Professional Documents
Culture Documents
Draft Version
All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.
No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.
Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
5 Columns
5.1 General
The calculations in this section illustrate:
5.2 Design of a non-slender column using design charts.
5.3 Design of a perimeter column using iteration of equations to determine reinforcement
requirements.
5.4 Design of an internal column with high axial load.
5.5 Design of a slender column requiring a two hour fire resistance.
In general axial loads and first order moments are assumed to be available. The designs
consider slenderness in order to determine design moments, MEd. The columns are designed
and checked for biaxial bending. The effects of allowing for imperfections are illustrated.
A general method of designing columns is as follows:
Figure 5.1
Forces in edge column
*
Effective lengths are covered in Eurocode 2 Section 5.8.3.2 and Exp (5.15). The effective length of most columns
will be l/2< l0 < l < Figure 5.7f)>. PD 6686[ref to] Cl 2.10 suggests that using the procedure outlined in
Eurocode 2 and <5.8.3.2(3) 5.8.3.2(5)> leads to similar effective lengths to those tabulated in BS 8110[ref
to] and reproduced in Table 5.1 of Concise EC2. For simplicity tabular values are used in this example. However,
experience suggests that these tabulated values are conservative.
a = 1.48 by interpolating between values given for NEd / NRd= 0.1 ,(1.0) and NEd / <5.8.9(4), Notes to
NRd = 0.7, (1.5) Exp. (5.39)>
(MEdz / MRdz)a + (MEdy / MRdy)a = (38.5 / 76.1)1.48 + (32.4 / 76.1)1.48 <Exp. (5.39)>
= 0.36 + 0.28
= 0.64 ∴ OK.
∴ 4 no. H25 OK.
Figure 5.2
Design summary: edge column
5.3.1 Cover
cnom = cmin + Δcdev <Exp. (4.1)>
where
cmin = max[cmin,b, cmin,dur]
where
cmin,b = diameter of bar. Assume 32 mm bars and 8 mm links <4.4.1.2(3)>
= 32 mm to main bars, 32 − 8 = 24 mm to links
= say 25 mm
cmin,dur = minimum cover due to environmental conditions. Assume XC1.
cmin,dur = 15 mm
cmin = 25 mm
Δcdev = 10 mm <4.4.1.3(3)>
Therefore cnom = 25 + 10 = 35 mm to links cnom= 35 mm to links
Check validity of using Method B and Table 5.2b: <BS EN 1992–1–2: 5.3.3>
emax = 0.25b = 75 mm ∴ no good.
Use BS EN 1992–1–2 Annex C Tables C1 – C9. <BS EN 1992–1–2: Annex C>
2 †
Assume min. 4 no. H25 = 1964 mm (≡ 2.2%)
ω = Asfyd / Acfcd = 0.022 × (500 / 1.15) / (0.85 × 30 / 1.5) <BS EN 1992–1–2: 5.3.3(2)>
= 0.56
e ≈ 0.25b and ≤ 100 mm
λ = l0 / i <BS EN 1992–1–2: 5.3.3(2),
where 5.3.3(3)>
l0 = 0.7 × 3.325 = 2327 mm
i = radius of gyration = (I / A)0.5 = h / 120.5
= 300 / 120.5 = 87 mm
λ = 2327 / 87 = 276
n = N0Ed,fi / 0.7(Acfcd + Asfyd) <BS EN 1992–1–2: 5.3.3(2)>
= 0.7 × 1129.6 / 0.7(3002 × 0.85 × 30 / 1.5 + 1964 × 500 / 1.15)
= 1129.6 / 2383.9
= 0.47
∴ interpolate for λ = 30 and n = 0.47 between
Table C5 (ω = 0.5, e = 0.25b) ⇒ bmin = 235, a = 35 mm
†
Using 4 no. H20 gives ω = 0.34, n = 0.54 and bmin = 310 mm ∴ no good!
‡
See Section 5.2.1
§
The effects of imperfections need only be taken into account in the most unfavourable direction.
<5.8.9(2)>
Figure 5.4
Section in axial compression and bending <Fig. 6.1>
Figure 5.5
Design summary: perimeter column
The suspended slabs (including the ground floor slab) are 300 mm thick flat slabs at 4500
mm vertical centres. Between ground and 5th floors the columns at C2 are 500 mm square;
above 5th floor they are 465 mm circular. Assume an internal environment, 1 hour fire
resistance and fck = 50 MPa.
Axial load to Exp. (6.10b) <BS EN 1990 Exp. (6.10) & NA>
NEd = ξγGGk + γQQk1 + ψ0,1γQQki
assuming the variable action of the roof is an independent variable action:
= 0.925 × 1.35 × 5553.6 + 1.5 × (2279.5 − 42.0) × 0.6 + 0.7 × 1.5 × 42.0
= 1.25 × 5553.6 + 1.5 × 2237.5 × 0.6 + 0.7 × 1.5 × 42.0
= 6942.1 + 2013.8+ 44.1
= 9000.0 kN
To Exp. (6.10b), NEd= 9000.0 kN
Modified
diagram
3 2 1 required
Figure 5.7
Subframe on column C2 along grid C
**
According to BS EN 1991–1–1 6.3.1.2(11) the imposed load on the roof is category H and therefore
does not qualify for reduction factor αn.
where
b = breadth d = depth L = length
lc = lower column uc = upper column
23 = beam 23 21 = beam 21
0.54 / 4.5
=
2 × 0.5 / 4.5 + 0.75 × 6.1 × 0.33 / 8.6 + 0.75 × 6.1 × 0.33 / 9.6
4
Modified
diagram
required
B C D
6200
Figure 5.8
Subframe on column C2 along grid 2
††
FEM 23 = Fixed end moment in span 23 at 2
‡‡
Using design actions to Exp (6.10) would have resulted in a requirement for 8500 mm2.
5.4.13 Links
Minimum diameter of links: = φ / 4 = 32 / 4 <9.5.3 & NA>
= 8 mm
Spacing: either
a) 0.6 × 20 × φ = 12 × 32 = 384 mm <9.5.3(3), 9.5.3(4)>
b) 0.6 × h = 0.6 × 500 = 300 mm or
c) 0.6 × 400 = 240 mm
∴ use H8 links at 225 mm cc.
Number of legs:
Bars at 127 mm cc i.e. < 150 mm ∴ no need to restrain bars in face but good <9.5.3(6)
practice suggests alternate bars should be restrained SMDSC 6.4.2>
∴ use single leg on face bars both ways @ 225 mm centres.
§§
Gk = 562.1; Qk = 755.6 × αn = 755.6 × 0.9; NEd = 562.1 × 1.25 + 755.6 × 0.9 × 1.5 = 1722.7 kN
5.5.1 Cover
Nominal cover, cnom
cnom = cmin + Δcdev <Exp. (4.1)>
where
cmin = max[cmin,b, cmin,dur]
where
cmin,b = diameter of bar. Assume 32 mm main bars and 10 mm links <4.4.1.2(3)>
cmin,dur = minimum cover due to environmental conditions. Assuming <BS 8500–1 Table
primarily XC3 / XC4, secondarily XF1, cmin,dur = 25 mm A4>
Δcdev = allowance in design for deviation
= 10 mm
∴ try cnom = 32 + 10 = 42 mm to main bars
or = 25 + 10 = 35 mm to 8 mm links
Try cnom = 35 mm to 8 mm links
c) As additional check, check adequacy of section to Annex B3 and Annex C. <BS EN 1992–1–2:
Using BS EN 1992–1–2 Table C.8 5.3.3(1), Annex C &
NA>
For ω = 1.0, e = 0.25b, R120, λ = 30 <BS EN 1992–1–2:
and interpolating between n = 0.3 and n = 0.5, Annex C(2)>
bmin = 350 mm, amin = 48 mm.
∴ Axis distance = 43 mm + φ / 2 is OK
∴ 4 no. H32 + 4 no. H25 with 35 mm cover to 8 mm links
(a = 55 mm min.) OK.
Figure 5.13
First order moments
***
With reference to Exp. (5.13N), ϕef may be taken as equal to 2.0. However, for the purpose of
illustration the full derivation is shown here.
†††
Imperfections need to be taken into account in one direction only. <5.8.9(2)>
Figure 5.14
Design summary: small perimeter column