You are on page 1of 2

Carlin 301GAS Power Gas Burner

1 Carlin 60200 primary 9 Gas pressure regulator


2 Air tube 10 Low gas pressure switch
3 Flange (welded shown) 11 Secondary gas valve
4 Carlin 41800 ignitor 12 Primary gas valve
5 Carlin PSC motor 13 High gas pressure switch
6 Cast aluminum housing 14 Manual gas cocks
7 Air flow switch 15 Orifice nipple
8 Gas connection, 1” NPT

Features Specifications Wiring


Converts from propane to natural gas with Input
just an orifice change — no conversion kit “B” head/tube................401,000 to 700,000 Btuh
needed “C” head/tube............ 550,000 to 1,100,000 Btuh
Fires negative or positive chambers from
401,000 to 1,100,000 Btuh input Fuels
. ...................................... Natural gas or propane gas
Dependable, direct-spark ignition of main
flame — for quick, clean light-offs Maximum supply pressure...................14 inches w.c.
Minimum supply pressure...................5.0 inches w.c.
Time-tested solid state ignition and state-
Manifold pressure...............................3.5 inches w.c.
of-the-art microprocessor primary control
technology Electrical
Diagnostic LED lights annunciate operat- Power........................................ 120 vac/60 hz/1-phase
ing mode: Self-check, Flame-on, Recycle, Limit circuit input...................................120 vac/60 hz
Lockout and Latch-up Motor.................................................... 1/6, 3450 rpm
Factory-packaged with combustion con- Current............................................Approx.  2.5 amps
trol and gas train (assembled, shipped Fuel valve power....................................120 vac/60 hz
loose; also available as knockdown)
Shipped completely pre-wired — for easy Ignition
installation and start-up (knockdown ver- Carlin Model 41800 solid state electronic ignitor
sion also available) Ignition voltage......................................... 9,000 volts
High-efficiency, compact flame pattern
Control
design ensures clean, quiet operation
. ......... Carlin Model 60200FR microprocessor control
Does not require a refractory liner — fires • 4-sec. Trial for ignition (TFI)
with or without a combustion chamber • 1.3-sec. FFRT
Swing-away flanged door design • Pre-purge and post-purge
• Serviceman reset protection
Available with custom welded air tube (Latch-up after three consective lockouts)
flange (and/or optional pedestal) to ac- • Interrupted duty ignition
• Recycle on flame failure
commodate most appliance mounting
requirements Agencies
Includes 1-year warranty . .......................................... UL Listed (United States)

T e c h  s u p p o r t  h o t l i n e    800-989-2275

Carlin Combustion Technology, Inc.


70 Maple Street East Longmeadow, MA 01028 Phone 413–525–7700 Fax 413–525–8306
e-mail us at: info@carlincombustion.com vist our website: www.carlincombustion.com

© Copyright 2008 — Carlin Combustion Technology, Inc. Carlin part number MN301GAS1C Rev. 03/12/08

You might also like