0.00 0.00 0.00 0.00
Prestressing Force (P1) T 0.00 0.00 0.00 0.00 0.00
CG of Tendons from Bottom m 0.0000 0.0000 0.0000 0.0000 0.0000
Eccentricity of Tendons m 1.2752 1.2560 1.2367 1.2367 1.2367
Prestressing Factor (Top) -1.0476 -1.1434 -1.1931 -1.1931 -1.1931
Prestressing Factor (Bottom) 2.2159 2.6020 3.2251 3.2251 3.2251

Combination of Stage 1 Cables


No of Tendons of 19T13 3.68 3.68 3.68 3.68 3.68
Prestressing Force (P1) T 891.79 898.22 924.71 944.59 942.51
CG of Tendons from Bottom m 0.7999 0.6123 0.2510 0.1538 0.1537
Eccentricity of Tendons m 0.4754 0.6437 0.9856 1.0829 1.0829
Prestressing Factor (Top) -0.0448 -0.2347 -0.7399 -0.9155 -0.9156
Prestressing Factor (Bottom) 1.1718 1.6847 2.7814 2.9533 2.9534

Dead Load Moments - Ist stage Tm 76.10 146.00 258.00 334.00 355.00

Stress Due to dead load


2
Top T/m 95.41 216.66 465.79 603.00 640.91
2
Bottom T/m -99.34 -218.73 -455.96 -590.27 -627.39

Eloss of cable (1a) for stressing of (1a) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1a) for stressing of (1b) T 6.04 6.04 6.04 6.04 6.04
Eloss of cable (1a) for stressing of (1c) T 5.50 5.50 5.50 5.50 5.50
Eloss of cable (1a) for stressing of (1d) T 2.98 2.98 2.98 2.98 2.98
Eloss of cable (1a) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1b) for stressing of (1b) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1b) for stressing of (1c) T 5.38 5.38 5.38 5.38 5.38
Eloss of cable (1b) for stressing of (1d) T 2.99 2.99 2.99 2.99 2.99
Eloss of cable (1b) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1c) for stressing of (1c) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1c) for stressing of (1d) T 2.94 2.94 2.94 2.94 2.94
Eloss of cable (1c) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1d) for stressing of (1d) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1d) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1e) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00

Total Eloss for Stage 1 cables T 25.83 25.83 25.83 25.83 25.83
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Stress after stressing of 1a


2
Top T/m -150.97 -203.30 -209.01 -209.01 -209.01
2
Bottom T/m 398.03 515.13 644.92 644.92 644.92
2
Stress at CG of 1a T/m 338.08 477.64 603.93 603.93 603.93
2
Avg stress for each segment T/m 407.86 540.79 603.93 603.93 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Average Stress at CG of 1a T/m 557.40

Stress after stressing of 1b


2
Top T/m -193.87 -286.77 -426.07 -428.51 -426.63
2
Bottom T/m 679.42 905.42 1314.94 1322.20 1316.41
2
Stress at CG of 1a T/m 584.06 843.21 1231.37 1238.17 1232.74
2
Avg stress for each segment T/m 713.64 1037.29 1234.77 1235.45 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1a T/m 544.16
2
Stress at CG of 1b T/m 447.86 669.36 1231.15 1238.17 1232.74
2
Avg stress for each segment T/m 558.61 950.25 1234.66 1235.45 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Average Stress at CG of 1b T/m 1052.58
Check Eloss of cable (1a) for (1b) T 6.04

Stress after stressing of 1c


2
Top T/m -138.24 -270.49 -582.22 -645.47 -644.05
2
Bottom T/m 859.02 1196.00 1909.01 1991.66 1987.27
2
Stress at CG of 1a T/m 750.12 1119.49 1789.43 1865.07 1860.96
2
Avg stress for each segment T/m 934.80 1454.46 1827.25 1863.02 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
Increase in Average Stress at CG of 1a T/m2 495.80
2
Stress at CG of 1b T/m 594.58 905.63 1789.11 1865.07 1860.96
2
Avg stress for each segment T/m 750.11 1347.37 1827.09 1863.02 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1b T/m 485.31
2
Stress at CG of 1c T/m 452.12 726.94 1658.31 1865.07 1860.96
2
Avg stress for each segment T/m 589.53 1192.63 1761.69 1863.02 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Average Stress at CG of 1c T/m 1448.77
Check Eloss of cable (1a) for (1c) T 5.50
Check Eloss of cable (1b) for (1c) T 5.38
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Stress after stressing of 1d


2
Top T/m -25.70 -171.37 -582.07 -741.57 -739.80
2
Bottom T/m 903.65 1305.11 2209.48 2397.38 2391.57
2
Stress at CG of 1a T/m 802.17 1228.07 2075.48 2246.71 2241.27
2
Avg stress for each segment T/m 1015.12 1651.78 2161.10 2243.99 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1a T/m 268.74
2
Stress at CG of 1b T/m 657.22 1012.76 2075.12 2246.71 2241.27
2
Avg stress for each segment T/m 834.99 1543.94 2160.92 2243.99 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1b T/m 269.09
2
Stress at CG of 1c T/m 524.46 832.86 1928.55 2246.71 2241.27
2
Avg stress for each segment T/m 678.66 1380.70 2087.63 2243.99 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1c T/m 264.78
2
Stress at CG of 1d T/m 376.90 600.62 1499.83 2020.71 2015.81
2
Avg stress for each segment T/m 488.76 1050.22 1760.27 2018.26 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Average Stress at CG of 1d T/m 1431.42
Check Eloss of cable (1a) for (1d) T 2.98
Check Eloss of cable (1b) for (1d) T 2.99
Check Eloss of cable (1c) for (1d) T 2.94

Stress after stressing of 1e


2
Top T/m -25.70 -171.37 -582.07 -741.57 -739.80
2
Bottom T/m 903.65 1305.11 2209.48 2397.38 2391.57
2
Stress at CG of 1a T/m 802.17 1228.07 2075.48 2246.71 2241.27
2
Avg stress for each segment T/m 1015.12 1651.78 2161.10 2243.99 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1a T/m 0.00
2
Stress at CG of 1b T/m 657.22 1012.76 2075.12 2246.71 2241.27
2
Avg stress for each segment T/m 834.99 1543.94 2160.92 2243.99 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1b T/m 0.00
2
Stress at CG of 1c T/m 524.46 832.86 1928.55 2246.71 2241.27
2
Avg stress for each segment T/m 678.66 1380.70 2087.63 2243.99 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1c T/m 0.00
2
Stress at CG of 1d T/m 376.90 600.62 1499.83 2020.71 2015.81
2
Avg stress for each segment T/m 488.76 1050.22 1760.27 2018.26 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1d T/m 0.00
2
Stress at CG of 1e T/m 903.65 1305.11 2209.48 2397.38 2391.57
2
Avg stress for each segment T/m 1104.38 1757.29 2303.43 2394.48 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Average Stress at CG of 1e T/m 1991.63
Check Eloss of cable (1a) for (1e) T 0.00
Check Eloss of cable (1b) for (1e) T 0.00
Check Eloss of cable (1c) for (1e) T 0.00
Check Eloss of cable (1d) for (1e) T 0.00
Immidiate Relaxation Loss T 20.82 20.82 20.82 20.82 20.82
Top 13.22 17.80 18.30 18.30 18.30
Bottom -34.85 -45.10 -56.46 -56.46 -56.46
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Stress after stressing of Stage1 Cables


2
Top T/m 82.92 63.09 -97.98 -120.27 -80.59
2
Bottom T/m 769.46 1041.28 1697.05 1750.64 1707.72

2
Stress at CG of cable 1a T/m 694.50 990.24 1610.89 1660.84 1621.88
2
Stress at CG of cable 1b T/m 587.42 847.59 1610.66 1660.84 1621.88
2
Stress at CG of cable 1c T/m 489.34 728.40 1516.41 1660.84 1621.88
2
Stress at CG of cable 1d T/m 380.33 574.54 1240.73 1526.13 1493.12
2
Stress at CG of cable 1e T/m 769.46 1041.28 1697.05 1750.64 1707.72

Losses From 14 to 28 day

Creep loss due to GR I Tendons T 2.70 2.70 2.70 2.70 2.70


Shrinkage loss due to GR I Tendons T 2.96 2.96 2.96 2.96 2.96
=(0.000225-0.000247)*3.68421052631579*0.0018753*19500000*1
Relaxation loss due to GR I Tendons

Relaxation loss due to GR I Tendons T 11.66 11.66 11.66 11.66 11.66

Total Loss (C+S+R) T 15.60 15.60 15.60 15.60 15.60

Stress Due to C+S+R


2
Top T/m 0.70 3.66 11.54 14.28 14.28
2
Bottom T/m -18.27 -26.28 -43.38 -46.06 -46.06

Stress before stressing of GR II cables at 28 day


2
Top T/m 96.84 84.55 -68.14 -87.69 -48.01
2
Bottom T/m 716.34 969.90 1597.21 1648.12 1605.20

2
Stress at CG of Stage 1 Cables T/m 518.13 753.06 1429.98 1541.35 1503.53
2
T/m

2
Average Stress at CG of Stage 1 Cables T/m 1254.65

Creep loss (check) T 2.70


=(0.00016-0)*3.68421052631579*0.0018753*19500000*1254.64639684021/10000*1
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Stress due to shuttering load (for casting of Deck Slab)


Top T/m2 33.83 75.12 161.43 208.76 222.08
2
Bottom T/m -35.22 -75.84 -158.03 -204.36 -217.39

Dead Load Moments -IInd stage Tm 77.48 145.38 256.78 332.07 353.24
Stress Due to dead load
2
Top T/m 97.14 215.73 463.59 599.51 637.74
2
Bottom T/m -101.14 -217.80 -453.80 -586.85 -624.27

2
Stress at CG of GR I Tendons T/m -37.70 -111.62 -361.68 -513.88 -546.67
2
Stress at CG of GR II Tendons T/m 3671.93 -216.06 -450.13 -582.11 -619.23

Dead Load Moments -Ist stage due to shift of


bearing Tm 10.20 11.00 11.00 10.00 10.00
2
Top T/m 12.79 16.32 19.86 18.05 18.05
2
Bottom T/m -13.31 -16.48 -19.44 -17.67 -17.67

Shuttering Load Moments Tm 26.98 50.62 89.42 115.63 123.01


Stress due to release of shuttering load
2
Top T/m -13.95 -26.95 -49.39 -63.87 -67.95
Top of Girder -10.73 -20.15 -35.62 -46.07 -49.01
2
Bottom T/m 22.76 50.70 107.80 139.41 148.30

Stress after release of shuttering load


2
Top of Deck Slab T/m -13.95 -26.95 -49.39 -63.87 -67.95
2
Top of Girder T/m 229.81 371.52 541.06 692.51 780.80
2
Bottom T/m 589.52 710.59 1073.89 978.79 894.30

Losses from 28 to 90 day

Creep Loss of Gr I Tendons T 1.14 1.14 1.14 1.14 1.14


Shrinkage loss of Gr I Tendons T 7.01 7.01 7.01 7.01 7.01
=(0.000225-0.000173)*3.68421052631579*0.0018753*19500000*1
Relaxation loss of Gr. I Tendons T 2.08 2.08 2.08 2.08 2.08

Total Loss due to C + S + R 9.21 9.20 9.20 9.20 9.20

Stresses due to C + S + R
2
Top T/m 0.84 1.62 3.15 3.64 3.64
2
T/m -0.15 0.17 0.84 1.20 1.20
2
Bottom T/m -10.53 -14.97 -23.17 -24.25 -24.25

Prestressing factor for composite section


Stage 1 Cables Top -0.087 -0.176 -0.342 -0.396 -0.396
Bottom 1.136 1.628 2.520 2.637 2.637

Stress at 90nd day before laying SIDL


2
Top of Deck Slab T/m -13.10 -25.34 -46.25 -60.23 -64.30
2
Top of Girder T/m 229.66 371.69 541.90 693.71 782.00
2
Bottom T/m 579.00 695.63 1050.72 954.54 870.06

2
Stress at CG of Tendon I T/m 467.23 616.29 999.63 938.50 864.64

2
Average Stress at CG of Tendon GRI T/m 841.27

Check for Creep Loss of Gr I Cables 1.14


=(0.000261-0.00016)*3.68421052631579*0.0018753*19500000*841.266701664274/10000*1

SIDL applied at 90nd day Tm 47.00 85.30 137.40 152.30 132.30


Stress due to SIDL
2
Top T/m 24.30 45.42 75.90 84.13 73.08
18.70 33.96 54.74 60.68 52.71
Bottom T/m2 -39.64 -85.42 -165.65 -183.61 -159.50

2
Stress at CG of Gr I Tendons T/m -20.98 -56.18 -143.52 -168.59 -146.45
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Creep, Shrinkage & Relaxation losses from 90 day upto infinity

Creep loss of Gr. I T =38.26 38.26 38.26 38.26 38.26


Shrinkage loss of Gr. I T 23.31 23.31 23.31 23.31 23.31
=(0.000173-0.000173)*3.68421052631579*0.0018753*19500000*1
Relaxation loss of Gr. I T 41.65 41.65 41.65 41.65 41.65

Total Loss due to C+S+R 92.88 92.88 92.88 92.88 92.88

Stress due to C+S+R


2
Top T/m 8.33 16.38 31.81 36.80 36.80
-1.67 1.70 8.53 12.13 12.13
2
Bottom T/m -105.88 -151.24 -234.02 -244.91 -244.92

Stress during Service at infinity


2
Top of Deck Slab T/m 19.52 36.46 61.46 60.70 45.58
2
Top of Girder T/m 246.68 407.35 605.17 766.52 846.83
2
Bottom T/m 433.47 458.97 651.05 526.02 465.64

2
Stress at CG of Tendon I T/m 373.71 446.33 646.44 540.81 489.08

2
Avg stress for each segment T/m 410.02 546.39 593.63 514.94 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Average Stress at CG of Tendon GRI T/m 532.16

Check for Creep Loss of Gr I Cables


=(0.000545-0.000261)*3.68421052631579*0.0018753*19500000*1 = =38.26

Moment Due to Live Load (Sagging) Tm 94.32 173.46 281.65 350.76 377.96
Stresses due to Live Load (Sagging)
2
Top of Deck Slab T/m 48.76 92.35 155.58 193.76 208.78
2
Top of Girder T/m 37.52 69.05 112.21 139.74 150.58
2
Bottom T/m -79.55 -173.71 -339.56 -422.88 -455.67

Stress at service with Live Load (Sagging)


2
Top of Deck Slab T/m 68.28 128.82 217.04 254.46 254.36
2
Top of Girder T/m 284.20 476.40 717.38 906.26 997.41
2
Bottom T/m 353.92 285.26 311.49 103.13 9.97

Stress at service with differential shrinkage and differential creep effect (without Live Load)
2
Top of Deck Slab T/m 19.52 36.46 61.46 60.70 45.58
2
Top of Girder T/m 246.68 407.35 605.17 766.52 846.83
2
Bottom T/m 433.47 458.97 651.05 526.02 465.64

Stress at service with differential shrinkage and differential creep effect (with 75% Live Load)
Top of Deck Slab T/m2 56.09 105.73 178.15 206.02 202.16
2
Top of Girder T/m 274.82 459.13 689.33 871.32 959.77
2
Bottom T/m 373.81 328.69 396.38 208.85 123.89
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Stress due to Temp (Rise) (Eigen stresses)


2
Top of Deck Slab T/m 209.37 209.37 207.25 206.99 206.99
2
Top of Girder T/m -130.13 -130.13 -134.36 -134.57 -134.57
2
Bottom T/m 158.80 158.80 132.57 132.85 132.85

Stress at Service with 75% Live Load (sag) + Temp rise (RARE COMBINATION)
2
Top of Deck Slab T/m 265.46 315.10 385.40 413.00 409.15
2
Top of Girder T/m 144.69 329.01 554.97 736.75 825.19
2
Bottom T/m 532.61 487.49 528.95 341.71 256.74

Stress at Service with 100% Live Load (sag) + 60% Temp rise (RARE COMBINATION)
2
Top of Deck Slab T/m 193.90 254.44 341.40 378.65 378.55
2
Top of Girder T/m 206.12 398.32 636.77 825.52 916.67
2
Bottom T/m 449.20 380.55 391.03 182.84 89.68

Stress at Service with 75% Live Load (sag) + 50% Temp rise (FREQUENT COMBINATION)
2
Top of Deck Slab T/m 160.78 210.41 281.78 309.51 305.66
2
Top of Girder T/m 209.76 394.07 622.15 804.04 892.48
2
Bottom T/m 453.21 408.09 462.66 275.28 190.31

Stress at Service with 20% Live Load (sag) + 60% Temp rise (FREQUENT COMBINATION)
2
Top of Deck Slab T/m 154.90 180.56 216.93 223.64 211.53
2
Top of Girder T/m 176.11 343.08 547.00 713.72 796.20
2
Bottom T/m 512.84 519.51 662.68 521.15 454.22

Stress due to Temp (Fall) (Eigen Stresses)


2
Top of Deck Slab T/m -301.87 -301.87 -316.30 -127.00 -127.00
2
Top of Girder T/m -90.19 -90.19 -105.27 59.00 59.00
2
Bottom T/m -109.29 -109.29 -131.10 -128.00 -128.00

Stress at Service with 75% Live Load (sag) + Temp Fall


2
Top of Deck Slab T/m -245.78 -196.14 -138.15 79.02 75.16
Top of Girder T/m2 184.63 368.94 584.06 930.32 1018.77
2
Bottom T/m 264.52 219.40 265.28 80.85 -4.11

Stress at Service with 100% Live Load (sag) +60 % Temp Fall (RARE COMBINATION)
2
Top of Deck Slab T/m -112.84 -52.31 27.26 178.26 178.16
2
Top of Girder T/m 230.08 422.28 654.22 941.66 1032.81
2
Bottom T/m 288.35 219.69 232.83 26.33 -66.83

Stress at Service with 75% Live Load (sag) + 50% Temp Fall (FREQUENT COMBINATION)
2
Top of Deck Slab T/m -94.85 -45.21 20.00 142.52 138.66
2
Top of Girder T/m 229.72 414.04 636.70 900.82 989.27
2
Bottom T/m 319.16 274.05 330.83 144.85 59.89

Stress at Service with 20% Live Load (sag) + 60% TempFall (FREQUENT COMBINATION)
Top of Deck Slab T/m2 -151.85 -126.19 -97.20 23.25 11.14
2
Top of Girder T/m 200.07 367.04 564.45 829.86 912.35
2
Bottom T/m 351.99 358.66 504.48 364.64 297.70
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

After Stage 1 ( 14th Day)


2 2
Maximum Stress = 1750.64 t/m < 2400 t/m

2
Minimum Stress = -120.27 t/m < -350 t/m2

After Stage 2
2 2
Maximum Stress = 1073.89 t/m < 2400 t/m

2 2
Minimum Stress = 229.81 t/m < 2400 t/m

Stress at service with differential shrinkage and differential creep effect (without Live Load)
2 2
Maximum Stress = 846.83 t/m < 2400 t/m

2
Minimum Stress = 246.68 < 2400 t/m

Stress at service with differential shrinkage and differential creep effect (with Live Load)
2 2
Maximum Stress = 997.41 t/m < 2400 t/m

2 2
Minimum Stress = 9.97 t/m < 2400 t/m

Stress at Service with Live Load (sag) + Temp Rise (FREQUENT COMBINATION)
2
Maximum Stress = 892.48 t/m < 1800 t/m2

2 2
Minimum Stress = 176.11 t/m < -350 t/m

Stress at Service with Live Load (sag) + TempFall (FREQUENT COMBINATION)


2
Maximum Stress = 989.27 t/m < 1800 t/m2

2 2
Minimum Stress = 59.89 t/m < -350 t/m

Stress at Service with Live Load (sag) + Temp Rise (Rare COMBINATION)
2 2
Maximum Stress = 916.67 t/m < 2400 t/m

2 2
Minimum Stress = 89.68 t/m < -350 t/m
Table 5.1.2 Ultimate forces at Sections:- Ultimate Force = 1.35xDL+1.75xSIDL+1.5xLL

Partial Factor of Safety For Dead Laod= 1.35

Partial Factor of Safety For Super Imposed Dead Laod= 1.75

Partial Factor of Safety For Live Laod= 1.5

Loadings Location Near support L/8 L/4 3L/8 L/2


Shear 749.44 632.54 430.95 201.71 0.12
Dead Load
Moment 1535.78 2913.77 5147.80 6660.65 7082.39
Shear 210.00 160.00 86.00 56.00 110.00
Superimposed Dead Load
Moment 470.00 853.00 1374.00 1523.00 1323.00
Shear 479.81 416.30 324.58 247.92 296.76
Live Load Shear for Maxm. Shear Moment 943.15 1734.60 2816.52 3507.62 3779.58
Torsion 0.00 0.00 0.00 0.00 0.00
Shear 479.81 416.30 324.58 247.92 296.76
Live Load Shear with Maxm. Moment Moment 943.15 1734.60 2816.52 3507.62 3779.58
Torsion 0.00 0.00 0.00 0.00 0.00
Shear 2098.96 1758.39 1219.15 742.18 637.80
Ultimate Load for Maxm. Shear Moment 4310.53 8028.23 13578.81 16918.56 17545.85
Torsion 0.00 0.00 0.00 0.00 0.00
Shear 2098.96 1758.39 1219.15 742.18 637.80
Ultimate Load for Maxm. Moment Moment 4310.53 8028.23 13578.81 16918.56 17545.85
Torsion 0.00 0.00 0.00 0.00 0.00
Shear Capacity
D in (mm) 2740 2740 2740 2740 2740
K 1.270 1.270 1.270 1.270 1.270
I 2.014 1.786 1.559 1.559 1.559
A 2.648 2.222 1.796 1.796 1.796
Deck width 2900 2900 2900 2900 2900
CG of section 1.699 1.789 1.879 1.879 1.879
Thickness of top slab 240 240 240 240 240
fck 50.000 50.000 50.000 50.000 50.000
Horz. Prestress 6591 6649 6887 7066 7047
Total Vertical Comp. 845.86 752.45 483.50 0.00 0.00
σcp 2.49 2.99 3.83 3.93 3.92
σcp(max) 2.49 2.99 3.83 3.93 3.92
Duct Dia 90.00 90.00 90.00 90.00 90.00
bw 665.00 665.00 665.00 665.00 665.00
ρ1 (Asl/bd) 0.004 0.004 0.004 0.004 0.004
ν 0.31 0.31 0.31 0.31 0.31
fctd 1.53 1.53 1.53 1.53 1.53
Area above centroid 1.229 1.169 1.109 1.109 1.109
CG of section above centroid 696 639 581 581 581
First moment of Area 0.85 0.75 0.64 0.64 0.64
Stress at bottom fibre due to prestress 4.33 4.59 6.51 5.26 4.66
Maximum M cracked kNm 6957 6114 6672 5635 5134
Section type Uncracked Cracked Cracked Cracked Cracked
Vrdc (Cracked) kN 1338 1476 1706 1733 1730
Vrdc (Uncracked) kN (10.4) 3892 4191 4618 4661 4656
CG of Cable 800 612 251 154 154
Maximum Shear capacity (Eqn 10.5) 7250 7951 9301 9664 9665
Shear requirement 1529 1227 897 905 778
Torsion requirement 0 0 0 0 0
Shear reinforcement requirment NO NO NO NO NO
Dia of stirrups 12.00 12.00 12.00 12.00 12.00
Number of legs 6.00 4.00 4.00 4.00 4.00
Spacing of stirrups 125 125 125 125 125
Fy 500 500 500 500 500
fwkd 435 435 435 435 435
Z=(D-cg of cable) 1940 2128 2489 2586 2586
θ 45 45 45 45 45
Asw 679 452 452 452 452
ρ 0.0082 0.0054 0.0054 0.0054 0.0054
Vrd 4581.6 3349.7 3918.4 4071.5 4071.6
ν1 0.50 0.50 0.50 0.50 0.50
αcw 1.11 1.13 1.17 1.18 1.17
Vrd.max 8094.2 9055.9 10944.5 11415.3 11410.9
Optimizatio by Vrd.max-V 3512.64 5706.25 10046.97 7343.72 7339.33
ρmin 0.0012 0.0012 0.0012 0.0012 0.0012
Check for shear capcity OK OK OK OK OK
Design of Anchor Block
Anchor block is designed as per Cl. No. 13 of IRC 112-2011

According to Manufacture's Catalog

Size of anchor flange = 345 mm

Dia of Hole = 179 mm

As per Cl No.16.11of IRC 112-2011, allowable Concentrated force/ stress

fb = fcdxSQRT(Acl/Aco) or 3xfcd Whichever is smaller

fcd = 30.15 N/mm2

Acl = 450x450- 3.14/4x179^2 = 177335.06 mm2

Aco = 345x345- 3.14/4x179^2 = 93860.057 mm2

fb = 41.44 N/mm2

Now, Maximum Cable Force after immediate Losses = 2196.05 kN

In general = 2/3rd of above force to be taken by End Bearing

= 1/3rd of above force to be taken by Anchorage

Cone and Concrete by friction

Bearing stress = N/A1 = 15.60 N/mm2

< 41.44 N/mm2 Hence O.K.

As per cl 13.5.1.1 of IRC 112:2011 2Yo = 500 mm

2Ypo = 345 mm

Ypo/Yo = 0.69

As per Table 13.1 of IRC 112:2011

Fbst/Pk = 0.124

Fbst = 0.12x2196.05

272.31 kN

Area of Steel Required = Fbst/(0.87xfy)

754.21856 mm2

Hence Provide 12T- 3L -3Nos along Web and Normal to Web

Ast = 1017.876 mm2

16 dia helix with 13 turns in 2Y0 region provided (Ast) 2613.805 mm2
Check for shear in flanged portion As per IRC: 112-2011 Clause 10.3.5.
Diffrence in stress (t/m2) 60.54

Length Ϫx (m) 2

Width of deck in one side beyond web of girder (m) 1.313

Depth of flange (deck slab) (m) 0.24

Difference in normal force between section (T) 19.07

vEDf (N/mm2) 0.40

θf 30

cotθf 1.73

fyd (N/mm2) 434.8

Asf/sf (mm) 0.127

spacing sf (mm) 200

Asf (mm2) 25.32

Dia of bar provided (mm) 16

Area provided (mm2) 201.1


DESIGN OF SHEAR CONNECTORS(OUTER GIRDER)AT SUPPORT SECTION

Width of beam = 950 mm


Shear = 2099 kN
Z (lever arm) = 681.2531 mm
Dia of interface reinforement = 12.00
Number of legs = 6.00
Spacing = 125.00 mm

Design value of interface shear stress: VEd = 3.243184 MPa


vEd 
zb
Design shear resistance at the interface:

2
Area of the interface = 228000 mm2 ; Area of interface reinforcement: 5428.672 mm /m

Angle of reinforcement to interface: a 90 deg

Surface roughness: Smooth 0.6

vEdi  cfctd  h


reinforcement ratio required:  min  = 0.012426
fyd Sina  Cosa 

Area of interface reinforcement required = 2833.126 mm2 OK


Maximum spacing of links using current preferred bar diameter =

DESIGN OF SHEAR CONNECTORS(OUTER GIRDER)AT MID SECTION

Width of beam = 950 mm


Shear = 1758 kN
Z (lever arm) = 591.1009 mm
Dia of interface reinforement = 12.00
Number of legs = 4.00
Spacing = 125.00 mm

Design value of interface shear stress: VEd = 3.131333 MPa


vEd 
zb
Design shear resistance at the interface:

2
Area of the interface = 228000 mm2 ; Area of interface reinforcement: 3619.115 mm /m

Angle of reinforcement to interface: a 90 deg

Surface roughness: Smooth 0.6

vEdi  cfctd  h


reinforcement ratio required:  min  = 0.011997
fyd Sina  Cosa 

Area of interface reinforcement required = 2735.417 mm2 OK


Maximum spacing of links using current preferred bar diameter =
Stress Check for Outer Girder
Basic Design Data

Characteristics value of prestressing 1.1

1st stage prestressing 14 day


2nd stage prestressing 28 day
Casting of Deck Slab 28 day
3rd stage prestressing 90 day
Shift of Bearing 90 day
SIDL(Wearing Coat & Crash Barrier) 90 day
Age of deck slab at time of 3rd stage 62 day

Fck 50 Mpa
Modulus of Elasticity (Conc) 14th Day 3.30E+06 t/m2
Modulus of Elasticity (Conc) 28th Day 3.40E+06 t/m2
Modulus of Elasticity (Conc) 28th Day 3.40E+06 t/m2
Modulus of Elasticity (Conc) 90th Day 3.51E+06 t/m2
Modulus of Elasticity (Strands) 1.95E+07 t/m2

Type of cables 19 T13


Area of 1 strand 0.0000987 m2
Area of one cable 1.8753E-03 m2
no of cables stressed in 1st stage 3.68
no of cables stressed in 2nd stage 0.001
no of tendons stressed in 3rd stage 0.00
Jacking Force 0.765 *UTS
No of Sections to be checked 5
Prestressing force per cable (UTS) 355.8 t
Increase Factors for losses
Elastic Shortening loss 1.0
Relaxation loss 1.0
Shrinkage loss 1.0
Creep loss 1.0

Factor for Shrinkage loss


14th day 2.47E-04
28th day 2.25E-04
90th day 1.73E-04
90th day 1.73E-04
90th day 1.73E-04
Infinity 1.73E-04

Factor for Creep Loss


14th day 0.00E+00
28th day 1.60E-04
90th day 2.61E-04
90th day 2.61E-04
90th day 2.61E-04
Infinity 5.45E-04

Factor for Relaxation Loss


1000hr relaxation 2.50%

Total Relaxation Loss at service condition (cl: 6.3.6 IRC 112) = 3 x (1000 hr. value)
Initial force after Friction, slip & ES loss = 893.05 t
Percentage of Initial force = 0.6813 UTS
Relaxation Loss at 1000hr. for low relaxation steel = 2.27 % of initial stress
Relaxation Loss at 1000hr. for low relaxation steel = 5.49 t/Cable
Immediate Loss i.e 1 hr. of stressing (Table 6.3 IRC:112) = 34 % of Total Loss
7 - 28 days Loss = 90 % of Total Loss
28 - 90 days Loss = 100 % of Total Loss
90 - a days Loss = 200 % of Total Loss
Immediate Loss i.e 1 hr. of stressing = 1.87 t/Cable
7 - 28 days Loss = 3.08 t/Cable
28 - 90 days Loss = 0.55 t/Cable
90 - a days Loss = 10.99 t/Cable
Strain due to differential shrinkage and creep 1.00E-04
Reduction factor due to differential creep 0.43
PSC BEAM AND RC SLAB STRUCTURE OF SIMPLY SUPPORTED SPAN
(OUTER GIRDER)
Item Unit 1 2 3 4 5
MEMBER NO
distance of Section from left support m 2.000 4.000 8.973 12.974 17.175

Details of Section property (Individual Beam Section)


Area of the section m2 1.8142 1.3881 0.9620 0.9620 0.9620
Depth of the section m 2.5000 2.5000 2.5000 2.5000 2.5000
CG of section from bottom m 1.2752 1.2560 1.2367 1.2367 1.2367
Moment of Inertia of section m4 0.9769 0.8383 0.6998 0.6998 0.6998

Details of Section property (Composite Section)


Area of the section m2 2.6482 2.2221 1.7960 1.7960 1.7960
Depth of the section m 2.7400 2.7400 2.7400 2.7400 2.7400
CG of section from bottom m 1.6987 1.7889 1.8791 1.8791 1.8791
Moment of Inertia of section m4 2.0141 1.7864 1.5586 1.5586 1.5586

Details of Section property (Composite Section)


Area of the section m2 2.6482 2.2221 1.7960 1.7960 1.7960
Depth of the section m 2.7400 2.7400 2.7400 2.7400 2.7400
CG of section from bottom m 1.6987 1.7889 1.8791 1.8791 1.8791
Moment of Inertia of section m4 2.0141 1.7864 1.5586 1.5586 1.5586

Details of Stage I prestressing after 14 day For Cable 1a/1


Prestressing Force (P1) (Hor) T 237.83 241.35 251.07 253.79 253.92
CG of Tendons from Bottom m 0.27 0.13 0.12 0.12 0.12
Prestressing Force (P1) (Ver) T 18.50 8.86 0.00 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1b/2


Prestressing Force (P1) (Hor) T 239.82 240.90 253.17 255.80 253.66
CG of Tendons from Bottom m 0.66 0.50 0.12 0.12 0.12
Prestressing Force (P1) (Ver) T 20.13 20.22 1.69 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1c/3


Prestressing Force (P1) (Hor) T 245.44 246.52 249.19 257.76 258.28
CG of Tendons from Bottom m 1.02 0.80 0.25 0.12 0.12
Prestressing Force (P1) (Ver) T 27.05 27.17 27.46 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1d/4


Prestressing Force (P1) (Hor) T 168.71 169.45 171.28 177.24 176.66
CG of Tendons from Bottom m 1.42 1.19 0.64 0.30 0.30
Prestressing Force (P1) (Ver) T 18.91 18.99 19.19 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1e/5


Prestressing Force (P1) (Hor) T 0.00 0.00 0.00 0.00 0.00
CG of Tendons from Bottom m 0.00 0.00 0.00 0.00 0.00
Prestressing Force (P1) (Ver) T 0.00 0.00 0.00 0.00 0.00
PSC BEAM AND RC SLAB STRUCTURE OF SIMPLY SUPPORTED SPAN
(OUTER GIRDER)
Item Unit 1 2 3 4 5
MEMBER NO
distance of Section from left support m 2.000 4.000 8.973 12.974 17.175
Details of Stage II prestressing after 28 day For Cable 2a
Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2b


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2c


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2d


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2e


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage III prestressing after 90th day


Prestressing Force (P3) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P3) (Ver) T 0.01 0.01 0.01 0.01 0.01
PSC BEAM AND RC SLAB STRUCTURE OF SIMPLY SUPPORTED SPAN
(OUTER GIRDER)
Item Unit 1 2 3 4 5
MEMBER NO
distance of Section from left support m 2.000 4.000 8.973 12.974 17.175

Dead Load - Ist stage


Moments Tm 76.1 146.0 258.0 334.0 355.0
Shear T 38.6 31.7 21.6 10.1 0.0

Dead Load - Ist stage due to permanent bearing


Moments Tm 86.3 157.0 269.0 344.0 365.0
Shear T 38.6 31.7 21.6 10.1 0.0

Dead Load - Ist stage due to shift of bearing


Moments Tm 10.2 11.0 11.0 10.0 10.0
Shear T 0.0 0.0 0.0 0.0 0.0

Construction load/Shuttering load


Moments Tm 27.0 50.6 89.4 115.6 123.0
shear 12.7 11.0 7.5 3.5 0.0

Dead Load - 2nd stage


Moments Tm 77.5 145.4 256.8 332.1 353.2
Shear T 36.3 31.6 21.5 10.1 0.0

SIDL
Moments Tm 47.0 85.3 137.4 152.3 132.3
Shear T 21.0 16.0 8.6 5.6 11.0

Live Load (Sagging) (max Moment Case & max Positive Shear case)
Moments Tm 94.3 173.5 281.7 350.8 378.0
Shear T 48.0 41.6 32.5 24.8 29.7

Stress due to Temp (Rise) (Eigen stresses)


top of deck slab T/m2 209.37 209.37 207.25 206.99 206.99
top of girder T/m2 -130.13 -130.13 -134.36 -134.57 -134.57
bottom T/m2 158.80 158.80 132.57 132.85 132.85

Stress due to Temp (Fall) (Eigen Stresses)


top of deck slab T/m2 -301.87 -301.87 -316.30 -127.00 -127.00
top of girder T/m2 -90.19 -90.19 -105.27 59.00 59.00
bottom T/m2 -109.29 -109.29 -131.10 -128.00 -128.00
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Details of Section property (Individual Beam Section)

2
Area of the section m 1.8142 1.38808125 0.96196 0.961963 0.9619625
Depth of the section m 2.500 2.500 2.500 2.500 2.500
CG of section from bottom m 1.2752406 1.255953054 1.23667 1.236665 1.236665476
4
Inertia of section m 0.9769032 0.838329327 0.69976 0.699755 0.699755494
3
Top Section Modulus m 0.7976 0.6739 0.5539 0.5539 0.5539
3
Bottom Section Modulus m 0.7661 0.6675 0.5658 0.5658 0.5658

Details of Section property (Composite Section) (62 day old slab)

2
Area of the section m 2.6482 2.22208125 1.79596 1.795963 1.7959625
Depth of the section m 2.740 2.740 2.740 2.740 2.740
CG of section from bottom m 1.6987469 1.788899142 1.87905 1.879051 1.879051379
4
Inertia of section m 2.0141187 1.786355282 1.55859 1.558592 1.558591853
3
Top Section Modulus m 1.9343 1.8782 1.8103 1.8103 1.8103
3
Bottom Section Modulus m 1.1856 0.9986 0.8295 0.8295 0.8295

Details of Section property (Composite Section)

2
Area of the section m 2.6482 2.22208125 1.79596 1.795963 1.7959625
Depth of the section m 2.740 2.740 2.740 2.740 2.740
CG of section from bottom m 1.6987469 1.788899142 1.87905 1.879051 1.879051379
4
Inertia of section m 2.0141187 1.786355282 1.55859 1.558592 1.558591853
3
Top Section Modulus m 1.9343 1.8782 1.8103 1.8103 1.8103
3
Bottom Section Modulus m 1.1856 0.9986 0.8295 0.8295 0.8295

Details of Stage I prestressing


For Cable 1a
No of Tendons of 19T13 1.00 1.00 1.00 1.00 1.00
Prestressing Force (P1) T 237.83 241.35 251.07 253.79 253.92
CG of Tendons from Bottom m 0.2730 0.1304 0.1200 0.1200 0.1200
Eccentricity of Tendons m 1.0023 1.1255 1.1167 1.1167 1.1167
Prestressing Factor (Top) -0.7053 -0.9498 -0.9765 -0.9765 -0.9765
Prestressing Factor (Bottom) 1.8595 2.4066 3.0130 3.0130 3.0130

For Cable 1b
No of Tendons of 19T13 1.00 1.00 1.00 1.00 1.00
Prestressing Force (P1) T 239.82 240.90 253.17 255.80 253.66
CG of Tendons from Bottom m 0.6629 0.4950 0.1203 0.1200 0.1200
Eccentricity of Tendons m 0.6123 0.7609 1.1163 1.1167 1.1167
Prestressing Factor (Top) -0.2165 -0.4088 -0.9759 -0.9765 -0.9765
Prestressing Factor (Bottom) 1.3505 1.8604 3.0124 3.0130 3.0130

For Cable 1c
No of Tendons of 19T13 1.00 1.00 1.00 1.00 1.00
Prestressing Force (P1) T 245.44 246.52 249.19 257.76 258.28
CG of Tendons from Bottom m 1.0200 0.7996 0.2516 0.1200 0.1200
Eccentricity of Tendons m 0.2552 0.4563 0.9851 1.1167 1.1167
Prestressing Factor (Top) 0.2313 0.0433 -0.7389 -0.9765 -0.9765
Prestressing Factor (Bottom) 0.8843 1.4041 2.7805 3.0130 3.0130
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

For Cable 1d
No of Tendons of 19T13 0.68 0.68 0.68 0.68 0.68
Prestressing Force (P1) T 168.71 169.45 171.28 177.24 176.66
CG of Tendons from Bottom m 1.4170 1.1929 0.6355 0.3000 0.3000
Eccentricity of Tendons m -0.1418 0.0631 0.6011 0.9367 0.9367
Prestressing Factor (Top) 0.7289 0.6268 -0.0457 -0.6515 -0.6515
Prestressing Factor (Bottom) 0.3662 0.8150 2.1019 2.6949 2.6949

For Cable 1e
No of Tendons of 19T13 0.00 0.00 0.00 0.00 0.00
Prestressing Force (P1) T 0.00 0.00 0.00 0.00 0.00
CG of Tendons from Bottom m 0.0000 0.0000 0.0000 0.0000 0.0000
Eccentricity of Tendons m 1.2752 1.2560 1.2367 1.2367 1.2367
Prestressing Factor (Top) -1.0476 -1.1434 -1.1931 -1.1931 -1.1931
Prestressing Factor (Bottom) 2.2159 2.6020 3.2251 3.2251 3.2251

Combination of Stage 1 Cables


No of Tendons of 19T13 3.68 3.68 3.68 3.68 3.68
Prestressing Force (P1) T 891.79 898.22 924.71 944.59 942.51
CG of Tendons from Bottom m 0.7999 0.6123 0.2510 0.1538 0.1537
Eccentricity of Tendons m 0.4754 0.6437 0.9856 1.0829 1.0829
Prestressing Factor (Top) -0.0448 -0.2347 -0.7399 -0.9155 -0.9156
Prestressing Factor (Bottom) 1.1718 1.6847 2.7814 2.9533 2.9534

Dead Load Moments - Ist stage Tm 76.10 146.00 258.00 334.00 355.00

Stress Due to dead load


2
Top T/m 95.41 216.66 465.79 603.00 640.91
2
Bottom T/m -99.34 -218.73 -455.96 -590.27 -627.39

Eloss of cable (1a) for stressing of (1a) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1a) for stressing of (1b) T 7.34 7.34 7.34 7.34 7.34
Eloss of cable (1a) for stressing of (1c) T 6.65 6.65 6.65 6.65 6.65
Eloss of cable (1a) for stressing of (1d) T 3.59 3.59 3.59 3.59 3.59
Eloss of cable (1a) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1b) for stressing of (1b) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1b) for stressing of (1c) T 6.51 6.51 6.51 6.51 6.51
Eloss of cable (1b) for stressing of (1d) T 3.61 3.61 3.61 3.61 3.61
Eloss of cable (1b) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1c) for stressing of (1c) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1c) for stressing of (1d) T 3.54 3.54 3.54 3.54 3.54
Eloss of cable (1c) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1d) for stressing of (1d) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1d) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1e) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00

Total Eloss for Stage 1 cables T 31.24 31.24 31.24 31.24 31.24
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Stress after stressing of 1a


2
Top T/m -184.52 -248.48 -255.46 -255.46 -255.46
2
Bottom T/m 486.48 629.60 788.23 788.23 788.23
2
Stress at CG of 1a T/m 413.21 583.78 738.14 738.14 738.14
2
Avg stress for each segment T/m 498.49 660.96 738.14 738.14 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Average Stress at CG of 1a T/m 681.26

Stress after stressing of 1b


2
Top T/m -235.94 -349.14 -519.35 -522.34 -520.04
2
Bottom T/m 827.74 1103.18 1602.84 1611.71 1604.63
2
Stress at CG of 1a T/m 711.59 1027.40 1500.97 1509.28 1502.65
2
Avg stress for each segment T/m 869.50 1264.19 1505.13 1505.96 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1a T/m 661.37
2
Stress at CG of 1b T/m 545.69 815.62 1500.70 1509.28 1502.65
2
Avg stress for each segment T/m 680.66 1158.16 1504.99 1505.96 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Average Stress at CG of 1b T/m 1282.96
Check Eloss of cable (1a) for (1b) T 7.34

Stress after stressing of 1c


2
Top T/m -166.79 -327.53 -707.76 -785.07 -783.33
2
Bottom T/m 1043.22 1452.98 2321.37 2422.38 2417.01
2
Stress at CG of 1a T/m 911.09 1360.08 2175.97 2268.42 2263.40
2
Avg stress for each segment T/m 1135.59 1768.03 2222.20 2265.91 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
Increase in Average Stress at CG of 1a T/m2 599.62
2
Stress at CG of 1b T/m 722.37 1100.44 2175.58 2268.42 2263.40
2
Avg stress for each segment T/m 911.40 1638.01 2222.00 2265.91 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1b T/m 587.09
2
Stress at CG of 1c T/m 549.52 883.48 2016.54 2268.42 2263.40
2
Avg stress for each segment T/m 716.50 1450.01 2142.48 2265.91 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Average Stress at CG of 1c T/m 1761.78
Check Eloss of cable (1a) for (1c) T 6.65
Check Eloss of cable (1b) for (1c) T 6.51
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Stress after stressing of 1d


2
Top T/m -28.78 -205.50 -705.77 -900.55 -898.39
2
Bottom T/m 1095.02 1582.52 2682.69 2912.19 2905.09
2
Stress at CG of 1a T/m 972.30 1489.23 2520.04 2729.18 2722.52
2
Avg stress for each segment T/m 1230.77 2004.63 2624.61 2725.85 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1a T/m 323.51
2
Stress at CG of 1b T/m 797.03 1228.49 2519.60 2729.18 2722.52
2
Avg stress for each segment T/m 1012.76 1874.05 2624.39 2725.85 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1b T/m 324.13
2
Stress at CG of 1c T/m 636.49 1010.62 2341.69 2729.18 2722.52
2
Avg stress for each segment T/m 823.56 1676.16 2535.44 2725.85 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1c T/m 319.16
2
Stress at CG of 1d T/m 458.05 729.38 1821.29 2454.66 2448.67
2
Avg stress for each segment T/m 593.72 1275.34 2137.98 2451.67 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Average Stress at CG of 1d T/m 1738.60
Check Eloss of cable (1a) for (1d) T 3.59
Check Eloss of cable (1b) for (1d) T 3.60
Check Eloss of cable (1c) for (1d) T 3.54

Stress after stressing of 1e


2
Top T/m -28.78 -205.50 -705.77 -900.55 -898.39
2
Bottom T/m 1095.02 1582.52 2682.69 2912.19 2905.09
2
Stress at CG of 1a T/m 972.30 1489.23 2520.04 2729.18 2722.52
2
Avg stress for each segment T/m 1230.77 2004.64 2624.61 2725.85 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1a T/m 0.00
2
Stress at CG of 1b T/m 797.03 1228.49 2519.60 2729.18 2722.52
2
Avg stress for each segment T/m 1012.76 1874.05 2624.39 2725.85 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1b T/m 0.00
2
Stress at CG of 1c T/m 636.49 1010.62 2341.69 2729.18 2722.52
2
Avg stress for each segment T/m 823.56 1676.16 2535.44 2725.85 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1c T/m 0.00
2
Stress at CG of 1d T/m 458.05 729.38 1821.29 2454.66 2448.67
2
Avg stress for each segment T/m 593.72 1275.34 2137.98 2451.67 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Increase in Average Stress at CG of 1d T/m 0.00
2
Stress at CG of 1e T/m 1095.02 1582.52 2682.69 2912.19 2905.09
2
Avg stress for each segment T/m 1338.77 2132.60 2797.44 2908.64 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Average Stress at CG of 1e T/m 2418.10
Check Eloss of cable (1a) for (1e) T 0.00
Check Eloss of cable (1b) for (1e) T 0.00
Check Eloss of cable (1c) for (1e) T 0.00
Check Eloss of cable (1d) for (1e) T 0.00
Immidiate Relaxation Loss T 20.24 20.24 20.24 20.24 20.24
Top 15.70 21.14 21.74 21.74 21.74
Bottom -41.39 -53.57 -67.07 -67.07 -67.07
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Stress after stressing of Stage1 Cables


2
Top T/m 82.33 32.30 -218.24 -275.81 -235.74
2
Bottom T/m 954.28 1310.22 2159.66 2254.85 2210.64

2
Stress at CG of cable 1a T/m 859.07 1243.54 2045.52 2133.38 2093.21
2
Stress at CG of cable 1b T/m 723.07 1057.19 2045.21 2133.38 2093.21
2
Stress at CG of cable 1c T/m 598.52 901.48 1920.36 2133.38 2093.21
2
Stress at CG of cable 1d T/m 460.06 700.47 1555.16 1951.17 1917.07
2
Stress at CG of cable 1e T/m 954.28 1310.22 2159.66 2254.85 2210.64

Losses From 14 to 28 day

Creep loss due to GR I Tendons T 3.45 3.45 3.45 3.45 3.45


Shrinkage loss due to GR I Tendons T 2.96 2.96 2.96 2.96 2.96
=(0.000225-0.000247)*3.68421052631579*0.0018753*19500000*1
Relaxation loss due to GR I Tendons

Relaxation loss due to GR I Tendons T 11.33 11.33 11.33 11.33 11.33

Total Loss (C+S+R) T 19.52 19.52 19.52 19.52 19.52

Stress Due to C+S+R


2
Top T/m 0.87 4.58 14.44 17.87 17.87
2
Bottom T/m -22.87 -32.88 -54.29 -57.65 -57.65

Stress before stressing of GR II cables at 28 day


2
Top T/m 98.91 58.03 -182.06 -236.21 -196.13
2
Bottom T/m 890.02 1223.77 2038.30 2130.13 2085.92

2
Stress at CG of Stage 1 Cables T/m 636.91 938.25 1815.34 1984.58 1945.59
2
T/m

2
Average Stress at CG of Stage 1 Cables T/m 1599.94

Creep loss (check) T 3.45


=(0.00016-0)*3.68421052631579*0.0018753*19500000*1599.93595330777/10000*1
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Stress due to shuttering load (for casting of Deck Slab)


Top T/m2 33.83 75.12 161.43 208.76 222.08
2
Bottom T/m -35.22 -75.84 -158.03 -204.36 -217.39

Dead Load Moments -IInd stage Tm 77.48 145.38 256.78 332.07 353.24
Stress Due to dead load
2
Top T/m 97.14 215.73 463.59 599.51 637.74
2
Bottom T/m -101.14 -217.80 -453.80 -586.85 -624.27

2
Stress at CG of GR I Tendons T/m -37.70 -111.62 -361.68 -513.88 -546.67
2
Stress at CG of GR II Tendons T/m 3671.93 -216.06 -450.13 -582.11 -619.23

Dead Load Moments -Ist stage due to shift of


bearing Tm 10.20 11.00 11.00 10.00 10.00
2
Top T/m 12.79 16.32 19.86 18.05 18.05
2
Bottom T/m -13.31 -16.48 -19.44 -17.67 -17.67

Shuttering Load Moments Tm 26.98 50.62 89.42 115.63 123.01


Stress due to release of shuttering load
2
Top T/m -13.95 -26.95 -49.39 -63.87 -67.95
Top of Girder -10.73 -20.15 -35.62 -46.07 -49.01
2
Bottom T/m 22.76 50.70 107.80 139.41 148.30

Stress after release of shuttering load


2
Top of Deck Slab T/m -13.95 -26.95 -49.39 -63.87 -67.95
2
Top of Girder T/m 231.86 344.99 427.13 543.99 632.66
2
Bottom T/m 763.22 964.48 1515.01 1460.84 1375.06

Losses from 28 to 90 day

Creep Loss of Gr I Tendons T 1.61 1.61 1.61 1.61 1.61


Shrinkage loss of Gr I Tendons T 7.01 7.01 7.01 7.01 7.01
=(0.000225-0.000173)*3.68421052631579*0.0018753*19500000*1
Relaxation loss of Gr. I Tendons T 2.02 2.02 2.02 2.02 2.02

Total Loss due to C + S + R 11.70 11.68 11.68 11.68 11.68

Stresses due to C + S + R
2
Top T/m 1.07 2.06 4.00 4.63 4.63
2
T/m -0.20 0.21 1.07 1.52 1.52
2
Bottom T/m -13.37 -19.02 -29.44 -30.81 -30.81

Prestressing factor for composite section


Stage 1 Cables Top -0.087 -0.176 -0.342 -0.396 -0.396
Bottom 1.136 1.628 2.520 2.637 2.637

Stress at 90nd day before laying SIDL


2
Top of Deck Slab T/m -12.88 -24.90 -45.39 -59.25 -63.32
2
Top of Girder T/m 231.67 345.20 428.20 545.51 634.19
2
Bottom T/m 749.85 945.47 1485.57 1430.03 1344.25

2
Stress at CG of Tendon I T/m 584.06 798.45 1379.40 1375.62 1300.59

2
Average Stress at CG of Tendon GRI T/m 1181.58

Check for Creep Loss of Gr I Cables 1.61


=(0.000261-0.00016)*3.68421052631579*0.0018753*19500000*1181.58366854924/10000*1

SIDL applied at 90nd day Tm 47.00 85.30 137.40 152.30 132.30


Stress due to SIDL
2
Top T/m 24.30 45.42 75.90 84.13 73.08
18.70 33.96 54.74 60.68 52.71
Bottom T/m2 -39.64 -85.42 -165.65 -183.61 -159.50

2
Stress at CG of Gr I Tendons T/m -20.98 -56.18 -143.52 -168.59 -146.45
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Creep, Shrinkage & Relaxation losses from 90 day upto infinity

Creep loss of Gr. I T =38.26 38.26 38.26 38.26 38.26


Shrinkage loss of Gr. I T 23.31 23.31 23.31 23.31 23.31
=(0.000173-0.000173)*3.68421052631579*0.0018753*19500000*1
Relaxation loss of Gr. I T 40.47 40.47 40.47 40.47 40.47

Total Loss due to C+S+R 112.23 112.23 112.23 112.23 112.23

Stress due to C+S+R


2
Top T/m 10.07 19.80 38.44 44.47 44.47
-2.02 2.06 10.30 14.65 14.65
2
Bottom T/m -127.95 -182.74 -282.78 -295.94 -295.94

Stress during Service at infinity


2
Top of Deck Slab T/m 21.49 40.32 68.94 69.35 54.23
2
Top of Girder T/m 248.35 381.21 493.25 620.84 701.55
2
Bottom T/m 582.26 677.30 1037.15 950.48 888.81

2
Stress at CG of Tendon I T/m 475.43 604.78 982.53 930.20 877.29

2
Avg stress for each segment T/m 540.11 793.66 956.37 903.75 0.00
Segment length m 2.00 4.97 4.00 4.20 -17.18
length m 15.18
2
Average Stress at CG of Tendon GRI T/m 833.62

Check for Creep Loss of Gr I Cables


=(0.000545-0.000261)*3.68421052631579*0.0018753*19500000*1 = =38.26

Moment Due to Live Load (Sagging) Tm 94.32 173.46 281.65 350.76 377.96
Stresses due to Live Load (Sagging)
2
Top of Deck Slab T/m 48.76 92.35 155.58 193.76 208.78
2
Top of Girder T/m 37.52 69.05 112.21 139.74 150.58
2
Bottom T/m -79.55 -173.71 -339.56 -422.88 -455.67

Stress at service with Live Load (Sagging)


2
Top of Deck Slab T/m 70.25 132.67 224.52 263.11 263.01
2
Top of Girder T/m 285.87 450.26 605.46 760.59 852.13
2
Bottom T/m 502.72 503.60 697.59 527.60 433.14

Stress at service with differential shrinkage and differential creep effect (without Live Load)
2
Top of Deck Slab T/m 21.49 40.32 68.94 69.35 54.23
2
Top of Girder T/m 248.35 381.21 493.25 620.84 701.55
2
Bottom T/m 582.26 677.30 1037.15 950.48 888.81

Stress at service with differential shrinkage and differential creep effect (with 75% Live Load)
Top of Deck Slab T/m2 58.06 109.58 185.63 214.67 210.82
2
Top of Girder T/m 276.49 433.00 577.40 725.65 814.48
2
Bottom T/m 522.60 547.02 782.48 633.32 547.06
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

Stress due to Temp (Rise) (Eigen stresses)


2
Top of Deck Slab T/m 209.37 209.37 207.25 206.99 206.99
2
Top of Girder T/m -130.13 -130.13 -134.36 -134.57 -134.57
2
Bottom T/m 158.80 158.80 132.57 132.85 132.85

Stress at Service with 75% Live Load (sag) + Temp rise (RARE COMBINATION)
2
Top of Deck Slab T/m 267.43 318.95 392.88 421.66 417.81
2
Top of Girder T/m 146.36 302.88 443.05 591.08 679.91
2
Bottom T/m 681.40 705.82 915.05 766.17 679.91

Stress at Service with 100% Live Load (sag) + 60% Temp rise (RARE COMBINATION)
2
Top of Deck Slab T/m 195.87 258.29 348.87 387.30 387.21
2
Top of Girder T/m 207.79 372.19 524.84 679.84 771.39
2
Bottom T/m 598.00 598.88 777.13 607.31 512.85

Stress at Service with 75% Live Load (sag) + 50% Temp rise (FREQUENT COMBINATION)
2
Top of Deck Slab T/m 162.74 214.27 289.25 318.16 314.31
2
Top of Girder T/m 211.42 367.94 510.23 658.36 747.20
2
Bottom T/m 602.00 626.42 848.76 699.74 613.48

Stress at Service with 20% Live Load (sag) + 60% Temp rise (FREQUENT COMBINATION)
2
Top of Deck Slab T/m 156.86 184.41 224.41 232.29 220.18
2
Top of Girder T/m 177.77 316.95 435.07 568.05 650.92
2
Bottom T/m 661.64 737.84 1048.78 945.61 877.39

Stress due to Temp (Fall) (Eigen Stresses)


2
Top of Deck Slab T/m -301.87 -301.87 -316.30 -127.00 -127.00
2
Top of Girder T/m -90.19 -90.19 -105.27 59.00 59.00
2
Bottom T/m -109.29 -109.29 -131.10 -128.00 -128.00

Stress at Service with 75% Live Load (sag) + Temp Fall


2
Top of Deck Slab T/m -243.82 -192.29 -130.67 87.67 83.82
Top of Girder T/m2 186.29 342.81 472.14 784.65 873.48
2
Bottom T/m 413.31 437.73 651.38 505.32 419.06

Stress at Service with 100% Live Load (sag) +60 % Temp Fall (RARE COMBINATION)
2
Top of Deck Slab T/m -110.88 -48.45 34.74 186.91 186.81
2
Top of Girder T/m 231.75 396.15 542.30 795.99 887.53
2
Bottom T/m 437.14 438.02 618.93 450.80 356.34

Stress at Service with 75% Live Load (sag) + 50% Temp Fall (FREQUENT COMBINATION)
2
Top of Deck Slab T/m -92.88 -41.36 27.48 151.17 147.32
2
Top of Girder T/m 231.39 387.90 524.77 755.15 843.98
2
Bottom T/m 467.96 492.38 716.93 569.32 483.06

Stress at Service with 20% Live Load (sag) + 60% TempFall (FREQUENT COMBINATION)
Top of Deck Slab T/m2 -149.89 -122.34 -89.72 31.90 19.79
2
Top of Girder T/m 201.73 340.91 452.53 684.19 767.07
2
Bottom T/m 500.78 576.99 890.58 789.10 720.88
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 8.973 12.974 17.175

After Stage 1 ( 14th Day)


2 2
Maximum Stress = 2254.85 t/m < 2400 t/m

2
Minimum Stress = -275.81 t/m < -350 t/m2

After Stage 2
2 2
Maximum Stress = 1515.01 t/m < 2400 t/m

2 2
Minimum Stress = 231.86 t/m < 2400 t/m

Stress at service with differential shrinkage and differential creep effect (without Live Load)
2 2
Maximum Stress = 1037.15 t/m < 2400 t/m

2
Minimum Stress = 248.35 < 2400 t/m

Stress at service with differential shrinkage and differential creep effect (with Live Load)
2 2
Maximum Stress = 852.13 t/m < 2400 t/m

2 2
Minimum Stress = 285.87 t/m < 2400 t/m

Stress at Service with Live Load (sag) + Temp Rise (FREQUENT COMBINATION)
2
Maximum Stress = 1048.78 t/m < 1800 t/m2

2 2
Minimum Stress = 177.77 t/m < -350 t/m

Stress at Service with Live Load (sag) + TempFall (FREQUENT COMBINATION)


2
Maximum Stress = 890.58 t/m < 1800 t/m2

2 2
Minimum Stress = 201.73 t/m < -350 t/m

Stress at Service with Live Load (sag) + Temp Rise (Rare COMBINATION)
2 2
Maximum Stress = 915.05 t/m < 2400 t/m

2 2
Minimum Stress = 146.36 t/m < -350 t/m
Table 5.1.2 Ultimate forces at Sections:- Ultimate Force = 1.35xDL+1.75xSIDL+1.5xLL

Partial Factor of Safety For Dead Laod= 1.35

Partial Factor of Safety For Super Imposed Dead Laod= 1.75

Partial Factor of Safety For Live Laod= 1.5

Loadings Location Near support L/8 L/4 3L/8 L/2


Shear 749.44 632.54 430.95 201.71 0.12
Dead Load
Moment 1535.78 2913.77 5147.80 6660.65 7082.39
Shear 210.00 160.00 86.00 56.00 110.00
Superimposed Dead Load
Moment 470.00 853.00 1374.00 1523.00 1323.00
Shear 479.81 416.30 324.58 247.92 296.76
Live Load Shear for Maxm. Shear Moment 943.15 1734.60 2816.52 3507.62 3779.58
Torsion 0.00 0.00 0.00 0.00 0.00
Shear 479.81 416.30 324.58 247.92 296.76
Live Load Shear with Maxm. Moment Moment 943.15 1734.60 2816.52 3507.62 3779.58
Torsion 0.00 0.00 0.00 0.00 0.00
Shear 2098.96 1758.39 1219.15 742.18 637.80
Ultimate Load for Maxm. Shear Moment 4310.53 8028.23 13578.81 16918.56 17545.85
Torsion 0.00 0.00 0.00 0.00 0.00
Shear 2098.96 1758.39 1219.15 742.18 637.80
Ultimate Load for Maxm. Moment Moment 4310.53 8028.23 13578.81 16918.56 17545.85
Torsion 0.00 0.00 0.00 0.00 0.00
Shear Capacity
D in (mm) 2740 2740 2740 2740 2740
K 1.270 1.270 1.270 1.270 1.270
I 2.014 1.786 1.559 1.559 1.559
A 2.648 2.222 1.796 1.796 1.796
Deck width 2900 2900 2900 2900 2900
CG of section 1.699 1.789 1.879 1.879 1.879
Thickness of top slab 240 240 240 240 240
fck 50.000 50.000 50.000 50.000 50.000
Horz. Prestress 8063 8133 8425 8643 8621
Total Vertical Comp. 845.86 752.45 483.50 0.00 0.00
σcp 3.04 3.66 4.69 4.81 4.80
σcp(max) 3.04 3.66 4.47 4.47 4.47
Duct Dia 90.00 90.00 90.00 90.00 90.00
bw 665.00 665.00 665.00 665.00 665.00
ρ1 (Asl/bd) 0.004 0.004 0.004 0.004 0.004
ν 0.31 0.31 0.31 0.31 0.31
fctd 1.53 1.53 1.53 1.53 1.53
Area above centroid 1.229 1.169 1.109 1.109 1.109
CG of section above centroid 696 639 581 581 581
First moment of Area 0.85 0.75 0.64 0.64 0.64
Stress at bottom fibre due to prestress 5.82 6.77 10.37 9.50 8.89
Maximum M cracked kNm 8722 8295 9875 9156 8644
Section type Uncracked Uncracked Cracked Cracked Cracked
Vrdc (Cracked) kN 1490 1658 1879 1879 1879
Vrdc (Uncracked) kN (10.4) 4152 4490 4882 4882 4882
CG of Cable 800 612 251 154 154
Maximum Shear capacity (Eqn 10.5) 7250 7951 9301 9664 9665
Shear requirement 1529 1227 897 905 778
Torsion requirement 0 0 0 0 0
Shear reinforcement requirment NO NO NO NO NO
Dia of stirrups 12.00 12.00 12.00 12.00 12.00
Number of legs 6.00 4.00 4.00 4.00 4.00
Spacing of stirrups 125 125 125 125 125
Fy 500 500 500 500 500
fwkd 435 435 435 435 435
Z=(D-cg of cable) 1940 2128 2489 2586 2586
θ 45 45 45 45 45
Asw 679 452 452 452 452
ρ 0.0082 0.0054 0.0054 0.0054 0.0054
Vrd 4581.6 3349.7 3918.4 4071.5 4071.6
ν1 0.50 0.50 0.50 0.50 0.50
αcw 1.14 1.16 1.21 1.21 1.21
Vrd.max 8274.6 9293.8 11301.0 11795.3 11790.0
Optimizatio by Vrd.max-V 3693.06 5944.11 10403.52 7723.79 7718.40
ρmin 0.0012 0.0012 0.0012 0.0012 0.0012
Check for shear capcity OK OK OK OK OK
Design of Anchor Block
Anchor block is designed as per Cl. No. 13 of IRC 112-2011

According to Manufacture's Catalog

Size of anchor flange = 345 mm

Dia of Hole = 179 mm

As per Cl No.16.11of IRC 112-2011, allowable Concentrated force/ stress

fb = fcdxSQRT(Acl/Aco) or 3xfcd Whichever is smaller

fcd = 30.15 N/mm2

Acl = 450x450- 3.14/4x179^2 = 177335.06 mm2

Aco = 345x345- 3.14/4x179^2 = 93860.057 mm2

fb = 41.44 N/mm2

Now, Maximum Cable Force after immediate Losses = 2141.92 kN

In general = 2/3rd of above force to be taken by End Bearing

= 1/3rd of above force to be taken by Anchorage

Cone and Concrete by friction

Bearing stress = N/A1 = 15.21 N/mm2

< 41.44 N/mm2 Hence O.K.

As per cl 13.5.1.1 of IRC 112:2011 2Yo = 500 mm

2Ypo = 345 mm

Ypo/Yo = 0.69

As per Table 13.1 of IRC 112:2011

Fbst/Pk = 0.124

Fbst = 0.12x2141.92

265.60 kN

Area of Steel Required = Fbst/(0.87xfy)

735.62758 mm2

Hence Provide 12T- 3L -3Nos along Web and Normal to Web

Ast = 1017.876 mm2

16 dia helix with 13 turns in 2Y0 region provided (Ast) 2613.805 mm2
Check for shear in flanged portion As per IRC: 112-2011 Clause 10.3.5.
Diffrence in stress (t/m2) 62.42

Length Ϫx (m) 2

Width of deck in one side beyond web of girder (m) 1.313

Depth of flange (deck slab) (m) 0.24

Difference in normal force between section (T) 19.66

vEDf (N/mm2) 0.41

θf 30

cotθf 1.73

fyd (N/mm2) 434.8

Asf/sf (mm) 0.131

spacing sf (mm) 200

Asf (mm2) 26.11

Dia of bar provided (mm) 16

Area provided (mm2) 201.1


DESIGN OF SHEAR CONNECTORS(OUTER GIRDER)AT SUPPORT SECTION

Width of beam = 950 mm


Shear = 2099 kN
Z (lever arm) = 681.2531 mm
Dia of interface reinforement = 12.00
Number of legs = 6.00
Spacing = 125.00 mm

Design value of interface shear stress: VEd = 3.243184 MPa


vEd 
zb
Design shear resistance at the interface:

2
Area of the interface = 228000 mm2 ; Area of interface reinforcement: 5428.672 mm /m

Angle of reinforcement to interface: a 90 deg

Surface roughness: Smooth 0.6

vEdi  cfctd  h


reinforcement ratio required:  min  = 0.012426
fyd Sina  Cosa 

Area of interface reinforcement required = 2833.126 mm2 OK


Maximum spacing of links using current preferred bar diameter =

DESIGN OF SHEAR CONNECTORS(OUTER GIRDER)AT MID SECTION

Width of beam = 950 mm


Shear = 1758 kN
Z (lever arm) = 591.1009 mm
Dia of interface reinforement = 12.00
Number of legs = 4.00
Spacing = 125.00 mm

Design value of interface shear stress: VEd = 3.131333 MPa


vEd 
zb
Design shear resistance at the interface:

2
Area of the interface = 228000 mm2 ; Area of interface reinforcement: 3619.115 mm /m

Angle of reinforcement to interface: a 90 deg

Surface roughness: Smooth 0.6

vEdi  cfctd  h


reinforcement ratio required:  min  = 0.011997
fyd Sina  Cosa 

Area of interface reinforcement required = 2735.417 mm2 OK


Maximum spacing of links using current preferred bar diameter =
Cable Forces inner girder
Cable No 1

Jacking Force 257.861


Symmetrical Cable

X Y Z Slope y Slope z Deviation Length Pfriction Pslip


0 0.400 0.000 -0.078 0.000 257.9 225.1
3 0.167 0.000 -0.078 0.000 0.000 3.009 256.3 226.7
4.2 0.120 0.000 0.000 0.000 0.078 1.201 252.3 230.7
4.5 0.120 0.000 0.000 0.000 0.000 0.300 252.2 230.8
6.3 0.120 -0.060 0.000 -0.067 0.067 1.801 248.5 234.6
7.2 0.120 -0.120 0.000 -0.067 0.000 0.902 248.0 235.0
9 0.120 -0.180 0.000 0.000 0.067 1.801 244.3 238.7
16.8075 0.120 -0.180 0.000 0.000 0.000 7.808 240.5 240.5
16.821
Length of Cable 33.643

Null point 16.82


Pmin 240.5

Pslipleft 241.5047 Xslipleft 14.8250


Pslipright 253.1 Xslipright 18.7900

Cable No 2

Jacking Force 257.861


Symmetrical Cable

X Y Z Slope y Slope z Deviation Length Pfriction Pslip


0 0.800 0.000 -0.084 0.000 257.9 227.2
4.5 0.422 0.000 -0.084 0.000 0.000 4.516 255.5 229.5
6.3 0.271 0.060 -0.084 0.067 0.067 1.807 251.8 233.3
7.2 0.196 0.120 -0.084 0.067 0.000 0.905 251.3 233.7
7.5 0.170 0.138 -0.084 0.056 0.011 0.302 250.7 234.3
8.7 0.120 0.178 0.000 0.011 0.128 1.202 244.7 240.3
9 0.120 0.180 0.000 0.000 0.011 0.300 244.1 240.9
16.8075 0.120 0.180 0.000 0.000 0.000 7.808 240.3 240.3
16.839
Length of Cable 33.678

Null point 16.84


Pmin 240.3

Pslipleft 242.5082 Xslipleft 12.2520


Pslipright 254.1 Xslipright 21.3630
Cable No 3

Jacking Force 257.861


Symmetrical Cable

X Y Z Slope y Slope z Deviation Length Pfriction Pslip


0 1.200 0.000 -0.110 0.000 257.9 233.1
9.2 0.186 0.000 -0.110 0.000 0.000 9.256 253.1 237.8
10.4 0.120 0.000 0.000 0.000 0.110 1.202 247.8 243.1
16.8075 0.120 0.000 0.000 0.000 0.000 6.408 244.7 244.7
16.865
Length of Cable 33.730

Null point 16.87


Pmin 244.7

Pslipleft 245.4708 Xslipleft 15.1973


Pslipright 257.0 Xslipright 18.4177

Cable No 4

Jacking Force 143.256


Symmetrical Cable

X Y Z Slope y Slope z Deviation Length Pfriction Pslip


0 1.600 0.000 -0.112 0.000 143.3 130.1
11 0.367 0.000 -0.112 0.000 0.000 11.069 140.1 133.3
12.2 0.300 0.000 0.000 0.000 0.112 1.202 137.1 136.2
16.8075 0.300 0.000 0.000 0.000 0.000 4.608 135.9 135.9
16.878
Length of Cable 33.756

Null point 16.88


Pmin 135.9

Pslipleft 136.6863 Xslipleft 13.8768


Pslipright 240.6 Xslipright 19.7382
Stress Check for Inner Girder
Basic Design Data

Characteristics value of prestressing 0.9

1st stage prestressing 14 day


2nd stage prestressing 28 day
Casting of Deck Slab 28 day
3rd stage prestressing 90 day
Shift of Bearing 90 day
SIDL(Wearing Coat & Crash Barrier) 90 day
Age of deck slab at time of 3rd stage 62 day

Fck 50 Mpa
Modulus of Elasticity (Conc) 14th Day 3.30E+06 t/m2
Modulus of Elasticity (Conc) 28th Day 3.40E+06 t/m2
Modulus of Elasticity (Conc) 28th Day 3.40E+06 t/m2
Modulus of Elasticity (Conc) 90th Day 3.51E+06 t/m2
Modulus of Elasticity (Strands) 1.95E+07 t/m2

Type of cables 19 T13


Area of 1 strand 0.0000987 m2
Area of one cable 1.8753E-03 m2
no of cables stressed in 1st stage 3.37
no of cables stressed in 2nd stage 0.001
no of tendons stressed in 3rd stage 0.00
Jacking Force 0.765 *UTS
No of Sections to be checked 5
Prestressing force per cable (UTS) 355.8 t
Increase Factors for losses
Elastic Shortening loss 1.0
Relaxation loss 1.0
Shrinkage loss 1.0
Creep loss 1.0

Factor for Shrinkage loss


14th day 2.47E-04
28th day 2.25E-04
90th day 1.73E-04
90th day 1.73E-04
90th day 1.73E-04
Infinity 1.73E-04

Factor for Creep Loss


14th day 0.00E+00
28th day 1.60E-04
90th day 2.61E-04
90th day 2.61E-04
90th day 2.61E-04
Infinity 5.45E-04

Factor for Relaxation Loss


1000hr relaxation 2.50%

Total Relaxation Loss at service condition (cl: 6.3.6 IRC 112) = 3 x (1000 hr. value)
Initial force after Friction, slip & ES loss = 825.82 t
Percentage of Initial force = 0.6891 UTS
Relaxation Loss at 1000hr. for low relaxation steel = 2.36 % of initial stress
Relaxation Loss at 1000hr. for low relaxation steel = 5.79 t/Cable
Immediate Loss i.e 1 hr. of stressing (Table 6.3 IRC:112) = 34 % of Total Loss
7 - 28 days Loss = 90 % of Total Loss
28 - 90 days Loss = 100 % of Total Loss
90 - a days Loss = 200 % of Total Loss
Immediate Loss i.e 1 hr. of stressing = 1.97 t/Cable
7 - 28 days Loss = 3.24 t/Cable
28 - 90 days Loss = 0.58 t/Cable
90 - a days Loss = 11.59 t/Cable
Strain due to differential shrinkage and creep 1.00E-04
Reduction factor due to differential creep 0.43
PSC BEAM AND RC SLAB STRUCTURE OF SIMPLY SUPPORTED SPAN
(INNER GIRDER)
Item Unit 1 2 3 4 5
MEMBER NO
distance of Section from left support m 2.000 4.000 6.090 12.180 16.970

Details of Section property (Individual Beam Section)


Area of the section m2 1.8142 1.3881 0.9620 0.9620 0.9620
Depth of the section m 2.5000 2.5000 2.5000 2.5000 2.5000
CG of section from bottom m 1.2752 1.2560 1.2367 1.2367 1.2367
Moment of Inertia of section m4 0.9769 0.8383 0.6998 0.6998 0.6998

Details of Section property (Composite Section)


Area of the section m2 2.5100 2.0840 1.6580 1.6580 1.6580
Depth of the section m 2.7400 2.7400 2.7400 2.7400 2.7400
CG of section from bottom m 1.6987 1.7579 1.8170 1.8170 1.8170
Moment of Inertia of section m4 1.8900 1.6830 1.4760 1.4760 1.4760

Details of Section property (Composite Section)


Area of the section m2 2.5100 2.0840 1.6580 1.6580 1.6580
Depth of the section m 2.7400 2.7400 2.7400 2.7400 2.7400
CG of section from bottom m 1.6987 1.7579 1.8170 1.8170 1.8170
Moment of Inertia of section m4 1.8900 1.6830 1.4760 1.4760 1.4760

Details of Stage I prestressing after 14 day For Cable 1a/1


Prestressing Force (P1) (Hor) T 225.31 228.65 237.85 240.43 240.55
CG of Tendons from Bottom m 0.27 0.13 0.12 0.12 0.12
Prestressing Force (P1) (Ver) T 17.52 8.40 0.00 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1b/2


Prestressing Force (P1) (Hor) T 227.20 228.23 239.84 242.34 240.31
CG of Tendons from Bottom m 0.66 0.50 0.12 0.12 0.12
Prestressing Force (P1) (Ver) T 19.07 19.16 1.60 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1c/3


Prestressing Force (P1) (Hor) T 232.52 233.54 236.08 244.20 244.69
CG of Tendons from Bottom m 1.02 0.80 0.25 0.12 0.12
Prestressing Force (P1) (Ver) T 25.62 25.74 26.02 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1d/4


Prestressing Force (P1) (Hor) T 129.77 130.34 131.75 136.34 135.89
CG of Tendons from Bottom m 1.42 1.19 0.64 0.30 0.30
Prestressing Force (P1) (Ver) T 14.54 14.61 14.77 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1e/5


Prestressing Force (P1) (Hor) T 0.00 0.00 0.00 0.00 0.00
CG of Tendons from Bottom m 0.00 0.00 0.00 0.00 0.00
Prestressing Force (P1) (Ver) T 0.00 0.00 0.00 0.00 0.00
PSC BEAM AND RC SLAB STRUCTURE OF SIMPLY SUPPORTED SPAN
(INNER GIRDER)
Item Unit 1 2 3 4 5
MEMBER NO
distance of Section from left support m 2.000 4.000 6.090 12.180 16.970
Details of Stage II prestressing after 28 day For Cable 2a
Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2b


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2c


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2d


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2e


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage III prestressing after 90th day


Prestressing Force (P3) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P3) (Ver) T 0.01 0.01 0.01 0.01 0.01
PSC BEAM AND RC SLAB STRUCTURE OF SIMPLY SUPPORTED SPAN
(INNER GIRDER)
Item Unit 1 2 3 4 5
MEMBER NO
distance of Section from left support m 2.000 4.000 6.090 12.180 16.970

Dead Load - Ist stage


Moments Tm 76.1 146.0 258.0 334.0 355.0
Shear T 38.6 31.7 21.6 10.1 0.0

Dead Load - Ist stage due to permanent bearing


Moments Tm 86.3 157.0 269.0 344.0 365.0
Shear T 38.6 31.7 21.6 10.1 0.0

Dead Load - Ist stage due to shift of bearing


Moments Tm 10.2 11.0 11.0 10.0 10.0
Shear T 0.0 0.0 0.0 0.0 0.0

Construction load/Shuttering load


Moments Tm 22.5 42.2 74.6 96.5 102.7
shear 10.6 9.2 6.2 2.9 0.0

Dead Load - 2nd stage


Moments Tm 59.0 111.0 197.5 258.6 279.5
Shear T 27.7 24.3 17.0 8.7 1.3

SIDL
Moments Tm 23.5 42.1 87.0 141.3 191.3
Shear T 11.2 10.6 11.4 11.8 10.7

Live Load (Sagging) (max Moment Case & max Positive Shear case)
Moments Tm 129.2 203.6 292.8 318.8 293.9
Shear T 50.0 40.9 28.8 31.1 41.4

Stress due to Temp (Rise) (Eigen stresses)


top of deck slab T/m2 -212.41 -212.41 209.68 209.68 209.68
top of girder T/m2 127.60 127.60 -132.35 -132.35 -132.35
bottom T/m2 -156.01 -156.01 130.19 130.19 130.19

Stress due to Temp (Fall) (Eigen Stresses)


top of deck slab T/m2 -296.60 -296.60 -312.79 -312.79 -312.79
top of girder T/m2 -85.64 -85.64 -102.17 -102.17 -102.17
bottom T/m2 -112.33 -112.33 -132.43 -132.43 -132.43
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Details of Section property (Individual Beam Section)

2
Area of the section m 1.8142 1.38808125 0.96196 0.961963 0.9619625
Depth of the section m 2.500 2.500 2.500 2.500 2.500
CG of section from bottom m 1.2752406 1.255953054 1.23667 1.236665 1.236665476
4
Inertia of section m 0.9769032 0.838329327 0.69976 0.699755 0.699755494
3
Top Section Modulus m 0.7976 0.6739 0.5539 0.5539 0.5539
3
Bottom Section Modulus m 0.7661 0.6675 0.5658 0.5658 0.5658

Details of Section property (Composite Section) (62 day old slab)

2
Area of the section m 2.51 2.084 1.658 1.658 1.658
Depth of the section m 2.740 2.740 2.740 2.740 2.740
CG of section from bottom m 1.6987469 1.757873453 1.817 1.817 1.817
4
Inertia of section m 1.89 1.683 1.476 1.476 1.476
3
Top Section Modulus m 1.8151 1.7136 1.5991 1.5991 1.5991
3
Bottom Section Modulus m 1.1126 0.9574 0.8123 0.8123 0.8123

Details of Section property (Composite Section)

2
Area of the section m 2.51 2.084 1.658 1.658 1.658
Depth of the section m 2.740 2.740 2.740 2.740 2.740
CG of section from bottom m 1.6987469 1.757873453 1.817 1.817 1.817
4
Inertia of section m 1.89 1.683 1.476 1.476 1.476
3
Top Section Modulus m 1.8151 1.7136 1.5991 1.5991 1.5991
3
Bottom Section Modulus m 1.1126 0.9574 0.8123 0.8123 0.8123

Details of Stage I prestressing


For Cable 1a
No of Tendons of 19T13 0.95 0.95 0.95 0.95 0.95
Prestressing Force (P1) T 225.31 228.65 237.85 240.43 240.55
CG of Tendons from Bottom m 0.2730 0.1304 0.1200 0.1200 0.1200
Eccentricity of Tendons m 1.0023 1.1255 1.1167 1.1167 1.1167
Prestressing Factor (Top) -0.7053 -0.9498 -0.9765 -0.9765 -0.9765
Prestressing Factor (Bottom) 1.8595 2.4066 3.0130 3.0130 3.0130

For Cable 1b
No of Tendons of 19T13 0.95 0.95 0.95 0.95 0.95
Prestressing Force (P1) T 227.20 228.23 239.84 242.34 240.31
CG of Tendons from Bottom m 0.6629 0.4950 0.1203 0.1200 0.1200
Eccentricity of Tendons m 0.6123 0.7609 1.1163 1.1167 1.1167
Prestressing Factor (Top) -0.2165 -0.4088 -0.9759 -0.9765 -0.9765
Prestressing Factor (Bottom) 1.3505 1.8604 3.0124 3.0130 3.0130

For Cable 1c
No of Tendons of 19T13 0.95 0.95 0.95 0.95 0.95
Prestressing Force (P1) T 232.52 233.54 236.08 244.20 244.69
CG of Tendons from Bottom m 1.0200 0.7996 0.2516 0.1200 0.1200
Eccentricity of Tendons m 0.2552 0.4563 0.9851 1.1167 1.1167
Prestressing Factor (Top) 0.2313 0.0433 -0.7389 -0.9765 -0.9765
Prestressing Factor (Bottom) 0.8843 1.4041 2.7805 3.0130 3.0130
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

For Cable 1d
No of Tendons of 19T13 0.53 0.53 0.53 0.53 0.53
Prestressing Force (P1) T 129.77 130.34 131.75 136.34 135.89
CG of Tendons from Bottom m 1.4170 1.1929 0.6355 0.3000 0.3000
Eccentricity of Tendons m -0.1418 0.0631 0.6011 0.9367 0.9367
Prestressing Factor (Top) 0.7289 0.6268 -0.0457 -0.6515 -0.6515
Prestressing Factor (Bottom) 0.3662 0.8150 2.1019 2.6949 2.6949

For Cable 1e
No of Tendons of 19T13 0.00 0.00 0.00 0.00 0.00
Prestressing Force (P1) T 0.00 0.00 0.00 0.00 0.00
CG of Tendons from Bottom m 0.0000 0.0000 0.0000 0.0000 0.0000
Eccentricity of Tendons m 1.2752 1.2560 1.2367 1.2367 1.2367
Prestressing Factor (Top) -1.0476 -1.1434 -1.1931 -1.1931 -1.1931
Prestressing Factor (Bottom) 2.2159 2.6020 3.2251 3.2251 3.2251

Combination of Stage 1 Cables


No of Tendons of 19T13 3.37 3.37 3.37 3.37 3.37
Prestressing Force (P1) T 814.80 820.76 845.53 863.30 861.44
CG of Tendons from Bottom m 0.7771 0.5910 0.2372 0.1484 0.1484
Eccentricity of Tendons m 0.4981 0.6650 0.9995 1.0882 1.0883
Prestressing Factor (Top) -0.0733 -0.2664 -0.7650 -0.9252 -0.9252
Prestressing Factor (Bottom) 1.2015 1.7167 2.8059 2.9628 2.9628

Dead Load Moments - Ist stage Tm 76.10 146.00 258.00 334.00 355.00

Stress Due to dead load


2
Top T/m 95.41 216.66 465.79 603.00 640.91
2
Bottom T/m -99.34 -218.73 -455.96 -590.27 -627.39

Eloss of cable (1a) for stressing of (1a) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1a) for stressing of (1b) T 5.67 5.67 5.67 5.67 5.67
Eloss of cable (1a) for stressing of (1c) T 5.26 5.26 5.26 5.26 5.26
Eloss of cable (1a) for stressing of (1d) T 2.39 2.39 2.39 2.39 2.39
Eloss of cable (1a) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1b) for stressing of (1b) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1b) for stressing of (1c) T 5.20 5.20 5.20 5.20 5.20
Eloss of cable (1b) for stressing of (1d) T 2.39 2.39 2.39 2.39 2.39
Eloss of cable (1b) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1c) for stressing of (1c) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1c) for stressing of (1d) T 2.36 2.36 2.36 2.36 2.36
Eloss of cable (1c) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1d) for stressing of (1d) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1d) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1e) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00

Total Eloss for Stage 1 cables T 23.27 23.27 23.27 23.27 23.27
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Stress after stressing of 1a


2
Top T/m -143.03 -192.60 -198.01 -198.01 -198.01
2
Bottom T/m 377.08 488.01 610.98 610.98 610.98
2
Stress at CG of 1a T/m 320.28 452.50 572.15 572.15 572.15
2
Avg stress for each segment T/m 386.39 512.32 572.15 572.15 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Average Stress at CG of 1a T/m 538.98

Stress after stressing of 1b


2
Top T/m -183.70 -271.72 -403.69 -406.00 -404.22
2
Bottom T/m 643.75 857.88 1245.88 1252.76 1247.27
2
Stress at CG of 1a T/m 553.40 798.94 1166.70 1173.14 1168.00
2
Avg stress for each segment T/m 676.17 982.82 1169.92 1170.57 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1a T/m 539.06
2
Stress at CG of 1b T/m 424.34 634.22 1166.49 1173.14 1168.00
2
Avg stress for each segment T/m 529.28 900.35 1169.81 1170.57 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Average Stress at CG of 1b T/m 1046.86
Check Eloss of cable (1a) for (1b) T 5.67

Stress after stressing of 1c


2
Top T/m -130.95 -256.22 -551.49 -611.41 -610.06
2
Bottom T/m 813.68 1132.89 1808.26 1886.56 1882.40
2
Stress at CG of 1a T/m 710.53 1060.41 1694.99 1766.66 1762.76
2
Avg stress for each segment T/m 885.47 1377.70 1730.82 1764.71 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
Increase in Average Stress at CG of 1a T/m2 501.39
2
Stress at CG of 1b T/m 563.20 857.84 1694.69 1766.66 1762.76
2
Avg stress for each segment T/m 710.52 1276.27 1730.67 1764.71 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1b T/m 494.97
2
Stress at CG of 1c T/m 428.26 688.58 1570.79 1766.66 1762.76
2
Avg stress for each segment T/m 558.42 1129.69 1668.72 1764.71 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Average Stress at CG of 1c T/m 1475.84
Check Eloss of cable (1a) for (1c) T 5.27
Check Eloss of cable (1b) for (1c) T 5.20
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Stress after stressing of 1d


2
Top T/m -44.32 -179.86 -551.15 -685.08 -683.47
2
Bottom T/m 847.67 1216.33 2038.63 2197.87 2192.62
2
Stress at CG of 1a T/m 750.27 1143.48 1914.32 2059.49 2054.57
2
Avg stress for each segment T/m 946.87 1528.90 1986.91 2057.03 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1a T/m 227.03
2
Stress at CG of 1b T/m 611.14 939.88 1913.99 2059.49 2054.57
2
Avg stress for each segment T/m 775.51 1426.93 1986.74 2057.03 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1b T/m 227.43
2
Stress at CG of 1c T/m 483.72 769.76 1778.01 2059.49 2054.57
2
Avg stress for each segment T/m 626.74 1273.88 1918.75 2057.03 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1c T/m 224.51
2
Stress at CG of 1d T/m 342.09 550.15 1380.27 1851.92 1847.49
2
Avg stress for each segment T/m 446.12 965.21 1616.10 1849.71 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Average Stress at CG of 1d T/m 1443.66
Check Eloss of cable (1a) for (1d) T 2.39
Check Eloss of cable (1b) for (1d) T 2.39
Check Eloss of cable (1c) for (1d) T 2.36

Stress after stressing of 1e


2
Top T/m -44.32 -179.86 -551.15 -685.08 -683.47
2
Bottom T/m 847.67 1216.33 2038.63 2197.87 2192.62
2
Stress at CG of 1a T/m 750.27 1143.48 1914.32 2059.49 2054.57
2
Avg stress for each segment T/m 946.87 1528.90 1986.91 2057.03 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1a T/m 0.00
2
Stress at CG of 1b T/m 611.14 939.88 1913.99 2059.49 2054.57
2
Avg stress for each segment T/m 775.51 1426.93 1986.74 2057.03 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1b T/m 0.00
2
Stress at CG of 1c T/m 483.72 769.76 1778.01 2059.49 2054.57
2
Avg stress for each segment T/m 626.74 1273.88 1918.75 2057.03 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1c T/m 0.00
2
Stress at CG of 1d T/m 342.09 550.15 1380.27 1851.92 1847.49
2
Avg stress for each segment T/m 446.12 965.21 1616.10 1849.71 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1d T/m 0.00
2
Stress at CG of 1e T/m 847.67 1216.33 2038.63 2197.87 2192.62
2
Avg stress for each segment T/m 1032.00 1627.48 2118.25 2195.25 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Average Stress at CG of 1e T/m 1929.25
Check Eloss of cable (1a) for (1e) T 0.00
Check Eloss of cable (1b) for (1e) T 0.00
Check Eloss of cable (1c) for (1e) T 0.00
Check Eloss of cable (1d) for (1e) T 0.00
Immidiate Relaxation Loss T 19.52 19.52 19.52 19.52 19.52
Top 12.39 16.68 17.15 17.15 17.15
Bottom -32.66 -42.27 -52.92 -52.92 -52.92
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Stress after stressing of Stage1 Cables


2
Top T/m 63.48 53.48 -68.20 -64.93 -25.40
2
Bottom T/m 715.66 955.33 1529.75 1554.68 1512.32

2
Stress at CG of cable 1a T/m 644.45 908.27 1453.05 1476.94 1438.51
2
Stress at CG of cable 1b T/m 542.73 776.76 1452.84 1476.94 1438.51
2
Stress at CG of cable 1c T/m 449.56 666.87 1368.94 1476.94 1438.51
2
Stress at CG of cable 1d T/m 346.01 525.02 1123.53 1360.33 1327.79
2
Stress at CG of cable 1e T/m 715.66 955.33 1529.75 1554.68 1512.32

Losses From 14 to 28 day

Creep loss due to GR I Tendons T 2.35 2.35 2.35 2.35 2.35


Shrinkage loss due to GR I Tendons T 2.71 2.71 2.71 2.71 2.71
=(0.000225-0.000247)*3.36842105263158*0.0018753*19500000*1
Relaxation loss due to GR I Tendons

Relaxation loss due to GR I Tendons T 10.93 10.93 10.93 10.93 10.93

Total Loss (C+S+R) T 14.39 14.39 14.39 14.39 14.39

Stress Due to C+S+R


2
Top T/m 1.06 3.83 11.01 13.31 13.31
2
Bottom T/m -17.29 -24.70 -40.38 -42.64 -42.64

Stress before stressing of GR II cables at 28 day


2
Top T/m 76.92 74.00 -40.04 -34.46 5.06
2
Bottom T/m 665.71 888.35 1436.45 1459.12 1416.76

2
Stress at CG of Stage 1 Cables T/m 482.69 695.85 1296.38 1370.45 1332.96
2
T/m

2
Average Stress at CG of Stage 1 Cables T/m 1192.76

Creep loss (check) T 2.35


=(0.00016-0)*3.36842105263158*0.0018753*19500000*1192.75968294732/10000*1
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Stress due to shuttering load (for casting of Deck Slab)


Top T/m2 28.23 62.69 134.72 174.22 185.33
2
Bottom T/m -29.39 -63.29 -131.88 -170.54 -181.42

Dead Load Moments -IInd stage Tm 58.96 110.96 197.50 258.56 279.55
Stress Due to dead load
2
Top T/m 73.92 164.65 356.56 466.80 504.69
2
Bottom T/m -76.96 -166.23 -349.03 -456.95 -494.04

2
Stress at CG of GR I Tendons T/m -30.06 -88.02 -282.10 -402.10 -434.76
2
Stress at CG of GR II Tendons T/m 2643.11 -164.91 -346.21 -453.25 -490.04

Dead Load Moments -Ist stage due to shift of


bearing Tm 10.20 11.00 11.00 10.00 10.00
2
Top T/m 12.79 16.32 19.86 18.05 18.05
2
Bottom T/m -13.31 -16.48 -19.44 -17.67 -17.67

Shuttering Load Moments Tm 22.52 42.25 74.62 96.50 102.65


Stress due to release of shuttering load
2
Top T/m -12.40 -24.65 -46.66 -60.35 -64.19
Top of Girder -9.55 -18.63 -34.53 -44.65 -47.50
2
Bottom T/m 20.24 44.13 91.86 118.79 126.37

Stress after release of shuttering load


2
Top of Deck Slab T/m -12.40 -24.65 -46.66 -60.35 -64.19
2
Top of Girder T/m 182.26 298.99 436.51 579.90 665.58
2
Bottom T/m 566.38 686.59 1028.11 932.90 850.14

Losses from 28 to 90 day

Creep Loss of Gr I Tendons T 1.03 1.03 1.03 1.03 1.03


Shrinkage loss of Gr I Tendons T 6.41 6.41 6.41 6.41 6.41
=(0.000225-0.000173)*3.36842105263158*0.0018753*19500000*1
Relaxation loss of Gr. I Tendons T 1.95 1.95 1.95 1.95 1.95

Total Loss due to C + S + R 8.44 8.43 8.43 8.43 8.43

Stresses due to C + S + R
2
Top T/m 0.96 1.69 3.24 3.71 3.71
2
T/m -0.03 0.29 1.08 1.42 1.42
2
Bottom T/m -10.42 -14.31 -21.48 -22.40 -22.40

Prestressing factor for composite section


Stage 1 Cables Top -0.109 -0.201 -0.385 -0.440 -0.440
Bottom 1.227 1.699 2.548 2.657 2.657

Stress at 90nd day before laying SIDL


2
Top of Deck Slab T/m -11.44 -22.96 -43.42 -56.63 -60.48
2
Top of Girder T/m 182.23 299.28 437.59 581.33 667.01
2
Bottom T/m 555.96 672.28 1006.63 910.50 827.74

2
Stress at CG of Tendon I T/m 439.79 584.11 952.65 890.96 818.20

2
Average Stress at CG of Tendon GRI T/m 824.12

Check for Creep Loss of Gr I Cables 1.03


=(0.000261-0.00016)*3.36842105263158*0.0018753*19500000*824.11661437369/10000*1

SIDL applied at 90nd day Tm 23.50 42.10 87.00 141.30 191.30


Stress due to SIDL
2
Top T/m 12.95 24.57 54.40 88.36 119.63
9.96 18.56 40.26 65.38 88.52
Bottom T/m2 -21.12 -43.97 -107.10 -173.94 -235.50

2
Stress at CG of Gr I Tendons T/m -11.46 -29.19 -93.12 -159.74 -216.26
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Creep, Shrinkage & Relaxation losses from 90 day upto infinity

Creep loss of Gr. I T =34.98 34.98 34.98 34.98 34.98


Shrinkage loss of Gr. I T 21.31 21.31 21.31 21.31 21.31
=(0.000173-0.000173)*3.36842105263158*0.0018753*19500000*1
Relaxation loss of Gr. I T 39.03 39.03 39.03 39.03 39.03

Total Loss due to C+S+R 85.78 85.78 85.78 85.78 85.78

Stress due to C+S+R


2
Top T/m 9.62 17.25 33.01 37.77 37.77
-0.47 2.98 10.97 14.49 14.50
2
Bottom T/m -105.63 -145.71 -218.57 -227.94 -227.94

Stress during Service at infinity


2
Top of Deck Slab T/m 11.13 18.85 43.99 69.49 96.91
2
Top of Girder T/m 191.72 320.82 488.82 661.21 770.03
2
Bottom T/m 429.20 482.60 680.96 508.62 364.31

2
Stress at CG of Tendon I T/m 355.38 444.36 662.74 517.68 388.39

2
Avg stress for each segment T/m 399.87 553.55 590.21 453.03 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Average Stress at CG of Tendon GRI T/m 515.77

Check for Creep Loss of Gr I Cables


=(0.000545-0.000261)*3.36842105263158*0.0018753*19500000*1 = =34.98

Moment Due to Live Load (Sagging) Tm 129.23 203.58 292.80 318.79 293.93
Stresses due to Live Load (Sagging)
2
Top of Deck Slab T/m 71.20 118.80 183.10 199.35 183.81
2
Top of Girder T/m 54.79 89.77 135.49 147.51 136.01
2
Bottom T/m -116.16 -212.64 -360.45 -392.44 -361.84

Stress at service with Live Load (Sagging)


2
Top of Deck Slab T/m 82.33 137.66 227.09 268.84 280.72
2
Top of Girder T/m 246.51 410.59 624.31 808.72 906.04
2
Bottom T/m 313.05 269.96 320.52 116.18 2.47

Stress at service with differential shrinkage and differential creep effect (without Live Load)
Top of Deck Slab T/m2 11.13 18.85 43.99 69.49 96.91
2
Top of Girder T/m 191.72 320.82 488.82 661.21 770.03
2
Bottom T/m 429.20 482.60 680.96 508.62 364.31

Stress at service with differential shrinkage and differential creep effect (with 75% Live Load)
2
Top of Deck Slab T/m 64.53 107.96 181.31 219.01 234.77
2
Top of Girder T/m 232.81 388.14 590.44 771.84 872.04
2
Bottom T/m 342.08 323.12 410.63 214.29 92.93
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Stress due to Temp (Rise) (Eigen stresses)


2
Top of Deck Slab T/m -212.41 -212.41 209.68 209.68 209.68
2
Top of Girder T/m 127.60 127.60 -132.35 -132.35 -132.35
2
Bottom T/m -156.01 -156.01 130.19 130.19 130.19

Stress at Service with 75% Live Load (sag) + Temp rise (RARE COMBINATION)
2
Top of Deck Slab T/m -147.88 -104.45 390.99 428.68 444.45
2
Top of Girder T/m 360.41 515.74 458.09 639.49 739.68
2
Bottom T/m 186.07 167.11 540.82 344.48 223.12

Stress at Service with 100% Live Load (sag) + 60% Temp rise (RARE COMBINATION)
2
Top of Deck Slab T/m -45.12 10.21 352.90 394.65 406.53
2
Top of Girder T/m 323.06 487.15 544.90 729.31 826.63
2
Bottom T/m 219.44 176.35 398.63 194.30 80.58

Stress at Service with 75% Live Load (sag) + 50% Temp rise (FREQUENT COMBINATION)
2
Top of Deck Slab T/m -41.68 1.75 286.15 323.84 339.61
2
Top of Girder T/m 296.61 451.94 524.26 705.67 805.86
2
Bottom T/m 264.08 245.11 475.72 279.39 158.02

Stress at Service with 20% Live Load (sag) + 60% Temp rise (FREQUENT COMBINATION)
2
Top of Deck Slab T/m -102.07 -84.83 206.42 235.17 259.48
2
Top of Girder T/m 279.23 415.33 436.51 611.30 717.82
2
Bottom T/m 312.36 346.46 686.99 508.25 370.05

Stress due to Temp (Fall) (Eigen Stresses)


2
Top of Deck Slab T/m -296.60 -296.60 -312.79 -312.79 -312.79
2
Top of Girder T/m -85.64 -85.64 -102.17 -102.17 -102.17
2
Bottom T/m -112.33 -112.33 -132.43 -132.43 -132.43

Stress at Service with 75% Live Load (sag) + Temp Fall


2
Top of Deck Slab T/m -232.07 -188.64 -131.47 -93.78 -78.01
Top of Girder T/m2 147.16 302.50 488.26 669.67 769.86
2
Bottom T/m 229.75 210.79 278.20 81.86 -39.50

Stress at Service with 100% Live Load (sag) +60 % Temp Fall (RARE COMBINATION)
2
Top of Deck Slab T/m -95.63 -40.30 39.42 81.17 93.05
2
Top of Girder T/m 195.12 359.20 563.01 747.42 844.73
2
Bottom T/m 245.65 202.56 241.06 36.73 -76.99

Stress at Service with 75% Live Load (sag) + 50% Temp Fall (FREQUENT COMBINATION)
2
Top of Deck Slab T/m -83.77 -40.34 24.92 62.61 78.38
2
Top of Girder T/m 189.99 345.32 539.35 720.76 820.95
2
Bottom T/m 285.92 266.95 344.42 148.08 26.71

Stress at Service with 20% Live Load (sag) + 60% TempFall (FREQUENT COMBINATION)
Top of Deck Slab T/m2 -152.59 -135.34 -107.06 -78.31 -53.99
2
Top of Girder T/m 151.29 287.38 454.61 629.41 735.92
2
Bottom T/m 338.57 372.67 529.42 350.68 212.48
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

After Stage 1 ( 14th Day)


2 2
Maximum Stress = 1554.68 t/m < 2400 t/m

2
Minimum Stress = -68.20 t/m < -350 t/m2

After Stage 2
2 2
Maximum Stress = 1028.11 t/m < 2400 t/m

2 2
Minimum Stress = 182.26 t/m < 2400 t/m

Stress at service with differential shrinkage and differential creep effect (without Live Load)
2 2
Maximum Stress = 770.03 t/m < 2400 t/m

2
Minimum Stress = 191.72 < 2400 t/m

Stress at service with differential shrinkage and differential creep effect (with Live Load)
2 2
Maximum Stress = 906.04 t/m < 2400 t/m

2 2
Minimum Stress = 2.47 t/m < 2400 t/m

Stress at Service with Live Load (sag) + Temp Rise (FREQUENT COMBINATION)
2
Maximum Stress = 805.86 t/m < 1800 t/m2

2 2
Minimum Stress = 158.02 t/m < -350 t/m

Stress at Service with Live Load (sag) + TempFall (FREQUENT COMBINATION)


2
Maximum Stress = 820.95 t/m < 1800 t/m2

2 2
Minimum Stress = 26.71 t/m < -350 t/m

Stress at Service with Live Load (sag) + Temp Rise (Rare COMBINATION)
2 2
Maximum Stress = 826.63 t/m < 2400 t/m

2 2
Minimum Stress = 80.58 t/m < -350 t/m

Stress at Service with Live Load (sag) + TempFall (Rare COMBINATION)


2 2
Maximum Stress = 844.73 t/m < 2400 t/m

2 2
Minimum Stress = -76.99 t/m < -350 t/m
Table 5.1.2 Ultimate forces at Sections:- Ultimate Force = 1.35xDL+1.75xSIDL+1.5xLL

Partial Factor of Safety For Dead Laod= 1.35

Partial Factor of Safety For Super Imposed Dead Laod= 1.75

Partial Factor of Safety For Live Laod= 1.5

Loadings Location Near support L/8 L/4 3L/8 L/2


Shear 663.39 559.59 385.51 187.51 13.43
Dead Load
Moment 1350.58 2569.56 4554.97 5925.59 6345.47
Shear 112.00 106.00 114.00 118.00 107.20
Superimposed Dead Load
Moment 235.00 421.00 870.00 1413.00 1913.00
Shear 499.80 409.25 288.12 310.93 414.22
Live Load Shear for Maxm. Shear Moment 1292.32 2035.83 2928.00 3187.88 2939.33
Torsion 0.00 0.00 0.00 0.00 0.00
Shear 499.80 409.25 288.12 310.93 414.22
Live Load Shear with Maxm. Moment Moment 1292.32 2035.83 2928.00 3187.88 2939.33
Torsion 0.00 0.00 0.00 0.00 0.00
Shear 1841.28 1554.82 1152.12 926.04 827.06
Ultimate Load for Maxm. Shear Moment 4173.02 7259.40 12063.71 15254.11 16323.14
Torsion 0.00 0.00 0.00 0.00 0.00
Shear 1841.28 1554.82 1152.12 926.04 827.06
Ultimate Load for Maxm. Moment Moment 4173.02 7259.40 12063.71 15254.11 16323.14
Torsion 0.00 0.00 0.00 0.00 0.00
Shear Capacity
D in (mm) 2740 2740 2740 2740 2740
K 1.270 1.270 1.270 1.270 1.270
I 1.890 1.683 1.476 1.476 1.476
A 2.510 2.084 1.658 1.658 1.658
Deck width 2900 2900 2900 2900 2900
CG of section 1.699 1.758 1.817 1.817 1.817
Thickness of top slab 240 240 240 240 240
fck 50.000 50.000 50.000 50.000 50.000
Horz. Prestress 6014 6068 6291 6451 6434
Total Vertical Comp. 767.66 679.02 423.86 0.00 0.00
σcp 2.40 2.91 3.79 3.89 3.88
σcp(max) 2.40 2.91 3.79 3.89 3.88
Duct Dia 90.00 90.00 90.00 90.00 90.00
bw 665.00 665.00 665.00 665.00 665.00
ρ1 (Asl/bd) 0.003 0.003 0.003 0.003 0.003
ν 0.31 0.31 0.31 0.31 0.31
fctd 1.53 1.53 1.53 1.53 1.53
Area above centroid 1.229 1.190 1.150 1.150 1.150
CG of section above centroid 696 658 621 621 621
First moment of Area 0.85 0.78 0.71 0.71 0.71
Stress at bottom fibre due to prestress 4.29 4.83 6.81 5.09 3.64
Maximum M cracked kNm 6481 6088 6777 5377 4205
Section type Uncracked Cracked Cracked Cracked Cracked
Vrdc (Cracked) kN 1294 1435 1676 1702 1699
Vrdc (Uncracked) kN (10.4) 3610 3731 3929 3965 3961
CG of Cable 777 591 237 148 148
Maximum Shear capacity (Eqn 10.5) 7335 8031 9353 9684 9684
Shear requirement 1310 1068 888 1130 1009
Torsion requirement 0 0 0 0 0
Shear reinforcement requirment NO NO NO NO NO
Dia of stirrups 12.00 12.00 12.00 12.00 12.00
Number of legs 6.00 4.00 4.00 4.00 4.00
Spacing of stirrups 125 125 125 125 125
Fy 500 500 500 500 500
fwkd 435 435 435 435 435
Z=(D-cg of cable) 1963 2149 2503 2592 2592
θ 45 45 45 45 45
Asw 679 452 452 452 452
ρ 0.0082 0.0054 0.0054 0.0054 0.0054
Vrd 4635.3 3383.3 3940.3 4080.0 4080.0
ν1 0.50 0.50 0.50 0.50 0.50
αcw 1.11 1.13 1.17 1.17 1.17
Vrd.max 8158.7 9117.9 10988.5 11419.9 11415.7
Optimizatio by Vrd.max-V 3523.41 5734.57 10100.01 7339.95 7335.66
ρmin 0.0012 0.0012 0.0012 0.0012 0.0012
Check for shear capcity OK OK OK OK OK
Design of Anchor Block
Anchor block is designed as per Cl. No. 13 of IRC 112-2011

According to Manufacture's Catalog

Size of anchor flange = 345 mm

Dia of Hole = 179 mm

As per Cl No.16.11of IRC 112-2011, allowable Concentrated force/ stress

fb = fcdxSQRT(Acl/Aco) or 3xfcd Whichever is smaller

fcd = 30.15 N/mm2

Acl = 450x450- 3.14/4x179^2 = 177335.06 mm2

Aco = 345x345- 3.14/4x179^2 = 93860.057 mm2

fb = 41.44 N/mm2

Now, Maximum Cable Force after immediate Losses = 2092.46 kN

In general = 2/3rd of above force to be taken by End Bearing

= 1/3rd of above force to be taken by Anchorage

Cone and Concrete by friction

Bearing stress = N/A1 = 14.86 N/mm2

< 41.44 N/mm2 Hence O.K.

As per cl 13.5.1.1 of IRC 112:2011 2Yo = 500 mm

2Ypo = 345 mm

Ypo/Yo = 0.69

As per Table 13.1 of IRC 112:2011

Fbst/Pk = 0.124

Fbst = 0.12x2092.46

259.46 kN

Area of Steel Required = Fbst/(0.87xfy)

718.63874 mm2

Hence Provide 12T- 3L -3Nos along Web and Normal to Web

Ast = 1017.876 mm2

16 dia helix with 13 turns in 2Y0 region provided (Ast) 2613.805 mm2
Check for shear in flanged portion As per IRC: 112-2011 Clause 10.3.5.
Diffrence in stress (t/m2) 55.33

Length Ϫx (m) 2

Width of deck in one side beyond web of girder (m) 1.313

Depth of flange (deck slab) (m) 0.24

Difference in normal force between section (T) 17.43

vEDf (N/mm2) 0.36

θf 30

cotθf 1.73

fyd (N/mm2) 434.8

Asf/sf (mm) 0.116

spacing sf (mm) 200

Asf (mm2) 23.14

Dia of bar provided (mm) 16

Area provided (mm2) 201.1


DESIGN OF SHEAR CONNECTORS(INNER GIRDER)AT SUPPORT SECTION

Width of beam = 950 mm


Shear = 1841 kN
Z (lever arm) = 681.2531 mm
Dia of interface reinforement = 12.00
Number of legs = 6.00
Spacing = 125.00 mm

Design value of interface shear stress: VEd = 2.845031 MPa


vEd 
zb
Design shear resistance at the interface:

2
Area of the interface = 228000 mm2 ; Area of interface reinforcement: 5428.672 mm /m

Angle of reinforcement to interface: a 90 deg

Surface roughness: Smooth 0.6

vEdi  cfctd  h


reinforcement ratio required:  min  = 0.010901
fyd Sina  Cosa 

Area of interface reinforcement required = 2485.315 mm2 OK


Maximum spacing of links using current preferred bar diameter =

DESIGN OF SHEAR CONNECTORS(INNER GIRDER)AT MID SECTION

Width of beam = 950 mm


Shear = 1555 kN
Z (lever arm) = 622.1265 mm
Dia of interface reinforement = 12.00
Number of legs = 4.00
Spacing = 125.00 mm

Design value of interface shear stress: VEd = 2.630737 MPa


vEd 
zb
Design shear resistance at the interface:

2
Area of the interface = 228000 mm2 ; Area of interface reinforcement: 3619.115 mm /m

Angle of reinforcement to interface: a 90 deg

Surface roughness: Smooth 0.6

vEdi  cfctd  h


reinforcement ratio required:  min  = 0.010079
fyd Sina  Cosa 

Area of interface reinforcement required = 2298.115 mm2 OK


Maximum spacing of links using current preferred bar diameter =
Stress Check for Inner Girder
Basic Design Data

Characteristics value of prestressing 1.1

1st stage prestressing 14 day


2nd stage prestressing 28 day
Casting of Deck Slab 28 day
3rd stage prestressing 90 day
Shift of Bearing 90 day
SIDL(Wearing Coat & Crash Barrier) 90 day
Age of deck slab at time of 3rd stage 62 day

Fck 50 Mpa
Modulus of Elasticity (Conc) 14th Day 3.30E+06 t/m2
Modulus of Elasticity (Conc) 28th Day 3.40E+06 t/m2
Modulus of Elasticity (Conc) 28th Day 3.40E+06 t/m2
Modulus of Elasticity (Conc) 90th Day 3.51E+06 t/m2
Modulus of Elasticity (Strands) 1.95E+07 t/m2

Type of cables 19 T13


Area of 1 strand 0.0000987 m2
Area of one cable 1.8753E-03 m2
no of cables stressed in 1st stage 3.37
no of cables stressed in 2nd stage 0.001
no of tendons stressed in 3rd stage 0.00
Jacking Force 0.765 *UTS
No of Sections to be checked 5
Prestressing force per cable (UTS) 355.8 t
Increase Factors for losses
Elastic Shortening loss 1.0
Relaxation loss 1.0
Shrinkage loss 1.0
Creep loss 1.0

Factor for Shrinkage loss


14th day 2.47E-04
28th day 2.25E-04
90th day 1.73E-04
90th day 1.73E-04
90th day 1.73E-04
Infinity 1.73E-04

Factor for Creep Loss


14th day 0.00E+00
28th day 1.60E-04
90th day 2.61E-04
90th day 2.61E-04
90th day 2.61E-04
Infinity 5.45E-04

Factor for Relaxation Loss


1000hr relaxation 2.50%

Total Relaxation Loss at service condition (cl: 6.3.6 IRC 112) = 3 x (1000 hr. value)
Initial force after Friction, slip & ES loss = 820.93 t
Percentage of Initial force = 0.6850 UTS
Relaxation Loss at 1000hr. for low relaxation steel = 2.31 % of initial stress
Relaxation Loss at 1000hr. for low relaxation steel = 5.63 t/Cable
Immediate Loss i.e 1 hr. of stressing (Table 6.3 IRC:112) = 34 % of Total Loss
7 - 28 days Loss = 90 % of Total Loss
28 - 90 days Loss = 100 % of Total Loss
90 - a days Loss = 200 % of Total Loss
Immediate Loss i.e 1 hr. of stressing = 1.92 t/Cable
7 - 28 days Loss = 3.16 t/Cable
28 - 90 days Loss = 0.56 t/Cable
90 - a days Loss = 11.27 t/Cable
Strain due to differential shrinkage and creep 1.00E-04
Reduction factor due to differential creep 0.43
PSC BEAM AND RC SLAB STRUCTURE OF SIMPLY SUPPORTED SPAN
(INNER GIRDER)
Item Unit 1 2 3 4 5
MEMBER NO
distance of Section from left support m 2.000 4.000 6.090 12.180 16.970

Details of Section property (Individual Beam Section)


Area of the section m2 1.8142 1.3881 0.9620 0.9620 0.9620
Depth of the section m 2.5000 2.5000 2.5000 2.5000 2.5000
CG of section from bottom m 1.2752 1.2560 1.2367 1.2367 1.2367
Moment of Inertia of section m4 0.9769 0.8383 0.6998 0.6998 0.6998

Details of Section property (Composite Section)


Area of the section m2 2.5100 2.0840 1.6580 1.6580 1.6580
Depth of the section m 2.7400 2.7400 2.7400 2.7400 2.7400
CG of section from bottom m 1.6987 1.7579 1.8170 1.8170 1.8170
Moment of Inertia of section m4 1.8900 1.6830 1.4760 1.4760 1.4760

Details of Section property (Composite Section)


Area of the section m2 2.5100 2.0840 1.6580 1.6580 1.6580
Depth of the section m 2.7400 2.7400 2.7400 2.7400 2.7400
CG of section from bottom m 1.6987 1.7579 1.8170 1.8170 1.8170
Moment of Inertia of section m4 1.8900 1.6830 1.4760 1.4760 1.4760

Details of Stage I prestressing after 14 day For Cable 1a/1


Prestressing Force (P1) (Hor) T 225.31 228.65 237.85 240.43 240.55
CG of Tendons from Bottom m 0.27 0.13 0.12 0.12 0.12
Prestressing Force (P1) (Ver) T 17.52 8.40 0.00 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1b/2


Prestressing Force (P1) (Hor) T 227.20 228.23 239.84 242.34 240.31
CG of Tendons from Bottom m 0.66 0.50 0.12 0.12 0.12
Prestressing Force (P1) (Ver) T 19.07 19.16 1.60 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1c/3


Prestressing Force (P1) (Hor) T 232.52 233.54 236.08 244.20 244.69
CG of Tendons from Bottom m 1.02 0.80 0.25 0.12 0.12
Prestressing Force (P1) (Ver) T 25.62 25.74 26.02 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1d/4


Prestressing Force (P1) (Hor) T 129.77 130.34 131.75 136.34 135.89
CG of Tendons from Bottom m 1.42 1.19 0.64 0.30 0.30
Prestressing Force (P1) (Ver) T 14.54 14.61 14.77 0.00 0.00

Details of Stage I prestressing after 14 day For Cable 1e/5


Prestressing Force (P1) (Hor) T 0.00 0.00 0.00 0.00 0.00
CG of Tendons from Bottom m 0.00 0.00 0.00 0.00 0.00
Prestressing Force (P1) (Ver) T 0.00 0.00 0.00 0.00 0.00
PSC BEAM AND RC SLAB STRUCTURE OF SIMPLY SUPPORTED SPAN
(INNER GIRDER)
Item Unit 1 2 3 4 5
MEMBER NO
distance of Section from left support m 2.000 4.000 6.090 12.180 16.970
Details of Stage II prestressing after 28 day For Cable 2a
Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2b


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2c


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2d


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage II prestressing after 28 day For Cable 2e


Prestressing Force (P2) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P2) (Ver) T 0.01 0.01 0.01 0.01 0.01

Details of Stage III prestressing after 90th day


Prestressing Force (P3) (Hor) T 0.01 0.01 0.01 0.01 0.01
CG of Tendons from Bottom m 0.01 0.01 0.01 0.01 0.01
Prestressing Force (P3) (Ver) T 0.01 0.01 0.01 0.01 0.01
PSC BEAM AND RC SLAB STRUCTURE OF SIMPLY SUPPORTED SPAN
(INNER GIRDER)
Item Unit 1 2 3 4 5
MEMBER NO
distance of Section from left support m 2.000 4.000 6.090 12.180 16.970

Dead Load - Ist stage


Moments Tm 76.1 146.0 258.0 334.0 355.0
Shear T 38.6 31.7 21.6 10.1 0.0

Dead Load - Ist stage due to permanent bearing


Moments Tm 86.3 157.0 269.0 344.0 365.0
Shear T 38.6 31.7 21.6 10.1 0.0

Dead Load - Ist stage due to shift of bearing


Moments Tm 10.2 11.0 11.0 10.0 10.0
Shear T 0.0 0.0 0.0 0.0 0.0

Construction load/Shuttering load


Moments Tm 22.5 42.2 74.6 96.5 102.7
shear 10.6 9.2 6.2 2.9 0.0

Dead Load - 2nd stage


Moments Tm 59.0 111.0 197.5 258.6 279.5
Shear T 27.7 24.3 17.0 8.7 1.3

SIDL
Moments Tm 23.5 42.1 87.0 141.3 191.3
Shear T 11.2 10.6 11.4 11.8 10.7

Live Load (Sagging) (max Moment Case & max Positive Shear case)
Moments Tm 129.2 203.6 292.8 318.8 293.9
Shear T 50.0 40.9 28.8 31.1 41.4

Stress due to Temp (Rise) (Eigen stresses)


top of deck slab T/m2 -212.41 -212.41 209.68 209.68 209.68
top of girder T/m2 127.60 127.60 -132.35 -132.35 -132.35
bottom T/m2 -156.01 -156.01 130.19 130.19 130.19

Stress due to Temp (Fall) (Eigen Stresses)


top of deck slab T/m2 -296.60 -296.60 -312.79 -312.79 -312.79
top of girder T/m2 -85.64 -85.64 -102.17 -102.17 -102.17
bottom T/m2 -112.33 -112.33 -132.43 -132.43 -132.43
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Details of Section property (Individual Beam Section)

2
Area of the section m 1.8142 1.38808125 0.96196 0.961963 0.9619625
Depth of the section m 2.500 2.500 2.500 2.500 2.500
CG of section from bottom m 1.2752406 1.255953054 1.23667 1.236665 1.236665476
4
Inertia of section m 0.9769032 0.838329327 0.69976 0.699755 0.699755494
3
Top Section Modulus m 0.7976 0.6739 0.5539 0.5539 0.5539
3
Bottom Section Modulus m 0.7661 0.6675 0.5658 0.5658 0.5658

Details of Section property (Composite Section) (62 day old slab)

2
Area of the section m 2.51 2.084 1.658 1.658 1.658
Depth of the section m 2.740 2.740 2.740 2.740 2.740
CG of section from bottom m 1.6987469 1.757873453 1.817 1.817 1.817
4
Inertia of section m 1.89 1.683 1.476 1.476 1.476
3
Top Section Modulus m 1.8151 1.7136 1.5991 1.5991 1.5991
3
Bottom Section Modulus m 1.1126 0.9574 0.8123 0.8123 0.8123

Details of Section property (Composite Section)

2
Area of the section m 2.51 2.084 1.658 1.658 1.658
Depth of the section m 2.740 2.740 2.740 2.740 2.740
CG of section from bottom m 1.6987469 1.757873453 1.817 1.817 1.817
4
Inertia of section m 1.89 1.683 1.476 1.476 1.476
3
Top Section Modulus m 1.8151 1.7136 1.5991 1.5991 1.5991
3
Bottom Section Modulus m 1.1126 0.9574 0.8123 0.8123 0.8123

Details of Stage I prestressing


For Cable 1a
No of Tendons of 19T13 0.95 0.95 0.95 0.95 0.95
Prestressing Force (P1) T 225.31 228.65 237.85 240.43 240.55
CG of Tendons from Bottom m 0.2730 0.1304 0.1200 0.1200 0.1200
Eccentricity of Tendons m 1.0023 1.1255 1.1167 1.1167 1.1167
Prestressing Factor (Top) -0.7053 -0.9498 -0.9765 -0.9765 -0.9765
Prestressing Factor (Bottom) 1.8595 2.4066 3.0130 3.0130 3.0130

For Cable 1b
No of Tendons of 19T13 0.95 0.95 0.95 0.95 0.95
Prestressing Force (P1) T 227.20 228.23 239.84 242.34 240.31
CG of Tendons from Bottom m 0.6629 0.4950 0.1203 0.1200 0.1200
Eccentricity of Tendons m 0.6123 0.7609 1.1163 1.1167 1.1167
Prestressing Factor (Top) -0.2165 -0.4088 -0.9759 -0.9765 -0.9765
Prestressing Factor (Bottom) 1.3505 1.8604 3.0124 3.0130 3.0130

For Cable 1c
No of Tendons of 19T13 0.95 0.95 0.95 0.95 0.95
Prestressing Force (P1) T 232.52 233.54 236.08 244.20 244.69
CG of Tendons from Bottom m 1.0200 0.7996 0.2516 0.1200 0.1200
Eccentricity of Tendons m 0.2552 0.4563 0.9851 1.1167 1.1167
Prestressing Factor (Top) 0.2313 0.0433 -0.7389 -0.9765 -0.9765
Prestressing Factor (Bottom) 0.8843 1.4041 2.7805 3.0130 3.0130
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

For Cable 1d
No of Tendons of 19T13 0.53 0.53 0.53 0.53 0.53
Prestressing Force (P1) T 129.77 130.34 131.75 136.34 135.89
CG of Tendons from Bottom m 1.4170 1.1929 0.6355 0.3000 0.3000
Eccentricity of Tendons m -0.1418 0.0631 0.6011 0.9367 0.9367
Prestressing Factor (Top) 0.7289 0.6268 -0.0457 -0.6515 -0.6515
Prestressing Factor (Bottom) 0.3662 0.8150 2.1019 2.6949 2.6949

For Cable 1e
No of Tendons of 19T13 0.00 0.00 0.00 0.00 0.00
Prestressing Force (P1) T 0.00 0.00 0.00 0.00 0.00
CG of Tendons from Bottom m 0.0000 0.0000 0.0000 0.0000 0.0000
Eccentricity of Tendons m 1.2752 1.2560 1.2367 1.2367 1.2367
Prestressing Factor (Top) -1.0476 -1.1434 -1.1931 -1.1931 -1.1931
Prestressing Factor (Bottom) 2.2159 2.6020 3.2251 3.2251 3.2251

Combination of Stage 1 Cables


No of Tendons of 19T13 3.37 3.37 3.37 3.37 3.37
Prestressing Force (P1) T 814.80 820.76 845.53 863.30 861.44
CG of Tendons from Bottom m 0.7771 0.5910 0.2372 0.1484 0.1484
Eccentricity of Tendons m 0.4981 0.6650 0.9995 1.0882 1.0883
Prestressing Factor (Top) -0.0733 -0.2664 -0.7650 -0.9252 -0.9252
Prestressing Factor (Bottom) 1.2015 1.7167 2.8059 2.9628 2.9628

Dead Load Moments - Ist stage Tm 76.10 146.00 258.00 334.00 355.00

Stress Due to dead load


2
Top T/m 95.41 216.66 465.79 603.00 640.91
2
Bottom T/m -99.34 -218.73 -455.96 -590.27 -627.39

Eloss of cable (1a) for stressing of (1a) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1a) for stressing of (1b) T 6.89 6.89 6.89 6.89 6.89
Eloss of cable (1a) for stressing of (1c) T 6.37 6.37 6.37 6.37 6.37
Eloss of cable (1a) for stressing of (1d) T 2.89 2.89 2.89 2.89 2.89
Eloss of cable (1a) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1b) for stressing of (1b) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1b) for stressing of (1c) T 6.29 6.29 6.29 6.29 6.29
Eloss of cable (1b) for stressing of (1d) T 2.89 2.89 2.89 2.89 2.89
Eloss of cable (1b) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1c) for stressing of (1c) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1c) for stressing of (1d) T 2.84 2.84 2.84 2.84 2.84
Eloss of cable (1c) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1d) for stressing of (1d) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1d) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00
Eloss of cable (1e) for stressing of (1e) T 0.00 0.00 0.00 0.00 0.00

Total Eloss for Stage 1 cables T 28.17 28.17 28.17 28.17 28.17
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Stress after stressing of 1a


2
Top T/m -174.81 -235.40 -242.01 -242.01 -242.01
2
Bottom T/m 460.87 596.46 746.75 746.75 746.75
2
Stress at CG of 1a T/m 391.46 553.06 699.29 699.29 699.29
2
Avg stress for each segment T/m 472.26 626.17 699.29 699.29 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Average Stress at CG of 1a T/m 658.75

Stress after stressing of 1b


2
Top T/m -223.57 -330.83 -492.09 -494.91 -492.74
2
Bottom T/m 784.31 1045.29 1518.69 1527.10 1520.39
2
Stress at CG of 1a T/m 674.25 973.49 1422.17 1430.04 1423.76
2
Avg stress for each segment T/m 823.87 1197.83 1426.11 1426.90 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1a T/m 655.28
2
Stress at CG of 1b T/m 517.06 772.81 1421.92 1430.04 1423.76
2
Avg stress for each segment T/m 644.93 1097.36 1425.98 1426.90 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Average Stress at CG of 1b T/m 1276.05
Check Eloss of cable (1a) for (1b) T 6.89

Stress after stressing of 1c


2
Top T/m -157.98 -310.23 -670.37 -743.61 -741.96
2
Bottom T/m 988.12 1376.25 2198.77 2294.46 2289.38
2
Stress at CG of 1a T/m 862.97 1288.25 2061.05 2148.64 2143.87
2
Avg stress for each segment T/m 1075.61 1674.65 2104.84 2146.25 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
Increase in Average Stress at CG of 1a T/m2 606.50
2
Stress at CG of 1b T/m 684.21 1042.32 2060.68 2148.64 2143.87
2
Avg stress for each segment T/m 863.27 1551.50 2104.66 2146.25 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1b T/m 598.84
2
Stress at CG of 1c T/m 520.49 836.82 1910.03 2148.64 2143.87
2
Avg stress for each segment T/m 678.66 1373.43 2029.34 2146.25 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Average Stress at CG of 1c T/m 1794.72
Check Eloss of cable (1a) for (1c) T 6.37
Check Eloss of cable (1b) for (1c) T 6.29
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Stress after stressing of 1d


2
Top T/m -51.72 -216.19 -668.49 -832.06 -830.09
2
Bottom T/m 1027.43 1475.15 2475.56 2670.06 2663.64
2
Stress at CG of 1a T/m 909.59 1386.90 2324.64 2501.96 2495.95
2
Avg stress for each segment T/m 1148.25 1855.77 2413.30 2498.95 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1a T/m 273.33
2
Stress at CG of 1b T/m 741.28 1140.26 2324.24 2501.96 2495.95
2
Avg stress for each segment T/m 940.77 1732.25 2413.10 2498.95 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1b T/m 273.92
2
Stress at CG of 1c T/m 587.12 934.17 2159.16 2501.96 2495.95
2
Avg stress for each segment T/m 760.65 1546.67 2330.56 2498.95 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1c T/m 270.54
2
Stress at CG of 1d T/m 415.77 668.14 1676.30 2249.81 2244.40
2
Avg stress for each segment T/m 541.96 1172.22 1963.05 2247.10 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Average Stress at CG of 1d T/m 1753.67
Check Eloss of cable (1a) for (1d) T 2.87
Check Eloss of cable (1b) for (1d) T 2.88
Check Eloss of cable (1c) for (1d) T 2.84

Stress after stressing of 1e


2
Top T/m -51.72 -216.19 -668.49 -832.06 -830.09
2
Bottom T/m 1027.43 1475.15 2475.56 2670.06 2663.64
2
Stress at CG of 1a T/m 909.59 1386.90 2324.64 2501.96 2495.95
2
Avg stress for each segment T/m 1148.25 1855.77 2413.30 2498.95 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1a T/m 0.00
2
Stress at CG of 1b T/m 741.28 1140.26 2324.24 2501.96 2495.95
2
Avg stress for each segment T/m 940.77 1732.25 2413.10 2498.95 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1b T/m 0.00
2
Stress at CG of 1c T/m 587.12 934.17 2159.16 2501.96 2495.95
2
Avg stress for each segment T/m 760.65 1546.67 2330.56 2498.95 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1c T/m 0.00
2
Stress at CG of 1d T/m 415.77 668.14 1676.30 2249.81 2244.40
2
Avg stress for each segment T/m 541.96 1172.22 1963.05 2247.10 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Increase in Average Stress at CG of 1d T/m 0.00
2
Stress at CG of 1e T/m 1027.43 1475.15 2475.56 2670.06 2663.64
2
Avg stress for each segment T/m 1251.29 1975.35 2572.81 2666.85 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Average Stress at CG of 1e T/m 2342.93
Check Eloss of cable (1a) for (1e) T 0.00
Check Eloss of cable (1b) for (1e) T 0.00
Check Eloss of cable (1c) for (1e) T 0.00
Check Eloss of cable (1d) for (1e) T 0.00
Immidiate Relaxation Loss T 18.98 18.98 18.98 18.98 18.98
Top 14.73 19.83 20.39 20.39 20.39
Bottom -38.83 -50.25 -62.91 -62.91 -62.91
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Stress after stressing of Stage1 Cables


2
Top T/m 58.41 20.30 -182.31 -208.67 -168.79
2
Bottom T/m 889.26 1206.17 1956.69 2016.88 1973.35

2
Stress at CG of cable 1a T/m 798.54 1144.30 1854.02 1910.05 1870.53
2
Stress at CG of cable 1b T/m 668.95 971.36 1853.74 1910.05 1870.53
2
Stress at CG of cable 1c T/m 550.26 826.87 1741.43 1910.05 1870.53
2
Stress at CG of cable 1d T/m 418.34 640.34 1412.93 1749.81 1716.29
2
Stress at CG of cable 1e T/m 889.26 1206.17 1956.69 2016.88 1973.35

Losses From 14 to 28 day

Creep loss due to GR I Tendons T 3.02 3.02 3.02 3.02 3.02


Shrinkage loss due to GR I Tendons T 2.71 2.71 2.71 2.71 2.71
=(0.000225-0.000247)*3.36842105263158*0.0018753*19500000*1
Relaxation loss due to GR I Tendons

Relaxation loss due to GR I Tendons T 10.63 10.63 10.63 10.63 10.63

Total Loss (C+S+R) T 18.00 18.00 18.00 18.00 18.00

Stress Due to C+S+R


2
Top T/m 1.32 4.80 13.77 16.65 16.65
2
Bottom T/m -21.63 -30.90 -50.51 -53.33 -53.33

Stress before stressing of GR II cables at 28 day


2
Top T/m 74.46 44.93 -148.15 -171.63 -131.75
2
Bottom T/m 828.81 1125.02 1843.27 1900.64 1857.11

2
Stress at CG of Stage 1 Cables T/m 594.33 869.71 1654.36 1777.61 1739.06
2
T/m

2
Average Stress at CG of Stage 1 Cables T/m 1534.70

Creep loss (check) T 3.02


=(0.00016-0)*3.36842105263158*0.0018753*19500000*1534.69839397839/10000*1
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Stress due to shuttering load (for casting of Deck Slab)


Top T/m2 28.23 62.69 134.72 174.22 185.33
2
Bottom T/m -29.39 -63.29 -131.88 -170.54 -181.42

Dead Load Moments -IInd stage Tm 58.96 110.96 197.50 258.56 279.55
Stress Due to dead load
2
Top T/m 73.92 164.65 356.56 466.80 504.69
2
Bottom T/m -76.96 -166.23 -349.03 -456.95 -494.04

2
Stress at CG of GR I Tendons T/m -30.06 -88.02 -282.10 -402.10 -434.76
2
Stress at CG of GR II Tendons T/m 2643.11 -164.91 -346.21 -453.25 -490.04

Dead Load Moments -Ist stage due to shift of


bearing Tm 10.20 11.00 11.00 10.00 10.00
2
Top T/m 12.79 16.32 19.86 18.05 18.05
2
Bottom T/m -13.31 -16.48 -19.44 -17.67 -17.67

Shuttering Load Moments Tm 22.52 42.25 74.62 96.50 102.65


Stress due to release of shuttering load
2
Top T/m -12.40 -24.65 -46.66 -60.35 -64.19
Top of Girder -9.55 -18.63 -34.53 -44.65 -47.50
2
Bottom T/m 20.24 44.13 91.86 118.79 126.37

Stress after release of shuttering load


2
Top of Deck Slab T/m -12.40 -24.65 -46.66 -60.35 -64.19
2
Top of Girder T/m 179.79 269.91 328.39 442.73 528.76
2
Bottom T/m 729.50 923.29 1434.96 1374.45 1290.53

Losses from 28 to 90 day

Creep Loss of Gr I Tendons T 1.44 1.44 1.44 1.44 1.44


Shrinkage loss of Gr I Tendons T 6.41 6.41 6.41 6.41 6.41
=(0.000225-0.000173)*3.36842105263158*0.0018753*19500000*1
Relaxation loss of Gr. I Tendons T 1.90 1.90 1.90 1.90 1.90

Total Loss due to C + S + R 10.72 10.71 10.71 10.71 10.71

Stresses due to C + S + R
2
Top T/m 1.22 2.15 4.12 4.71 4.71
2
T/m -0.04 0.37 1.37 1.81 1.81
2
Bottom T/m -13.24 -18.18 -27.27 -28.45 -28.45

Prestressing factor for composite section


Stage 1 Cables Top -0.109 -0.201 -0.385 -0.440 -0.440
Bottom 1.227 1.699 2.548 2.657 2.657

Stress at 90nd day before laying SIDL


2
Top of Deck Slab T/m -11.18 -22.51 -42.55 -55.63 -59.48
2
Top of Girder T/m 179.74 270.27 329.76 444.53 530.57
2
Bottom T/m 716.26 905.11 1407.68 1346.00 1262.08

2
Stress at CG of Tendon I T/m 549.49 755.05 1305.43 1292.48 1218.66

2
Average Stress at CG of Tendon GRI T/m 1161.16

Check for Creep Loss of Gr I Cables 1.44


=(0.000261-0.00016)*3.36842105263158*0.0018753*19500000*1161.1600946061/10000*1

SIDL applied at 90nd day Tm 23.50 42.10 87.00 141.30 191.30


Stress due to SIDL
2
Top T/m 12.95 24.57 54.40 88.36 119.63
9.96 18.56 40.26 65.38 88.52
Bottom T/m2 -21.12 -43.97 -107.10 -173.94 -235.50

2
Stress at CG of Gr I Tendons T/m -11.46 -29.19 -93.12 -159.74 -216.26
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Creep, Shrinkage & Relaxation losses from 90 day upto infinity

Creep loss of Gr. I T =34.98 34.98 34.98 34.98 34.98


Shrinkage loss of Gr. I T 21.31 21.31 21.31 21.31 21.31
=(0.000173-0.000173)*3.36842105263158*0.0018753*19500000*1
Relaxation loss of Gr. I T 37.96 37.96 37.96 37.96 37.96

Total Loss due to C+S+R 103.67 103.67 103.67 103.67 103.67

Stress due to C+S+R


2
Top T/m 11.63 20.85 39.89 45.64 45.64
-0.57 3.60 13.26 17.52 17.52
2
Bottom T/m -127.66 -176.09 -264.14 -275.46 -275.47

Stress during Service at infinity


2
Top of Deck Slab T/m 13.40 22.91 51.75 78.37 105.79
2
Top of Girder T/m 189.14 292.43 383.28 527.43 636.61
2
Bottom T/m 567.48 685.05 1036.45 896.60 751.12

2
Stress at CG of Tendon I T/m 449.88 592.24 974.49 874.68 744.32

2
Avg stress for each segment T/m 521.06 783.36 924.58 809.50 0.00
Segment length m 2.00 2.09 6.09 4.79 -16.97
length m 14.97
2
Average Stress at CG of Tendon GRI T/m 814.13

Check for Creep Loss of Gr I Cables


=(0.000545-0.000261)*3.36842105263158*0.0018753*19500000*1 = =34.98

Moment Due to Live Load (Sagging) Tm 129.23 203.58 292.80 318.79 293.93
Stresses due to Live Load (Sagging)
2
Top of Deck Slab T/m 71.20 118.80 183.10 199.35 183.81
2
Top of Girder T/m 54.79 89.77 135.49 147.51 136.01
2
Bottom T/m -116.16 -212.64 -360.45 -392.44 -361.84

Stress at service with Live Load (Sagging)


2
Top of Deck Slab T/m 84.60 141.71 234.85 277.72 289.60
2
Top of Girder T/m 243.93 382.21 518.77 674.95 772.63
2
Bottom T/m 451.33 472.41 676.00 504.16 389.28

Stress at service with differential shrinkage and differential creep effect (without Live Load)
Top of Deck Slab T/m2 13.40 22.91 51.75 78.37 105.79
2
Top of Girder T/m 189.14 292.43 383.28 527.43 636.61
2
Bottom T/m 567.48 685.05 1036.45 896.60 751.12

Stress at service with differential shrinkage and differential creep effect (with 75% Live Load)
2
Top of Deck Slab T/m 66.80 112.01 189.07 227.88 243.65
2
Top of Girder T/m 230.23 359.76 484.90 638.07 738.62
2
Bottom T/m 480.36 525.57 766.11 602.27 479.74
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

Stress due to Temp (Rise) (Eigen stresses)


2
Top of Deck Slab T/m -212.41 -212.41 209.68 209.68 209.68
2
Top of Girder T/m 127.60 127.60 -132.35 -132.35 -132.35
2
Bottom T/m -156.01 -156.01 130.19 130.19 130.19

Stress at Service with 75% Live Load (sag) + Temp rise (RARE COMBINATION)
2
Top of Deck Slab T/m -145.61 -100.40 398.75 437.56 453.32
2
Top of Girder T/m 357.83 487.36 352.54 505.72 606.27
2
Bottom T/m 324.35 369.56 896.30 732.46 609.93

Stress at Service with 100% Live Load (sag) + 60% Temp rise (RARE COMBINATION)
2
Top of Deck Slab T/m -42.85 14.26 360.65 403.53 415.41
2
Top of Girder T/m 320.49 458.76 439.36 595.54 693.21
2
Bottom T/m 357.72 378.80 754.12 582.27 467.39

Stress at Service with 75% Live Load (sag) + 50% Temp rise (FREQUENT COMBINATION)
2
Top of Deck Slab T/m -39.41 5.80 293.91 332.72 348.49
2
Top of Girder T/m 294.03 423.56 418.72 571.90 672.45
2
Bottom T/m 402.36 447.56 831.21 667.36 544.83

Stress at Service with 20% Live Load (sag) + 60% Temp rise (FREQUENT COMBINATION)
2
Top of Deck Slab T/m -99.81 -80.78 214.17 244.05 268.36
2
Top of Girder T/m 276.66 386.95 330.97 477.53 584.40
2
Bottom T/m 450.64 548.91 1042.47 896.22 756.86

Stress due to Temp (Fall) (Eigen Stresses)


2
Top of Deck Slab T/m -296.60 -296.60 -312.79 -312.79 -312.79
2
Top of Girder T/m -85.64 -85.64 -102.17 -102.17 -102.17
2
Bottom T/m -112.33 -112.33 -132.43 -132.43 -132.43

Stress at Service with 75% Live Load (sag) + Temp Fall


2
Top of Deck Slab T/m -229.80 -184.59 -123.71 -84.90 -69.14
Top of Girder T/m2 144.59 274.12 382.72 535.90 636.45
2
Bottom T/m 368.03 413.24 633.69 469.84 347.31

Stress at Service with 100% Live Load (sag) +60 % Temp Fall (RARE COMBINATION)
2
Top of Deck Slab T/m -93.36 -36.25 47.18 90.05 101.93
2
Top of Girder T/m 192.54 330.82 457.46 613.64 711.32
2
Bottom T/m 383.93 405.01 596.55 424.70 309.82

Stress at Service with 75% Live Load (sag) + 50% Temp Fall (FREQUENT COMBINATION)
2
Top of Deck Slab T/m -81.50 -36.29 32.68 71.49 87.25
2
Top of Girder T/m 187.41 316.94 433.81 586.98 687.53
2
Bottom T/m 424.20 469.40 699.90 536.06 413.52

Stress at Service with 20% Live Load (sag) + 60% TempFall (FREQUENT COMBINATION)
Top of Deck Slab T/m2 -150.32 -131.29 -99.30 -69.43 -45.12
2
Top of Girder T/m 148.71 259.00 349.07 495.63 602.51
2
Bottom T/m 476.85 575.12 884.90 738.65 599.29
Item Unit 1 2 3 4 5

Chainage of Section from left support m 2.000 4.000 6.090 12.180 16.970

After Stage 1 ( 14th Day)


2 2
Maximum Stress = 2016.88 t/m < 2400 t/m

2
Minimum Stress = -208.67 t/m < -350 t/m2

After Stage 2
2 2
Maximum Stress = 1434.96 t/m < 2400 t/m

2 2
Minimum Stress = 179.79 t/m < 2400 t/m

Stress at service with differential shrinkage and differential creep effect (without Live Load)
2 2
Maximum Stress = 1036.45 t/m < 2400 t/m

2
Minimum Stress = 189.14 < 2400 t/m

Stress at service with differential shrinkage and differential creep effect (with Live Load)
2 2
Maximum Stress = 772.63 t/m < 2400 t/m

2 2
Minimum Stress = 243.93 t/m < 2400 t/m

Stress at Service with Live Load (sag) + Temp Rise (FREQUENT COMBINATION)
2
Maximum Stress = 1042.47 t/m < 1800 t/m2

2 2
Minimum Stress = 276.66 t/m < -350 t/m

Stress at Service with Live Load (sag) + TempFall (FREQUENT COMBINATION)


2
Maximum Stress = 884.90 t/m < 1800 t/m2

2 2
Minimum Stress = 148.71 t/m < -350 t/m

Stress at Service with Live Load (sag) + Temp Rise (Rare COMBINATION)
2 2
Maximum Stress = 896.30 t/m < 2400 t/m

2 2
Minimum Stress = 320.49 t/m < -350 t/m

Stress at Service with Live Load (sag) + TempFall (Rare COMBINATION)


2 2
Maximum Stress = 711.32 t/m < 2400 t/m

2 2
Minimum Stress = 144.59 t/m < -350 t/m
Table 5.1.2 Ultimate forces at Sections:- Ultimate Force = 1.35xDL+1.75xSIDL+1.5xLL

Partial Factor of Safety For Dead Laod= 1.35

Partial Factor of Safety For Super Imposed Dead Laod= 1.75

Partial Factor of Safety For Live Laod= 1.5

Loadings Location Near support L/8 L/4 3L/8 L/2


Shear 663.39 559.59 385.51 187.51 13.43
Dead Load
Moment 1350.58 2569.56 4554.97 5925.59 6345.47
Shear 112.00 106.00 114.00 118.00 107.20
Superimposed Dead Load
Moment 235.00 421.00 870.00 1413.00 1913.00
Shear 499.80 409.25 288.12 310.93 414.22
Live Load Shear for Maxm. Shear Moment 1292.32 2035.83 2928.00 3187.88 2939.33
Torsion 0.00 0.00 0.00 0.00 0.00
Shear 499.80 409.25 288.12 310.93 414.22
Live Load Shear with Maxm. Moment Moment 1292.32 2035.83 2928.00 3187.88 2939.33
Torsion 0.00 0.00 0.00 0.00 0.00
Shear 1841.28 1554.82 1152.12 926.04 827.06
Ultimate Load for Maxm. Shear Moment 4173.02 7259.40 12063.71 15254.11 16323.14
Torsion 0.00 0.00 0.00 0.00 0.00
Shear 1841.28 1554.82 1152.12 926.04 827.06
Ultimate Load for Maxm. Moment Moment 4173.02 7259.40 12063.71 15254.11 16323.14
Torsion 0.00 0.00 0.00 0.00 0.00
Shear Capacity
D in (mm) 2740 2740 2740 2740 2740
K 1.270 1.270 1.270 1.270 1.270
I 1.890 1.683 1.476 1.476 1.476
A 2.510 2.084 1.658 1.658 1.658
Deck width 2900 2900 2900 2900 2900
CG of section 1.699 1.758 1.817 1.817 1.817
Thickness of top slab 240 240 240 240 240
fck 50.000 50.000 50.000 50.000 50.000
Horz. Prestress 7357 7423 7695 7891 7870
Total Vertical Comp. 767.66 679.02 423.86 0.00 0.00
σcp 2.93 3.56 4.64 4.76 4.75
σcp(max) 2.93 3.56 4.47 4.47 4.47
Duct Dia 90.00 90.00 90.00 90.00 90.00
bw 665.00 665.00 665.00 665.00 665.00
ρ1 (Asl/bd) 0.003 0.003 0.003 0.003 0.003
ν 0.31 0.31 0.31 0.31 0.31
fctd 1.53 1.53 1.53 1.53 1.53
Area above centroid 1.229 1.190 1.150 1.150 1.150
CG of section above centroid 696 658 621 621 621
First moment of Area 0.85 0.78 0.71 0.71 0.71
Stress at bottom fibre due to prestress 5.67 6.85 10.36 8.97 7.51
Maximum M cracked kNm 8020 8027 9665 8529 7347
Section type Uncracked Uncracked Cracked Cracked Cracked
Vrdc (Cracked) kN 1440 1612 1860 1860 1860
Vrdc (Uncracked) kN (10.4) 3848 3994 4170 4170 4170
CG of Cable 777 591 237 148 148
Maximum Shear capacity (Eqn 10.5) 7335 8031 9353 9684 9684
Shear requirement 1310 1068 888 1130 1009
Torsion requirement 0 0 0 0 0
Shear reinforcement requirment NO NO NO NO NO
Dia of stirrups 12.00 12.00 12.00 12.00 12.00
Number of legs 6.00 4.00 4.00 4.00 4.00
Spacing of stirrups 125 125 125 125 125
Fy 500 500 500 500 500
fwkd 435 435 435 435 435
Z=(D-cg of cable) 1963 2149 2503 2592 2592
θ 45 45 45 45 45
Asw 679 452 452 452 452
ρ 0.0082 0.0054 0.0054 0.0054 0.0054
Vrd 4635.3 3383.3 3940.3 4080.0 4080.0
ν1 0.50 0.50 0.50 0.50 0.50
αcw 1.13 1.16 1.21 1.21 1.21
Vrd.max 8334.5 9351.6 11343.2 11796.5 11791.3
Optimizatio by Vrd.max-V 3699.13 5968.34 10454.71 7716.53 7711.27
ρmin 0.0012 0.0012 0.0012 0.0012 0.0012
Check for shear capcity OK OK OK OK OK
Design of Anchor Block
Anchor block is designed as per Cl. No. 13 of IRC 112-2011

According to Manufacture's Catalog

Size of anchor flange = 345 mm

Dia of Hole = 179 mm

As per Cl No.16.11of IRC 112-2011, allowable Concentrated force/ stress

fb = fcdxSQRT(Acl/Aco) or 3xfcd Whichever is smaller

fcd = 30.15 N/mm2

Acl = 450x450- 3.14/4x179^2 = 177335.06 mm2

Aco = 345x345- 3.14/4x179^2 = 93860.057 mm2

fb = 41.44 N/mm2

Now, Maximum Cable Force after immediate Losses = 2043.49 kN

In general = 2/3rd of above force to be taken by End Bearing

= 1/3rd of above force to be taken by Anchorage

Cone and Concrete by friction

Bearing stress = N/A1 = 14.51 N/mm2

< 41.44 N/mm2 Hence O.K.

As per cl 13.5.1.1 of IRC 112:2011 2Yo = 500 mm

2Ypo = 345 mm

Ypo/Yo = 0.69

As per Table 13.1 of IRC 112:2011

Fbst/Pk = 0.124

Fbst = 0.12x2043.49

253.39 kN

Area of Steel Required = Fbst/(0.87xfy)

701.82088 mm2

Hence Provide 12T- 3L -3Nos along Web and Normal to Web

Ast = 1017.876 mm2

16 dia helix with 13 turns in 2Y0 region provided (Ast) 2613.805 mm2
Check for shear in flanged portion As per IRC: 112-2011 Clause 10.3.5.
Diffrence in stress (t/m2) 57.11

Length Ϫx (m) 2

Width of deck in one side beyond web of girder (m) 1.313

Depth of flange (deck slab) (m) 0.24

Difference in normal force between section (T) 17.99

vEDf (N/mm2) 0.37

θf 30

cotθf 1.73

fyd (N/mm2) 434.8

Asf/sf (mm) 0.119

spacing sf (mm) 200

Asf (mm2) 23.89

Dia of bar provided (mm) 16

Area provided (mm2) 201.1


DESIGN OF SHEAR CONNECTORS(INNER GIRDER)AT SUPPORT SECTION

Width of beam = 950 mm


Shear = 1841 kN
Z (lever arm) = 681.2531 mm
Dia of interface reinforement = 12.00
Number of legs = 6.00
Spacing = 125.00 mm

Design value of interface shear stress: VEd = 2.845031 MPa


vEd 
zb
Design shear resistance at the interface:

2
Area of the interface = 228000 mm2 ; Area of interface reinforcement: 5428.672 mm /m

Angle of reinforcement to interface: a 90 deg

Surface roughness: Smooth 0.6

vEdi  cfctd  h


reinforcement ratio required:  min  = 0.010901
fyd Sina  Cosa 

Area of interface reinforcement required = 2485.315 mm2 OK


Maximum spacing of links using current preferred bar diameter =

DESIGN OF SHEAR CONNECTORS(INNER GIRDER)AT MID SECTION

Width of beam = 950 mm


Shear = 1555 kN
Z (lever arm) = 622.1265 mm
Dia of interface reinforement = 12.00
Number of legs = 4.00
Spacing = 125.00 mm

Design value of interface shear stress: VEd = 2.630737 MPa


vEd 
zb
Design shear resistance at the interface:

2
Area of the interface = 228000 mm2 ; Area of interface reinforcement: 3619.115 mm /m

Angle of reinforcement to interface: a 90 deg

Surface roughness: Smooth 0.6

vEdi  cfctd  h


reinforcement ratio required:  min  = 0.010079
fyd Sina  Cosa 

Area of interface reinforcement required = 2298.115 mm2 OK


Maximum spacing of links using current preferred bar diameter =
Minimum Reinfocement for crack control in top flange
Grade of concrete M 50
Grade of steel Fe 500

Section dimensions of flange


Width of the section = 1000 mm Length of the section = 337.5 mm
Depth of the section = 188 mm

Miscellaneous details
E of reinforcement = 200 GPa Ecm of concrete = 3500 MPa As per IRC112-2011,Table No.-6.5
fctm = Mean value of axial tensile strength of concrete = 3.5 MPa As per IRC112-2011,Table No.-6.5

As per clause 12.3.3 of IRC:112-2011, Equation 12.1


=
As.min (Kc*K*fct eff* Act)/σs

σs = fyk = Fe 500
fct,eff = max(fctm ,2.9) = 3.5
k= 1
Kc = 0.4
Act =0.5bd = 31640.63 mm2 (considering without reinforcement)
=
As.min 88.59375 mm2
Reinfoecement provided = 678.24 mm2 ok

Minimum Reinfocement for crack control in bottom flange


Grade of concrete M 50
Grade of steel Fe 500

Section dimensions of flange


Width of the section = 1000 mm Length of the section = 217.5 mm
Depth of the section = 340 mm

Miscellaneous details
E of reinforcement = 200 GPa Ecm of concrete = 3500 MPa As per IRC112-2011,Table No.-6.5
fctm = Mean value of axial tensile strength of concrete = 3.5 MPa As per IRC112-2011,Table No.-6.5

As per clause 12.3.3 of IRC:112-2011, Equation 12.1


=
As.min (Kc*K*fct eff* Act)/σs

σs = fyk = Fe 500
fct,eff = max(fctm ,2.9) = 3.5
k= 1
Kc = 0.4
Act =0.5bd = 36975 mm2 (considering without reinforcement)
=
As.min 103.53 mm2
Reinfoecement provided = 226.08 mm2 ok
Minimum Reinfocement for crack control in WEB at mid section
Grade of concrete M 50
Grade of steel Fe 500

Section dimensions of flange


Width of the section = 1000 mm Length of the section = 275.0 mm
Depth of the section = 2500 mm

Miscellaneous details
E of reinforcement = 200 GPa Ecm of concrete = 3500 MPa As per IRC112-2011,Table No.-6.5
fctm = Mean value of axial tensile strength of concrete = 3.5 MPa As per IRC112-2011,Table No.-6.5

As per clause 12.3.3 of IRC:112-2011, Equation 12.1


As.min = (Kc*K*fct eff* Act)/σs

σs = fyk = Fe 500
fct,eff = max(fctm ,2.9) = 3.5
k= 1
Kc = 0.4
Act =0.5bd = 343750 mm2 (considering without reinforcement)

As.min = 962.5 mm2


Reinfoecement provided = 2939.04 mm2 ok

Minimum Reinfocement for crack control in WEB at Support section


Grade of concrete M 50
Grade of steel Fe 500

Section dimensions of flange


Width of the section = 1000 mm Length of the section = 710.0 mm
Depth of the section = 2500 mm

Miscellaneous details
E of reinforcement = 200 GPa Ecm of concrete = 3500 MPa As per IRC112-2011,Table No.-6.5
fctm = Mean value of axial tensile strength of concrete = 3.5 MPa As per IRC112-2011,Table No.-6.5

As per clause 12.3.3 of IRC:112-2011, Equation 12.1


As.min = (Kc*K*fct eff* Act)/σs

σs = fyk = Fe 500
fct,eff = max(fctm ,2.9) = 3.5
k= 1
Kc = 0.4
Act =0.5bd = 887500 mm2 (considering without reinforcement)
=
As.min 2485 mm2
Reinfoecement provided = 2939.04 mm2 ok
DESIGN OF CROSS GIRDER
ULS BASIC SLS RARE SLS QUASI
Intermediate Cross Girder DL 1.35 1 1
SIDL OTHERS 1.35 1 1
SIDL WC 1.750 1 1
LL 1.500 1 0
3.13 m 3.13 m Impact foctor 1.12
A B (SKW) C
UNFACORED ULS SLS RARE SLS QUASI
From STAAD output T-m T-m T-m T-m
= HOG 4.70 6.35 4.70 4.70
Max moment (DL)
= SAG 1.72 2.32 1.72 1.72
= HOG 68.50 92.48 68.50 68.50
Max Hogging moment (SIDL OTHERS)
= SAG 0.00 0.00 0.00 0.00
= HOG 0.03 0.05 0.03 0.03
Max Hogging moment (SIDL WC)
= SAG 0.50 0.88 0.50 0.50
Max Hogging Moment due to Footpath live load = HOG 0.00 0.00 0.00 0.00
only = SAG 0.00 0.00 0.00 0.00

Max Hogging Moment due to live load only = HOG 87.30 130.95 87.30 0.00

Max Sagging Moment due to live load only = SAG 145.00 217.5 145 0

Live Load Hogging Moment-Including Impact = HOG 97.78 146.66 97.78 0.00

Live Load Sagging Moment-Including Impact = SAG 162.40 243.60 162.40 0.00
Total Hogging moment (at top) = HOG 171.01 245.54 171.01 73.23
Total Sagging moment (at bottom) = SAG 164.62 246.80 164.62 2.22

Designed of deep beam [ As per Clause 29.2, IS 456-2000 ]

For span AB L = 3.127 D= 2.5


L/D = 1.251 < 2.5 for contineous beam

Lever arm Z = 0.2*(3.127+1.5*2.5) = 1.375 m

2
Required Ast at top =Mu/(0.87*fy*Z) =171.01*10000/(0.87*500*100*1.3754) = 41.04 cm

Provide 3 nos 25 f + 3 nos 25 f + 3 nos 25 f

Provided Ast at Top = 44.18 cm2 Thus OK

(Distributed as per clause 29.3.2 (b) IS:456-2000)

In Top 0.2*D = 0.500 m fraction of steel = 0.5*(1.251 - 0.5) = 0.375

2
i.e. 15.41 cm

2
In Next 0.6*D depth rest of the reinforcement will be distributed equally i.e. 25.63 cm

Required Ast at bottom =Mu/(0.87*fy*Z) =164.62*10000/(0.87*500*100*1.3754) = 41.25 cm2

Provide 3 nos 25 f + 3 nos 25 f + 3 nos 25 f

2
Provided Ast at bottom = 44.18 cm Thus OK

(Distributed as per clause 29.3.1 (c) IS:456-2000)

at bottom within a depth of (0.25D - 0.05L) = 0.469 m

Minimum embedment from bottom face with a development length of (0.8*30*dia of bar)

= 600 mm

Minimum Ast =0.2%bd =0.002*30*250 = 15.00 cm2


Hanging reinforcement [ As per clause 29.3.3, IS 456-2000 ]

DL+SIDL+FPLL shear =4.53*1.35+18.5*1.35+0.1*1.75 31.3 t

Live Load shear = 37.5 t

Live Load shear including impact = 42.0 t

Total shear (DL+Live load) (31.2655 + 42.00) = 73.27 t

Required Ast as hanging R/F =73.2655*10000/(0.87*500*100) = 16.8 cm2

2
Required Ast per m length =16.8/3.127 = 10.77 cm /m

Provide 2L 12 f @ 150 c/c as Vertical Reinforcement

Provided Ast = 15.1 cm2/m


Thus OK
Side face reinforcement [As per clause 32.4 IS-456, 2000]

0.1 % of web area on either face with spacing not more then 450 mm.

Required Ast =0.001 *250*30 = 7.50 cm2

Provide 14 nos 10 f on each face

2
Provided Ast = 11.00 cm
Thus OK
STRESS CHECK FOR SLS COMBINATION

Stress in steel =M/(Ast*Z) = 28143.0 t/m2


= 281.43 N/mm2 < 400 Mpa SAFE
Permissible stress =0.8 fy < 300 N/mm2 Fatigue Check not Required

End Cross Girder

The end cross girder is designed as a continuous deep beam for bearing replacement condition, continuous over knife supports at the jack locations.
The center line of jacks are taken to be 800 (SQ) mm from the center line of main girders.

167.50 t 161.00 t 167.50 t ULS(1.35*DL+1.35*SIDL+1.75*SIDL)

121.00 t 117.00 t 121.00 t SLS(1.0*DL+1.0*SIDL+1.0*SIDL)


3.127 3.127

0.8628 1.401 0.863 0.8628 1.4014 0.8628


(SKW) (SKW)

Max support moment (1.35*DL+*1.35*SIDL(OTHERS)+1.75*SIDL(WC) (From Staad Output) = 615 t-m


Max span moment (1.35*DL+*1.35*SIDL(OTHERS)+1.75*SIDL(WC) (From Staad Output) = 0 t-m

Max support moment (1.0*DL+*1.0*SIDL(OTHERS)+1.0*SIDL(WC) (From Staad Output) = 441 t-m


Max span moment (1.0*DL+*1.0*SIDL(OTHERS)+1.0*SIDL(WC) (From Staad Output) = 0 t-m

Design of deep beam [ As per Clause 29.2, IS 456-2000 ]

For span CD L= 3.540 D = 3.04


L/D = 1.164 < 2.5 for contineous beam

Lever arm Z = 0.2*(3.540+1.5*3.04) = 1.620 m

Required Ast for max span Moment =Mu/(0.87*fy*Z) =0*10000/(0.87*500*100*1.62) = 0.00 cm2

Minimum Ast at bottom =0.2%bd =0.002*70*304 = 42.56 cm2

Provide 8 nos 20 f + 8 nos 20 f + nos f

at bottom within a depth of (0.25D - 0.05L) = 0.583 m


Minimum embedment from bottom face with a development length of (0.8*30*dia of bar)
= 480 mm
2
Provided Ast = 50.3 cm Thus OK

=Mu/(0.87*fy*Z)
2
Required Ast for max support Moment =615*10000/(0.87*500*100*1.62) = 87 cm

At Top, Provide 8 nos 25 f + 8 nos 25 f + 8 nos 25 f

Distributed as per clause 29.3.2 (b) IS 456-2000

Provided Ast at Top = 118 cm2 Thus OK

In Top 0.2*D = 0.608 m fraction of steel = 0.5*(1.164 - 0.5) = 0.332


1.824
2
i.e. 28.99 cm

2
In Next 0.6*D depth rest of the reinforcement will be distributed equally i.e. 58.28 cm

STRESS CHECK FOR SLS COMBINATION

Stress in steel =M/(Ast*Z) = 23106.9 t/m2


= 231.07 N/mm2 < 400 Mpa SAFE
Permissible stress =0.8 fy < 300 N/mm2 Fatigue Check not Required

Hanging reinforcement [ As per Clause 29.3.3, IS 456-2000 ]

Maximum shear (From Staad Output) = 167 t

Required Ast as hanging R/F =167.0*10000/(0.87*500*100) = 38.4 cm2

Width considered = = 0.863 m

2
Required Ast per m width =38.4/0.863 = 44.5 cm /m

Provide 2L 16 f @ 100 c/c as vertical reinforcement

2
Provided Ast = 40.2 cm /m
Thus Not OK

Side face reinforcement [As per clause 32.4 IS-456, 2000]

0.1 % of web area on either face with spacing not more then 450 mm.

Required Ast =0.001 *304*70 = 21.28 cm2

Provide 14 nos 16 f on each face

2
Provided Ast = 28.15 cm
Thus OK
STAAD INPUT FOR END CROSS GIRDER

STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 03-Nov-15
END JOB INFORMATION
INPUT WIDTH 79
UNIT METER MTON
JOINT COORDINATES
1 9.1686 0 -23.2; 2 7.9969 0 -20.3; 3 6.8252 0 -17.4; 4 5.6535 0 -14.5;
5 4.4818 0 -11.6; 6 3.3101 0 -8.7; 7 2.1384 0 -5.8; 8 0.9667 0 -2.9;
9 -0.205 0 0; 10 9.9866 0 -25.225; 11 -1.023 0 2.025;
12 8.84538 0 -22.4; 13 7.67368 0 -19.5; 14 6.50198 0 -16.6;
15 5.33028 0 -13.7; 16 4.15858 0 -10.8; 17 2.98688 0 -7.90003;
18 1.81518 0 -5.00003; 19 0.643484 0 -2.10003; 20 8.32014 0 -21.1;
21 7.14844 0 -18.2; 22 5.97674 0 -15.3; 23 4.80504 0 -12.4;
24 3.63334 0 -9.50003; 25 2.46164 0 -6.60003; 26 1.28994 0 -3.70003;
27 0.118239 0 -0.800027;
MEMBER INCIDENCES
1 1 12; 2 2 13; 3 3 14; 4 4 15; 5 5 16; 6 6 17; 7 7 18; 8 8 19; 9 10 1;
10 9 11; 11 12 20; 12 13 21; 13 14 22; 14 15 23; 15 16 24; 16 17 25;
17 18 26; 18 19 27; 19 20 2; 20 21 3; 21 22 4; 22 23 5; 23 24 6;
24 25 7; 25 26 8; 26 27 9;
DEFINE MATERIAL START
ISOTROPIC CONCRETE
E 2.21467e+006
POISSON 0.17
DENSITY 2.40262
ALPHA 1e-005
DAMP 0.05
TYPE CONCRETE
STRENGTH FCU 2812.28
END DEFINE MATERIAL
MEMBER PROPERTY
1 TO 26 PRIS YD 1 ZD 1
CONSTANTS
MATERIAL CONCRETE ALL
SUPPORTS
10 11 PINNED
LOAD 1 LOADTYPE None TITLE 1.35 DL+1.35 SIDL CB+1.75SIDL WC
JOINT LOAD
1 9 FY -167.5
2 TO 8 FY -161
12 TO 27 FY 91.4
***
LOAD 2 LOADTYPE None TITLE 1.0 DL+1.0 SIDL CB+1.0SIDL WC
JOINT LOAD
1 9 FY -121
2 TO 8 FY -117
12 TO 27 FY 66.3
PERFORM ANALYSIS
FINISH
Transverse analysis
Staad Input
STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 01-Dec-09
END JOB INFORMATION
INPUT WIDTH 79
UNIT METER MTON
JOINT COORDINATES
1 0 0 0; 2 27.25 0 0; 3 2.025 0 0; 4 4.925 0 0; 5 7.825 0 0; 6 10.725 0 0;
7 13.625 0 0; 8 16.525 0 0; 9 19.425 0 0; 10 22.325 0 0; 11 25.225 0 0;
12 2.5 0 0; 13 5.4 0 0; 14 8.3 0 0; 15 11.2 0 0; 16 14.1 0 0; 17 17 0 0;
18 19.9 0 0; 19 22.8 0 0; 20 25.7 0 0; 21 4.45 0 0; 22 7.35 0 0; 23 10.25 0 0;
24 13.15 0 0; 25 16.05 0 0; 26 18.95 0 0; 27 21.85 0 0; 28 24.75 0 0;
29 1.55 0 0; 30 4.26 0 0; 31 7.16 0 0; 32 10.06 0 0; 33 12.96 0 0;
34 15.86 0 0; 35 18.76 0 0; 36 21.66 0 0; 37 24.56 0 0; 38 2.69 0 0;
39 5.59 0 0; 40 8.49 0 0; 41 11.39 0 0; 42 14.29 0 0; 43 17.19 0 0;
44 20.09 0 0; 45 22.99 0 0;
MEMBER INCIDENCES
1 1 29; 2 3 12; 3 4 13; 4 5 14; 5 6 15; 6 7 16; 7 8 17; 8 9 18; 9 10 19;
10 11 20; 11 12 38; 12 13 39; 13 14 40; 14 15 41; 15 16 42; 16 17 43; 17 18 44;
18 19 45; 19 20 2; 20 21 4; 21 22 5; 22 23 6; 23 24 7; 24 25 8; 25 26 9;
26 27 10; 27 28 11; 28 29 3; 29 30 21; 30 31 22; 31 32 23; 32 33 24; 33 34 25;
34 35 26; 35 36 27; 36 37 28; 37 38 30; 38 39 31; 39 40 32; 40 41 33; 41 42 34;
42 43 35; 43 44 36; 44 45 37;
START GROUP DEFINITION
MEMBER
_DEFF 37 TO 44
END GROUP DEFINITION
DEFINE MATERIAL START
ISOTROPIC CONCRETE
E 2.21466e+006
POISSON 0.17
DENSITY 2.5
ALPHA 5.5e-006
DAMP 0.05
END DEFINE MATERIAL
MEMBER PROPERTY AMERICAN
1 TO 44 PRIS YD 0.24 ZD 1
CONSTANTS
MATERIAL CONCRETE ALL
SUPPORTS
3 TO 11 PINNED
LOAD 1
MEMBER LOAD
37 UNI GY -18.71 0 0.2
11 UNI GY -18.71 0 0.19
2 UNI GY -18.71 0 0.475
28 UNI GY -18.71 0 0.475
1 UNI GY -18.71 1.43 1.55
20 UNI GY -7.9 0 0.37
29 UNI GY -7.9 0 0.19
37 UNI GY -7.9 0.67 1.57
LOAD 2
MEMBER LOAD
37 UNI GY -8.79 0 0.7
11 UNI GY -8.79 0 0.19
2 UNI GY -8.79 0 0.475
28 UNI GY -8.79 0.38 0.475
3 UNI GY -10.36 0 0.395
20 UNI GY -10.36 0 0.475
29 UNI GY -10.36 0 0.19
37 UNI GY -10.36 1.17 1.57
LOAD 3
MEMBER LOAD
37 UNI GY -7.41 0 1.2
11 UNI GY -7.41 0 0.19
2 UNI GY -7.41 0.405 0.475
38 UNI GY -16.9 0 0.23
12 UNI GY -16.9 0 0.19
3 UNI GY -16.9 0 0.475
20 UNI GY -16.9 0 0.475
29 UNI GY -16.9 0.1 0.19
LOAD 4
MEMBER LOAD
29 UNI GY -7.24 0 0.13
37 UNI GY -7.24 0.24 1.57
38 UNI GY -8.65 0 0.73
12 UNI GY -8.65 0 0.19
3 UNI GY -8.65 0 0.475
20 UNI GY -8.65 0.41 0.475
LOAD 5
MEMBER LOAD
20 UNI GY -8.1 0 0.44
29 UNI GY -8.1 0 0.19
37 UNI GY -8.1 0.74 1.57
38 UNI GY -7.37 0 1.23
12 UNI GY -7.37 0 0.19
3 UNI GY -7.37 0.435 0.475
LOAD 6
MEMBER LOAD
3 UNI GY -11.66 0 0.465
20 UNI GY -11.66 0 0.475
29 UNI GY -11.66 0 0.19
37 UNI GY -11.66 1.24 1.57
30 UNI GY -7.26 0 0.16
38 UNI GY -7.26 0.27 1.57
LOAD 7
MEMBER LOAD
38 UNI GY -13.9 0 0.3
12 UNI GY -13.9 0 0.19
3 UNI GY -13.9 0 0.475
20 UNI GY -13.9 0 0.475
29 UNI GY -13.9 0.17 0.19
21 UNI GY -8.19 0 0.47
30 UNI GY -8.19 0 0.19
38 UNI GY -8.19 0.77 1.57
LOAD 8
MEMBER LOAD
38 UNI GY -8.37 0 0.8
12 UNI GY -8.37 0 0.19
3 UNI GY -8.37 0.00499964 0.475
13 UNI GY -12.4 0 0.0199995
4 UNI GY -12.4 0 0.475
21 UNI GY -12.4 0 0.475
30 UNI GY -12.4 0 0.19
38 UNI GY -12.4 1.27 1.57
LOAD 9
MEMBER LOAD
38 UNI GY -7.3 0 1.3
12 UNI GY -7.3 0.0299997 0.19
39 UNI GY -12.95 0 0.33
13 UNI GY -12.95 0 0.19
4 UNI GY -12.95 0 0.475
21 UNI GY -12.95 0.0100002 0.475
LOAD 10
MEMBER LOAD
21 UNI GY -7.32 0 0.04
30 UNI GY -7.32 0 0.19
38 UNI GY -7.32 0.34 1.57
39 UNI GY -8.26 0 0.83
13 UNI GY -8.26 0 0.19
4 UNI GY -8.26 0.0349998 0.475
LOAD 11
MEMBER LOAD
4 UNI GY -8.45 0 0.0649996
21 UNI GY -8.45 0 0.475
30 UNI GY -8.45 0 0.19
38 UNI GY -8.45 0.84 1.57
39 UNI GY -7.27 0 1.33
13 UNI GY -7.27 0.0599995 0.19
LOAD 12
MEMBER LOAD
13 UNI GY -14.63 0 0.0900002
4 UNI GY -14.63 0 0.475
21 UNI GY -14.63 0 0.475
30 UNI GY -14.63 0 0.19
38 UNI GY -14.63 1.34 1.57
22 UNI GY -7.35 0 0.0700002
31 UNI GY -7.35 0 0.19
39 UNI GY -7.35 0.369999 1.57
LOAD 13
MEMBER LOAD
39 UNI GY -11.23 0 0.4
13 UNI GY -11.23 0 0.19
4 UNI GY -11.23 0 0.475
21 UNI GY -11.23 0.0799999 0.475
5 UNI GY -8.57 0 0.0949998
22 UNI GY -8.57 0 0.475
31 UNI GY -8.57 0 0.19
39 UNI GY -8.57 0.87 1.57
LOAD 14
MEMBER LOAD
39 UNI GY -8.04 0 0.9
13 UNI GY -8.04 0 0.19
4 UNI GY -8.04 0.105 0.475
14 UNI GY -15.9 0 0.119999
5 UNI GY -15.9 0 0.475
22 UNI GY -15.9 0 0.475
31 UNI GY -15.9 0 0.19
39 UNI GY -15.9 1.37 1.57
LOAD 15
MEMBER LOAD
39 UNI GY -7.22 0 1.4
13 UNI GY -7.22 0.13 0.19
40 UNI GY -10.65 0 0.429999
14 UNI GY -10.65 0 0.19
5 UNI GY -10.65 0 0.475
22 UNI GY -10.65 0.109999 0.475
LOAD 16
MEMBER LOAD
22 UNI GY -7.44 0 0.14
31 UNI GY -7.44 0 0.19
39 UNI GY -7.44 0.44 1.57
40 UNI GY -7.95 0 0.93
14 UNI GY -7.95 0 0.19
5 UNI GY -7.95 0.134999 0.475
LOAD 17
MEMBER LOAD
5 UNI GY -8.88 0 0.164999
22 UNI GY -8.88 0 0.475
31 UNI GY -8.88 0 0.19
39 UNI GY -8.88 0.94 1.57
40 UNI GY -7.21 0 1.43
14 UNI GY -7.21 0.159998 0.19
LOAD 18
MEMBER LOAD
14 UNI GY -20.17 0 0.189999
5 UNI GY -20.17 0 0.475
22 UNI GY -20.17 0 0.475
31 UNI GY -20.17 0 0.19
39 UNI GY -20.17 1.44 1.57
23 UNI GY -7.48 0 0.17
32 UNI GY -7.48 0 0.19
40 UNI GY -7.48 0.469998 1.57
LOAD 19
MEMBER LOAD
40 UNI GY -9.97 0 0.499999
14 UNI GY -9.97 0 0.19
5 UNI GY -9.97 0 0.475
22 UNI GY -9.97 0.180001 0.475
6 UNI GY -9.03 0 0.195001
23 UNI GY -9.03 0 0.474999
32 UNI GY -9.03 0 0.19
40 UNI GY -9.03 0.97 1.57
LOAD 20
MEMBER LOAD
40 UNI GY -7.77 0 1
14 UNI GY -7.77 0 0.19
5 UNI GY -7.77 0.205 0.475
41 UNI GY -22.9 0 0.0300004
15 UNI GY -22.9 0 0.19
6 UNI GY -22.9 0 0.475
23 UNI GY -22.9 0 0.474999
32 UNI GY -22.9 0 0.19
40 UNI GY -22.9 1.47 1.57
LOAD 21
MEMBER LOAD
40 UNI GY -7.19 0.0400004 1.5
41 UNI GY -9.75 0 0.53
15 UNI GY -9.75 0 0.19
6 UNI GY -9.75 0 0.475
23 UNI GY -9.75 0.209999 0.474999
LOAD 22
MEMBER LOAD
24 UNI GY -7.82 0 0.34
33 UNI GY -7.82 0 0.19
41 UNI GY -7.82 0.640001 1.57
42 UNI GY -7.51 0 1.13
16 UNI GY -7.51 0 0.190001
7 UNI GY -7.51 0.335002 0.475
LOAD 29
MEMBER LOAD
7 UNI GY -10.12 0 0.365001
24 UNI GY -10.12 0 0.474998
33 UNI GY -10.12 0 0.19
41 UNI GY -10.12 1.14 1.57
34 UNI GY -7.2 0 0.0599998
42 UNI GY -7.2 0.170001 1.57
LOAD 30
MEMBER LOAD
42 UNI GY -18.71 0 0.2
16 UNI GY -18.71 0 0.190001
7 UNI GY -18.71 0 0.475
24 UNI GY -18.71 0 0.474998
33 UNI GY -18.71 0.0699998 0.19
25 UNI GY -7.9 0 0.370001
34 UNI GY -7.9 0 0.19
42 UNI GY -7.9 0.670001 1.57
LOAD 31
MEMBER LOAD
42 UNI GY -8.79 0 0.7
16 UNI GY -8.79 0 0.190001
7 UNI GY -8.79 0 0.475
24 UNI GY -8.79 0.380001 0.474998
8 UNI GY -10.36 0 0.395002
25 UNI GY -10.36 0 0.474998
34 UNI GY -10.36 0 0.19
42 UNI GY -10.36 1.17 1.57
LOAD 32
MEMBER LOAD
42 UNI GY -7.41 0 1.2
16 UNI GY -7.41 0 0.190001
7 UNI GY -7.41 0.405002 0.475
43 UNI GY -16.9 0 0.230001
17 UNI GY -16.9 0 0.190001
8 UNI GY -16.9 0 0.475
25 UNI GY -16.9 0 0.474998
34 UNI GY -16.9 0.0999998 0.19
LOAD 33
MEMBER LOAD
34 UNI GY -7.24 0 0.13
42 UNI GY -7.24 0.240001 1.57
43 UNI GY -8.65 0 0.730001
17 UNI GY -8.65 0 0.190001
8 UNI GY -8.65 0 0.475
25 UNI GY -8.65 0.410002 0.474998
LOAD 34
MEMBER LOAD
25 UNI GY -8.1 0 0.440001
34 UNI GY -8.1 0 0.19
42 UNI GY -8.1 0.740001 1.57
43 UNI GY -7.37 0 1.23
17 UNI GY -7.37 0 0.190001
8 UNI GY -7.37 0.435003 0.475
LOAD 35
MEMBER LOAD
8 UNI GY -11.66 0 0.465002
25 UNI GY -11.66 0 0.474998
34 UNI GY -11.66 0 0.19
42 UNI GY -11.66 1.24 1.57
35 UNI GY -7.26 0 0.16
43 UNI GY -7.26 0.270002 1.57
LOAD 36
MEMBER LOAD
43 UNI GY -13.9 0 0.300001
17 UNI GY -13.9 0 0.190001
8 UNI GY -13.9 0 0.475
25 UNI GY -13.9 0 0.474998
34 UNI GY -13.9 0.17 0.19
26 UNI GY -8.19 0 0.470001
35 UNI GY -8.19 0 0.19
43 UNI GY -8.19 0.770002 1.57
LOAD 37
MEMBER LOAD
43 UNI GY -8.37 0 0.800001
17 UNI GY -8.37 0 0.190001
8 UNI GY -8.37 0.00500298 0.475
18 UNI GY -12.4 0 0.0200024
9 UNI GY -12.4 0 0.475
26 UNI GY -12.4 0 0.474998
35 UNI GY -12.4 0 0.19
43 UNI GY -12.4 1.27 1.57
LOAD 38
MEMBER LOAD
43 UNI GY -7.3 0 1.3
17 UNI GY -7.3 0.0300026 0.190001
44 UNI GY -12.95 0 0.330001
18 UNI GY -12.95 0 0.190001
9 UNI GY -12.95 0 0.475
26 UNI GY -12.95 0.0100021 0.474998
LOAD 39
MEMBER LOAD
26 UNI GY -7.32 0 0.0400009
35 UNI GY -7.32 0 0.19
43 UNI GY -7.32 0.340002 1.57
44 UNI GY -8.26 0 0.829999
18 UNI GY -8.26 0 0.190001
9 UNI GY -8.26 0.0350037 0.475
LOAD 40
MEMBER LOAD
9 UNI GY -8.45 0 0.0650024
26 UNI GY -8.45 0 0.474998
35 UNI GY -8.45 0 0.19
43 UNI GY -8.45 0.839999 1.57
44 UNI GY -7.27 0 1.33
18 UNI GY -7.27 0.0600033 0.190001
LOAD 41
MEMBER LOAD
18 UNI GY -14.63 0 0.0900021
9 UNI GY -14.63 0 0.475
26 UNI GY -14.63 0 0.474998
35 UNI GY -14.63 0 0.19
43 UNI GY -14.63 1.34 1.57
27 UNI GY -7.35 0 0.0700016
36 UNI GY -7.35 0 0.19
44 UNI GY -7.35 0.370002 1.57
LOAD 71 DEAD LOAD
SELFWEIGHT Y -1
LOAD 72 SIDL CRASH BARRIER
MEMBER LOAD
1 CON GY -1 0
19 CON GY -1 1.55
LOAD 73 SIDL WEARING COARSE
MEMBER LOAD
1 TO 44 UNI GY -0.2
PERFORM ANALYSIS
FINISH
Force Summary for intermediate span
SLSQUASI ULS BASIC SLS RARE
PERMANENTCOM COMB. COMB.
ULS BASIC COMB. SLS RARE COMB. B. (Favourable) (Favourable)
Factor
DL & SIDL 1.35 1 1 1
SURFACING 1.75 1.2 1.2 1 1
LIVE LOAD (LEADING) 1.5 1 0
(FOR ACCOMPANYING ) 1.15 0.75 0

Load case SPAN MOMENT AT SUPPORT


MOMENT (kN-
MOMENT (kN-m) m) SHEAR FORCE (kN)
DL 2.90 4.20 1.16
SIDL CRASH BARRIER 3.72 0.19 8.65
SIDL W/C SURFACING 0.97 1.40 0.386
LIVE LOAD 40.5 60.5 65.9
Impact factor 1.5 1.5 1.5
vehicle max(+) LLMAX 60.75 90.75 98.85
FOR ULS BASIC COMBINATION B.M (kN-m) B.M (kN-m) SHEAR (kN)
DL+SIDL+LL 101.8 144.5 162.194
FOR SLS RARE COMBINATION B.M (kN-m) B.M (kN-m) SHEAR (kN)
DL+SIDL+LL 68.53 96.82 109.1232
FOR SLS QUASI PERMANENT COMBINATION B.M (kN-m) B.M (kN-m) SHEAR (kN)
DL+SIDL 7.78 6.07 10.2732

Force Summary for cantilever span


At Intermediate Section :
0.50m 1.625m CL Girder

RCC Crash Barrier 0.4


0.240m 0.24 m

2.025 m

Live Load moment (Class A)

Effective width (beff) = 1.2a + b1


Where,
a is the distance of load cg from support. = 1.1250 m
b1 is tyre width + twice the thickness of wearing coat = 0.38 m
beff = 1.730 m
As beff > 1.2m, Hence overlaping occurs.
Therefore, beff for both axles acting together =0.5*(1.73+1.2) = 1.465 m
beff for a single axle

Impact factor (As per Clause 208.2 IRC-6,2014) = 1.50

Therefore, live load /m width including impact both axles


acting together =(5.7*1.50)/1.465 = 5.836 t/m
Therefore, live load /m width including impact single axle loading = (5.7*1.50)/1.465 = 5.836 t/m
Critical Intensity considered = 5.836 t/m

Moment at the face of support due to live load =5.836*1.125 = 6.566 tm/m

Load case AT FACE OF SUPPORT


MOMENT (kN-m)
DL 12.10
SIDL CRASH BARRIER 19.90
SIDL W/C SURFACING 4.05
LIVE LOAD 65.657
vehicle max(+) LLMAX 65.66
FOR ULS BASIC COMBINATION B.M (kN-m)
DL+SIDL+LL 148.8
FOR SLS RARE COMBINATION B.M (kN-m)
DL+SIDL+LL 102.52
FOR SLS QUASI PERMANENT COMBINATION B.M (kN-m)
DL+SIDL 36.86
Design of slab AT Support

Design forces
Grade of concrete M 35 ULS bending moment = 145 kNm (FACE OF SUPPORT)
Grade of steel Fe 500 ULS design shear force = 162 kN (at effective depth)
SLS bending moment = 97 kNm (RARE COMBINATION)
SLS design shear force = 109 kN (RARE COMBINATION) (at effective depth)
SLS bending moment =6 kNm (QUASI COMBINATION)
SLS design shear force = 10 kN (QUASI COMBINATION)

Section dimensions Reinforcement details


Width of the section = 1000 mm Clear cover = 40 mm
Depth of the section = 240 mm Dia of transverse bars = 16 mm

Miscellaneous details
E of reinforcement = 200 GPa Ecm of concrete = 32000 MPa As per IRC112-2011,Table No.-6.5
Modular ratio = 15.00 Modular ratio = 6.25
Max strain in concrete = 0.0035 Min strain in steel = 0.0042
fctm = Mean value of axial tensile strength of concrete = 2.8 MPa As per IRC112-2011,Table No.-6.5

Minimum Reinforcement required = 0.26*(fctm/fyk)*btd or 0.13%btd As per IRC112-2011,Clause:16.5.1.1


a) 0.13%btd = 249.6 mm2
OR
b) 0.26*(fctm/fyk)*btd = 279.552 mm2

Maximum Reinforcement =2.5%b t d 4800 mm2

Table : Details of main reinforcements


Total
Diameter Spacing Area
Layer Area
(mm) (mm/m) (mm2)
(mm2)
b1 16 90 2234.02
2234.02
b2 0 200 0.00

ULS moment capacity


(Ast/bdx100) of reinforcement at the section = 1.164 %
Moment of resistance of the section = 155.6 kNm Hence OK

Minimum Area of Distribution steel 0.2% of R/F required for bending 414.164875
Area of Distribution steel provided 10 @ 150 c/c 523.60 mm2 Hence O.K.

SLS moment capacity


Permissible tensile stress of steel (0.8Fy) as per IRC:112-2011 clause 12.2.2 = 400.0 MPa
Average modular ratio = 10.6
balanced neutral axis depth = 0.341
Balance neutral axis depth = 65.392
Neutral axis depth = 74.6 mm
maximum Neutral axis X umax = (for fe 500) = 0.456*deff = 87.6 mm
Moment of resistance of the section = 149.3 kNm Hence ok
STRESS CHECK IN SERVICEABILITY LIMIT STATE

Design bending moment SLS (RARE COMBINATION) = = 97 KNm


Neutral axis = Kd = 74.64 mm
Stress check in Steel :
Max. Tensile stress in steel shall be limited to 0.8fyk As per IRC112-2011,Clause:12.2.2
M = Ast*fy*(d-kd/3)
fy = 259.334 N/mm2 < 400 N/mm2 SAFE
< 300 N/mm3 Fatigue Check not Required
Stress check in Concrete :
Max. Compressive stress in concrete shall be limited to0.48fck As per IRC112-2011,Clause:12.4.1
M = (b*K d*Ca*(d-kd/3))/2
Ca = 15.524 N/mm2 < 16.8 N/mm2 SAFE

Crack width check

SLS bending moment (QUASI COMBINATION) = = 6 Knm


IRC:112:2011 Clause 12.3.4
In the calculation below the stress in reinforcement has been calculated igoring concrete in tension region. The calculation has been performed
Srmax = 282.1042
εsm-εcm = 4.88E-05 fcteff = 1.940 MPa
d = 192 mm σs = 16.26 MPa
αe = 6.25 hcef = 120.00 mm
Aceff = 120000 mm2 ρeff = 0.01862
kt = 0.5 Es = 200000 MPa
K1 = 0.8 K2 = 0.5
K3 = 3.4 K4 = 0.425
effective φ = 16.00 mm
Wk = 0.014 mm < 0.3 mm, OK

Minimum Reinfocement for crack control


As per clause 12.3.3 of IRC:112-2011, Equation 12.1
As.min = (Kc*K*fct eff* Act)/σs

σs = fyk = Fe 500
fct,eff = max(fctm ,2.9) = 2.9
k= 1
Kc = 0.4
Act =0.5bd = 120000 mm2 (considering without reinforcement)
=
As.min 278.4 mm2
Reinfoecement provided = 2234.02 mm2 ok
Design of slab AT SPAN

Design forces
Grade of concrete M 35 ULS bending moment = 102 kNm (FACE OF SUPPORT)
Grade of steel Fe 500 SLS bending moment = 69 kNm (RARE COMBINATION)
SLS bending moment =8 kNm (QUASI COMBINATION)

SLS design shear force = 10 kN (QUASI COMBINATION)

Section dimensions Reinforcement details


Width of the section = 1000 mm Clear cover = 40 mm
Depth of the section = 240 mm Dia of transverse bars = 16 mm

Miscellaneous details
E of reinforcement = 200 GPa Ecm of concrete = 32000 MPa As per IRC112-2011,Table No.-6.5
Modular ratio = 15.00 Modular ratio = 6.25
Max strain in concrete = 0.0035 Min strain in steel = 0.0042
fctm = Mean value of axial tensile strength of concrete = 2.8 MPa As per IRC112-2011,Table No.-6.5

Minimum Reinforcement required = 0.26*(fctm/fyk)*btd or 0.13%btd As per IRC112-2011,Clause:16.5.1.1


a) 0.13%btd = 249.6 mm2
OR
b) 0.26*(fctm/fyk)*btd = 279.552 mm2

Maximum Reinforcement =2.5%b t d 4800 mm2

Table : Details of main reinforcements


Total
Diameter Spacing Area
Layer Area
(mm) (mm/m) (mm2)
(mm2)
b1 16 180 1117.01
1745.33
b2 12 180 628.32

ULS moment capacity


(Ast/bdx100) of reinforcement at the section = 0.909 %
Moment of resistance of the section = 126.8 kNm Hence OK

Minimum Area of Distribution steel 0.2% of R/F required for bending 270.982739
Area of Distribution steel provided 10 @ 150 c/c 523.60 mm2 Hence O.K.

SLS moment capacity


Permissible tensile stress of steel (0.8Fy) as per IRC:112-2011 clause 12.2.2 = 400.0 MPa
Average modular ratio = 10.6
balanced neutral axis depth = 0.341
Balance neutral axis depth = 65.392
Neutral axis depth = 67.9 mm
maximum Neutral axis X umax = (for fe 500) = 0.456*deff = 87.6 mm
Moment of resistance of the section = 118.3 kNm Hence ok
STRESS CHECK IN SERVICEABILITY LIMIT STATE

Design bending moment SLS (RARE COMBINATION) = = 69 KNm


Neutral axis = Kd = 67.86 mm
Stress check in Steel :
Max. Tensile stress in steel shall be limited to 0.8fyk As per IRC112-2011,Clause:12.2.2
M = Ast*fy*(d-kd/3)
fy = 231.814 N/mm2 < 400 N/mm2 SAFE
< 300 N/mm3 Fatigue Check not Required
Stress check in Concrete :
Max. Compressive stress in concrete shall be limited to0.48fck As per IRC112-2011,Clause:12.4.1
M = (b*K d*Ca*(d-kd/3))/2
Ca = 11.925 N/mm2 < 16.8 N/mm2 SAFE

Crack width check

SLS bending moment (QUASI COMBINATION) = = 8 Knm


IRC:112:2011 Clause 12.3.4
In the calculation below the stress in reinforcement has been calculated igoring concrete in tension region. The calculation has been performed
Srmax = 302.9763
εsm-εcm = 7.9E-05 fcteff = 1.940 MPa
d = 192 mm σs = 26.32 MPa
αe = 6.25 hcef = 120.00 mm
Aceff = 120000 mm2 ρeff = 0.01454
kt = 0.5 Es = 200000 MPa
K1 = 0.8 K2 = 0.5
K3 = 3.4 K4 = 0.425
effective φ = 14.29 mm
Wk = 0.024 mm < 0.3 mm, OK

Minimum Reinfocement for crack control


As per clause 12.3.3 of IRC:112-2011, Equation 12.1
As.min = (Kc*K*fct eff* Act)/σs

σs = fyk = Fe 500
fct,eff = max(fctm ,2.9) = 2.9
k= 1
Kc = 0.4
Act =0.5bd = 120000 mm2 (considering without reinforcement)
=
As.min 278.4 mm2
Reinfoecement provided = 1745.33 mm2 ok
Design of cantilever slab (transverse direction)

Design forces
Grade of concrete M 35 ULS bending moment = 149 kNm (FACE OF SUPPORT)
Grade of steel Fe 500 SLS bending moment = 103 kNm (RARE COMBINATION)
SLS bending moment = 37 kNm (QUASI COMBINATION)
Section dimensions Reinforcement details
Width of the section = 1000 mm Clear cover = 40 mm
Depth of the section = 240 mm Dia of transverse bars = 16 mm

Miscellaneous details
E of reinforcement = 200 GPa Ecm of concrete = 32000 MPa As per IRC112-2011,Table No.-6.5
Modular ratio = 15.00 Modular ratio = 6.25
Max strain in concrete = 0.0035 Min strain in steel = 0.0042
fctm = Mean value of axial tensile strength of concrete = 2.8 MPa As per IRC112-2011,Table No.-6.5

Minimum Reinforcement required = 0.26*(fctm/fyk)*btd or 0.13%btd As per IRC112-2011,Clause:16.5.1.1


a) 0.13%btd = 249.6 mm2
OR
b) 0.26*(fctm/fyk)*btd = 279.552 mm2

Maximum Reinforcement =2.5%b t d 4800 mm2

Table : Details of main reinforcements


Total
Diameter Spacing Area
Layer Area
(mm) (mm/m) (mm2)
(mm2)
b1 16 90 2234.02
2234.02
b2 0 200 0.00

ULS moment capacity


(Ast/bdx100) of reinforcement at the section = 1.164 %
Moment of resistance of the section = 155.6 kNm Hence OK

Minimum Area of Distribution steel 0.2% of R/F required for bending 403.21873
Area of Distribution steel provided 10 @ 150 c/c 523.60 mm2 Hence O.K.

SLS moment capacity


Permissible tensile stress of steel (0.8Fy) as per IRC:112-2011 clause 12.2.2 = 400.0 MPa
Average modular ratio = 10.6
balanced neutral axis depth = 0.341
Balance neutral axis depth = 65.392
Neutral axis depth = 74.6 mm
maximum Neutral axis X umax = (for fe 500) = 0.456*deff = 87.6 mm
Moment of resistance of the section = 149.3 kNm Hence ok
STRESS CHECK IN SERVICEABILITY LIMIT STATE

Design bending moment SLS (RARE COMBINATION) = = 103 KNm


Neutral axis = Kd = 74.64 mm
Stress check in Steel :
Max. Tensile stress in steel shall be limited to 0.8fyk As per IRC112-2011,Clause:12.2.2
M = Ast*fy*(d-kd/3)
fy = 274.588 N/mm2 < 400 N/mm2 SAFE
< 300 N/mm3 Fatigue Check not Required
Stress check in Concrete :
Max. Compressive stress in concrete shall be limited to0.48fck As per IRC112-2011,Clause:12.4.1
M = (b*K d*Ca*(d-kd/3))/2
Ca = 16.437 N/mm2 < 16.8 N/mm2 SAFE

Crack width check

SLS bending moment (QUASI COMBINATION) = = 37 Knm


IRC:112:2011 Clause 12.3.4
In the calculation below the stress in reinforcement has been calculated igoring concrete in tension region. The calculation has been performed
Srmax = 282.1042
εsm-εcm = 0.000296 fcteff = 1.940 MPa
d = 192 mm σs = 98.73 MPa
αe = 6.25 hcef = 120.00 mm
Aceff = 120000 mm2 ρeff = 0.01862
kt = 0.5 Es = 200000 MPa
K1 = 0.8 K2 = 0.5
K3 = 3.4 K4 = 0.425
effective φ = 16.00 mm
Wk = 0.084 mm < 0.3 mm, OK

Minimum Reinfocement for crack control


As per clause 12.3.3 of IRC:112-2011, Equation 12.1
As.min = (Kc*K*fct eff* Act)/σs

σs = fyk = Fe 500
fct,eff = max(fctm ,2.9) = 2.9
k= 1
Kc = 0.4
Act =0.5bd = 120000 mm2 (considering without reinforcement)
=
As.min 278.4 mm2
Reinfoecement provided = 2234.02 mm2 ok
DESIGN OF DECK SLAB BEYOND DIAPHRAGM :

20 t

0.400 m

0.916 m
0.36 m

0.263 m

Cantilever slab projection beyond diaphragm has been checked for 40t boggie load,for the wheel placing
as shown as above.

(1) Live Load Moment :

Effective width at support = 1.2a+b , where, a= (0.916-0.263/2) = 0.785m

= 1.2*0.7845+0.85 b= (0.36*2+0.065*2) = 0.850m

= 1.8m ,Overlap will not occur


10 t 1.93 m 10 t
Net effective width = 1.791 m

SPAN= 0.916m

Impact facor = 1.500 m 1.8 m 1.8 m


(Clause 211.2 of I.R.C 6-2000)

Load intensity = (10*1.500)/1.7914= 8.37 t/m

(1) Moment at the face of cantilever due to Live Load = 8.37*(0.916-0.263/2)

= 6.57 t-m/m

(2) Moment at the face of cantilever due to Dead Load = 0.4*2.5*0.916*0.916/2

= 0.420 t-m/m

(3) Moment at the face of cantilever due to wearing coat = 0.15*0.916*0.916/2

= 0.06 t-m/m

(4) Moment at the face of cantilever due to Crash Barrier = (1*0.916*0.916)/2

= 0.42 t-m/m

Load case
MOMENT (kN-
m)
DL 4.20
SIDL CRASH BARRIER 4.20
SIDL W/C SURFACING 0.63
LIVE LOAD 65.7
vehicle max(+) LLMAX 65.69
FOR ULS BASIC COMBINATION B.M (kN-m)
DL+SIDL+LL 111.0
FOR SLS RARE COMBINATION B.M (kN-m)
DL+SIDL+LL 74.83
FOR SLS QUASI PERMANENT COMBINATION B.M (kN-m)
DL+SIDL 9.15
Design of cantilever slab (longitudinal direction)
Design forces
Grade of concrete M 35 ULS bending moment = 111 kNm (FACE OF SUPPORT)
Grade of steel Fe 500 SLS bending moment = 75 kNm (RARE COMBINATION)
SLS bending moment =9 kNm (QUASI COMBINATION)
Section dimensions Reinforcement details
Width of the section = 1000 mm Clear cover = 40 mm
Depth of the section = 400 mm Dia of transverse bars = 16 mm

Miscellaneous details
E of reinforcement = 200 GPa Ecm of concrete = 32000 MPa As per IRC112-2011,Table No.-6.5
Modular ratio = 15.00 Modular ratio = 6.25
Max strain in concrete = 0.0035 Min strain in steel = 0.0042
fctm = Mean value of axial tensile strength of concrete = 2.8 MPa As per IRC112-2011,Table No.-6.5

Minimum Reinforcement required = 0.26*(fctm/fyk)*btd or 0.13%btd As per IRC112-2011,Clause:16.5.1.1


a) 0.13%btd = 457.6 mm2
OR
b) 0.26*(fctm/fyk)*btd = 512.512 mm2

Maximum Reinforcement =2.5%b t d 8800 mm2

Table : Details of main reinforcements


Total
Diameter Spacing Area
Layer Area
(mm) (mm/m) (mm2)
(mm2)
b1 16 150 1340.41
1340.41
b2 0 200 0.00

ULS moment capacity


(Ast/bdx100) of reinforcement at the section = 0.381 %
Moment of resistance of the section = 194.1 kNm Hence OK

Minimum Area of Distribution steel 0.2% of R/F required for bending 149.467776
Area of Distribution steel provided 10 @ 150 c/c 523.60 mm2 Hence O.K.

SLS moment capacity


Permissible tensile stress of steel (0.8Fy) as per IRC:112-2011 clause 12.2.2 = 400.0 MPa
Average modular ratio = 10.6
balanced neutral axis depth = 0.341
Balance neutral axis depth = 119.886
Neutral axis depth = 86.9 mm
maximum Neutral axis X umax = (for fe 500) = 0.456*deff = 160.5 mm
Moment of resistance of the section = 173.2 kNm Hence ok
STRESS CHECK IN SERVICEABILITY LIMIT STATE

Design bending moment SLS (RARE COMBINATION) = = 75 KNm


Neutral axis = Kd = 86.90 mm
Stress check in Steel :
Max. Tensile stress in steel shall be limited to 0.8fyk As per IRC112-2011,Clause:12.2.2
M = Ast*fy*(d-kd/3)
fy = 172.828 N/mm2 < 400 N/mm2 SAFE
< 300 N/mm3 Fatigue Check not Required
Stress check in Concrete :
Max. Compressive stress in concrete shall be limited to0.48fck As per IRC112-2011,Clause:12.4.1
M = (b*K d*Ca*(d-kd/3))/2
Ca = 5.332 N/mm2 < 16.8 N/mm2 SAFE

Crack width check

SLS bending moment (QUASI COMBINATION) = = 9 Knm


IRC:112:2011 Clause 12.3.4
In the calculation below the stress in reinforcement has been calculated igoring concrete in tension region. The calculation has been performed
Srmax = 379.5071
εsm-εcm = 6.34E-05 fcteff = 1.940 MPa
d = 352 mm σs = 21.12 MPa
αe = 6.25 hcef = 120.00 mm
Aceff = 120000 mm2 ρeff = 0.01117
kt = 0.5 Es = 200000 MPa
K1 = 0.8 K2 = 0.5
K3 = 3.4 K4 = 0.425
effective φ = 16.00 mm
Wk = 0.024 mm < 0.3 mm, OK

Minimum Reinfocement for crack control


As per clause 12.3.3 of IRC:112-2011, Equation 12.1
As.min = (Kc*K*fct eff* Act)/σs

σs = fyk = Fe 500
fct,eff = max(fctm ,2.9) = 2.9
k= 1
Kc = 0.4
Act =0.5bd = 200000 mm2 (considering without reinforcement)
=
As.min 464 mm2
Reinfoecement provided = 1340.41 mm2 ok