SUBJECT: _KFSH8&RC-MEGA PROJECT
dy Mix Concrete — Structural We
In reference to S8G Material Submittal MS/CN1169P01/000002 dated July 9, 2013; please note that M/s Unibeton
Ready Mix is approved subject to the following comments:
1. For each class of RC. concrete, the trial mixes shall represent at least 2 different water cement ratios. For
structural concrete, W/C ratio to be below 0.30.
2. Gelium / High range super-plasticizer (BASF) is eecommended to be used in high-strength structural
concrete grade 40 & SO MPa instead of conventional Fosroc admixture. Glenlum has advantages for its
high early & ultimate strength, increased stability and improved dural
3. _Gylinders shall be prepared for comprehensive strength of concrete. Specified cylinder crushing strength
shall be checked as per ASTM-C39 / C214.
4, Proposed to check fine aggregate for sand equivalent (SE) test as per local Ministry MOT / SASO
standard,
Provision of high density concrete for Hospital X-rays / CT scan rooms for Radiation control
6. Times Slump Loss and Haul Time to be described by Unibeton,
‘adel EIhamninady, Architect
Director
Engineering and Utilities
« Michael Manish, Senior Project Manager, Vanir Construction Management Ine
Saudi Dar Consultants
SAYRE: GSW HIT TWYYYY: S5La — dye gall Say jal ASlaall WYER San ffY peege, 8 Bod
Jeddah Branch + P.O. Box 40047 Jeddah 21499 Kingdom of Saudi Arabia * Tel: #966 2.667777 Fax: +966 2 6630073 » wwwkishreedu.sa
oro 100-1362) 1. 2121501063
Chapter 6 Duct Systems California Mechanical Code - Matrix Adoption Table Chapter 6 - Duct Systems (Matrix Adoption Tables Are Non-Regulatory, Intended Only As An Aid To The Code User. See