You are on page 1of 6

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/280829787

Development of a benchmark for the Interpretation of Transformer


Frequency Response Analysis result

Conference Paper · March 2015


DOI: 10.1109/CCIP.2015.7100714

CITATIONS READS

4 151

2 authors:

Munish Manas Bharat Sharma


Tezpur University Jamia Millia Islamia
2 PUBLICATIONS   10 CITATIONS    28 PUBLICATIONS   61 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

MPPT Tracker View project

All content following this page was uploaded by Bharat Sharma on 10 August 2015.

The user has requested enhancement of the downloaded file.


Development of a benchmark for the Interpretation of Transformer
Frequency Response Analysis results
Munish Manas Zaheeruddin Bharat Bhushan Sharma
Dept. of Electrical Engg. Dept. of Electrical Engg. Dept. of Electrical Engg.
Jamia Millia Islamia, New Delhi, India Jamia Millia Islamia, New Delhi, India Jamia Millia Islamia, India
msd.gkg85@gmail.com zaheeruddin@jmi.ac.in mbbs.research@gmail.com

Abstract— Frequency Response Analysis (FRA) is one of the most displacement or deformation. But, many a times
effective tools for the condition monitoring and mechanical fault irregularities in the transformer design, testing procedure
detection of power transformers. Accurate interpretation of FRA
is critical while evaluating the condition of a transformer. The
set up or noises and disturbances or manufacturing
analysis of FRA responses is done by comparing the measured tolerance may create nominal differences on FRA
parameters with the reference measurements that could be responses [9], [10], thus making the FRA results
previous measurements on the same or identical units. For the interpretations and diagnosis very complex. Thus, even
accurate interpretation of FRA results, it is important to follow after mastering the technique of frequency response
the recommendations given in IEEE guide, IEC standards. This
measurement it is necessary to follow the guidance of
paper presents the basic guidelines for developing a benchmark
for the Interpretation and test procedures of the transformer standards developed for the interpretations of the FRA
Frequency Response Analysis based upon the analysis of test results. In understanding the accurate interpretation
standards, reports, guides and case studies published by IEEE, of comparison between two FRA results we must try to
IEC and CIGRÉ etc. learn the factors governing the shapes and characteristics
of FRA responses.
Keywords — Frequency response analysis, power transformer,
In this paper we would try to analyze different
capacitive inter-winding, inductive inter-winding
standards that are established by IEEE, IEC, CIGRÉ etc.
for the measurement set-up, interpretations and
I. INTRODUCTION parameters identifications for the transformer frequency
response analysis.
A Power transformer holds a high strategical and functional
importance in any modern power system and the combined II. FRA MEASUREMENT SET-UP AND PROCEDURES
fact that its quite expensive makes its condition monitoring and
maintenance a vital issue in healthy operation and maintenance A. FREQUENCY RESPONSE MEASUREMENT FOR
practices of power system. Frequency response Analysis PRIMARY PARAMETERS
(FRA) is one of the most important test measurement that is
performed during periodical maintenance tests or after fault
The frequency response measurement is done by supplying
occurrence [1]. Frequency response Analysis (FRA) is the
a low-voltage signal to a winding terminal with respect to the
measurement of the electrical transfer functions for a wide
tank. The measured voltage at this input terminal is designated
range of frequency for the evaluation of the mechanical
as the reference signal (Vs) and another voltage signal
integrity of the windings, core and clamping structures within
designated as response signal (Vr) is measured at a second
power transformers. FRA is also defined as the process of off-
terminal. In order to match the characteristic impedance of the
line measuring the impedance of the transformer winding as
coaxial connecting cables, Vs and Vr are measured across an
the frequency’s function [2]. The motive behind the
input impedance of 50 ohms. The ratio between the Vr and Vs
development of FRA was the detection of winding
(expressed in dB) is designated as the amplitude of the
displacement and deformation in power transformer [3]-[8].
frequency response. This amplitude of frequency response is
The damages during transportation, online tap-changer fault,
given as a function of frequency in the range of few Hz to a few
seismic occurrence etc. can be assessed by FRA. IEEE, IEC
MHz. The basic principal that the geometry of windings is
and CIGRÉ have studied FRA for defining a benchmark for tightly related to the distributed capacitances and inductances
the interpretation of FRA results. In this method frequency between conductors and layers forms the basis of the sensitivity
response measurements made previously on the same of the measurement for detecting winding displacement
unit or identical ones or different phases of the same because these distributed capacitances and inductances
units are taken as reference and then compared with the characterize most of the series and parallel resonances in the
new measurements. Any significant difference between recorded frequency response [11].
the previous and new FRA measurements would indicate
a mechanical fault in the winding like winding

978-1-4799-7171-8/15/$31.00 ©2015 IEEE


impedance of the test set required for FRA measurements. Test
leads should be verified for the integrity and continuity before
connecting them in the test set up. In situations where
additional winding grounds are used for FRA testing, extreme
care must be taken that the FRA results of such measurements
should not be compared to a reference historical measurements
where additional winding grounds connections were not
incorporated in the test set up. This is done because the FRA
results for both these cases may be quite different owing to the
variations in the grounding configurations. Any analysis or
Figure 1. Primary parameters for the frequency response
interpretation on such a comparison is not valid.
measurement
III RECOMMENDATIONS FOR INTERPRETATIONS
B. FRA TEST PROCEDURE RECOMMENDATIONS
ON FRA RESULTS
IEEE Std C57.149-2012 recommends that the transformer
A. IEC 60076-18 recommendations
configuration should be in close “in service” configuration as
much as possible.
IEC 60076-18:2012 particularize the measurement technique
All the external bushing connections including neutral and measuring equipment to be used while performing a
connections, phase connections, tertiary grounds and stabilizing frequency response measurement either on-site or at the
windings should be disconnected. Considering the fact that the manufacturing place on the transformer which may be new or
extra length of conductor that may be included in the path of in its later stage [12]. The recommendations in this standard
test circuit, may interfere with FRA test response, all the test apply to power transformers, phase shifting transformers and
leads should be connected directly to the bushing terminal. It is reactors. For Power Transformers this standard specifies the
a good practice to exclude any external bus bar connections. connection, configuration of the test set up in which the
It is important to consider that the state of the transformer specified set of measurements is the end to end measurement
under test is a vital parameter to be supervised in order to for each phase of each winding with all other terminals left
formulate a consistent testing method that would give precise floating [13]. The details about the connection for all type of
results. For example, if a field located transformer has been windings are given in this standard. One case of such
tested with small bus bar lengths in the past, then it must be connection specification is that for a star and auto connected
tested in that same way in the subsequent testing events. This is windings with a neutral terminal, the response lead is
because in FRA analysis the comparison of the test connected to the neutral and the reference and source leads are
measurement with the historical reference data is the foundation connected to the line terminal.
of interpretation of results. Interpretation of such FRA test
results should comprise the analysis of the variations caused by B. CIGRÉ Working Group A2.26
the connections of the test leads and their supports.
The instructions for grounding of the test set laid down CIGRÉ in 2008 presented the guidelines on the
by the manufacturer of the test equipment is of utmost
assessment of the mechanical condition of transformer
importance in FRA testing procedure. It is a widely followed
practice to choose the transformer tank grounding point winding by Frequency Response Analysis [14]. Several
potential as the reference potential for FRA test measurements. recommendations for measurement configurations such
The grounding techniques that consist of ground conductor as end-to-end (open and short circuit), capacitive inter-
selection and their routing selection should be documented. winding, inductive inter-winding and end-to-end short-
These techniques should be repeated for the same precise value circuit measurements to ensure good repeatability and
of measurements since they have a considerable amount of precision of the test results were specified. There were
effect on the test results. test sessions for comparing the accuracy of the
For validating the calibration of the test equipment measurement techniques on one transformer in the field
according to the recommended calibration interval level, a and on one in the manufacturing place. Certain case
checking operation on the test equipment relative to the studies and modeling results are presented in this guide
standard test object with a known FRA response should be to present the expected changes in FRA traces for
performed. standard failure modes in order to validate the
The coaxial test leads that should be used for FRA interpretation of differences in responses. This guide
testing are Excitation leads (source leads). Specimen input lead recognizes the approaches that incorporate objective
should be set as reference lead and Specimen Output lead as the
automatic techniques to compare FRA results (pole-zero
measure lead. Even though it is best if all these three leads are
of same length but at least the “ measure ” and “reference” must
modeling, cross correlation coefficients) and make future
be the exact replica of eachother. Also, the characteristic work on such automated interpretation methods [15].
impedance of theses leads should match the characteristic
frequency network impedances of the winding stack is the
C. IEEE Guide for the application and interpretation of FRA dominating parameter. At higher frequency above 500 kHz the
for transformer results are confined to the tap winding impedances or tap leads
and displaced turns.
In addition to the recommendations in the IEC standard there
are other vital suggestions in the IEEE guide for the application • Short Circuit Tests- The influence of the increased
and Interpretation of FRA for Oil immersed transformer such as impedance of the core can be ruled out in this FRA test type
end-to-end short circuit measurements are recommended in where secondary windings are short-circuited. The result of
addition to the end-to-end short circuit measurements. The such a test configuration is seen in an overall increase in FRA
recommendations regarding the tap changer position during the trace’s magnitude in the low frequency region and also by
FRA test measurement are also very significant in this guide. more phase angle.
On one hand where IEC specifies measurements with and
without the tap winding in the circuit IEEE recommends that • Capacitive inter-winding- these tests measures the
any fresh measurement tests should be performed only by network impedance between two windings of different voltage
keeping the Load tap-changer in extreme position [16]. class. This test’s trace shows an varying magnitude as a
function of frequency. As the frequency is increased this test
D. Recommendations for interpretations of FRA as per IEEE leads to the formulation of a series of resonances due to the
Std C57.149-2012 network impedances between the two windings of different
Two basic strategies for the analysis of FRA results are classes.
deployed in this standard that are; identifying a expected trace
characteristics, and the comparison of a trace with reference • Inductive inter-winding- Voltage ratio between two
historical results. winding is measured by this test. The trace in this test shows a
flat magnitude response at lowest frequencies. A series of
• Trace Characteristics Interpretations - Because of low resonances are created at higher frequencies that may be
frequency core effects, main winding effects and short circuit neglected as it falls out of the scope of these test objectives.
responses, the FRA trace has a degree of predictability over
certain ranges of frequency that can be utilized to diagnose E. Trace Comparison per IEEE Std C57.149-2012
fundamental problematic issues in a transformer. Also, owing
to the relationship between different phases and the core, This is the fundamental method for FRA tests
different configurations of windings show different patterns on Interpretation in which the new measurements are compared to
FRA testing. Thus, physical deformations identification can be the baselines and historical data, identical unit tests or tests
brought down to certain specific transformer sections by between different phases of the same unit. Certain tools and
understanding the relationship between frequency range and algorithms that are available for such comparisons, analysis and
transformer configuration. Interpretations of FRA tests results are as follows

The different types of measurements produce different


wave shapes of characteristic trace. Specific characteristics of
the trace points to certain important insulation degradation and
winding deformation as compared to other types of mechanical
faults. One such indicator is the appearance of the resonance
peak or peaks in the magnitude trace or the loss of such
resonance peaks. On the other hand the increment in the
magnitude of the trace as compared to previous reference trace,
at higher frequencies, is an indication of looseness of winding
structure.

• Effect of type of FRA tests on trace characteristics

Open-circuit tests (OC), short circuit (SC) tests,


capacitive inter-winding, Inductive inter-winding produce Figure 2. FRA trace for HV winding at three different times
different trace characteristics which can be interpreted in
respective specified ways. • Plot Inspection – The FRA transfer function is plotted
and the plot in decibels versus logarithmic frequency known as
• Open circuit Tests- In the low frequency region the Bode plot is displayed and analyzed by skilled professionals.
High-voltage windings display the most recognizable pattern. This type of Bode plot leads to the easier inspection of
At 20 Hz and 5kHz Wye connected windings often show a resonances due to the simplification of the display of
single resonance or two tightly placed null resonance. At mid exponentially changing impedances. The success of this type of
inspection depends upon the selective analysis of the trace E [(X- Xavg) (Y- Yavg )] is the mean of the covariance of the
resonances and magnitude/phase angle deviations. Figure 2. X and Y variables.
Shows the FRA trace of a 10 KVA power transformer when the X is trace X and its measured values
test was performed for a same fault on the HV winding at three Xavg is the mean of the X trace measured values
different times. The resonance peaks observed at the Y is trace Y and its measured values
frequencies of 10, 100 and 1000 MHz can be analysed and Yavg is the mean of the Y trace measured values
interpreted for the fault recognition in the transformer windings. is the correlation constant which is greater than or equal to
An approximation of the three traces is shown in Figure 3., 1 and less than or equal to 1
which could be used as a reference for trace comparison for x, y are the standard deviation of trace x measured values
future tests. and the standard deviation of trace y measured values
respectively.
At last, the correlation constant is computed by dividing the
covariance of the two traces analyzed by the product of the
standard deviation of each trace as given in equation 3. This
step normalizes the covariance for each trace.

• Baseline data- By recording a FRA response for a


commissioning test conducted on the transformer unit when it
is manufactured and filled with oil in the factory, the baseline
FRA measurement can be formulated. This baseline
measurement can also be formulated by routine test for in-
service transformers but this baseline data should have a high
reproducibility. Now the response recorded before and after
the transformer relocation should coincide. If residual
Figure 3. Approximate FRA trace for HV winding magnetism is present in the transformer then at lower
frequency the trace could be a little offset, thus this response
comparison can be neglected. At higher frequencies if the
• Difference plotting- This method considers two traces
temperature difference between two tests is large then it can
for comparative analysis and subtracts one from the other
cause some discrepancies in the FRA response comparison.
leading to a difference trace. Now this difference trace may
exhibit traces areas magnitude that deviates from zero
• Similar Units- The FRA response of two
indicating an abnormal phenomenon that leads to specific
transformer units manufactured by the same manufacturing
analysis for the suspected frequency areas.
factory of same brand, may differ if the two units are
purchased at two different timings at a gap of a year or so
• Correlation coefficients- This method also known as during which the manufacturing utility might have
Pearson’s Product Moment Correlation indicates the similarity
incorporated slight modifications in the design of the
between two traces. This type of correlation takes the value
transformer. The best way is to plot the FRA response of more
between 1 and -1 and shows if the range of number from the
than one identical units (say for example four single phase
two traces is random or similar. The more the correlation is
transformer) on the same graph and analyze the results. All
near to 1 the more is the similarity between the two traces. If tests on identical units must be performed with same
the correlation takes the value of -1 it shows inverse relation positioning of the tap changers.
between the two traces and zero value indicates complete
randomness. Correlation coefficients are computed by
• Phase- In phase comparison using FRA the
calculating the Covariance of the two traces. Covariance of the
tests should be performed at a very young age of the
two traces to be analyzed is mathematically calculated by FRA
transformer unit in order to set the benchmark measurement
softwares for acting as an input to the inbuilt algorithm for
response for reference. Owing to different flux paths related
analyzing and interpreting FRA response. Covariance of the
with each phase, the FRA response of the central phase differ a
two traces is expressed is given by equation 1 and 2 [16].
lot with respect to other two phases where as the FRA response
of the outer two phases might be similar. The core affects the
Cov (X,Y)= xy (1)
FRA response at lower frequency but at higher frequencies the
core effects are negligible. Since, in different connection
xy = E [(X- Xavg) (Y- Yavg )] (2) schemes, all the three winding phase of the transformer are at
different distances from the neutral (for example in Wye
= xy / x y 1 x y (3) windings connection) LTC Thus, since spacing of the windings
differ so as the test leads length which in turn affects the
Where transfer function of each winding measurement. Thus the
xy is the covariance of the x and y measured values. overall phase response of FRA tests depends upon the physical
size and configuration of the transformers components Inst. Elect. Eng. Colloq. Condition Monitoring of Electrical
associated with the test set up. One of the interesting fact to be Machines, London, U.K., Jan. 30, 1995.
considered is that if there is no identical units for FRA [6] M. Florkowski and J. Furgal, “Detection of transformer winding
response comparison and also there is no baseline reference de- formations based on the transfer function—Measurements and
simula- tions,” Meas. Sci. Technol., vol. 14, pp. 1986–1992, Sep.
response data available then an comparison between FRA 2003.
responses of different phases of same transformer unit can [7] E. Rahimpour, J. Christian, K. Feser, and H. Mohseni, “Transfer
serve the purpose of interpretation and diagnosis. func- tion method to diagnose axial displacement and radial
deformation of transformer windings,” IEEE Trans. Power Del., vol.
18, no. 2, pp. 493–505, Apr. 2003.
IV. CONCLUSION [8] K. G. N. B. Abeywickrama, Y. V. Serdyuk, and S. M. Gubanski,
“Ex- ploring possibilities for characterization of power transformer
The above discussed standards and recommendations published insula- tion by frequency response analysis (FRA),” IEEE Trans.
Power Del., vol. 21, no. 3, pp. 1375–1382, Jul. 2006.
by different international working agencies in their guides
[9] S. A. Ryder, “Diagnosing transformer faults using frequency
provides a benchmark for all the engineers involved in the response analysis,” IEEE Elect. Insul. Mag., vol. 19, no. 2, pp. 16–22,
interpretation of the Frequency Response Analysis for power Apr. 2003.
transformers. Following the these recommendation in the FRA [10] J. Christian and K. Feser, “Procedures for detecting winding
test procedures and thereafter in analysis and interpretations of displace- ments in power transformers by the transfer function
FRA responses will lead to more accurate diagnosis of the method,” IEEE Trans. Power Del., vol. 19, no. 1, pp. 214–220, Jan.
mechanical faults associated with transformer components like 2004.
winding or core etc. in case of component faults or short circuit [11] Picher, P.; Rajotte, C.; Tardif, C., "Experience with frequency
incidence. Thus, more precise preventive or corrective response analysis (FRA) for the mechanical condition assessment of
transformer windings," Electrical Insulation Conference (EIC), 2013
measures can be taken in time to save transformer that acts as
IEEE , vol., no., pp.220,224, 2-5 June 2013
the backbone of power transmission infrastructure.
[12] Available at:
V. REFERENCES http://webstore.iec.ch/webstore/webstore.nsf/artnum/046626!opendoc
ument
[1] Zhongdong Wang; Jie Li; Sofian, D.M., "Interpretation of [13] IEC 60076-18 Ed.1: Power transformers – Part 18,
Transformer FRA Responses— Part I: Influence of Winding “Measurement of frequency response”, 2012.
Structure," Power Delivery, IEEE Transactions on, vol.24, no.2, [14] CIGRÉ WG A2.26, “Mechanical Condition Assessment of
pp.703, 710, April 2009. Transformer Windings using Frequency Response Analysis (FRA)”,
[2] Available at: Brochure # 342 & Electra no. 237 and no. 228, April 2008.
www05.abb.com/global/.../1zba004509-001_advanceddiagnostics.pdf
[3] S. A. Ryder, “Diagnosing transformer faults using frequency [15] Available at:
response analysis,” IEEE Elect. Insul. Mag., vol. 19, no. 2, pp. 16–22, http://www.scribd.com/doc/207245891/CiGRE-342-2008
Apr. 2003. [16] IEEE Std C57.149-2012, “IEEE Guide for the Application and
[4] J. Christian and K. Feser, “Procedures for detecting winding Interpretation of Frequency Response Analysis for Oil-Immersed
displace- ments in power transformers by the transfer function Transformers,” December 2012.
method,” IEEE Trans. Power Del., vol. 19, no. 1, pp. 214–220, Jan.
2004.
[5] N. Al-Khayat, L. Haydock, and G. McDowell, “Swept frequency
response tests for condition monitoring of power transformers,” in

View publication stats

You might also like