FIRE CONTROL
INSTRUMENTS
301 2nd Ave. Waltham, MA 02451-1133 USA TEL: (781) 487-0088 FAX: (781) 370-4132
Content
Section 1
Overview ...................................................................................................................................................... 1-1
Section 2
Agency Requirements ............................................................................................................... 2-1
Section 3
Before You Begin Installing ............................................................................................... 3-1
Section 4
Hardware Installation .................................................................................................................. 4-1
9000-0484 i
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
Section 5
System Configuration ................................................................................................................ 5-1
Section 6
System Operation ............................................................................................................................ 6-1
Appendix A
Compatible Devices ..................................................................................................................... A-1
ii 9000-0484
Section 1
Overview
• Auxiliary power output (.5 amp max.) for powering special applications, such as door
holders.
9000-0484 1-1
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
1-2 9000-0484
Section 2
Agency Requirements
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use UL listed smoke detectors and notification appliances compatible with the FC-2224
from those specified in the Appendix to this manual.
3. If you are using the smoke verification feature:
• Do not use smoke detectors with built-in alarm verification.
4. A full system checkout must be performed any time the panel is programmed.
5. UL installations require use of Model 7628 EOL resistor assembly.
9000-0484 2-1
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
2-2 9000-0484
Section 3
Before You Begin Installing
Containing
Main Part Part Number
Part Quantity/Item
1 Cabinet 151-00006
1 Installation/ 9000-0484
Operation Manual
2 #8 Screws
2 #8 Nuts
1 battery Jumper
1 Transformer or a
1 Viewing Bezel
4 End-of-line Resistors
9000-0484 3-1
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
Model
Name Description
Number
FC-2884 Serial Driver Board Used to interface all FC-2224 expansion devices to the FC-
2224 panel. Supports 1 DACT (Model FC-2104) and any
combination of 4 LED Annunciators (Model FC-2866) or I/O
Modules (Model FC-2880).
*FC-2880 Input/Output (I/O) Module Used to drive customized annunciators and interface devices.
*FC-2866 LED Annunciator Remote LED annunciator with Silence and Reset keyswitch
inputs.
3-2 9000-0484
Before You Begin Installing
AC Power FC-2884
Connector Serial
Interface
Connector
On-Board
Piezo Sounder
Backup
Battery
Connector
9000-0484 3-3
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
Circuit Rating
It is important to protect the FC-2224 control panel from water. To prevent water damage, the
following conditions should be AVOIDED when mounting the units:
• Do not mount directly on exterior walls, especially masonry walls (condensation)
• Do not mount directly on exterior walls below grade (condensation)
• Protect from plumbing leaks
• Protect from splash caused by sprinkler system inspection ports
• Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)
3-4 9000-0484
Before You Begin Installing
1. Place the cabinet on the mounting surface, level the cabinet and mark the top two
mounting holes.
2. Screw the top two mount screws about 3/4 of the way into the mounting surface.
3. Hang the control panel cabinet on the top mounting screws through the top mounting
screw keyholes.
12-1/2”
11”
Top Mounting
Screw Keyholes
15”
Bottom
Mounting Holes
4. Insert the bottom two mounting screws into the cabinet’s bottom mounting holes.
5. Tighten all four mounting screws until the cabinet is properly secured.
6. Insert all cabinet components. See Section 3.7.
9000-0484 3-5
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
3.7 Assembly
The components listed in Table 3-1 are all packed within the cabinet and require some
assembly. Follow these steps to assemble the components inside the cabinet:
1. Remove keys from the envelope taped to the top of the cabinet.
2. Unlock the cabinet door.
3. Remove the packing material and the FC-2224 components.
4. Snap the bezel into the opening in the front of the cabinet. See Figure 3-3.
Note: The bezel will fit in only one way.
Side View of
Slotted Stand-Off
Transformer
Installation
Bezel Insertion
CPU Mounting
Screws
Figure 3-3 The FC-2224 Assembly Diagram
5. With the two #8 screws and the two #8 nuts (with built in washers), mount the transformer
in the holes in the upper left hand corner of the cabinet. See Figure 3-3.
Important! The electronic components on the control panel are sensitive to electrostatic discharge
(static electricity). Wear a grounding strap when handling the control board.
6. With the three self-tapping screws mount the control board on the cabinet stand-offs.
Note: See Section 4 for transformer connections and battery connections.
3-6 9000-0484
Before You Begin Installing
Important! Do not run 120 VAC line voltage in fire alarm raceways.
9000-0484 3-7
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
1. For the FC-2224, the worst case current draw is listed for the panel and is recorded in the
table at Line A.
2. Add up the current draw for all smoke detectors and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. Any additional devices should be recorded at Line D.
5. Make sure that the alarm current without the panel (Lines B-D) does not exceed 2.5 A.
The total alarm current (including the panel, Lines A-D) should not exceed 2.75 A.
6. Complete the remaining instructions in Table 3-6 for determining battery size require-
ments.
7 AH 270 mA 110 mA
3-8 9000-0484
Before You Begin Installing
3-10 9000-0484
Section 4
Hardware Installation
4.1 AC Power
At installation, connect the transformer AC inputs to the AC power source as shown in Figure
4-1. It may be necessary for a professional electrician to make this connection.
The AC inputs are rated as 120 VAC, 60 Hz or 230 VAC, 50 Hz. See Table 3-1 for more
information.
Transformer Yellow
9000-0484 4-1
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
4-2 9000-0484
Hardware Installation
9000-0484 4-3
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
4-4 9000-0484
Hardware Installation
9000-0484 4-5
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
FM-998-24
4-6 9000-0484
Hardware Installation
1. Unplug the AC power connector from the FC-2224 control panel. See Figure 4-1.
2. Unplug the battery connector from the FC-2224 control panel. See Figure 4-2.
3. Plug the FC-2884 Serial board onto the FC-2224 control panel by aligning the 4-pin con-
nector and the stand-offs with their respective receptors. See Figure 4-8.
4. Reconnect the AC power connector to the control panel. See Figure 4-1.
5. Reconnect the battery connector to the control panel. See Figure 4-2.
9000-0484 4-7
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
To
FC-2884
FC-2224 Expansion
Terminals
Device Terminal
- -
+ +
D (Data) D (Data)
Circuit Rating
Data 50Ω
+ 50Ω
Alarm: 85 mA
Max. Current:
Standby: 35 mA
1. Unplug the AC power connector from the FC-2224 control panel. See Figure 4-1.
2. Unplug the battery connector from the FC-2224 control panel. See Figure 4-2.
4-8 9000-0484
Hardware Installation
3. Terminate the wiring as shown in Figure 4-9. See also Table 4-2.
FC-2884
FC-2866
Supervised
Power Limited
FC-2866
FC-2884 Terminals
Terminals
D (Data) D (Data)
+ +
- -
9000-0484 4-9
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
Equivalent
Dip Switch Position
Address
1. Make sure that the FC-2866 is properly wired to the control panel. See Figure 4-9.
2. Slide the printed annunciator label into place on the FC-2866. The label fits in between the
LEDs and the clear plastic plate.
3. Place the FC-2866 into the 3-gang electrical switch box. See Figure 4-10.
Slide Printed
Annunciator 3-gang
Label In Electrical Box
Cover Plate
Screw
FC-2866
Cover Plate
4. Place the cover plate over the top of the FC-2866 and align the holes. See Figure 4-10.
5. Insert the four cover plate screws into the four screw holes on the 3-gang electrical switch
box.
6. Screw the four cover plate screws into the cover plate until the cover plate fits firmly
against the FC-2866 and the electrical box. Do not over tighten.
4-10 9000-0484
Hardware Installation
Terminal
Strip 1 Status
LED
Open Collector
Outputs
Terminal
Strip 2
FC-2880 Specifications
Table 4-4: Specifications
Circuit Rating
Data 25Ω
Max. Circuit Resistance: - 25Ω
+ 25Ω
Alarm: 35 mA
Max. Current: Standby: 35 mA
Open Collector: 20 mA each or 680 mA total
Operating Voltage: 24 VDC
Operating Temperature: 32° - 120° F (0° - 49° C)
Form C Relays 2.5 A @ 30 VDC Resistive
Max. Short
Silence/Reset Inputs 2.8 mA
circuit current:
9000-0484 4-11
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
Supervised
Power Limited FC-2880
FC-2884
4-12 9000-0484
Hardware Installation
Pin
Pin Number Output Description
Connector
Pin 1 Zone 1 Alarm/Supervisory Outputs when there is an alarm or supervisory on Zone 1.
Pin 2 Zone 1 Trouble Outputs when a trouble condition exists on Zone 1.
Pin 3 Not Used
Pin 4 Zone 2 Alarm/Supervisory Outputs when there is an alarm or supervisory on Zone 2.
Pin 5 Zone 2 Trouble Outputs when a trouble condition exists on Zone 2.
Pin 6 Not Used
P1
Pin 7 Not Used Not Used
Pin 8 Not Used Not Used
Pin 9 Not Used
Pin 10 Not Used Not Used
Pin 11 Not Used Not Used
Pin 12 Not Used
Pin 1 Not Used Not Used
Pin 2 Not Used Not Used
Pin 3 Not Used
Pin 4 Not Used Not Used
Pin 5 Not Used Not Used
Pin 6 Not Used
Pin 2
Pin 7 Zone 1 & 2 Pre-Alarm Not Used
Pin 8 Not Used Not Used
Pin 9 Not Used Not Used
Pin 10 Unused Not Used.
Pin 11 +24 VDC Positive 24 DC voltage output.
Pin 12 GND Circuit Ground
9000-0484 4-13
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
Pin
Pin Number Output Description
Connector
Pin 1 NAC 1 Trouble Outputs when a trouble condition exists on NAC 1.
Pin 2 NAC 2 Trouble Outputs when a trouble condition exists on NAC 2.
Pin 3 Not Used
Outputs when any type of trouble occurs with the DACT,
Pin 4 DACT Trouble
such as, no line voltage or a communication failure.
Outputs when one of the Serial Devices connected to the
Pin 5 Expander Trouble
control panel is in trouble.
Pin 6 Alarm Silenced Outputs when an alarm has been silenced.
Outputs if the control panel looses AC power or AC
Pin 7 Low AC
Pin 3 power drops below the control panels low AC threshold.
Outputs when the backup battery voltage drops below
Pin 8 Low Battery
20.4 VDC.
Outputs when the control panel detects a ground fault
Pin 9 Ground Fault
condition.
Pin 10 Walk Test Active Outputs when the control panel is in walk test mode.
Outputs correspond to any trouble condition output from
Pin 11 Piezo Output
the control panel.
Outputs if the end-of-line resistor on the Reset or silence
Pin 12 Local Trouble inputs not detected or if a serial communication problem
occurs between this device and the control panel.
Current Limiting
Resistor Must Be
at Least 1 kΩ
To P2, Pin 11 or
+ on Terminal Strip 1
4-14 9000-0484
Hardware Installation
UL Supervised
Listed Power Limited
EOL
4.7 KΩ Model 4.7 KΩ
7628
Supervised
Power Limited Dry Contact outputs
must be connected
to a power limited
source.
Figure 4-14 Wiring Examples for Input Switches and Form C Relays
Note: Reset and Silence switches must be UL Recognized switches. Reset and Silence switches must be in the same
room as the UL Listed Graphic Annunciator.
9000-0484 4-15
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
Circuit
Board
Base
Retaining
Tabs
Base
3. Mount the plastic base in a UL listed enclosure using any of the mounting holes in the
plastic base. See Figure 4-16 for locations of base mounting holes.
Mounting
Mounting Holes
Holes
Mounting
Holes
4. Verify the proper wire termination and then snap the I/O module cover in place.
4-16 9000-0484
Section 5
System Configuration
To configure the FC-2224 system, set the DIP switch that controls the option you want to
select. The following chart shows how to program the DIP switches that control system, zone,
and notification appliance operation. Refer to Figure 3-1 for location of the DIP switches.
Important!
When you change a DIP switch, be sure to power down the panel. DIP switch changes will be
recognized on power up only. Some switches are unused and are not referred to in this chart.
Leave all unused switches in their factory-programmed OFF position.
9000-0484 5-1
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
5-2 9000-0484
Section 6
System Operation
The annunciator on the FC-2224 board is used for all system operation. It contains the
switches for enabling silencing, resetting, and so on. The LEDs that indicate system status are
also located on the annunciator.
9000-0484 6-1
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
6-2 9000-0484
System Operation
Operation Keystrokes
Disable notification appliance circuit. Press the appropriate [NAC DISABLE] key. The NAC circuit will be disabled and
To re-enable the circuit, press [NAC the corresponding TROUBLE LED will Double Flash. This function is not available
DISABLE] again. during an alarm condition.
Disable a zone Press the appropriate [ZONE DISABLE] key. The zone will be disabled and the
To re-enable the circuit, press [ZONE corresponding TROUBLE LED will Double Flash. This function is not available
DISABLE] again. during an alarm or supervisory condition.
Begin Walk Test Press [WALK TEST]. Walk Test LED turns on.
Note: Walk test will not activate if the control panel has a trouble, alarm,
or supervisory condition.
End Walk Test Press [WALK TEST].
(The test ends automatically after 10 NOTE: The Walk Test feature is not operational during an alarm, supervisory or any
minutes of no system activity.) system trouble condition.
Acknowledge condition (alarm, Press [ACK]. The corresponding LED will change from blinking to steady for the
supervisory, trouble) duration of the condition.
Silence Panel Press [SILENCE]. This will silence the on-board PZT and all active NAC circuits
that have been configured as "silenceable".
Perform system reset Press [RESET]. Resets alarms, supervisories, troubles and all LEDs.
Manual Dialer Test. Press the [ACK] and [ SILENCE] buttons at the same time.
Dialer Reset. Press the [RESET] and [WALK TEST] buttons at the same time.
9000-0484 6-3
Model FC-2224 Fire Alarm Control Panel Installation/Operation Manual
6-4 9000-0484
Appendix A
Compatible Devices
This section of the manual lists devices (smoke detectors and notification appliances) that are
compatible with the FC-2224. Contact FCI if you have a question about whether a device not
listed here is compatible.
FC-2224
Identifier 24F
Note: The maximum number of smoke detectors per zone is determined by both the current draw and the imped-
ance of the smoke detector. If too many smoke detectors are used on any zone, false alarms could occur.
Warning! Do not mix different models or manufacturers of smoke detectors on the initiating circuits.
9000-0484 A-1
Model FC-2224 Fire Control Panel Installation/Operation Manual
A-2 9000-0484
Table A-1: Compatible Two-Wire Smoke Detectors
1151 (110LP) A A 20
1400 A N/A 20
1451 (B401B) A A 20
1451DH A A 20
2100AT A N/A 20
2100S A N/A 20
2100TS A N/A 20
System Sensor 2100TR A N/A 20
2151 (B110LP or B110LRP) A A 20
2400 A N/A 20
2400TH A N/A 20
2451 (B401B) A A 20
2451DH (DH 400) A A 20
2451TH (B401B) A A 20
DH100P N/A N/A 30
9000-0484 A-3
Model FC-2224 Fire Control Panel Installation/Operation Manual
A-4 9000-0484
Table A-2: Compatible Notification Appliances
P2475K-FC Horn/Strobe
P24110-FC Horn/Strobe
P24110W-FC Horn/Strobe
P24110K-FC Horn/Strobe
S2415-FC Strobe
S241575-FC Strobe
S241575W-FC Strobe
S241575K-FC Strobe
S2430-FC Strobe
FCI (Cont.) S2430W-FC Strobe
S2430K-FC Strobe
S2475-FC Strobe
S2475W-FC Strobe
S2475K-FC Strobe
S24110-FC Strobe
S24110W-FC Strobe
S24110K-FC Strobe
MDL-FC Sync. Module
MDLW-FC Sync. Module
H12/24 Horn
HC12/24 Horn
P2415 Horn/Strobe
P241575 Horn/Strobe
P2430 Horn/Strobe
P2475 Horn/Strobe
P24110 Horn/Strobe
System Sensor
S2415 Strobe
S241575 Strobe
S2430 Strobe
S2475 Strobe
S24110 Strobe
MDL Sync. Module
MDLW Sync. Module
MIZ-24-R Mini-Horn
Wheelock
MIZ-24-W Mini-Horn
9000-0484 A-5
Model FC-2224 Fire Control Panel Installation/Operation Manual
A-6 9000-0484
FC-2224 Basic Operating Instructions P/N 9000-0488 Ver. 1.0
These instructions must be framed and displayed next to the FC-2224 panel in accordance
with NFPA 72 fire code for Local Fire Alarm System.
LED (Color) Function
AC (green) ON = Good AC
OFF = Low AC trouble condition and it was acknowledged
FLASHING = Unacknowledged AC Low trouble condition
GENERAL TROUBLE ON = System trouble
(yellow) OFF = System OK
FLASHING = At least one serial device is in trouble
DOUBLE FLASHING = Two types of serial devices are in trouble.
WALK TEST (yellow) ON = Walk test is in progress
OFF = Walk test is off.
FLASHING = Walk test is on and at least one zone is not ready
GND FAULT (yellow) ON = Ground fault condition exists and was acknowledged
OFF = No fault
FLASHING = A ground fault condition detected
LOW BATTERY (yellow) ON = Battery low condition that has been acknowledged
OFF = Good battery condition
FLASHING = Battery low condition
ZONE 1 ALARM (red) ON = Zone in alarm which has been acknowledged
and OFF = No Alarm
ZONE 2 FLASHING = Zone in alarm has not yet been acknowledged.
SUPERVISORY ON = Zone has a supervisory condition (self-restoring condition)
(yellow) OFF = No supervisory condition exists.
Cut Along the Dotted Line
Operation Keystrokes
Disable notification appliance circuit. Press the appropriate [NAC DISABLE] key. The NAC circuit will be disabled and the corresponding
To re-enable the circuit, press [NAC TROUBLE LED will Double Flash. This function is not available during an alarm condition.
DISABLE] again.
Disable a zone Press the appropriate [ZONE DISABLE] key. The zone will be disabled and the corresponding TROUBLE
To re-enable the circuit, press [ZONE LED will Double Flash. This function is not available during an alarm or supervisory condition.
DISABLE] again.
Begin Walk Test Press [WALK TEST]. Walk Test LED turns on.
Note: Walk test will not activate if the control panel has a trouble, alarm, or supervisory condition.
End Walk Test Press [WALK TEST].
NOTE: The Walk Test feature is not operational during an alarm, supervisory or any system trouble
condition.The test ends automatically after 10 minutes of no system activity.
Acknowledge condition (alarm, supervisory, Press [ACK]. The corresponding LED will change from blinking to steady for the duration of the condition.
trouble)
Silence Panel Press [SILENCE]. This will silence the on-board PZT and all active NAC circuits that have been configured as
"silenceable".
Perform system reset Press [RESET]. Resets alarms, supervisories, troubles and all LEDs.
Manual Dialer Test. Press the [ACK] and [ SILENCE] buttons at the same time.
Dialer Reset. Press the [RESET] and [WALK TEST] buttons at the same time.
FIRE CONTROL
INSTRUMENTS
151216