Instruction manual
Except where specifically stated otherwise, this manual Check burner cartons carefully. The Model 702G/O
must be used only by a qualified service technician. combination gas/oil burner was assembled and tested
at the factory before shipment. If the burner was ordered
In the state of Massachusetts, this product must be with a completed assembled gas train, the train was
installed by a licensed Plumber or Gas Fitter. pressure tested and electrically checked for proper
operation. Where possible, the gas train or components
Failure to comply with the above or other requirements
were shipped in the same carton as the burner. Check
in this manual could result in severe personal injury,
your packing slip for the number of cartons shipped
death or substantial property damage.
from the factory.
USER — Refer only to User care and maintenance
on back page for information regarding operation of
this burner. The burner Instruction Manual is intended
© Copyright 2011 — Carlin Combustion Technology, Inc.
only for your service technician. The burner and heat Carlin Combustion Technology, Inc.
exchanger must be inspected and started at least an- 126 Bailey Road North Haven, CT 06473
nually by your service technician. Ph 203-680-9401 Fx 203-680-9403
Contents
PLEASE read this first..................................................................2
Before installing or
General information......................................................................3 servicing:
Should overheating occur:
1. The Carlin Model 702G/O combination gas/oil burner............4
(1) Shut off the oil and gas supplies to the burner.
(2) DO NOT shut off the control switch to the boiler
2. Prepare site • assemble burner • mount burner..............6
circulator or the burner.
3. Install gas piping....................................................................12 Follow the guidelines below to avoid potential severe
personal injury, death or substantial property dam-
age.
4. Install oil piping......................................................................14
General information
Verify the burner is correct for the appliance being used and for all ap- Oil Input
plicable codes/standards. . ...............................................................High fire: 6.0 to 11.2 GPH
Adjust the nozzle selection/firing rate if necessary due to positive overfire . ................................................................ Low fire: 3.5 to 6.5 GPH
pressure and/or altitudes more than 2,000 feet above sea level. See the Gas Input
NOTICE under the Ratings information at right. Where appliance appli- . ........................................................... High fire: 840 to 1,600 MBH
cation information is available, the recommended firing rate and burner . .............................................................. Low fire: 490 to 940 MBH
information will include appropriate adjustments for positive overfire Fuels
pressure and recommendations for high altitudes. Follow the appliance . .....................................................................No. 1 or No. 2 Fuel oil
manual guidelines when available. . ...................................................................Natural gas or propane
Fuel unit & oil valves:
. ............... Fuel unit, 2-stage, 300 psig (with internal blocking valve)
Damage or shortage claims . .................................................................... (2) Oil solenoid valves
The consignee of the shipment must file damage or shortage claims Gas train: (available in straight or angled configuration)
immediately against the transportation company. See the NOTICE on . ...........................(2) Main gas valves & RV-61 or RV-81 regulator
page 1 for burner carton information. . ........................................... Butterfly gas valve for input regulation
. ............... 1" gas train standard; 1¼", 1½" or 2" gas train available
Electrical
When calling or writing about the Power.............................................................. 120V/60 Hz/1-Phase
burner: Limit circuit input (RM7895C or RM7897C)............... 120 vac/60 hz
Control circuit load (120 vac).............................................. 1.2 amps
Please provide us with the UL serial number and burner model number
Motor.................................... 1/2 hp, 3450 rpm, 48-frame, “N” flange
to assist us in locating information. This information can be helpful when
. ............................. 115 / 208-230 vac/60 hz/1-ph, 8.4 / 3.8-4.2 amps
troubleshooting or obtaining replacement parts.
Oil valve/gas valve power........................................... 120 vac/60 hz
Damper motor (with end switch)..........................Honeywell M436A
Codes and standards Ignition & primary control
. ............................Carlin Model 41000 solid state electronic ignitor
Certification Ignition voltage.............................................................. 14,000 volts
Primary control................................................Honeywell RM7897C
702G/O burners are U.L. listed for the U.S., certified to comply with:
Agencies
• ANSI/UL 296, for use with #1 or #2 heating oil (per standard ASTM D396). . ................................................................................ UL Listed (US)
• UL 795, for use with natural gas or propane.
• Burner labels list compliance, when required, with special local, state Reduce nozzle/firing rate when required — Maximum burner
capacity is reduced when overfire pressure is positive and for
or provincial approvals. altitudes above 2,000 feet. See below, and adjust firing rate/
nozzle selection if necessary.
Install this burner in accordance with all local codes and
authorities having jurisdiction. Regulations of these authori- 702G/O — Maximum firing rate for
ties take precedence over the general instructions provided positive overfire pressure and high altitude
in this manual. Overfire pressure (Inches w.c.) Oil – GPH Gas – MBH
0.00 11.2 1,600
United States installations 0.10 10.9 1,530
Burner/appliance installations in the United States must comply with the 0.20 10.7 1,500
latest editions of: 0.30 10.6 1,480
0.40 10.3 1,440
• Installation of Domestic Gas Conversion Burners, ANSI Z21.8.
0.50 10.2 1,430
• National Fuel Gas Code, ANSI Z223.1/NFPA 54. 0.60 9.9 1,390
• Standard for the Installation of Oil-Burning Equipment, NFPA 31 Altitudes: For altitudes more than 2,000 feet above sea level, reduce the above
capacities an additional 4% per 1,000 feet higher than 2,000 feet
• National Electrical Code, ANSI/NFPA 70. above sea level.
• Firing rate is determined by the oil nozzle. Air flow is matched to the oil
flow for oil firing. Then gas flow is adjusted to match the air flow at low
and high fire rates.
Gas pressure requirements
The 702G/O burner requires 3.4" w.c. minimum pressure at the butterfly
• See the “Starting and operating” section of this manual for the complete valve during high fire. Select a gas train that has a pressure drop no
description of the adjustment process. The following is a brief summary more than the available pressure at the gas train inlet minus the 3.4"
only. needed at the butterfly valve. See page 13 for gas train pressure drop
• High-fire air is set by adjusting the combustion head position (to control information. The burner is equipped with a 1" gas train unless a larger
air flow through and around the retention ring). gas train is ordered.
Example: A boiler has an input rating of 1,300,000 Btuh. Gas pressure
• Low-fire air is then adjusted by fine-tuning the position of the low fire
adjusting screw. available at the gas train entrance is 6.0" w.c. Subtract 3.4” from the
available 6.0" w.c. The gas train pressure drop must be 2.6” or less. A 1"
• Pilot gas flow is set for a smooth light-off. Then gas inputs are adjusted gas train has a pressure drop of 3.3" w.c., and cannot be used. Select a
for good combustion at low and high-fire air settings. 1¼" RV-61 regulator gas train, which has a pressure drop of 0.87" w.c.
–4– Carlin part number MN702GO Rev. 06/23/14
Model 702G/O Advanced gas/oil burners — Instruction manual
Where appliance instructions differ from this manual, follow the appliance instructions.
Vent/chimney sizing
1. Follow all local codes when sizing the vent and chimney.
2. Refer to the appliance manufacturer’s manual, when available, for venting
recommendations.
Prepare vent/chimney
1. Secure all metal vent joints with screws, following the vent manufacturer’s
instructions. Seal all joints in the vent system and chimney. Repair ma-
sonry chimney lining and repair all mortar joints as needed.
2. Where draft fluctuations are likely, install a double-acting barometric draft
regulator in the vent piping. (The damper must be located in the same
space as the appliance.) Install a manual reset spill switch in the top of
the draft regulator outlet. Wire the switch into the appliance limit circuit to
shut off the appliance/burner if sustained downdraft should occur. Refer
to the appliance manufacturer’s instruction manual for recommendations
regarding the need for a barometric draft regulator.
3. Provide support for the vent piping. Do not rest the weight of any of the
vent piping on the appliance flue outlet.
Positive overfire pressure reduces maximum burner capac- NIOSH First aid procedures:
ity. See Page 3 for estimated reduction in burner capacity Eye exposure — irrigate immediately
with pressurized firing and high altitude applications.
Breathing — fresh air.
Failure to comply could result in severe personal injury,
death or substantial property damage.
Prepare burner and components Figure 3 Chamber dimensions & tube configurations
1. When using refractory liners or lightweight chambers, use insulating- 8.70 1218 31 17.5 9.0 18
type refractory rated 2600°F minimum, or as specified by the appliance
9.50 1330 34 18.0 9.0 18
manufacturer.
2. You must install a target wall liner if flame length is close to the length 10.40 1456 38 19.0 9.5 19
of the chamber.
11.20 1568 43 20.0 10.0 20
3. Use a floor liner when possible. The floor liner will improve firing in most
applications. Extend floor liner 3 to 4 inches up the side walls.
Refactory combustion chamber applications
High fire input
4. Target wall liners — Extend target wall liners at least 3 to 4 inches above (all dimensions in inches)
the center of the flame corbel the top 1½ to 2½ inches deep. “L” “L”
Oil–GPH Gas–MBH “W” “C” “D”
W/ target No target
5. Use preformed chamber liners when available. Lining the floor and tar-
get wall water-backed combustion chambers with lightweight insulating 6.00 840 21 25 17.0 8.5 10.5
refractory will accomplish the same.
6.50 910 23 27 17.5 9.0 11.0
6. When converting coal-fired units, install a combustion chamber in the
ashpit area, or fill the ashpit with sand up to 2 inches above the “mud 6.90 966 25 29 18.0 9.0 11.0
ring” of the boiler (firing through the door). Install a lightweight refractory 7.80 1092 28 32 19.0 9.5 11.5
liner on the target wall.
8.70 1218 31 35 19.5 10.0 12.0
Air tube insertion length (UTL)
9.50 1330 34 38 20.0 10.0 12.0
1. Usable air tube length (UTL) is the distance from mounting flange to end
of air tube. Verify that the end of the air tube will be flush with, or no more 10.40 1456 38 42 21.0 10.5 12.5
than ¼ inch short of, the inside of the appliance combustion chamber front 11.20 1568 43 47 22.0 11.0 13.0
wall when the burner is mounted. See Figure 3 for further information.
• Check the air tube length. Verify the usable length of the tube UTL will
be long enough (see “Mount burner in appliance”).
• Visually inspect all burner components and wiring.
• Verify that wiring is intact and leads are securely connected.
• Verify that all burner components are in good condition.
5. Slide the flame scanner sight pipe assembly forward until the 3/8" pipe Install gas train on burner
fits against the retention ring assembly. Then tighten the 1/8" Allen screw
to secure the tube in place. 1. The standard burner gas train is shipped fully assembled, with the piping
disconnected at the gas train unions. See separate instructions if installing
6. Check the electrodes and reposition if necessary. Position the electrodes an optional knocked down gas train. The gas train is available in either
as shown in Figure 5. These settings are critical in ensuring a reliable an angled (standard) or straight (optional) configuration.
ignition.
2. Connect the main and pilot gas trains at the unions (Figure 6).
7. Once the electrodes are set, check all clamps to be sure they are securely
tightened. To avoid damage to gas train components, do not hold compo-
nents with a pipe wrench or overtighten. Use only a crescent
8. Insert the combustion head/nozzle assembly into the burner and secure wrench or other means. Failure to comply could result in severe
in place. See instructions on page 24. personal injury, death or substantial property damage.
3. Connect the flexible conduit, pre-attached to the burner J-box, to the gas
Figure 5 Electrode settings train J-box, and attach the wires to the terminal strip inside the gas train
J-box.
a. Match wire colors of the incoming wires to those pre-wired to the terminal
strip inside the gas train J-box.
b. See the label in the burner junction box or the wiring diagram on page 17.
Gas valve vent opening — The V48 diaphragm gas valve is
NOT fitted with a vent limiting orifice in the vent connection.
If local codes require, install piping from the vent connection
to outside, sized and installed as required by codes. Because
this is a diaphragm-assisted solenoid valve, a small amount of
gas will exit from the vent orifice each time the valve opens.
Connect from the gas supply to the burner gas train inlet using new, clean black iron pipe and malleable iron fittings only. Do not use
copper, brass, cast iron or galvanized pipe or fittings.
Provide support for gas piping. Do not rest the weight of the gas piping on burner gas train.
Provide a support for the burner gas train.
Apply pipe dope sparingly at all joints. Use only pipe dope listed for use with propane gas. Do not use pipe sealing tape.
Do not hold the gas valve with pipe wrench. Use crescent wrench or other smooth-jawed device. Do not overtighten.
Failure to comply with above could result in severe personal injury, death or substantial property damage.
Do not expose the gas train to gas pressure in excess of 14 inches water column. Higher pressure could damage the valve seat,
resulting in potentially hazardous condition. When pressure testing piping at higher pressures, disconnect burner from gas line before
testing.
If the gas supply pressure can exceed 14 inches water column at any time, you must install a lockup type gas pressure regulator in
the gas supply piping, ahead of the main manual gas valve installed at the burner.
Check pilot gas line orifice nipple 5 Sediment leg 9 Gas train wire junction box
Check the label on the pilot line gas orifice nipple (item 1,
page 29). The label on the orifice nipple must agree with the
gas used (natural or propane gas). If the nipple is not correct
for the gas being used, obtain the correct orifice nipple and
replace. Make sure the nipple is installed in the correct direc-
tion, as shown by the arrow on the label.
Table 3 Capacities of black iron pipe, cubic feet gas/hour Figure 8 Gas train pressure drop
NATURAL GAS
Capacities in Cubic feet per hour
for Schedule 40 metal pipe
Natural gas @ .60 specific gravity, pressure drop 0.3 in. w.c. (note 1)
1¼ 730 500 400 350 305
1½ 1,100 760 610 530 460
2 2,100 1,450 1,150 990 870
2½ 3,300 2,300 1,850 1,600 1,400
Natural gas @ .60 specific gravity, pressure drop 0.5 in. w.c. (note 1)
1¼ 950 660 530 460 400
1½ 1,460 990 810 690 620
2 2,750 1,900 1,520 1,300 1,150
2½ 4,350 3,000 2,400 2,050 1,850
Note 1 For natural gas with specific gravity other than 0.60,
consult National Fuel Gas Code for correction factor.
PROPANE GAS
Capacities in Btuh for
Schedule 40 metal pipe
Propane gas @ 1.5 specific gravity, pressure drop 0.5 in. w.c.
1 787 541 434 372 330
1¼ 1,616 1,111 892 677 543
1½ 2,422 1.664 1,337 1,114 1,014
Regulator spring:
The standard main gas pressure regulator spring (see item 8, Figure 7, page 12)
is plated. The range is from 3.0 to 6.0 inches water column.
The 1" RV61 regulator is available with an optional blue spring, with a range of
5.0 to 12.0 inches water column.
The 1¼" or 1½" RV81 regulator is available with the standard plated spring (3.0
to 6.0 inches water column) or a violet spring, with a range of 4.0 to 12.0 inches
water column.
Fuel unit bypass plug 2. See page 15, Figures 10 and 11, for fuel unit oil flow diagrams.
The fuel unit is shipped with its bypass plug not in- 3. Install the fuel unit bypass plug (two-line systems only).
stalled. Install the bypass plug only when connecting
to a two-line oil system. Operating with the plug in
place on a one-line system (not recommended) will
Fuel supply to multiple burners
damage the fuel unit and could lead to oil leakage • When possible, use separate fuel supply lines for each oil burner. Using
and fire hazard. manifolded oil supply lines can create problems. If the lines are under-
sized, operating vacuum will exceed limits. If the lines are oversized,
If the fuel line or fuel supply is above the burner, never fuel units may have difficulty priming. Because the lines must be sized
exceed 3 PSIG pressure at the fuel unit inlet. Install to handle the capacity of all the burners, the line size will almost always
a suitable OSV to reduce the pressure. Operating be too large when only a single burner is running.
the fuel unit with higher inlet pressure could result
in fuel unit seal damage, oil leakage and potential • If manifolding cannot be avoided, carefully size the lines following the
fire hazard. fuel units manufacturer’s instructions.
Figure 9 Two-line fuel system Figure 10 702G/O fuel unit and flow diagram
(Low fire pressure is 100 PSIG, adjusted by screw
on top of blocking valve; High fire pressure is 300
PSIG, applied when blocking valve is powered)
0 41 100
2 37 100
Figure 11 702G/O burner with NYC-DAR pressure regulation
4 32 100 kit
6 28 100 Obtain pressure regulator kits for New York City Department
of Air Resources from Carlin. Kits must be set for the proper
8 24 96 nozzle pressure.
10 20 80
12 16 64
14 — 48
16 — 32
Wire the burner (RM7895C or RM7897C primary control only) Figure 12 Legend for Figures 13 and 14
1. All wiring must comply with:
• In the U.S. — the National Electrical Code, ANSI Z223.1/NFPA 54.
• In Canada — the Canadian Electrical Code Part 1, CSA standard C22.1.
• All applicable local codes/standards.
2. Connect the burner following Figures 13 and 14 and any special instructions
or wiring diagrams provided with the appliance, burner or other components.
3. The burner requires a 120 VAC/60 hz/single-phase control power supply, with
a 10-amp fuse. The control circuit current draw is approximately 1.2 amps. An
additional power source is required for the motor (120 VAC or 208-220 VAC,
60 hz), with fuse sized accordingly. See Figure 14 for field wiring connections.
4. Read the Honeywell RM7897C instructions for information on setting a room
thermostat, if used.
5. Make sure the burner and appliance are correctly wired and the line switch
is properly fused for the load.
Figure 13 702G/O burner wiring using Honeywell RM7897C primary control (see appliance manual or separate wiring information for
burner equipped with a primary control not covered in this manual); see Figure 12 for a legend to callouts.
Figure 14 702G/O field wiring connections (RM7897C only) Low-High-Low step modulation
1. To take advantage of the energy-saving potential of the Model 702G/O
combination gas/oil burner, it should be wired to operate at low-high-low
cycles. The firing cycle can be much longer using low-high-low firing,
because the burner can cycle to low fire as demand decreases. This
keeps the burner on longer, reducing cyclic losses.
2. The appliance must be equipped with a high fire control. This would be a
make-on-fall control, either temperature (water boiler) or pressure (steam
120 VAC
boiler) activated. Read the appliance manual for the location of the high
Appliance fire control, when used.
high fire
control 3. See Figure 14 to connect the high fire control to the burner firing rate
(remove jumper)
circuit.
4. The burner includes a pre-wired manual high-fire switch. Close this switch
to hold the burner in high fire mode. Open the switch to hold the burner
in low fire mode.
Before firing the burner . . . ❏❏ Burner nozzle verified per appliance manufacturer’s instructions,
Carlin OEM Spec Guide or Table 1, page 4?
Should overheating or an emergency occur, immediately
do the following: ❏❏ Gas and oil supply lines in good condition, sized and designed
correctly?
• Shut off oil supply line and gas supply valves.
• Under some circumstances power should remain ❏❏ Gas and oil line connections and fittings tight?
on for water pumps or blowers. Determine proper ❏❏ Oil tank has oil, and oil line valves are open. Oil supply and return
response before attempting start-up. lines purged?
• If burner fails ignition on several attempts, use burner
❏❏ Burner, appliance and all components inspected and in good
blower to purge appliance chamber before restart.
condition?
Table 5 Initial burner settings (see the pages 20 through 21 for final adjustments using test instruments)
Low-fire input High-fire input Combustion Air damper Butterfly valve
head position low-fire open – low fire
#2 Fuel oil Natural gas #2 Fuel oil Natural gas Dimension “A” opening (factory set)
GPH @ 100 PSIG Inches Inches %
MBH GPH @ 300 PSIG MBH
(Nozzle rating) (approximately) (approximately) (approximately)
3.50 490 6.00 840 0 3/8 50
3.75 525 6.50 910 1/16 3/8 50
4.00 560 6.90 966 1/8 7/16 50
4.50 630 7.80 1092 3/16 7/16 50
5.00 700 8.70 1218 3/8 1/2 50
5.50 770 9.50 1330 5/8 1/2 50
6.00 840 10.40 1456 1-1/8 9/16 50
6.50 910 11.20 1568 1-3/8 9/16 50
4. Slip one end of a 3/16-inch I.D. clear plastic hose over the end of the fuel
unit bleed valve, the other end into a container. Then open bleed valve.
12. Operate burner for 15 minutes before making final adjustments using
Use test instruments test equipment.
1. Use combustion test equipment and an accurate manometer or draft 13. Check for leaks in fuel piping.
gauge to correctly set the burner as required.
Inspect fuel piping system for leaks. Repair any leaks to
2. Overfire pressure must not exceed the appliance manufacturer’s recom-
avoid fire hazard from oil leakage or combustion problems
mendations. The burner must never be fired at an overfire pressure more
than 0.60 inches w.c. due to air infiltration into oil.
3. Adjust the burner fuel and air settings using the following procedures. Do not attempt to confirm combustion simply by inspect-
When adjustment has been completed, the CO2 (or O2) should be within ing the flame visually. You must use combustion test
the ranges in Table 6, at both low fire and high fire.
instruments. Failure to properly verify/adjust combustion
could allow unsafe operation of the burner, resulting in severe
Table 6 Allowable values of CO2 and O2 personal injury, death or substantial property damage.
CO2 O2 15. Insert the combustion equipment test probe into a vent sample opening
Fuel
Minimum Maximum Maximum Minimum to sample flue products.
#2 Fuel Oil 10.5 % 12.5 % 6.6 % 3.9 %
All installations should be checked after one to two weeks of
Natural Gas 8.5 % 10.0 % 6.2 % 3.6 %
operation to ensure the appliance/burner units are operating
Propane 9.5 % 11.2 % 6.0 % 3.5 %
correctly.
– 20 – Carlin part number MN702GO Rev. 06/23/14
Model 702G/O Advanced gas/oil burners — Instruction manual
Where appliance instructions differ from this manual, follow the appliance instructions.
3. See Figure 17, page 19. Adjust the low-fire damper screw until the low-fire
CO2 is between 11% and 12%. Rotate the screw clockwise to increase
The linkage between the damper motor arm and airflow (reduced CO2). Rotate the screw counterclockwise to decrease
the air damper crank is set at the factory, and airflow (increase CO2).
should ONLY need adjustment if the damper motor
or the damper rod is replaced. With the burner in 4. Smoke at low fire must be zero or a trace. Note that too much air can
high-fire position, there should be minimal play in actually increase smoke.
the connecting rod. DO NOT change this linkage
setting.
Step 3 (firing on oil)
Set combustion head (Dimension “A”) 2. If the swing from low fire to high fire is rough (burner bangs or rumbles),
or the fire is very smoky, the damper end switch may be in the wrong
1. Allow the burner to operate approximately 15 minutes to ensure the ap-
position. High-fire oil should pull in as the air damper, NOT THE DAMPER
pliance is heated and combustion is steady.
ARM, is about halfway through its swing.
2. Set the overfire draft to -.02 inches w.c., or as specified in the appliance
manual. 3. For different appliance applications, it is sometimes necessary to have
high-fire oil pressure pull in earlier or later than normal during the swing
3. The combustion head adjusting screw is used to set the spacing between to achieve a smoother, cleaner transition.
the retention ring and throttle ring, regulating how much air passes
around the retention ring. (See Figure 16, page 19.) The larger the value 4. If the swing is rough (flame goes out, bangs or rumbles), there could
of dimension A, the larger the clearance, so the larger the airflow. The be air in the oil, or the nozzle may be defective. Check, and replace the
smaller the value of dimension A, the smaller the airflow. nozzle if necessary. Then retry.
4. Measure the %CO2 in the appliance flue. The value should be approxi- 5. If the fire is too lean, the flame could lift off of the head, causing rumble or
mately 12.5% for high fire oil. If the CO2 is higher than 12.5%, adjust the unsteady combustion. In this case, adjust the damper motor end switch
head adjusting screw (see Figure 16, page 19) to a larger dimension A to energize earlier.
to increase airflow. If the CO2 is less than 12.5%, adjust the screw to a
smaller dimension A to decrease airflow. 6. If the flame is very smoky, then cleans up again, the damper motor end
5. Reset overfire draft to -.02 inches w.c., or as specified in the appliance switch should be set to energize later. To adjust the damper motor end
manual, after any airflow adjustment. switch:
6. Check the smoke value in the appliance flue. It must be zero to a trace. • Remove the damper motor cover.
If not, try increasing airflow (reducing the CO2). If increasing airflow
increases smoke, the combustion is probably on the wrong side of the • This will expose a white plastic gear with notches.
CO2 curve. To correct, increase the airflow until the smoke is eliminated.
• With the burner OFF, use the end of a small-bladed screwdriver inserted
7. When adjustments are completed, the CO2 must be between 12.0% into one of the notches of the white gear to rotate the gear as needed.
and 12.5% at high fire oil, with smoke equal to zero or a trace. Overfire
draft must be -.02 inches w.c., or as specified in the appliance manual. • Turn the gear one notch CLOCKWISE for a LATER PULL-IN.
2. The burner fuel unit blocking valve will be deactivated, and the oil nozzle 8. Turn off the burner when Step 3 is completed before proceeding with
pressure will drop to 100 PSIG. setup for gas combustion, Step 4.
Combustion/ventilation air
❏❏ Verify combustion/ventilation air openings are not, and will not be ob-
structed.
❏❏ Verify air opening louvers are fully open.
❏❏ If louvers are motor-operated, verify motor and end switch are interlocked
with appliance/burner wiring to prevent operation of the burner if the air
6. Raise the damper motor linkage by pulling up on the damper linkage louvers are not fully opened.
locknut and hold in this position.
7. Loosen the two hex head screws on the butterfly valve linkage arm boss. Prepare burner for normal operation
Then lower the damper linkage to the low fire position with the damper
linkage locknut. Release the locknut.
❏❏ Cycle burner off with appliance controls.
8. Mark the position of the butterfly valve linkage arm swivel joint locknut
❏❏ Turn off power to the appliance.
with a pencil or felt-tip pen. Then loosen the swivel joint locknut. ❏❏ Seal the appliance flue test opening.
To adjust the linkage, move the swivel joint locknut in small ❏❏ Verify all components and wires are in place and burner is ready for
increments. A 1/8-inch move can cause CO2 to change as operation.
much as 1.5%. ❏❏ Restore power to the appliance.
• If more gas is needed (to increase CO2), move the swivel joint to the RIGHT.
Train the user
• If less gas is needed (to decrease CO2,), move the swivel joint to the LEFT.
❏❏ Train the user to operate the burner and appliance under normal condi-
9. Tighten the swivel joint in place.
tions.
10. Raise the damper motor linkage by pulling up on the damper linkage
❏❏ Explain the procedure to shut down the burner/appliance when required.
locknut and hold in this position. The butterfly valve shaft slot must
be horizontal. If not, use a common-bit screwdriver to rotate the valve ❏❏ Review the back cover of this manual (and the appliance manual) with
slot to horizontal. the user.
11. Tighten the two hex head screws on the butterfly valve linkage arm boss. ❏❏ Verify the user is aware of all procedures specified in the manuals.
Then lower the damper motor linkage to the low fire position.
❏❏ Verify that the user will not store or use combustible liquids or materials
12. Restart and repeat as necessary until CO2 and CO are acceptable. or contaminants in the vicinity of the burner/appliance.
Carlin part number MN702GO Rev. 06/23/14 – 23 –
Model 702G/O Advanced gas/oil burners — Instruction manual
Where appliance instructions differ from this manual, follow the appliance instructions.
Motor maintenance ❏❏ If the inside surface of the air tube and/or retention ring need to be
cleaned, clean them with a vacuum cleaner with brush attachment while
• Refer to motor manufacturer’s instructions for oiling the motor as needed.
the combustion head assembly is out of the burner.
Checking ignitor ❏❏ Replace the oil nozzle with the correct size specified in this manual or
the OEM guide. See page 10 for the access/replacement procedure.
Never test an ignitor by placing a screwdriver (or other metallic
object) across the high voltage clips. This could cause ignitor ❏❏ Inspect and adjust the ignition electrodes and insulators per instructions
damage or severe personal injury. on page 11 of this manual. Replace if proper spacing cannot be achieved
1. Checking 41000 ignitors only: or if components are damaged.
• Disconnect electrical power to burner. ❏❏ Close the housing cover plate and secure in place.
• Open the burner access cover and remove ignitor wires from the elec- ❏❏ Inspect the fuel line oil filter. Replace if necessary.
trodes. Lightly clamp each ignitor wire to the burner housing, with the
wire ends pointed toward one another, spaced apart by a ½" to ¾" gap. Oil line filters — Use a non-bypassing filter to prevent nozzle
• Carefully energize ignitor and check for spark arcing at the high voltage plugging caused by poor oil filtration. Non-bypassing filters
terminals. If spark jumps the gap, ignitor is good. prevent small foreign particles from bypassing the filter, a
Removing the combustion head assembly common problem with fiber element type filters. Another
problem of some filters is the fiber from filter element tears
1. To check the electrode settings or change the nozzle, you must remove
can break away and plug the nozzle or fuel unit.
the combustion head assembly from the air tube. Follow the steps below,
and reverse the sequence to reassemble. ❏❏ Perform the complete checkout procedures of pages 18 to 23, including
2. Shut off the burner. system inspection and checks.
3. Remove the four gas orifice spuds from the manifold. ❏❏ Inform the user of any problems found.
– 24 – Carlin part number MN702GO Rev. 06/23/14
Model 702G/O Advanced gas/oil burners — Instruction manual
Where appliance instructions differ from this manual, follow the appliance instructions.
Installation/service certificate
Installation data
Burner model Serial number Measured gas firing rate, Oil nozzle size & pattern: Manifold gas pressure, Inlet gas pressure, IWC
Btuh IWC (High fire/Low fire)
Service history
11. Dimensions
2 Air tube
5 Junction box
6 Motor, 48N-frame
2 Air tube
5 Junction box
6 Motor, 48N-frame
702G/O burner