DESIGN REVIEW FOR NEW GRID STATION AT GETZ PHARMA AND GIS EXTENSION A
Title: Comments on Schematics Drawings At Getz Pharma and GIS bay extension a
Drawing No.
DESIGN REVIEW LOG
Description Reference
Submission Of Technical Data For Approval.
Comments by K-Electric
S.N KE Comments Status
o
A General Comments
36 Open
37 Open
38 Open
39 Open
F101, F103, F201 & F202 has only one 1 C/O these
23 Open
should be supplied with at least 2 C/O
-X2, -X3, -X4, -X5, –X10, -X9, -X17, -X101, - X102, &
24 -x103 Spring loaded Terminal blocks are required and Open
hook type lugs should be used. At least 20% Spare
TBs in each terminal block should be provided.
Sheet # 30,31 and 32, K10, 11, 12, 13, 14, 15, 16 & 17
are used to remote end indication, Remote end
indications should be wired from auxiliary contacts
34 instead of K10, K17 contact and open and close Open
indications should be segregated and description
should be mentioned on sheet NO.32.
Sheet # 30,31 and 32, K10, 11, 12, 13, 14, 15, 16 & 17
are used to remote end indication, Remote end
36 indications should be wired on Annunciation DC (A+, Open
A-).
Sheet # 32, Function of lamp description is not clear,
37 please mention the clear function for which it is used Open
and labels on Panel should be installed accordingly.
Date
6-Nov-17 12-Feb-18
There is no sheet A20, but SLD in SLD is still incomplete. Sheet No. A32/D10
sheet A32 has been updated
See sheet S10 & S11 Noted
Updated Noted
Connected CT ratio should be marked/underlined
See sheet S10 & S11
in the CT circuit.
See sheet S10 & S11 Kindlly update
Updated(SG2L002970) Noted
Updated(SG2L002971) Noted
Drawings are not revised, please submit the
Show on SLD Sheet A32 revised drawings as Rev-1 or B.
Updated Noted & Closed
Updated Noted
Already Incorporated in the Drawings are not revised, please submit the
modifications for BB protection Panel revised drawings as Rev-1 or B.
The Symbol is revised, The Q53 Earth Symbol is still on line side, please update.
Switch is Earhing ciruit breaker side.
The point relates to Breaker Failure Drawings are not revised, please submit the
protection & will be incorporated. revised drawings
Comment Complied, PT supply fail Drawings are not revised, please submit the
indication is wired up on annunciator. revised drawings
Cross references now mentioned on Drawings are not revised, please submit the
the Drawings. revised drawings
Cross references now mentioned on Drawings are not revised, please submit the
the Drawings. revised drawings
In Drawings all secondary wired are reflected as
shorted, shorting links should not be reflected in
Please eleborate the requirement. drawings and parking for shorting screws has to be
provided.
Comment Complied, Please find Drawings are not revised, please submit the
attached the Revised Schematic revised drawings
Drawings
Comment Complied, As Energy Drawings are not revised, please submit the
metering is now merged with Control revised drawings
Panel .
Comment Complied, Please find Drawings are not revised, please submit the
attached the Revised Schematic revised drawings
Drawings
Comment Complied, As Energy Drawings are not revised, please submit the
metering is now merged with Control revised drawings
Panel .
Comment Complied, Please find Drawings are not revised, please submit the
attached the Revised Schematic revised drawings
Drawings
Noted. Closed
Noted. Closed
Comment Complied, Please find
attached the Revised Schematic noted and closed
Drawings
Will be incorporated after receiving Reflected in drawings.
the The SDH panel drawings
The required signals are wired up on Response is not clear, please elobrate
the input of Line Diff relay 411L in RP3
No power Factor meter is required in Mentioned in KE Specs (Pls. refer to section 3.1
Line Control Panel as per KE Technical (PID/TS/CPM/1.0) Pls incorporate numerical type
Specifications for Control , Protection Frequency and Power factor meters.
& Metering
Comment Complied, Please find
attached the Revised Schematic Noted & Closed
Drawings
Will be provided after approval of Noted
schematics
There is no HMI in revised BoQ of K- Signals should be available at both Control Panel
Electric Annunciator as well as Station HMI. Futhermore
MIMIC - LCC - SCADA Selector switch Pls. incorporate in relevant drawings e.g panel
is already available. view (sheet 100).
Comment Complied, Synch Check
selected or Bypass switch is now Noted & Closed
provided.
Auto Recloser In/Out Switch is Need to be provided.
available in relay panel.
Comment Complied, Please find Two separate 220VDC sources should be provided
attached the Revised Schematic with internal change over scheme.
Drawings
Comment Complied, Please find
attached the Revised Schematic Noted & Closed
Drawings
Comment Complied, Please find comments is still not compiled sheet 100 shows
attached the Revised Schematic Klamsen Annunciator instead of E-Labs
Drawings Annunciator.
Ensured. Noted
There is no O/G relay mentioned on This is mentioned as symbol, please follow
Sheet # 4
Auxilary Supplies will be used from The same modification shall be incorporated with
Existing AC DC Panels modifications
Cross reference are already
mentioned on the drawings. For IFC Cross references with drawing number, sheet
panel the drawings will be update number, row and colomn to be provided.
after receiving the IFC panel drawing
Please find attached the literature of Sheet #31, Time setting of flicker circuit (K50) is
Time Relay for Time setting missing, this may please be reflected in drawing.
Noted Noted
Noted Noted
Noted Noted
Noted Noted
Noted Noted
Noted Noted
Noted
Noted Noted
Noted
Noted Noted
Noted Noted
Noted Noted
its 40kA @ 50° C It should be mentioned on drawing
Complied, Please find Attached the Is it K1 or K14? In previous drawing it is K14 and
Revised Schematic Drawings (Refer: in revised drawing it is K1. Relay should have set
Sheet 20).Along with literature of reset mechanical interlock
K14 Contactor.
Noted Noted
Noted Noted
Noted Noted
Noted Noted
Noted Noted
Comment incorporated, Energy
Metering is now part of Control CT/PT details still to be mentioned
Panel. (Refer: Sheet 51,52)
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Noted
Complied, Please find Attached the
Revised Schematic Drawings
Noted
Noted
Noted
Noted
Noted
Noted
Complied, Please find Attached the
Revised Schematic Drawings
Noted
Noted
Noted
As Discussed/Explained in meeting
Dated 7-3-2018, Two DC and one AC
Annunciator is provided
Noted
Noted
Noted