You are on page 1of 7

Project Name: Sondu (Therdibuoro)- Homa

Bay (Ndhiwa)- Awendo Electrification Project


Customer: Republic of Kenya- Ministry of
Energy
PO number:

Commissioning Nr: COMS307

Switchgear Identification: E01+RE01 132KV AWENDO LINE


F650 Feeder Protection
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51-50G Type : Multifunctional Protection
Comments:

INSPECTION TEST

1. VISUAL INSPECTION
 Ok

2. USB/ETHERNET PORT COMMUNICATION


 OK

3. CONFIGURATION FILE UPLOAD


 OK. Ndhiwa_BCU_132_RE01.650

4. POWER SUPPLY
 107.2Vdc

5. CONTACT INPUTS
 Verified

6. CONTACT OUTPUTS
 Verified

7. LOGIC
 Verified

8. VOLTAGE AND CURRENT INPUTS METERING TESTS


 Verified

9. PROTECTION AND FUNCTIONAL TESTS


 Verified
Switchgear Identification: E01+RE01 132KV NDHIWA LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51P-50G Type : Multifunctional Protection

SUMMARY OF WIRED CONTACT OUTPUTS


Contact
Description State Tested
ID

F3 OPEN PHASE A TC1 NO

F4 OPEN PHASE B TC1 NO

F5 OPEN PHASE C TC1 NO

F6 BLOCK AR NO

F7 SYNC OK NO

F8 CB MANUAL CLOSE NO

G3 CB CLOSE COMMAND NO

G4 PROT GEN TRIP NO

H3 OPEN DS1 NO

H4 CLOSE DS1 NO

H6 OPEN DS2 NO

H7 CLOSE DS2 NO

J3 OPEN LINE DS NO

J4 CLOSE LINE DS NO

SUMMARY OF WIRED CONTACT INPUTS

2
Switchgear Identification: E01+RE01 132KV NDHIWA LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51P-50G Type : Multifunctional Protection

Contact ID Description Tested Remarks

F_CC1 (F1) CB 3P-Cose Posit

F_CC2 (F2) CB PHA Open

F_CC3 (F3) CB PHB Open

F_CC4 (F4) CB PHC Open

F_CC5 (F5) CB AL SF6 0.51MP

F_CC6 (F6) CB Op Lockout SF

F_CC7 (F7) SPARE

F_CC8 (F8) CB Closing LocDV


F_CC9 (F9)
CB Pole Discrep
F_CC10 (F10)
CB Prot Mot Swi
F_CC11 (F11)
CB Exc Mot run
F_CC12 (F12)
CB Heating fail

F_CC13 (F13) CB in remote

F_CC14 (F14) CB in local

G_CC1 (G1) Line DS Mot trip

G_CC2 (G2) Line DS remote

G_CC3 (G3) Line DS local

G_CC4 (G4) Line DS Closed

G_CC5 (G5) Line DS Open

G_CC6 (G6) ES Open

G_CC7 (G7) ES Closed

G_CC8 (G8) DSES MCB heat FA

G_CC9 (G9) DS1 Mot Prot TRP


G_CC10
DS1 In Remote
(G10)
G_CC11 (G11) DS1 In Local

3
Switchgear Identification: E01+RE01 132KV NDHIWA LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51P-50G Type : Multifunctional Protection

G_CC12
DS1 Closed
(G12)
G_CC13
DS1 Open
(G13)
G_CC14
DS1 MCB Heat FA
(G14)
H_CC1(H01) DS2 Mot Prot TRP

H_CC2 (H02) DS2 In Remote

H_CC3 (H03) DS2 In Local

H_CC4 (H04) DS2 Closed

H_CC5 (H05) DS2 Open

H_CC6 (H06) DS2 MCB Heat FA

H_CC7 (H07) SPARE

H_CC8 (H08) BCPU VT SupplyFA

H_CC9 (H09) Block CB Close

H_CC10 (H10) SPARE

H_CC11 (H11) TC 1 FAIL

H_CC12 (H12) TC 2 FAIL

H_CC13 (H13) MCB DISCN SUP T)

H_CC14 (H14) V METER FAIL

H_CC15 (H15) VT REF SINCRO F

H_CC16 (H16) SPARE

J_CC1 (J01) SYNC Overide OUT

J_CC2 (J02) SYNC Overide IN

J_CC3 (J03) ILOCK Overide SW

4
Switchgear Identification: E01+RE01 132KV NDHIWA LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51P-50G Type : Multifunctional Protection

UNBALANCED SYSTEM TO IDENTIFY PHASES (Read values on Primary values)

VOLTAGE CURRENT
Phase ACTUAL VALUE ACTUAL VALUE
INJECTION INJECTION
V Mag V Angle V Mag V Angle I Mag I Angle I Mag I Angle

A 20 V 0º 24kV 0º 1A 0º 597A 459.7º

B 40 V -120º 47,9 kV 199.8º 2A -120º 1,198kA 119.4º

C 60 V -240º 71.9 kV 239.5º 3A 120º 1,8 kA 239,2º

METERING OK METERING OK
VOLTAGE CURRENT
ACTUAL VALUE ACTUAL VALUE
INJECTION INJECTION (G)
V Mag V Angle I Mag I Angle I Mag I Angle

AUX 63.5V 76,1 kV 1A 600A

METERING OK METERING OK

BALANCED V&I SYSTEM (Read values on Primary values)

VOLTAGE CURRENT
Phase ACTUAL VALUE ACTUAL VALUE
INJECTION INJECTION
V Mag V Angle V Mag V Angle I Mag I Angle I Mag I Angle
76.12
A 63,5 V 0º 0 1A 0º 598 A 359.3 º
Kv
B 63,5 V -120º 76.07 Kv 119.6 1A -120º 598 A 119 º

C 63,5 V -240º 76.08 Kv 239.6 1A 120º 600 A 238,8 º

METERING OK METERING OK

5
Switchgear Identification: E01+RE01 132KV NDHIWA LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51P-50G Type : Multifunctional Protection

51P – PHASE TIME OVERCURRENT-


CURRENT INJECTION SETTING VALUE TESTED VALUE CONCLUSION

I Mag I Angle PKP TIME PKP TIME RESULT DATE


(OK/NOT OK)

A 1.5A 0º 1,56*PKP 5s OK
IEC CURVE A
B 1.92A -120º 0.96A TDM:0.38 2*PKP 3.7s OK 24/03/17
(3.59s)
C 2.88A 120º 3*PKP 2s OK

CONTACT
OUTPUTS G04 OK 24/03/17
ACTIVATED

LED LED 1 OK 24/03/17

51G– GROUND TIME OVERCURRENT-


CURRENT INJECTION SETTING VALUE TESTED VALUE CONCLUSION

I Mag I Angle PKP TIME PKP TIME RESULT DATE


(OK/NOT OK)

G 0.21A 0º NO PKP - OK
0.22A 3s 24/03/17
G 0.23A 0º 0.23 3.007 OK

CONTACT
OUTPUTS G04 OK 24/03/17
ACTIVATED

LED LED 2 OK 24/03/17

6
Switchgear Identification: E01+RE01 132KV NDHIWA LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51P-50G Type : Multifunctional Protection

25 – SYNCHROCHECK-

SYNC SETTING VALUE TESTED VALUE RESULT DATE


(OK/NOT OK)

7V -> No Permission to
OK 24/03
synchronize.
Voltage Difference 6.35V
6V -> Permission to
OK 24/03
synchronize.
21º -> No Permission to
OK 24/03
synchronize.
Phase Angle Difference 20º
19º -> Permission to
OK 24/03
synchronize.

21mHz -> No Permission


OK 24/03
to synchronize.
Frequency Slip 20 mHz
13 mHz -> Permission to
OK 24/03
synchronize.

CONTACT OUTPUTS
F07 OK 24/03
ACTIVATED

REMARKS:

GE Digital Energy Customer


INSPECTORS Representati Representati
ve ve
ALICIA VALERO
NAME
MASA

SIGNATURE

DATE