You are on page 1of 10

Data Sheet Status: For Design Review

API Std 650 Storage Tank


Data Sheet Page
1 of 10
*For boxes marked with *, if blank, Mfr. Shall determine and submit as per Appendix L. For all lines, see Appendix L for line-by line instructions.

GENERAL Special Documentation Package Requirements:


Measurement Units to be used in API Std 650: Y SI US Customary

1. Manufacturer* Contract No.*


Address*
Mfg. Serial No.* Year Built* Edition & Addendum to API 650*
2. Purchaser Contract No.
Address Alpallana E8- 86 y Av. 6 de Diciembre
Tank Designation TQ - 04
3. Owner Operator EP PETROECUADOR Location Refinerìa La Libertad
4. Size Limitations* Ø 32 m X 12,192 m Tank Diameter Ø 32 m Shell Height 12,192 m
Capacity: Maximum* 57.448 bbl Net Working* 50.004 bbl Criteria:* API-2350
5. Products Stored:
Liquid Diesel 02 Max. S.G.: 0,88 at 48 deg C
Blanketing Gas N/A Vapor Pressure N/A PSIA at Max. Operating Temp.
% Aromatic 25 Suppl. Spec. N/A H2S Service? N Suppl. Spec. N/A
Other Special Service Conditions? N Suppl. Specs. N/A
DESIGN AND TESTING Purchaser to Review Design Prior to Ordering Material Y
6. Applicable API Standard 650 Appendices:* A E F L P
7. Max. Design Temp. 90 deg C Design Metal Temp.* -1 deg C Design Liquid Level 11,4 m.
Design Pressure 0,64 Kpa External Pressure 0,25 Kpa Pressure Combination Factor 0,4
Maximum Fill Rate 794,85 m3/hr Maximum Emptying Rate 340,53 m3/hr

Floatation Considerations? N Flot. Suppl. Spec.* N/A Applied Suppl. Load Spec. N/A
8. Seismic Design? Y Appendix E Y Alt. Seismic Criteria NEC SE DS Seismic Use Group III
MBE Site Class C Vertical Seismic Design? Y Vertical Ground Motion Accelerator Av: 0,583
Basis of Lat. Accel. (Select one):
N Mapped Seismic Parameters Ss 1,25 S1 0,63 So 0,5 I 1,5
Site-Specific Procedures MCE Design Required?
Y Other (Non-ASCE) Methods NORMA ECUATORIANA CONSTRUCCION EDICION 14
Freeboard Required for SUG 1 Design Roof Tie Rods at Outer Ring?* N
9. Wind Velocity for non-U.S. sites, 50-yr wind speed (3-sec Gust)* 120 kph
Top Windgirder Style* Top Angle Dimensions* L100 x 10 mm Use Top WG as a Walkway? N
Intermediate Wind Girders?* N Intermediate Windgirder Style* Dimensions*
Check Buckling in Corroded Cond.? N
10. Shell Design: 1-Ft Mthd?* Y Variable-Des-Pt Mthd?* Elastic Anal. Mthd?*
Plate Stacking Criteria* Centerline Stacked? N Flush-Stacked? Y Inside
Plate Widths (in.) (Shell course heights) and Thicknesses (in.)* Numbers Below Indicate Course Number
1. 2440 mm / 15,86 mm 2. 2440 mm / 14,27 mm 3. 2440 mm / 9,52 mm 4. 2440 mm / 8 mm
5. 2420 mm / 6,35 mm 6. x 7. x 8. x
9. x 10. x 11. x 12. x
13. x 14. x 15. x 16. x
Joint Efficiency* 0,85 % Shell-to-Bottom Weld Type* Fillets Shell-to-Bottom Weld Insp Mthd*
Approvals: Revisions (no./date) Title:
1 2 3 4 5 6 By Ckd Date
Draw. No.: Sheet 1 of 10
Data Sheet Status:
API Std 650 Storage Tank
Data Sheet Page
2 of 10
*If box is blank, Mfr. shall determine and submit as per Appendix L.

11. Open-Top and Fixed Roofs: (See Sheet 6 for Floating Roofs) Open Top?* N
Fixed Roof Type* Multi Bay Int Struct. Roof Support Columns* Structural Shape
Cone Slope* 1
: 16 Dome or Umbrella IS Radius* N/A in Weld Joints* Lap
Seal Weld Underside of Lap Joints? Y ; Seal Weld Underside of Windgirder Joints? Y
Gas Tight? Y Joint Efficiency* 85 % Roof Thickness* 6,35 mm
Minimum Roof Live Load 0 psf Balanced Snow Load 0 psf Unbalanced Snow Load 0 psf
App. Suppl. Load Spec.* 20 psf Column Lateral Load 1,4 psf
Normal Venting Devices*: Qty 2 Type
Emergency Venting Devices*: Qty 2 Type
For Non-Frangible Roofs: Seal Weld Roof Plates to Top Angle IS N ; Weld Rafters to Roof Plates N
Roof-to-Shell Detail* Top Angle Lapped Radial Projection of Horizontal Component* Outward
12. Bottom: Thickness* 9,53 mm Style* Cone Up to Center Slope* 1 : 120 Weld Joint* SW Lap
Provide Drip Ring? N Alternate Spec. N/A
SK/Ann. Ring? N Annular Ring: Minimum Radial Width* mm. Thickness* mm.
13. Foundation: Furnished By* Type* Ringwall
Soil Allow. Bearing Press.* N/A psi Per Spec. N/A Anchor: Size 2 inch Dia Qty 34
Design Loads: Base Shear: Wind* N/A Seis.* N/A Moment: Wind* N/A Seis.* N/A
Ring Forces: Shell+Roof Weight New* N/A Corroded* N/A Roof LL* 20 psf Internal Pressure* atm
Partial Vacuum* N/A Wind* Siesmic*
Btm Forces: Flr Wt. New* N/A Corr.* N/A Prod. Wt.* Water Wt.* Int. Press.* atm
Partial Vacuum* N/A Other Found. Loads* N/A Min. Proj. of Found. Above Grade: TBD
14. Responsibility for Heating Water, if Required? Purchaser
Hydro-test Fill Height* 11,24 m Settlement Measure Req'd? Y Extended Duration of Hydro-test: API 650
Predicted Settlement Profile is Attached
Responsibility for Setting Water Quality Purchaser Suppl. Test Water Quality Spec. N/A
Test Water Source & Disposal Tie-in Locations Purchaser Hydro-test Appendix J Tank N
Post-Press.-Test Activities Req'd of Mfr: Broom Clean Potable Water Rinse Y Dry Interior Other
List Other
15. Inspection by: Shop Purchaser Field Purchaser
Supplemental NDE Responsibility Manufacturer Supplemental NDE Spec. Purchaser
Positve Material Identification? N PMI Requirements: N/A
Max. Plate Thickness for Shearing TBD
Must Welds not exceeding .25" be Multi-Pass? N Must Welds greater than .25" be Multi-Pass? Y
Leak Test Method: Roof* Hermeticity Test Shell* Hydrostatic Testing Shell Noz./MW Rein. PL* Pneumatic Testing
Bottom* Vaccum Box Floating Roof Components* N/A
Modify or Waive API Dimensional Tolerances (see 7.5) N Specify: N/A
Specify additional Tolerances, if any, and Circumferential and Vertical Measurement Locations:
Allowable Plumbness: N/A Measure and Record at a Min. of N/A Locations or Every N/A ft around the
Tank , at the Following Heights: Specify Other: N/A
Allowable Roundness:** Measure Radius and Record at a Min. of Locations or Every ft
around the Tank, at the Following Shell Heights: Specify Other:
** See Data Sheet Instructions for the Maximaum Allowable Additional Tolerance
Approvals: Revisions (no./date) Title:
1 2 3 4 5 6 By Ckd Date
Draw. No.: Sheet 2 of 10
Data Sheet Status:
API Std 650 Storage Tank
Data Sheet Page
3 of 10
*If box is blank, Mfr. shall determine and submit as per Appendix L.

16. Coatings:
Internal Linings by: ATC HEMPADUR 300 MICRONS`S Per Spec.* NORMA DE PETROECUADOR 02
External Coating by: ATC HEMPADUR 300 MICRONS`S Per Spec.* NORMA DE PETROECUADOR 02
Under-Bottom Coating by: ATC Per Spec.* NORMA DE PETROECUADOR 02
17. Cathodic Protection System? Y Per Spec.* API RP 651
18. Leak Detection System? Y Per Spec.* API RP 650
19. Release Detection Barrier? N Per Spec.* N/A
20. Tank Measurement System: Required? Y Remote Capability Required? N
By:* MANUFACTURER Per Spec.* TDD
21. Weight of Tank:
Full of Water* 9398487 kgs Empty* 230063 kgs Shipping* lbs Brace/Lift Spec.
22. References*:

23. Remarks*:

Approvals: Revisions (no./date) Title:


1 2 3 4 5 6 By Ckd Date
Draw. No.: Sheet 3 of 10
Data Sheet Status:
API Std 650 Storage Tank
Data Sheet Page
4 of 10
*If box is blank, Mfr. shall determine and submit as per Appendix L.

Table 1 MATERIALS OF CONSTRUCTION


Component Material* C.A. (mm.) Component Material* C.A. (mm.)
Shell Course 1 ASTM A283 C / 15,86 mm 3 Manhole Necks ASTM A283 C -
Shell Course 2 ASTM A283 C / 14,27 mm 3 Nozzle Necks ASTM A283 C / ASTM A-106 Gr.B -
Shell Course 3 ASTM A283 C / 9,52 mm 3 Manhole Flanges ASTM A283 C -
Shell Course 4 ASTM A283 C / 8 mm 3 Nozzle Flanges ASTM A283 C / ASTM A105 -
Shell Course 5 ASTM A283 C / 6,35 mm 3 Manhole Covers ASTM A283 C -
Roof ASTM A283 C / 6,35 mm 1,2 Nozzle Covers ASTM A105 -
Bottom ASTM A283 C / 9,53 mm 3

Annular Ring -

Anchor Attachments ASTM A36 - Internal Piping ASTM A-106 Gr.B

Reinforcing Pads ASTM A283 C - Wetted Structurals+ ASTM A36

Non-Wetted Struct.+ ASTM A36

Table 2 BOLTS and ANCHORS


Flange Bolts Head Type* Material* Nut Material* Thread Series* C.A. (in.)
Flange Bolting++ Hex ASTMA-193-B7 ASTM A-194-2H STD GALV.
Structural Bolting++ Hex ASTM A-307 ASTM A-194-2H STD GALV.
Anchor Bolts++ Hex ASTM A-307 ASTM A-194-2H STD GALV.

Remarks:

Approvals: Revisions (no./date) Title:


1 2 3 4 5 6 By Ckd Date
Draw. No.: Sheet 4 of 10
Data Sheet Status:
API Std 650 Storage Tank
Data Sheet Page
5 of 10
*If box is blank, Mfr. shall determine and submit as per Appendix L.

Table 3 NOZZLE and MANHOLE SCHEDULE*


Bottom

Hor Azimuth
Mark Service Diameter (in) Depth (in) Thk (in) Rad(in) "x" Dim "y" Dim (deg) Notes

Shell

Nom. Wall Flange Flg Cl. Offset Elev. Azimuth Proj. Trim
Mark Service Dia. Thk Type or Thk Hillside (mm) (mm.) (deg) (mm) Flush Notes
N1 LEVEL INDICATOR 2 XS RFWN 150 1600 23 153
N2 LEVEL INDICATOR 2 XS RFWN 150 2800 23 153
N3 TERMOWELL 1 CPLG 680 25
N4 CLEANOUT 35" X 47" API 650 API 332 34 206
N5 FILLING 6 XS RFWN 150 306 286 200
N6 BOTTOM DRAIN 4 XS RFWN 150 259 179 175
N7 BOTTOM DRAIN 4 XS RFWN 150 259 359 175
N8 TRANS. PRESSURE 2 XS RFWN 150 293 164 150
N9 SUCCTION 12 XS RFWN 150 449 290 225
N10 FREE PUMP 6 XS RFWN 150 306 295 200
M1 MANHOLE 30 8MM API 900 75 150
CS1 FOAM CHAMBER 8 XS RFWN 150 10842 108 200
CS2 FOAM CHAMBER 8 XS RFWN 150 10842 288 200
M2 MANHOLE 30 " 8MM API 900 255 150

Notes:

Approvals: Revisions (no./date) Title:


1 2 3 4 5 6 By Ckd Date
Draw. No.: Sheet 5 of 10
Data Sheet Status:
API Std 650 Storage Tank
Data Sheet Page
6 of 10
*If box is blank, Mfr. shall determine and submit as per Appendix L.

Table 3 NOZZLE and MANHOLE SCHEDULE* (cont'd)


Roof
Horz Slope
Nom. Wall Flange Flg Cl. Vert or Rad(mm Dim(m Azimuth Proj. Trim
Mark Service Dia. Thk Type or Thk Radial ) m) (deg) (mm) Flush Notes
RM1 ROOF MANHOLE 20 6,35 MM API 0 150
RM2 ROOF MANHOLE 20 6,35 MM API 180 150
V1 VENT 10 XS FFWN 150 Radial 132 200
V2 VENT 10 XS FFWN 150 Radial 312 200
GH GAGE HATCH 8 XS FFWN 150 Radial 140 200
LT TRANS. LEVEL 20 6,35 API Radial 153 150
TT TEMP. SENSOR 2 XS RFWN 150 Radial 165 289
LS S. NIVEL 4 XS RFWN 150 Radial 160 150

Notes:

Approvals: Revisions (no./date) Title:


1 2 3 4 5 6 By Ckd Date
Draw. No.: Sheet 6 of 10
Data Sheet Status:
API Std 650 Storage Tank
Data Sheet Page
7 of 10
*If box is blank, Mfr. shall determine and submit as per Appendix L.

OTHER TANK APPURTENANCES


24. Platform: Top: Y Roof: Inter. Y Other Specify Other
Platform Material Carbon Walk. Surface Grating Finish Galv.
Stairs: Type Dbl String Specify Other Min. Width (mm) 710 mm
Min. Tread Max. Rise Tread Surface Grating Tread Nose Chkd PL
IS Rail HR Height (in) HR Type Spec. Other Finish
Handrail: Type 1 1/2 Pipe Spec. Other HR Height (in) Finish
Architectural/Structural Specs* HELICAL / SPIRAL National Safety Standards OSHA Specifications
Gauger's Platform Req'd? N Qty. Req'd* N/A Per Spec.* N/A
25. Jacket Req'd?* N Other Heaters/Coolers Req'd?* N
Suppl. Jacket, Heater or Cooler Specs.* N/A
26. Mixer/Agitator: Quantity N/A Size N/A Per Spec.* N/A
27. Insulation: Roof Req'd? Thick Mat'l Per Spec.
Shell Req'd? Thick Mat'l Per Spec.
Purchased By: Installation By:
28. Struct. Attachments: Lifting Lugs?* N Description* N/A
Shell Anchorage?* Y Type* Anchor Chairs Specify Other Scaffold Cable Support? Y
29. Other Items: Flush Drain? N Type Specify Other Size
Flush Cleanout? Y Size Specify Other
Ground. Lugs? Y Qty Type Mat'l
Waive Application of Appendix P?
Miscellany #1 Miscellany #2
Miscellany #3 Miscellany #4
Miscellany #5 Miscellany #6

Table 4 OTHER TANK APPURTENANCES*


Mark Qty Service or Description Size Orientation Elevation Material Remarks

Remarks:

Approvals: Revisions (no./date) Title:


1 2 3 4 5 6 By Ckd Date
Draw. No.: Sheet 7 of 10
Data Sheet Status:
API Std 650 Storage Tank
Data Sheet Page
8 of 10
*If box is blank, Mfr. shall determine and submit as per Appendix L.

FLOATING ROOF DATA


30. Floating Roof Selection:
Design Basis: Appendix C Appendix H
Type of Roof: (External or Internal): Sgl. Deck Pontoon* Double Deck*
(Internal Only): Tubular Pontoon* Metallic Sandwich Panel* Other
Specify Other Suppl. Spec.:
31. Seals:
Primary Seal: Shoe Envelope Wiper/Comp Plate Other Specify Other
Shoe Mechanism: Mfg. Std. Other Specify Other
Electrically Isolate Mechanism from Shoes? Wax Scrapers Required?
Nominal Shoe Thick.* Carbon Steel Shoes to be Galv.?
Secondary Seal: Shoe Envelope Wiper None Other Specify Other
32. Data for All Floating Roofs:
Overflow Openings in Shell Acceptable? Shell Extension Roof Drain Check Valves Required?
Roof Drain Isolation Valves Required? Freeze Protection for Roof Drains Req'd? Suppl. Req.
Roof Drain to Ext. Noz.: Mfg. Std. Arm. Flex Pipe Swivel/Rig. Pipe Other
Foam Dam Supplemental Spec.
Nominal Deck Thick. (in) Bulkhead Top Edges to be Liquid-Tight Seal-weld Underside of Roof
Electrical Bonding: Shunts Cables Supplemental Spec.
Qty of Non-Guide Pole Gauge Wells Qty of Sample Hatches
Guide Pole for Gauging? Slots in Guide Pole? Datum Plates? Striking Plates?
GP Emmis.-Limit. Devices: Sliding Cover Pole Wiper Float Float Wiper Pole Cap
Qty of Roof Manholes* Minimum High Roof Clearance above Bottom
Removable Leg Storage Racks? ; Leg Sleeves Fixed Low Legs
33. Additional Data for External Floating Roofs:
Weather Shield? Suppl. Spec.
Rolling Ladder Req'd? Field Adjustable Legs?
Design Rainfall Intensity In/Hr Based on a Minute Duration Associated with the Storm
Design Accumulated 24-Hour Rainfall in Based on the Storm
Distortion and Stability Determinations Required? Suppl. Spec.
Landed Live Load* lbs

Remarks:

Approvals: Revisions (no./date) Title:


1 2 3 4 5 6 By Ckd Date
Draw. No.: Sheet 8 of 10
Data Sheet Status:
API Std 650 Storage Tank
Data Sheet Page
9 of 10
*If box is blank, Mfr. shall determine and submit as per Appendix L.

34. Additional Data for Internal Flaoting Roofs:


Two Position Legs? Cable Supported Roof? Fixed Roof Inspection Hatches Required?
Internal Roof Drain Required? Omit Distribution Pads Supporting Uniform Live Loads?
Corrosion Gauge Required? Fixed Ladder required? Type of Roof Vent:*
Modified Minimum Point Load? Supplemental Specification
Mfr To Leak Test* % of Compartments in Assembly Yard in Erected Position Unknown++
Roof Erector's Floatation Test: w/Tank Hydro at completion of roof at later date Not Req'd
Floatation Test Media: Water Product Water Quality: Potable Other Specify Other
Floatation Test : Test Duration Fill Height
Flotation Test Items provided by Purchaser (see H.6.7): None List Attached
Responsible Party for Inspecting Roof during Initial Fill: Purchaser Other
Table 5 FLOATING ROOF MATERIALS
Component Mat'l/Thick.* C.A./Coat.* Component Mat'l/Thick.* C.A./Coat.*
Deck Plate Datum Plate
Inner Rim Plate Tubular Pontoon
Outer Rim Plate Pontoon Bulkhead
Foam Dam Submerged Pipe
Sandwich Panel Face Plate Guide Pole
Sandwich Panel Core Secondary Seal
Gauge Well Secondary Seal Fabric
Drain Sumps Wiper Tip
Opening Sleeves Wax Scraper
Floating Suction Lines Weather Seal
Primary Fabric Seal Envelope Fabric
Foam Log Core Shoe Mechanisms
Landing Legs Primary Seal Shoe
Landing Leg Bottom Pads Removable Covers
Manhole Necks Rolling Ladder
Vents Inlet Diffusers

Approvals: Revisions (no./date) Title:


1 2 3 4 5 6 By Ckd Date
Draw. No.: Sheet 9 of 10
Data Sheet Status:
API Std 650 Storage Tank
Data Sheet Page
10 of 10
*If box is blank, Mfr. shall determine and submit as per Appendix L.

Tank Plan and Sketches:

Notes:

Approvals: Revisions (no./date) Title:


1 2 3 4 5 6 By Ckd Date
Draw. No.: Sheet 10 of 10