You are on page 1of 14

Project Name: Sondu (Therdibuoro)- Homa Bay (Ndhiwa)-

Awendo Electrification Project


Customer: Republic of Kenya- Ministry of Energy
JOB Number:
Commissioning Number:
GE GRID SOLUTIONS Representative
Engineer Name: Organization: GE Grid Solutions

INDEX
1 GENERAL INFORMATION ............................................................................................................................ 3
1.1 RELAY DATA ..................................................................................................................................... 3
1.1.1 T60 PROTECTION RELAY DATA ............................................................................................................................3
2 INSPECTION TESTS T60 ............................................................................................................................... 4
3 INPUTS/OUTPUTS TESTS T60 ...................................................................................................................... 5
3.1 TERMINAL BLOCKS V&I CONNECTIONS ........................................................................................... 5
3.2 SUMMARY OF WIRED CONTACT OUTPUTS ..................................................................................... 5
3.3 SUMMARY OF WIRED CONTACT INPUTS......................................................................................... 6
4 MEASUREMENTS VERYFICATION T60 .......................................................................................................... 7
4.1 UNBALANCED SYSTEM TO IDENTIFY PHASES .................................................................................. 7
4.2 BALANCED I SYSTEM........................................................................................................................ 8
5 PROTECTION FUNCTIONS TESTS T60A ......................................................................................................... 9
5.1 87A-5TA DIFFERENTIAL TRANSF...................................................................................................... 9
5.1.1 DIFFERENCIAL FIRST STEP ...................................................................................................................................9
5.1.2 DIFFERENCIAL SECOND STEP.............................................................................................................................10
5.1.3 DIFFERENCIAL FIRST STEP 2º HARMONIC BLOCK..............................................................................................11
5.1.4 DIFFERENCIAL FIRST STEP 5º HARMONIC BLOCK..............................................................................................11
5.2 RESTRICTED GROUND FAULT ........................................................................................................ 12
6 COMMENTS/OPEN POINTS ....................................................................................................................... 13
7 CONCLUSION............................................................................................................................................ 13

2
Project Name: Sondu (Therdibuoro)- Homa Bay (Ndhiwa)-
Awendo Electrification Project
Customer: Republic of Kenya- Ministry of Energy
JOB Number:
Commissioning Number:
GE GRID SOLUTIONS Representative
Engineer Name: Organization: GE Grid Solutions

1 GENERAL INFORMATION

1.1 RELAY DATA

1.1.1 T60 PROTECTION RELAY DATA

MANUFACTURER GE MULTILIN
RELAY ORDER CODE T60-N03-HKH-F8N-H6P-M6N-P6C-U6D
SERIAL NUMBER ABHC16001537
FIRMWARE REVISION 6.0x
PROTECTION ELEMENTS 87, 64.

3
Project Name: Sondu (Therdibuoro)- Homa Bay (Ndhiwa)-
Awendo Electrification Project
Customer: Republic of Kenya- Ministry of Energy
JOB Number:
Commissioning Number:
GE GRID SOLUTIONS Representative
Engineer Name: Organization: GE Grid Solutions

2 INSPECTION TESTS T60

1. VISUAL INSPECTION
 Ok

2. USB/ETHERNET PORT COMMUNICATION


 OK

3. CONFIGURATION FILE UPLOAD


 OK. NDHIWA_T60_13032017.urs

4. POWER SUPPLY
 106.9Vdc

5. CONTACT INPUTS
 Verified

6. CONTACT OUTPUTS
 Verified

7. LOGIC
 Verified

8. VOLTAGE AND CURRENT INPUTS METERING TESTS


 Verified

9. PROTECTION AND FUNCTIONAL TESTS


 Verified

4
Project Name: Sondu (Therdibuoro)- Homa Bay (Ndhiwa)-
Awendo Electrification Project
Customer: Republic of Kenya- Ministry of Energy
JOB Number:
Commissioning Number:
GE GRID SOLUTIONS Representative
Engineer Name: Organization: GE Grid Solutions

3 INPUTS/OUTPUTS TESTS T60


3.1 TERMINAL BLOCKS V&I CONNECTIONS

HV SIDE CURRENT LV SIDE CURRENT

[F1-F3] [F5-F7]

A A

B B
I-Diff I-Diff
C C

N N

3.2 SUMMARY OF WIRED CONTACT OUTPUTS

Contact ID Description State Terminal/End Tested

H1 Trip A TC1 NO GEN TRIP On (VO1) OK


H2 Trip B TC1 NO GEN TRIP On (VO1) OK
H3 Trip C TC1 NO GEN TRIP On (VO1) OK
H4 Trip A TC2 NO GEN TRIP On (VO1) OK
H5 Trip B TC2 NO GEN TRIP On (VO1) OK
H6 Trip C TC2 NO GEN TRIP On (VO1) OK
M1 TRIP K86 NO GEN TRIP On (VO1) OK
M2 TRIP CBF NO GEN TRIP On (VO1) OK
M3 CBF Init MV NO GEN TRIP On (VO1) OK
M4 LO RESET K86 NO RESET OP OK

5
Project Name: Sondu (Therdibuoro)- Homa Bay (Ndhiwa)-
Awendo Electrification Project
Customer: Republic of Kenya- Ministry of Energy
JOB Number:
Commissioning Number:
GE GRID SOLUTIONS Representative
Engineer Name: Organization: GE Grid Solutions

3.3 SUMMARY OF WIRED CONTACT INPUTS

Contact ID Description Tested

(H7a) -
(H7c) -
(H8a) -
(H8c) -
(M5a) Bucholz Trip OK
(M5c) Oil TempTrip OK
(M6a) WTI HV Trip OK
(M6c) WTI LV Trip OK
(M7a) OLTCRlayTrip OK
(M7c) PresOLTCTrip OK
(M8a) MechTFO Trip OK
(M8c) -
(U1a) DC fail M2 OK
(U1c) BCPU Fail OK
(U2a) -
(U2c) -
(U3a) OL_Xmfr_Min OK
(U3c) OL_Xmfr_Max OK
(U4a) OL_OLTC_Min OK
(U4c) OL_OLTC_Max OK
(U5a) BucholzAlarm OK
(U5c) Oil Temp Ind OK
(U6a) WTI HV Alarm OK
(U6c) WTI LV Alarm OK
(U7a) -
(U7c) -
(U8a) -
(U8c) -

6
Project Name: Sondu (Therdibuoro)- Homa Bay (Ndhiwa)-
Awendo Electrification Project
Customer: Republic of Kenya- Ministry of Energy
JOB Number:
Commissioning Number:
GE GRID SOLUTIONS Representative
Engineer Name: Organization: GE Grid Solutions

4 MEASUREMENTS VERYFICATION T60


4.1 UNBALANCED SYSTEM TO IDENTIFY PHASES

5TA HV SIDE CURRENT


ACTUAL VALUES
[F1-F3]

Phase I Mag I Angle I Mag I Angle

A 1A 0º 149.974A 0.0º

B 2A -120º 299.627A -120.3º

C 3A -240º 449.528A -240.2º

METERING OK

5TA LV SIDE CURRENT


ACTUAL VALUES
[F5-F7]

Phase I Mag I Angle I Mag I Angle

A 1A 0º 499.744A 0.0º

B 2A -120º 998.438A -120.2º

C 3A -240º 1.499KA -240.3º

METERING OK

GROUND CURRENT
ACTUAL VALUES
[F8]

Phase I Mag I Angle I Mag I Angle

A 1A 0º 499.870A 0.1º

METERING OK

7
Project Name: Sondu (Therdibuoro)- Homa Bay (Ndhiwa)-
Awendo Electrification Project
Customer: Republic of Kenya- Ministry of Energy
JOB Number:
Commissioning Number:
GE GRID SOLUTIONS Representative
Engineer Name: Organization: GE Grid Solutions

4.2 BALANCED I SYSTEM

5TA HV SIDE CURRENT


ACTUAL VALUES
[F1-F3]

Phase I Mag I Angle I Mag I Angle

A 1A 0º 149.991A 0.0º

B 2A -120º 149.942A -120.2º

C 3A -240º 149.960A -240.1º

METERING OK

5TA LV SIDE CURRENT


ACTUAL VALUES
[F5-F7]

Phase I Mag I Angle I Mag I Angle

A 1A 0º 499.674A 0.0º

B 2A -120º 499.601A -120.2º

C 3A -240º 499.741A -240.2º

METERING OK

8
Project Name: Sondu (Therdibuoro)- Homa Bay (Ndhiwa)-
Awendo Electrification Project
Customer: Republic of Kenya- Ministry of Energy
JOB Number:
Commissioning Number:
GE GRID SOLUTIONS Representative
Engineer Name: Organization: GE Grid Solutions

5 PROTECTION FUNCTIONS TESTS T60A


5.1 87A-5TA DIFFERENTIAL TRANSF.

5.1.1 DIFFERENCIAL FIRST STEP

The following graph


shows Total
Differential
characteristic.

Phase INJECTION SETTING VALUE TESTED VALUE CONCLUSION

5TA HV SIDE 5TA LV SIDE CURRENT


CURRENT (132kV) (33kV)
[F1-F3] [F5-F7]
I Mag I Angle I Mag I Angle PKP & TIME PKP TIME RESULT DATE

A 0,67 A 150º 0,805 A 0º 0,3pu, slope1=30%,


brkp1=1,5pu,
B 0,67 A 30º 0,805 A -120º brkp2=3pu, NO - OK 15/3/17
slope2=98%, delay
C 0,67 A 270º 0,805 A 120º 0 sec

I Mag I Angle I Mag I Angle PKP & TIME PKP TIME RESULT DATE

A 0A 30º 0,24 A  0º 0,3pu, slope1=30%,


brkp1=1,5pu,
B 0A -90º 0,24 A  -120º brkp2=3pu, 0.25A 36.2ms OK 15/3/17
slope2=98%, delay
C 0A 150º 0,24 A  120º 0 sec

a
I Mag I Angle I Mag I Angle PKP & TIME PKP TIME RESULT DATE
(OK/NOT OK)
A 1A 150º 1A 0º 0,3pu, slope1=30%,
brkp1=1,5pu,
B 1A 30º 1A -120º brkp2=3pu, 0.84A 37.6ms OK 15/3/17
slope2=98%, delay
C 1A 270º 1A 120º 0 sec

CONTACT OUTPUTS
H1, H2, H3, H4, H5, H6, M1, M2, M3 OK 15/3/17
ACTIVATED

LED LED 1 (XFMR PCNT DIFF OP) ON OK 15/3/17

9
Project Name: Sondu (Therdibuoro)- Homa Bay (Ndhiwa)-
Awendo Electrification Project
Customer: Republic of Kenya- Ministry of Energy
JOB Number:
Commissioning Number:
GE GRID SOLUTIONS Representative
Engineer Name: Organization: GE Grid Solutions

5.1.2 DIFFERENCIAL SECOND STEP

5TA HV SIDE CURRENT


(132kV)
[F1-F3]

I Mag I Angle PKP & TIME TEST TIME RESULT DATE


A 6A 0º 8.00 pu
B 6A -120º Instantaneous 8A 51ms OK 15/3/17
C 6A 120º (8A)

CONTACT OUTPUTS
H1, H2, H3, H4, H5, H6, M1, M2, M3 OK 15/3/17
ACTIVATED

LED LED 2 (87I TRIP On (VO2)) ON OK 15/3/17

5TA LV SIDE CURRENT


(33kV)
[F5-F7]

I Mag I Angle PKP & TIME TEST TIME RESULT DATE


A 6A 0º 8.00 pu
B 6A -120º Instantaneous 6.7A 50.3ms OK 15/3/17
C 6A 120º (6.67A)

CONTACT OUTPUTS
H1, H2, H3, H4, H5, H6, M1, M2, M3 OK 15/3/17
ACTIVATED

LED LED 2 (87I TRIP On (VO2)) ON OK 15/3/17

10
Project Name: Sondu (Therdibuoro)- Homa Bay (Ndhiwa)-
Awendo Electrification Project
Customer: Republic of Kenya- Ministry of Energy
JOB Number:
Commissioning Number:
GE GRID SOLUTIONS Representative
Engineer Name: Organization: GE Grid Solutions

5.1.3 DIFFERENCIAL FIRST STEP 2º HARMONIC BLOCK

5TA HV SIDE CURRENT


th
(132kV) Block 2 =20%fo
[F1-F3]

I Mag I Angle Freq. (Hz) Amplitude (A) at 100Hz

A 2A 0º 100 Hz (no trip)

B 2A -120º 100 Hz (no trip)

C 2A 120º 100 Hz (no trip)

5.1.4 DIFFERENCIAL FIRST STEP 5º HARMONIC BLOCK

5TA HV SIDE CURRENT


th
(132kV) Block 5 =10%fo
[F1-F3]

I Mag I Angle Freq. (Hz) Amplitude (A) at 250Hz

A 2A 0º 250 Hz (no trip)

B 2A -120º 250 Hz (no trip)

C 2A 120º 250 Hz (no trip)

11
Project Name: Sondu (Therdibuoro)- Homa Bay (Ndhiwa)-
Awendo Electrification Project
Customer: Republic of Kenya- Ministry of Energy
JOB Number:
Commissioning Number:
GE GRID SOLUTIONS Representative
Engineer Name: Organization: GE Grid Solutions

5.2 RESTRICTED GROUND FAULT

INJECTION
Phase 5TA LV SIDE SETTING VALUE TESTED VALUE CONCLUSION
PH & GROUND CT

I Mag I Angle PKP & TIME PKP TIME RESULT DATE

G 5A 0º
0,08pu, slope=40%
NO PKP - OK 15/3/17
delay 0,02 sec
A, B or C 5A 180º

INJECTION
Phase 5TA LV SIDE GROUND CURRENT SETTING VALUE TESTED VALUE CONCLUSION
Auxiliary CT

I Mag I Angle PKP & TIME PKP TIME RESULT DATE

0,08pu, slope=40%
G 0,07 A  0º 80mA 55ms OK 15/3/17
delay 0,02 sec

CONTACT OUTPUTS
H1, H2, H3, H4, H5, H6, M1, M2, M3 OK 15/3/17
ACTIVATED

LED LED 3 (RESTD GND FT1 OP) ON OK 15/3/17

INJECTION
Phase 5TA LV SIDE PHASE CURRENT SETTING VALUE TESTED VALUE CONCLUSION
PH CT

I Mag I Angle PKP & TIME PKP TIME RESULT DATE

0,08pu, slope=40%
A, B or C 0,08 A  0º 80mA 57ms OK 15/3/17
delay 0,02 sec

CONTACT OUTPUTS
H1, H2, H3, H4, H5, H6, M1, M2, M3 OK 15/3/17
ACTIVATED

LED LED 3 (RESTD GND FT1 OP) ON OK 15/3/17

12
Project Name: Sondu (Therdibuoro)- Homa Bay (Ndhiwa)-
Awendo Electrification Project
Customer: Republic of Kenya- Ministry of Energy
JOB Number:
Commissioning Number:
GE GRID SOLUTIONS Representative
Engineer Name: Organization: GE Grid Solutions

6 COMMENTS/OPEN POINTS

- The customer asked to add 50G protection (pkp: 0.17pu, t=0.9s). It has been enabled and included in
the tripping logic, but it has not been tested. It will have to be tested during the FAT.

7 CONCLUSION

13