QATAR POWER TRANSMISSION


SYSTEM EXPANSION - PHASE VIII
CONTRACT N° GTC / 144D / 2006

SITE NAME
PROJECT DRAWING NUMBER

COMMON TO ALL SUBSTATIONS PH8-4D-10-36-P-113

1 FA 05.06.09 Rev. as per DTA Ref. No: PH8-MML-4D-DTA-09-1420 TUSHAR ANBARASU LAIJU

0 FA 20.05.09 ORIGINAL ISSUE TUSHAR ANBARASU LAIJU


REV STAT DATE MODIFICATION DRAWN CHECK APPRO

T&D
Tour AREVA
1, Place de la coupole
92084 Paris La Défense
France DRAWING
DATE NAME VISA
TITLE
DRAWN 20.05.09 TUSHAR
CHECK. 20.05.09 ANBARASU SCALE
TESTING PROCEDURE+ TEST FORMAT
APPRO. 20.05.09 LAIJU NONE

Manufacturer’s name Responsible Dept PILOT WIRE DIFFERENTIAL RELAY MBCI


EAM
A4 1

SIZE REV
AREVA T&D,Dubai SHEET 1 OF 6 SHEETS
SITE TEST REPORT

QATAR POWER TRANSMISSION SYSTEM EXPENSION PHASE VIII


Contract:
CONTRACT No. GTC/144A/2006
Client: QATAR GENERAL ELECTRICITY & WATER
CORPORATION Consultant:

Site location: Drawing No: PH8-4D-XX-YY-R113


Bay No: Name : Voltage level: kV Page : 1 of 5
Equipment : PILOT WIRE DIFFERENTIAL RELAY Chapter No: Revision : 1

REVISION HISTORY RECORD

Rev. Date Create / Updating

0 20/05/2009 First Issue

1 05/06/2009 Rev. as per DTA Ref. No: PH8-MML-4D-DTA-09-1420


2
Rev. as per DTA Ref. No: PH8-MML-4D-DTA-09-

AREVA T&D MOTT MACDONALD KAHRAMAA


Name Name Name
Signature Signature Signature
Date Date Date
SITE TEST REPORT

QATAR POWER TRANSMISSION SYSTEM EXPENSION PHASE VIII


Contract:
CONTRACT No. GTC/144A/2006
Client: QATAR GENERAL ELECTRICITY & WATER
CORPORATION Consultant:

Site location: Drawing No: PH8-4D-XX-YY-R113


Bay No: Name : Voltage level: kV Page : 2 of 5
Equipment : PILOT WIRE DIFFERENTIAL RELAY Chapter No: Revision : 1

SUMMARY

1. PURPOSE OF TESTS ........................................................................................................................................... 4


2. SCOPE ............................................................................................................................................................... 4
3. TERMINOLOGY................................................................................................................................................. 4
4. COMMISSIONING TEST ................................................................................................................................... 4
5. RECORDING OF INSPECTION AND TEST DATA ........................................................................................... 4

AREVA T&D MOTT MACDONALD KAHRAMAA


Name Name Name
Signature Signature Signature
Date Date Date
SITE TEST REPORT

QATAR POWER TRANSMISSION SYSTEM EXPENSION PHASE VIII


Contract:
CONTRACT No. GTC/144A/2006
Client: QATAR GENERAL ELECTRICITY & WATER
CORPORATION Consultant:

Site location: Drawing No: PH8-4D-XX-YY-R113


Bay No: Name : Voltage level: kV Page : 3 of 5
Equipment : PILOT WIRE DIFFERENTIAL RELAY Chapter No: Revision : 1

1. PURPOSE OF TEST

The tests are intended to check the Pilot Wire Diff.Protection Relay form
secondary injection in relay panel for proper connection, operation
and accuracy.

2. SCOPE

All working sites.

3. TERMINOLOGY

Pilot Wire Diff.Protection Relay : 87P

4. COMMISSIONING

To be performed using the following manufacturer technical


documentation.

a) If require, Enable O/C start by temporary jumper as per the scheme


drawing.
b) Checking of each phase element pickup and operating time by
injecting current in one end.

5. RECORDING OF INSPECTION AND TEST DATA

The results of checks and measurement made during the field tests
shall be recorded on the following test form.

AREVA T&D MOTT MACDONALD KAHRAMAA


Name Name Name
Signature Signature Signature
Date Date Date
SITE TEST REPORT

QATAR POWER TRANSMISSION SYSTEM EXPENSION PHASE VIII


Contract:
CONTRACT No. GTC/144A/2006
Client: QATAR GENERAL ELECTRICITY & WATER
CORPORATION Consultant:

Site location: Drawing No: PH8-4D-XX-YY-R113


Bay No: Name : Voltage level: kV Page : 4 of 5
Equipment : PILOT WIRE DIFFERENTIAL RELAY Chapter No: Revision : 1

MBCI01- PILOT WIRE DIFF. RELAY


1. GENERAL DATA AND INFORMATION: DATE :
Sub. Name Designation
Circuit Ref. Serial No.
Panel No. Model No. MBC101V1AB076113
Make AREVA Aux. Voltage 110 DC
Dwg & Sh No. PH8-4D-45-35-1-013/ SHT NO :22 No. of Contacts
Flag Type
Test Kit Details :
Test Kit Used Equipment S. No:
Calibration Date:
2. MECHANICAL CHECKS AND VISUAL INSPECTION:
Item Description Checked
1 Inspect for any physical damage or defects.
2 Verify connections as per approved drawings.
3 Check that serial no. of relay matching with serial no. of case.
4 Check Relay case Earthing
3. ELECTRICAL TESTS:
3.1 PICK UP TEST:
(Operation Values with Pilots) ---Setting: Rpp = 5x100, Ks = 1, Kt = 20, N = 3.

Operating Calculated Actual Operating Value (A) Time at 5 x


Phase
Value Value (A) Pick-up (A) Reset (A) Pickup in mS

R–N 1x 19% In 0.190


Y–N 1 x 25% In 0.250
B–N 1 x 33% In 0.330
R-Y 1 x 80% In 0.800
Y-B 1 x 100% In 1.000
B-R 1 x 44% In 0.440
R-Y-B 1 x 50% In 0.500
Note: pickup current should be +/- 10% of calculated value.

AREVA T&D MOTT MACDONALD KAHRAMAA


Name Name Name
Signature Signature Signature
Date Date Date
SITE TEST REPORT

QATAR POWER TRANSMISSION SYSTEM EXPENSION PHASE VIII


Contract:
CONTRACT No. GTC/144A/2006
Client: QATAR GENERAL ELECTRICITY & WATER
CORPORATION Consultant:

Site location: Drawing No: PH8-4D-XX-YY-R113


Bay No: Name : Voltage level: kV Page : 5 of 5
Equipment : PILOT WIRE DIFFERENTIAL RELAY Chapter No: Revision : 1

3.2. PICKUP TEST:


(Operation Values With Pilots) ---Setting: Rpp = 5x100, Ks = 1, Kt = 20, N = 6.
Operating Calculated Actual Operating Value (A)
Phase
Value Value (A) Pick-up (A) Reset (A)

R–N 1 x 12% In 0.120

Y–N 1 x 14% In 0.140

B–N 1 x 17% In 0.170


Note: pickup current should be +/- 10% of calculated value.

3.3 TIMIG TEST:

Current = 5 Actual Operating Time at Multiples of KT in milliseconds


Phase
x Pick-up 3 6 14 20 40
Typical 300 90 65 50 30
R
Actual

3.3 Characteristic check

Fault Type Current (Relay1) Current (Relay2) Measured Diff

L1-E

L2-E
L3-E
4. FUNCTIONAL TEST:

Item Description Checked


1 All output contacts operation checked.
2 LED operation checked.

Remarks:

AREVA T&D MOTT MACDONALD KAHRAMAA


Name Name Name
Signature Signature Signature
Date Date Date