You are on page 1of 8

Switchgear Identification: H02+RH02 33KV MBITA LINE

RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

SUMMARY OF WIRED CONTACT OUTPUTS


Contact
Description State Tested
ID

F3 CB TC1 NO OK

F4 CB TC2 NO OK

F5 TRP CB T02 CBF Stag NO OK

F7 CB remote open NO OK

F8 CB remote close NO OK

G3 AR Init to D30 NO OK

G4 BLCK Autoreclose NO OK

G5 CB_MAN_CLOSE_COMND NO OK

H3 Open DS NO OK

H4 Close DS NO OK

H6 POS REPT DS & CB in NO OK

H7 POS REPT DS & CB in NO OK

J4 Line DS Open NO OK

J5 Line DS Close NO OK

2
Switchgear Identification: H02+RH02 33KV MBITA LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

SUMMARY OF WIRED CONTACT INPUTS


Contact ID Description Tested Remarks

F_CC2 (F2) DC suply fail P1 OK

F_CC4 (F4) Distance IntFAUL OK

F_CC6 (F6) CBF INI distance OK


F_CC9 (F9)
Heat Suply fail OK
F_CC10 (F10)
VT BCPU fai OK
F_CC11 (F11)
BCPU IL Ovrd/sw OK
F_CC12 (F12)
CB CLS BLCK Dis OK

G_CC2 (G2) CB OPEN pos OK

G_CC3 (G3) CB CLOSE pos OK

G_CC6 (G6) CB SF6 AL OK

G_CC7 (G7) CB SF6 Block OK

G_CC9 (G9) CB CLS LOCK DRIV OK

G_CC10 (G10) CB EXC MOT RUN OK

G_CC11 (G11) CB MOT PROT TRP OK

G_CC12 (G12) CB HEAT FAIL OK

G_CC13 (G13) CB In Remote OK

G_CC14 (G14) CB In Local OK

H_CC1(H01) DS Mot Prot TRP OK

H_CC2 (H02) DS In Remote OK

H_CC3 (H03) DS In Local OK

H_CC4 (H04) DS Closed OK

H_CC5 (H05) DS Open OK

H_CC6 (H06) DS MCB Heat FA OK

3
Switchgear Identification: H02+RH02 33KV MBITA LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

H_CC9 (H09) DSES mot Prt TRP OK

H_CC10 (H10) DSES in remote OK

H_CC11 (H11) DSES in local OK

H_CC12 (H12) Line DS closed OK

H_CC13 (H13) Line DS open OK

H_CC14 (H14) ES open OK

H_CC15 (H15) ES closed OK

H_CC16 (H16) DSES MCB heat F OK

J_CC1 (J01) DC DS/DSES FAIL OK

J_CC3 (J03) VT meter FAIL OK

J_CC5 (J05) TC 1 FAIL OK

J_CC6 (J06) TC 2 FAIL OK

4
Switchgear Identification: H02+RH02 33KV MBITA LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

UNBALANCED SYSTEM TO IDENTIFY PHASES (Read values on Primary values)

Phase VOLTAGE INJECTION ACTUAL VALUE CURRENT INJECTION ACTUAL VALUE

V Mag V Angle V Mag V Angle I Mag I Angle I Mag I Angle

A 20 V 0º 6.002KV 0.0º 1A 0º 0.249KA 359.938º

B 40 V -120º 11.974KV 119.750º 2A -120º 0.499KA 119.704º

C 60 V -240º 17.962KV 239.497º 3A 120º 0.750KA 239.296º

CURRENT INJECTION (G) ACTUAL VALUE

I Mag I Angle I Mag I Angle

1A 0.249KA

BALANCED V&I SYSTEM (Read values on Primary values)

Phase VOLTAGE INJECTION ACTUAL VALUE CURRENT INJECTION ACTUAL VALUE

V Mag V Angle V Mag V Angle I Mag I Angle I Mag I Angle

A 63,5 V 0º 19.048KV 0.0º 1A 0º 0.249KA 359.740º

B 63,5 V -120º 19.012KV 119.454º 1A -120º 0.249KA 119.333º

C 63,5 V -240º 19.007KV 239.264º 1A 120º 0.249KA 238.775º

5
Switchgear Identification: H02+RH02 33KV MBITA LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

51P – PHASE TIME OVERCURRENT-


CURRENT INJECTION SETTING VALUE TESTED VALUE CONCLUSION

I Mag I Angle PKP TIME PKP TIME RESULT DATE


(OK/NOT OK)

A 1.5A 0º 1.06A 1.022ms OK


IEC CURVE A
B 1.5A -120º 1.05A TDM:0.05 1.06A 1.012ms OK 14/3/17
(0.97s)
C 1.5A 120º 1.06A 1.007s OK

CONTACT
OUTPUTS F03, F04, G03 OK 14/3/17
ACTIVATED

LED LED 1 OK 14/3/17

50P – PHASE INSTANTANEOUS OVERCURRENT-


CURRENT INJECTION SETTING VALUE TESTED VALUE CONCLUSION

I Mag I Angle PKP TIME PKP TIME RESULT DATE


(OK/NOT OK)

A 7.1A 0º 7.1A 35.3ms OK

B 7.1A -120º 7A 0s 7.1A 41.0ms OK 14/3/17

C 7.1A 120º 7.1A 36.4ms OK

CONTACT
OUTPUTS F03, F04, G03 OK 14/3/17
ACTIVATED

LED LED 2 OK 14/3/17

6
Switchgear Identification: H02+RH02 33KV MBITA LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.102
Functions Tested: 51P-50P-51G Type : Multifunctional Protection

51G– GROUND TIME OVERCURRENT-


CURRENT INJECTION SETTING VALUE TESTED VALUE CONCLUSION

I Mag I Angle PKP TIME PKP TIME RESULT DATE


(OK/NOT OK)

G 0.19A 0º NO PKP - OK
0.2A 0.3s 14/3/17
G 0.21A 0º 0.21 334.3ms OK

CONTACT
OUTPUTS F03, F04, G03 OK 14/3/17
ACTIVATED

LED LED 2 OK 14/3/17

REMARKS:

GE Digital Energy Customer


INSPECTORS Representative
Representative

NAME EDER LAFRAGUA

SIGNATURE

DATE 23/3/2017

You might also like