BUCO PROJECT
PRIMARY INJECTION TEST -MCCB Substation/Location:

FIELD INSTALLATION TESTS


VISUAL AND MECHANICAL INSPECTION

REMARKS
DESCRIPTION
Yes No
1. Check circuit breaker for proper mounting, conductor size and feeder designation.
2. Inspect case for cracks or other defects.
3. Check tightness of connection with torque wrench in accordance with manufacturer's
recommendations or requirements of P-000.
4. Operate circuit breaker to insure smooth operation.

RECOMMENDED OVER-CURRENT TRIP TEST VALUES


(at 300 Percent of Rated Continuous Current of Breaker)
Rated Voltage, Range of Rated Thermal Minimum Thermal Magnetic trip or MCP
Volts Continuous Current, Tripping Time Maximum Trip (instantaneous)
Amperes Seconds Tripping Time Set and tested at 3X
Seconds
240 15-45 3 50 --
240 50-100 5 70 --
600 15-45 5 80 --
600 50-100 5 150 --
240 110-225 10 200 --
600 110-225 10 200 --
600 250-450 25 250 --
600 500-600 25 250 --
600 700-1200 25 450 --
600 1400-2500 25 600 --
Note: MCP’s only have magnetic pickup. Therefore, only the instantaneous trip is checked. Few circuit
breakers rated less that 600 amps have thermal and magnetic trip units. Usually they contain only thermal trip
units. Therefore, only the long delay or thermal trip time is checked.

COMPLETED BY DATE NAME SIGNATURE


IPMS
NSH‘QC’
Accepted
By

DAELIM
IMT
Page 2 of 3

BUCO PROJECT
PRIMARY INJECTION TEST -MCCB Substation/Location:

MOLDED CASE CIRCUIT BREAKER DESCRIPTION (NAME PLATE DATA)

DESIGNATION
PANEL REFERENCE
BREAKER TYPE
BREAKER MANUFACTURE
VOLTAGE RATING
1sFRAME RATING in AMPS

ELECTRICAL TEST

REMARKS
DESCRIPTION
YES NO
1. Measure contact resistance. For CB having rating 600A and higher value in excess
of 200 micro-ohms or deviation of more than 20 % shall be investigated. For CB less
than 600A value may be higher and deviation should not be greater than 5%
2. To perform the instantaneous test current should be injected to the breaker is 5-16
times of its manufacturer rated value mentioned on the name plate.
3. Perform time-current characteristic test by passing 300% of rated current through
each pole separately. Record result on field data sheet. All trip times shall fall within
the value attached in the above table.
4. Check instantaneous (magnetic) pickup current by run-up of pulse method. Clearing
time and pick-up current level should be with in manufacturer’s published value.
5. Insulation resistance should be determined pole to pole, line to line across the pole,
and pole to ground. The test value @1000 volts DC insulation should not be less
than 50 meg-ohms
6. Check auxiliary device that may be supplied i.e shunt trip, ground fault & under volt.

TEST DATA
TRIP-TIME CHARACTERISTICS

COMPLETED BY DATE NAME SIGNATURE


IPMS
NSH‘QC’
Accepted
By

DAELIM
IMT
Page 3 of 3

BUCO PROJECT
PRIMARY INJECTION TEST -MCCB Substation/Location:
INJECTED
TRIP UNIT SETTING SET VALUE PHASE A PHASE B PHASE C
CURRENT
INSTANTANEOUS TRIP SETTING
TRIP TIME AT 300% CURRENT

OTHER

CONTACT RESISTANCE TEST

BREAKER CLOSE
CB-REF. NO. REMARKS
R-R’ Y-Y’ B-B’

INSULATION RESISTANCE TEST

APPLIED TEST BREAKER IS IN CLOSE POSITION


REMARKS
VOLTAGE R-G Y-G B-G R-Y Y-B B-R

TESTING EQUIPMENT USE:


Equipment name
Manufacturer
Serial no
Calibration date

COMPLETED BY DATE NAME SIGNATURE


IPMS
NSH‘QC’
Accepted
By

DAELIM
IMT