The Engineer refers to the Contractor’s correspondence reference 20180508 CHE ENG 1300
dated 08 May 2018 and the accompanying material submittal reference PMPT-MAS-016-03
regarding the above subject.
The Engineer has reviewed this revised submission and has the following comments:
Comment
Section Comment
Category
Fire Pump Noted that the Contractor has changed the dimensions of the
Unit Size and dolphin. The Contractor is required to resubmit RFD-009
accordingly and to provide full details of the proposed 3
Location
dolphin in that RFD.
Accesses for Noted the proposed procedure to remove diesel engines for 1
Maintenance maintenance. No further comments.
Comment
Section Comment
Category
Air Outlet Noted that the Contractor has confirmed that the direction of
from the air from the radiator will be from inside of the pump house to
1
Engine outside. No further comments.
Radiators
Other general a) We note that the Contractor has adopted the SI system. 2
Comments on Please add a legend in the drawings noting the units being
Drawings used for dimensions.
Posorja Multipurpose Terminal - Terminal Infrastructure Works Page 3
20180517 ENG CHE 1424 – Pre-Assembled Fire Pump Building and Accessories – MAS 016 17 May 2018
Comment
Section Comment
Category
Comment
Section Comment
Category
Jockey Pump Noted the Contractor’s advice that the Jockey Pump is only 1
Voltage available as 460V. No further comments.
Jockey Pump Noted the Contractor’s advice that the Jockey Pump is only 1
Connection available with NPT connection. No further comments.
Posorja Multipurpose Terminal - Terminal Infrastructure Works Page 5
20180517 ENG CHE 1424 – Pre-Assembled Fire Pump Building and Accessories – MAS 016 17 May 2018
Comment
Section Comment
Category
For the avoidance of doubt, on the basis that the maintenance of the filter systems is
unacceptable, the Engineer considers the status of this submission at this time to be:
Category 1
Category 2
Category 3 X
Category 4
The Engineer’s comments provided above do not relieve the Contractor from its obligations
under the Contract.
Yours sincerely
Mike Jackson
Resident Engineer
For and on behalf of
Cullen Grummitt & Roe