Professional Documents
Culture Documents
Overturning, sliding, contact area, and allowable soil pressure have been verified on the support of
the electrical room.
The seismic coefficients for the maximum and minimum periods are:
The seismic coefficients must be less than the 𝐶𝑚á𝑥 indicated in Table 5.7 of the NCh 2369, where:
Then the seismic coefficient to be used for the calculation shall be Cmax.
𝑄0 = 0.21 × 1.20 𝑥 𝑃
𝑄0 = 0.252 × 29.95𝑘𝑁
𝑄0 = 7.55𝑘𝑁 (0.77 𝑡)
The coefficient for the vertical seismic according with Nch2369 Section 5.5 is:
𝐶𝑣 = 2(𝐴𝑜/3𝑔)
𝐶𝑣 = 0.23
Category C2 (4.3.2)
I 1.0
The seismic coefficients must be less than the 𝐶𝑚á𝑥 indicated in Table 5.7 of the NCh 2369, where:
The seismic coefficient used for the calculation was C max. Thus, for each support, the shear at the
base was estimated as:
𝑄0 = 1.13 𝑘𝑁 (0.12 𝑡)
The force was applied at two-thirds of the height of the column as shown in Figure 6.
Seismic Deformations
According to Section 6.1 of standard NCh2369, the lateral deformations were calculated as follows:
𝑑𝑋 = 𝑑0 + 𝑅1 × 𝑑𝑑
𝑑𝑋 = 0 + 3 × 0.32 𝑚𝑚 = 9.3 𝑚𝑚
Thus, the seismic deformations are less than those allowable. The maximum horizontal deformation
is shown in Figure 9
Max. Def. = 0.32 mm
The design of the connection between the footing and column is detailed in Appendix A.
Footing Reinforcement Design
Error! Reference source not found. shows the vertical bending moments.
Due to low bending moments on foundations, the longitudinal reinforcement is determined by the
minimum ratio.
𝜌𝑚𝑖𝑛 = 0.0015
Due to low bending moments on foundations, the transversal reinforcement is determined by the
minimum ratio.
𝜌𝑚𝑖𝑛 = 0.0015
Final Design
The reinforcement requirements are presented in Table 9.
Table 9: Reinforcement Requirements
Foundation