Professional Documents
Culture Documents
目 录
Catalog
一﹒产品特点 Characteristics-------------------------------------------------------- 1
五﹒机组安装Unit Installation-------------------------------------------------------- 5
六﹒调试运行Test----------------------------------------------------------------------- 10
七﹒使用维护保养 Maintenance----------------------------------------------------- 13
壱、 产品特点:(Characteristics)
本公司生产的冷水机组,采用高效率、低噪音、振动小、可靠性高的全封闭涡旋式
或半封闭双螺杆压缩机,两器采用高效换热铜管,配以各种进口元配件及电控元件,电控
部分采用 PLC 西门子控制器。机组制冷效率高、结构紧凑、外型美观、控制精度高,安
装使用与维护简便,运行性能安全可靠。
机组有单回路和双回路两种型式,有多种规格可供选择,广泛应用于宾馆、办公楼、
商场、医院、仓库及现代化工厂等需要空气调节的场所。
Our water-cooled unit adopts hermetic scroll compressor or semi-hermetic double screw
0
水冷冷水机组安装使用说明书
compressor, which is of high efficiency ,low voice, little quiver and high reliability. All the two
type of compressors use heat exchange copper pipe with high efficiency , alongside many
imported or electrical components ,and use Siemens PLC controller as electric control. This type
of unit is of high efficiency in refrigeration, compact structure, elegant exterior and high accuracy
in controlling. It is easy to install and maintain, and operate with safety and reliability.
There are two patterns of units- single loop and double loop - which can be provided
with different standards. The units can be applied in various places such as hotel, office,
marketplace, hospital, warehouse and modernized factory.
1
水冷冷水机组安装使用说明书
干式壳管式蒸发器
6 、防冻开关 7 、冷冻水温控器 8 、壳管式冷凝器 9 、截止阀 10、充注阀
11、干燥过滤器
12、视液镜 13、电磁阀 14、外平衡式热力膨胀阀 15、充注阀 16、低压压力表
17、低压保护器
2
水冷冷水机组安装使用说明书
10、截止阀
11、充注阀 12、干燥过滤器 13、视液镜 14、电磁阀 15、外平衡式热力
膨胀阀
16、充注阀 17、低压压力表 18、低压保护器
1. Semi-hermetic Screw Compressor 2.Cut-off Valve 3. High-pressure Controller
4. High-pressure Gauge 5. Charging Valve 6.Shell and Tube Evaporator
7.Anti-frostbite switch 8.Cold Water Temperature Controller
9. Shell and Tube Type Condenser 10.Cut-off valve 11. Charging Valve 12. Dryer-filter
panel 13. Liquid indicator 14. Solenoid Valve 15. Exterior-balance-type Heat
Expansion Value 16. Charging Valve 17.Low-pressure Gauge 18.Low-pressure
controller
注:以上主要参数可见于铭牌,此列表供参考。无级调载机组参数参考对应或最相近冷量
的普通螺杆式机组。
Note: The data list is for reference, major parameters can be seen on the nameplates in detail. For
parameters of Infinity Capacity Control Unit, refer to common screw series unit corresponding or
has similar refrigeration capacity.
机组出厂前已经过严格的调试,用户只需将机组在专用机房内正确安装好,不要
安装在露天场所,接好冷却水、冷冻水循环管路系统及空气调节端设备,按需求接通
电源便可使用。
Units have been debugged strictly before leaving workshop. Users only need to
correctly install the units in special room (do not install outdoors), connect system of cooling
5
水冷冷水机组安装使用说明书
and cold water circulation, join the air control terminal equipment, and connect the power
source according to the requirements, then the units can be used.
6
水冷冷水机组安装使用说明书
ceiling
7
水冷冷水机组安装使用说明书
型 LS1150
号
A 2200
B 1300
8
水冷冷水机组安装使用说明书
Water Pump.
b. Install manual or automatic air-outlet value on the top of Cold Water System.
c. Install Water-Outlet Value at the bottom of Water System.
d. The whole water piping system should be clean and out of rust, dregs, etc. Otherwise, pipes
would be blocked. After piping and pressure test, discharge water into the inner system and
run for 8hours,then discharge completely. Once more , afflux clean water, connect the
water pump and run the system.
e. Heat insulation treatment should be carried through in all Cold Water Outlet or Inlet pipes.
Before heat insulation ,test gas tightness to make sure no leakage throughout the whole
system.
1.Evaporater 2.Condenser
3.Shockproof connecter
4.Pressure Gauge
5.thermometer
6.Regulation valve
7.Water Current Switch
8.Cold water pump
9.Water filer
10.Valve
11.Cooling Water Tank
12.Cooling Tower
13.Check Valve 14.Valve
15.Expansion Water Tank
16.Cold Water Pump
17.Regulation Valve
(with scale)
9
水冷冷水机组安装使用说明书
Fuse
六、调试运行 Test
初次启动机组,必须有专业人员在场监督下进行。
If run the unit for the first time , there should be professional personal to supervise the operation.
1 、初步检查 First Check
a.
初次启动前,都要检查附属设备,如水泵,末端设备等的接驳水管是否安装妥当;
a. Before start up for the first time, check accessories equipments, to make sure the water
10
水冷冷水机组安装使用说明书
12
水冷冷水机组安装使用说明书
七、使用维护保养 Maintenance
1、 油加热至少通电 8 小时方可启动机组;
1. Oil heater should be connected to power source for 8hours before starting up the unit.
13
水冷冷水机组安装使用说明书
2、 系统的用水应该干净,对管道没有腐蚀性,建议用水的 PH 值在 7~8.5 范围
内;
2. Water used in system must be clean and no causticity to the pipes, PH value within 7~8.5
is preferable.
3、 机组设有多种自动保护装置,各项保护的设定值在出厂前已设定好,用户不要
随意改动;
3. All the protectors of the unit have already been set before leaving workshop, please do not
change the settings.
4、 若非紧急情况下,不要通过切断主电源来关闭机组;
4. Unless under emergency, do not disconnect the power source to shut down the unit.
5、 当机组发生故障报警停机时,先按下机组停止按钮,再检查故障原因,在故障
未排除前不得强行开机运行;
5. When the unit stops after malfunction alarm occurs, first press the button ”Stop”, then
check the causes , do not restart until malfunctions are eliminated.
6、 如需短期停机,只需按下机组的停止按钮即可,不要关闭主要电源;若机组冬
季长期停止使用,请排干系统里的水,以免冻结;
6. If unit is not being used for a short period of time, you only need to press the “Stop”
button, do not disconnect the power source; If it is a long time, please dry the system so as
not to get frosted.
7、 要经常检查机组的运行情况,包括冷却水、冷冻水的水质、水温、水压、冷媒 、
润滑油及水泵、冷却塔等运行是否正常,发现异常要及时处理。
7. Check unit’s operating condition regularly, including quality of cooling and cold water, the
temperature, pressure, refrigerant intermediary, lubricant, water pump and cooling tower ,etc.
Deal with abnormity in time.
8、 要保持机房干燥、清洁及通风良好。
8. Keep the room dry, clean and in good ventilation.
为了延长机组寿命,提高效率和节约能源,定期对机组进行检查,维护,保养是
必要的。用户需在每月度,每季度,每年度的检查,维护及保养情况记录好填写好,
更要将机组的损坏维修情况作详细记录,好让机组维修人员易于处理机组故障。
In order to expand service life, enhance efficiency and save energy, regular examination
and maintenance are necessary. Users should note down the examination and maintenance result
monthly, quarterly and annually. Moreover, damage and repair must be noted down in detail , so
as to make the malfunction easy to handle by maintainer.
14
水冷冷水机组安装使用说明书
压缩机维护保养周期
Compressor Maintenance Cycle
机组系统维护保养周期
Unit Maintenance Cycle
检查压缩机润滑油油位 每月
Check lubricant level of compressor monthly
检查吸入温度(过热度) 每月
Check the temperature of compressor inlet monthly
检查循环水系统水流量 每月
Check the current of water circulation system monthly
检查电压和电源 每月
Check the pressure and power source monthly
检查冷媒量(视镜指示) 每月
Check the refrigerant intermediary(Sight Glass) monthly
检查压缩机曲轴箱油加热 每月
Check the condition of oil heating in
15
水冷冷水机组安装使用说明书
附件 1 能效标识
16