You are on page 1of 3

9/18/2010 5 Common Questions Involing Psychro…

Join
Directory
Search
Go Find A Forum Go
Tell A Friend
Whitepapers
Jobs

Home > Forums > Mechanical Engineers > Activities > HVAC/R engineering > FAQs
HVAC/R engineering FAQ
Psychrometrics
5 Common Questions Involing Psychrometrics
faq403-1255
Posted: 19 Jul 06 (Edited 26 Jul 06)

Many times the use of a psychrometric chart can help us make an analysis of a HVAC systems’ performance, or help us
predict how well a design will function under different operating conditions. This FAQ’s main focus is to provide some
tips on how to use a psychrometric chart to calculate typical heating, cooling/dehumidification, and mixed air problems
encountered in the field or at the early stages of design.
This exercise assumes the use of an ASHRAE sea level 29.92” Hg chart.

Question 1:
I'm starting with an outdoor condition of 95 degrees F and 80% Relative Humidity and I'm mixing that
air with return air that is at 80 degrees F and 50% relative humidity. If the mixed air is 80% return air
and 20% outside air, how do I find the correct mixed air temperature and % Rh and graph this on the
psychrometric chart properly?

To find the solutions for this question I would approach the problem like this:

1. Plot OSA point on chart at 95 degrees 80% Rh

2. Plot RA point on chart at 80 degrees 50% Rh

3. Connect the OSA point and the RA points to form the mixed air line.

4. Measure length of line 5.625" x 20% = 1.125”(This measurement will depend on the size of your chart I'm using an
11" x 17" yours may be smaller)

5. Measure along the MA line starting from the RA point 1.125" this is your MA temperature and humidity. Read 83
degrees 60% Rh

6. Or use the following simple formula to find the mixed air Db temperature.
(R.A. degrees F x %) + (OSA degrees F x %) = Mixed Air degrees F, plot this on the MA line to find the
corresponding %Rh

Question 2:
How do I figure out the required supply air temperature for the room? I know that I need to find the
structural heat gains, electrical heat gain, occupant load and infiltration load. I can add the sensible heat
and latent heat gains for the space and figure out what the total heat gain for the room is. But how do I
figure out the necessary supply air temperature and % Rh to maintain that room at say 80F and 50%
Rh?

To find this answer requires the use of the sensible heat ratio. The sensible heat ratio is a ratio of sensible heat to total
heat based on your space load. The protractor on the upper left side of the psychrometric chart lets you plot the ratio
or slope on the chart. Look closely at the protractor, the numbers on the inside radius are the ratios of sensible heat.
Suppose your sensible heat ratio for your problem was .65 based on your rooms' sensible heat loads and latent heat
loads: (sensible heat + latent heat = total heat) so that sensible heat divided by total heat = The Sensible Heat Ratio
(SHR)

1. Draw a line from the center point on the base line of the protractor through the .65 on the radius of the protractor.
This establishes your slope.

2. Now plot your desired Db and %RH for the space on the chart, 80 degrees Db 50%RH.

3. Transfer the sensible heat line or slope (remember the protractor?) so that it starts at your desired room
temperature (the RA point) and travels to the left at the .65 SHR slope and intersects the 95% curve on the chart, at
95%Rh (read 50 degrees Db).

4. The point of intersection will establish the required supply air temperature (the SA point) to maintain the desired
space temperature.

5. You could select any desired supply air temperature located on this line in theory and adjust your CFM, but most A/C
equipment delivers air at 90% Rh or higher so you are some what limited, so much for theories.

Question 3:
Now that I know what the required supply air temperature is how do figure out what my CFM
requirements are?
www.eng-tips.com/faqs.cfm?fid=1255 1/3
9/18/2010 5 Common Questions Involing Psychro…

Once you have established your supply air temperature, use the supply air temperature and the desired room air
temperature to find the CFM, use the following formula:

1. BTU/Hr = 1.08 x CFM x ∆T with the known sensible heat load for BTU/HR, T1 as the space temperature and T 2 as
supply temperature, you can now solve for the CFM.

2. Another method would involve the total heat formula:


BTU/Hr = 4.5 x CFM x ∆H, this requires you to find the enthalpy of the return air and supply air from the psychrometric
chart.

3. Connect a straight line from the RA point to the SA point.

4. Form a right triangle using the SA point and the RA points, making a horizontal line to the right from the SA point
and intersecting it with a vertical line down from the RA point.

5. Locate enthalpy values at the SA point, the RA point, and at the 90 degree intersection of the horizontal and vertical
lines of the triangle. These enthalpy lines run diagonally care must be used in accurately locating.

6. At SA point read 19.8 BTU/Lbs, at RA point read


31.4 BTU/Lbs, at 90 degree intersection read 27.6 BTU/Lbs

7. The difference between 27.6 and 19.8 is sensible heat BTU/Lbs, the difference between 31.4 and 27.6 is latent heat
BTU/Lbs, and the total heat is the difference between 31.4 and 19.8 this is the load in the room BTU/Lbs.

8. Using the known total heat load BTU/Hr for the room, the return air enthalpy and supply air enthalpy find the∆H,
apply to: BTU/Hr = 4.5 x CFM x ∆H to find the CFM

Question 4.
In my original problem I was bringing in 20% OSA at 95 degrees and 80% Rh, to achieve a mixed air
temperature of 83 degrees 60 %Rh does this affect the load in the room?

Simply stated NO! The mixed air temperature of 83 degrees 60 %Rh is higher than the desired space air temperature,
it does put an additional load on the cooling coil but the room never sees this added load. So we must size the coil to
handle this extra heat. Here’s a method using the psychrometric chart to find the load on the coil.

1. Locate the MA point on the mixed air line and find the enthalpy corresponding to this point (read 36 BTU/Lbs)

2. Locate the SA point on the chart and find the corresponding enthalpy read (19.8 BTU/Lbs)

3. Using the difference of these two values and the CFM that we found in question 3 apply them to the Total Heat
formula and solve for total BTU/Hr:
BTU/Hr = 4.5 x CFM x ∆H to find Total BTU/HR

4. Notice in this problem the total heat the coil sees is going to be more than the load of the room, the CFM will remain
the same.

Question 5.
Is there a way to find the amount of moisture that the coil is removing from the air?

Yes there is, the psychrometric chart that we’ve been using lists these values as, Lbs of water/ Lbs of dry air. This is
referred to as the humidity ratio W. Some charts list this as grains of moisture; note there are 7000 grains/lbs. Here’s
how to find the answer using our problem as an example.

1. Locate the MA point on the chart and extend a horizontal line to the right side of the chart and find the MA humidity
ratio W (read .0145)

2. Locate the SA point on the chart and extend a horizontal line to the right side of the chart and find the SA humidity
ratio W (read .0072)

3. Take the difference (.0073) and use this modified formula:


Lbs/Hr = 4.5 x CFM x ∆W to find the pounds of water per hour removed.

Let me finish off by saying, this site is my favorite source for technical information that I have found. I want to thank
Quark for encouraging me to post this as a FAQ. I only hope I didn't come up too short. Please feel free to provide any
added data that I may have over looked.

Back to HVAC/R engineering FAQ Index


Back to HVAC/R engineering Forum
My FAQ Archive
Email This FAQ To A Friend
Print This FAQ
Laboratory Equipment
Specialising in laboratory equipmen spectrophotometers, etc, email us
www.acte c-scientific.co m

Join | Jobs | Advertise | About Us | Contact Us | Site Policies

Copy right © 1998-2010 Tecumseh Group, Inc. All rights reserved.

www.eng-tips.com/faqs.cfm?fid=1255 2/3
9/18/2010 5 Common Questions Involing Psychro…
Unauthorized reproduction or link ing forbidden without express written permission.

www.eng-tips.com/faqs.cfm?fid=1255 3/3

You might also like