TE Series of Temperature Controller

1 、P a n e l
PV PV
PV SV
PV SV
AL OUT AT
SV
SV
AL OUT AT
AL OUT AT


AL OUT AT SET

SET

△ AT AT SET △ △ AT

△ AT
SET

48 × 48 72 × 72 48 × 96 96 × 96

NO Panel Words Specifications


1 PV ℃
Displaying measuring value or Parameter code. Range: -199-999℃
2 SV Displaying setting value or Parameter setting
3 AL Indicate lamp for alarm: ON/OFF
4 OUT Indicate lamp for output: ON/OFF
5 AT(LRD) Indicate lamp for Auto-turn: ON: Auto-turn OFF: No Auto-turn
6 SET Select/confirm key
Decrease key

7
8 ▲ Increase key
9 SET+▲ Shift key
10 AT(key) Auto-turn key

Applications:
The unit is a temperature controller that with digital displaying, alarm, adjust functions. PID relay control
output, SSR output, SCR output, PWM control output make it can be widely applied to the temperature
control systems in all the industries.
2 、F e a t u r e s
2 . 1 Input signals: : Thermocouple T/C: :K ( 0 ~ 9 9 9 ℃ )、 E( ( 0 ~ 9 9 9 ℃ )、 J(
( 0 ~ 9 9 9 ℃ )、
T ( 0 ~ 4 0 0 ℃ );
Thermo resistance RTD: :Pt100( (-199
-199~ ~800
800℃℃) 、Cu100( (-50
-50~~150
150℃℃)
Select by software. Range:::-199 ℃~
-199℃~
℃~999999℃。( Cu50 input must be menlioned when order)
999℃ )
2 . 2 Control output: : R :RELAY; ;S :SSR; ;K :SCR; ;P :proportional control out put
(PWM). ). Change different output only need to change output mode.
: One relay high value alarm output. Capacity 250VAC/3A
2 . 3 Auxiliary control output:
or 30VDC/ 3A
2 . 4 Sampling rate: ≤0.5S
2 . 5 Accuracy:± ± 0.5%FS
2 . 6 Power:220V/110VAC ± 15%, ~60HZ,Comsumption < 5VA
,50~

3 、Ordering Code
TE□□—□□□□ 10:1 lop input R,J,K,Pt100,Cu100
Alarm Output :1:1alarm
Control output: R:RELAY output
S:SSR output
K:SCR output
P:PWM output
Default:Auto PID controller
Power Supply:Default: 110V/220VAC F:24V.DC
Size4:48W××48H 6:48W× ×96H 7:72W× ×72H 7:96W×
×96H
TE Series of economical temperature controller KK051B-1
Mode High Alarm High Alarm
TE □ -RB10(TE □ -R10) YES Relay
TE □ -SB10(TE □ -S10) YES SSR control output
TE □ -KB10(TE □ -K10) YES SCR control output
TE □ -PB10(TE □ -P10) YES PWM proportional control output
4 、Figure and Dimensions
★Mode ★Size
A


↑ ↑
↑ + + ↑B ↑
F

D ↑
+ +



E G H

C
Size A B C D E F G H
Mode
TE4 44+0.5 44+0.5 30 25 48 72 5 102
TE6 44+0.5 91+0.5 25 30 48 96 12 100
TE7 67.5+0.8 67.5+0.8 30 14 72 72 12 100

★Terminal Connections
→ 10 20

←1
110V
6 →9

←TC- 19
220V
→ 6
~ 220V/110V Rt → 8 18
7←+
←2 7 7 17
6 ← 16 +
16
3 8 Rt
TC
15 -
AL
PWM/SSR

5 15
+←3
RELAY

SSR/PWM

G +4 4 14
-← 4

4
RELAY
SCR

4 9 ▲

G AL 2 →
3 3 13
▲ 3 T -
▲ 2 12
5 5 10
T 1 11

TE4 TE6
- G
7 ← 7 19 19 →
-

RELAY

TC Rt ▲ SCR 18
6 6 18 →
SSR/PWM
+ 17
5 17 17 +
T
4 16
AL
3 15
2 14 ←~220V/110V
1 13 ←
TE7
If these connections changed, the user will not be informed.You can refer the connection on the label.

5 、Key operation:
、Press SET key for 3 seconds, enter the PID parameter adjust menu.
5.1、
、Press SET key to select the parameter you want to modify, then pressSET+△,
5.2、 △,key at the same time,
LED flashes. Hold△ SET press△△key again and shift the figure you want to modify,
,Then release SET
key and press△ △/ key you can increase/de crease the value.Press SET key to confirm at last.
、The unit will go back to measuring estate without key operation for 25 seconds. Or SET key for 3
5.3、
seconds, it also go back to the measuring estate.

KK051B-2
6 、SV setting and Auto-turn operation
SV setting:In the measuring estate,the SV can be set as you want as the process of 5.2。。
Auto-tune operation:When PID not work (P≠ ≠0), press AT key for 3 seconds,When PID not work
(P≠≠0), press AT key for 3 secondsdon’t modify the parameter at this moment. The AT lamp
will off when the auto-turn finished. The unit will refresh PID value and go to the adjust estate.
Press AT key for 3 seconds, AT lamp off, the unit also can go to the adjust estate during the
course of auto-turn. If necessary, the user can modify the PID parameter by themselves to
get better result.
(℃)or ( F)
The unit can be select( F)to display temperature.

7 、Operation Process
FDFD PID parameter setting mode

Power on
↓ 0 % ~9 9 9 % (P=0 is on/off control )
Proportional band(
Self-Test All lamp on ↓SET
Integral time

0 ~9 9 9 I=0 cancel integral function
Display the input signal ↓SET

Derivative time,
↓ 0 ~9 9 9 D=0 cancel differential function
×××× PV ↓SET
Enter working estate
×××× SV P=0 HY is on/off control,
↓SET> > 3S 0 . 0 ~9 9 9 ≠0, this parameter no function.
P≠
Enter PID param- ↓SET
eter setting mode Output mode, 1=SSR/SCR, 4-250=relay.
0 ~2 5 0 In case PWM output, CT is the cycle of pulse wide.
↓SET
High Alarm value.
- 1 9 9 ~9 9 9 Hysteresis set as 1 and it can not be modified
↓SET
Parameter adjust value,It′s for compensation
of sensor deviation.For example,Set PS=10.0,
- 5 0 . 0 ~5 0 . 0
when sensor input100,The PV display 110.
↓SET
Input signals selection

means K 、E 、J 、T 、Pt100 、Cu100

8 、Application examples
1 、Relay control (TE7)
7 Pt
19
6 OUT 18
5 17
4 16 AL1
3 15
2 14 ←
~2 2 0 V
1 13 ←
R
J
C

J-1 FUSE
J-2

Note:The use life of the relay and the instrument will be,much more longer if you use AC contactor
to control the heater.
Reference value:R:100 Ω /1W,C:103P,>275V.
KK051B-3
、Heating control
2、

7 - 19
TC -
6 18

+
SSR/PWM
5 17
4 16
+
3 15
2 14 ←
~ 220V
1 13 ←

S
- +
~SSR +
~ -

3 、SCR control connection

7 G 19
Pt ▲
6 SCR ▲ 18
T
5 17
4 16
3 15
2 14 ←
~ 220V
1 13 ←

SCR FUSE
G

9 、Malfunction information indicate :


Information Specifications Eliminate method
No sensor connected or input signal lower than low SV Check sensor connection or modify low SV

No sensor connected or input signal higher than high SV Check sensor connection or modify high SV

TC compensation off or overload Check if connection of compensation diode


is correct

KK051B-4