You are on page 1of 4

Optimal Overcurrent COOPER POWER

Transformer Protection SERIES

Defend the backbone of your


distribution system
Only Eaton’s Cooper Defend the backbone of your Optimal transformer can be quickly and economically
distribution system from low- protection replaced or reset by field
Power™ series fuses can and high-current faults with the technicians from outside the
With proper fuse coordination,
provide a comprehensive, widest offering of coordinated
this two-part, primary-with-
tank. No tank dismantling is
primary and backup protection necessary.
cost-effective, and easy- devices in the industry.
backup package provides optimal
transformer protection with • Bay-O-Net (BON) fuses
to-restore transformer Proper selection and application easy and efficient serviceability, • MagneX™ interrupter
overcurrent protection of fuses in single- and and greater flexibility than a full-
three-phase, pad-mounted range, under-oil fuse: • The backup under-oil, current-
package. The package transformers is essential to limiting fuses guard against
• Low-current protection devices
consists of transformer provide a reliable system and
guard against damaging
primary/high-fault current –
minimize the harmful effects of which can cause catastrophic
low-current protection overcurrents. There are many
overloads and secondary faults
transformer failure, and
– which can cause premature
devices and current- options available to provide
transformer failure. In the
protect apparatus downline
overcurrent protection to
limiting fuses through 38 distribution class transformers.
event of a secondary fault, the • Energy Limiting Submersible
low-current protection devices Partial-range (ELSP) fuses
kV—plus the tool to easily The most widely accepted
option is the Eaton’s Cooper
coordinate the devices. Power™ series two-part method
which combines the use of a
More than 50 years of primary low-current protection
experience designing device with a partial-range,
backup current-limiting fuse.
and manufacturing
transformers and fuses
assures you of best-in-
class products and the
expertise for optimal
overcurrent coordination.

The Bay-O-Net and ELSP backup current-limiting fuses work together, now
up to 38 kV, for optimal protection of a three-phase transformers.
Bay-O-Net (BON) holder and replaceable fuse-link
• Widest breadth of fuse-link ratings • BON holder and replaceable
available fuse-link
• Highest rated fuse-links in the • Current-sensing link – senses
industry, up to 38 kV secondary faults
• Provides economical solutions • Dual-sensing link – secondary
for a wide range of applications fault and temperature protection
• Quick and easy fuse-link • Dual-element link – enhanced
replacement in the field device coordination options
Reduced downtime and labor High-amp link* – senses high oil
Low-Current Protection Devices

• •
costs lessen customer impact temperature due to overloads
• Flapper™ valve on sidewall • 38 kV Link - senses secondary
mounted BON fuse holder faults
• Minimizes oil leakage and area
contamination

MagneX interrupter*
• Quick and easy field-resettable • Efficient, economical operation
overcurrent protection • Virtually eliminates load-losses
• Easily reset by the operating associated with a secondary
handle breaker – up to a 96%
improvement in efficiency
• Quicker fault diagnosis and
service restoration • Environmental advantage
• Doubles as transformer on/off • Transformer tank remains sealed
switch at all times
• Overload sensing device • Eliminates potential of oil
dripping on cable accessories
• Protects transformers from
increased oil temperatures and • Eliminates contamination of the
high-current surrounding environment

ELSP backup current-limiting fuse


High-Current Current Protection

• High-current current-limiting design • Designed for use in series with


• Minimizes the effects of high BON or MagneX low-current
fault current stresses on protection devices
equipment and the distribution • When coordinated properly, the
system ELSP fuse will operate only to
prevent transformer failure from
• Maximum interrupting rating
primary faults
(50,000A rms symmetrical) will
quickly clear the highest fault • Protects equipment down the
currents likely to occur line by stopping the fault at the
affected transformer
• Self contained design does not
emit gas or debris into the trans-
former tank when operating

Protect the backbone of your distribution system


with the widest offering in the industry of
transformer low-current protection devices and
backup current-limiting fuses.
*Eaton’s Cooper Power Systems Division innovation
2 eaton corporation Optimal Overcurrent Transformer Protection
Fuse coordination is made easy with TransFusion™
Coordination Program, a few simple inputs and the TCCs
for your specific application can be printed, or emailed
to yourself or a co-worker.
The free, web-based, easy-to- you can quickly find the right of trying various combinations This program is the perfect
use coordination tool makes Eaton’s Cooper Power series before deciding on the one that tool for utility specification
transformer fuse selection ELSP and MagneX interrupter or best fits your application needs. engineers, transformer
effortless. By simply inputting a BON fuses for your application. A simple click of the print button designers, and transformer
few pieces of data and selecting The TransFusion coordination allows you to print your TCC manufacturers.
the desired level of protection, program provides the flexibility curves and part numbers.

www.coopertransfusion.com
1. Transformer specification:
Specify the values for your
particular application

2. Low current protection


selection criteria:
1 Select your desired level of
4 protection

5 3. Characteristic curves:
View coordination of
2 transformer and protection
devices

4. Device recommendation
with part numbers:
Order Eaton’s Cooper
6 7 Power series devices using
the provided part numbers

5. Email results:
Share your results
with a co-worker for
3 easy collaboration and
coordination

6. Download results:
Save a PDF copy of your
device(s) and curves

7. Transformer overload curve:


View the per-unit load
allowed by selected fuse

When selecting low-current protection devices and backup fuses, proper fuse coordination is critical to
insuring full-range transformer protection. Plotting the characteristics of each protective device using
Time Current Curves (TCCs) is the ideal way to visualize proper coordination. This is best done through
the use of electronic tools such as the TransFusion Coordination Program.

For a more information on fuse coordination, please reference the following documents:
TD132004EN Pad-Mounted Transformer Fusing Philosophies
W240-11018 BON & ELSP Coordination and Transformer Life

eaton corporation Optimal Overcurrent Transformer Protection 3


Optimal overcurrent protection
Proper selection and • Minimize the effects of With a full array of transformer overcurrents. Put our expertise
coordination of protection overcurrents, including protection devices and to work for you by contacting
devices in single- and three- protection from: coordination tools that are Eaton today.
phase transformers is essential • Extended overloads engineered to work together,
to: Eaton makes sourcing, selecting
• Excessive current due to and coordinating your devices
• Provide a reliable system for
secondary faults quick and easy. No other
power customers
manufacturer can match our
• The effects of failures within
• Protect the public or operator experience with protecting
transformer
transformers from harmful
• Protect the value of the
transformer

Bay-O-Net Fuse Links


Current Dual Dual High MagneX ELSP Backup
Sensing Sensing Element Amp 38 kV Interrupter Current-Limiting Fuse
30-250 A
Continuous Ratings 6-140 A 3-140 A 5-65 A 135-185 A 10-65 A 0.5-42 A up to 500A paralleled
Interruption Ratings Up to 3,500 A Up to 3,500 A Up to 3,500 A Up to 3,500 A Up to 1,000 A Up to 2,800 A Up to 50,000 A
(RMS-Symetrical)
Overload Protection X X X X
Secondary Fault Protection X X X X X X
High Fault Current Protection X
High Oil Temperature X X X X
Protection
Field Replaceable X X X X X
Field Resettable X
Emergency Overload Feature X
On/Off Switch X
CA132017EN
Reference Catalog Section CA132009EN CA132010EN CA132011EN CA132007EN CA132006EN CA132002EN
CA132016EN

For Eaton's Cooper Power series


product information,
call 1-877-277-4636 or
visit: www.CooperPower.com
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

Eaton's Cooper Power Systems Division


2300 Badger Drive
Waukesha, WI 53188
United States
CooperPower.com

© 2015 Eaton
All Rights Reserved Eaton, Cooper Power, MagneX, Flapper and Follow us on social media to get the
Printed in USA TransFusion are valuable trademarks of Eaton latest product and support information.
Publication No. PA132008EN in the U.S. and other countries. You are
Supersedes B240-11013 not permitted to use the Eaton trademarks
March 2015 without the prior written consent of Eaton.

You might also like