OLFLEX UNITRON TRONIG' | ec FLEXI ACCESSORIES Appendi T35 |LAPPGROUP 35: Fire Performance Test of Fire Resistant Cables mTable 35- Fire Performance Test of Fire Resistant Cables LAPP KABEL FR-6307 cable range have been tested, certified and approved to achieved the fie test ratings: i. BS 6387 Category ©, W, andZ 4H, $$ 209 PLS Class 1A Circuit Integrity Resistance to fire alone: IEC 60331-21, 3 hrs at 750°C. © BS 6387 Cat. C, 3 hrs at 950°C. © 8.299-1, Bhs at 950°C. jet Resistance to fire with water: ‘© BS 6387 Cat, W, 15 mins at 650°C plus 15 mins with water spray. 1©SS 299-1, 18 mins at 650°C plus 15 mins with water spray io Resistance to with mechanical shock: ‘© BS 6367 Cat. Z, 15 mins at 950°C with mechanical shock. ‘©88 299-1, 15 mins at 950°C with mechanical shock The compound used inthis Fire Resistant cables are also In accordance to: Flame Propagation Gas Evolved During Combustion Test on single insulated cable: IEC 60332-1-2, 60 sec / 120 see. Test on bunch cable: ‘® EC 60332-3-22, 7 tres flammable material/meter for 40 mins. {®1EC 60292-3-24, 1.5 lites flammable material/meter for 20 mins Determination of the amount of halogen acid gases: ‘*IEC 60784-1, Halogen cantent af all non-metallic components must be less than 0.5% or § mg/g. Measuring of PH and conductivity: ‘IEC 60754-2, PH value must be less than 4.3, and conducvity at min, 10 usee/m, ‘Smoke Emission Measurement of smoke density of cables: *1EC 6 1034-2, Min, 60% of ligt transmitted fora duration of 40 mins For currant information see wwu.appeabloasialappgroup.com