Professional Documents
Culture Documents
Prospect / Retrospect
The power losses resulting in the
fuse were not given due
HRC fuse-links offer one of the best persons or installation and shall be Here the fuse-link is selected
forms of protection for motor starting suitable for further use. The risk of based on its time-current
applications in view of very low short contact welding is recognised, in characteristics and the time
circuit stresses generated in case of which case the manufacturer shall current-characteristics of the
a fault as compared to other indicate the measures to be taken overload relay.
protective devices. However, the as regards the maintenance of the
best possible rating of a HRC fuse- equipment." (d) Low Power-loss
link selected/recommended for such
It is very evident from the above One of the most important factors
application depends on following
that it is advantageous to have while selecting a HRC fuse-link is
requirements:
type '2' co-ordination with SCPD. its Power-loss. The rated power-
The fuse-link selected should be loss of the fuse-link is the power-
(a) Ability to withstand motor
able to provide type '2' co- loss value as stated by the
starting currents
ordination. manufacturer when the fuse-link
The fuse-link selected should not Thus the fuse-link selection will is carrying its current under
blow during motor starting. Also the also depend on its short-circuit specified conditions. The fuse-
fuse-link should withstand repeated characteristics i.e. the Cut-off link selected should preferably
starting currents without any 2
current and l t characteristics. have low power-loss.
deterioration. The rating of fuse-link
is decided by: (i) Saving in power/energy
(c) Discrimination (ii) Lower temperature rise at
(i) The motor starting current and There should exist discrimination fuse-switch terminals and
its starting time. This will between the overload relay and the fuse-knives.
depend on two factors: SCPD i.e. the fuse-link. This means
that for overload currents less than Table 1 gives the power-loss
- Type of starter (e. g. DOL or value limits as recommended in
Star-Delta) Ic (Ic=the current corresponding to
the intersection point of overload the relevant
- Motor characteristics National/International standards.
relay and the fuse-link
(ii) The time current characteristic characteristics), the relay should It is evident that over a period of
Of the fuse-link. operate and protect the device and time the Standards recognised
not the fuse-link. Also there should the importance of power-loss and
(b) SCPD co-ordination revised to reduce the limiting
be no damage to the starter. For
The fuse-link should meet the overload currents more than Ic, the values. More and more
criteria for co-ordination as specified fuse-link should operate before the manufacturers in the country and
in the relevant National/International starter and protect the circuit. abroad have reduced the
Standards. For example, as per the
Standards IEC 947-4-1/IS 13947,
part 4 section 1, for the Short Circuit TABLE 1
Protective Device co-ordination, Permissible Watt-Loss Values in 'W'
"two types of co-ordination are
permissible 'Type 1 or 2'. Type '1'
co-ordination requires that under Standard 100 A 160 A 250 A 400 A 630 A
short circuit conditions, the Size 00 Size 0 Size 1 Size 2 Size 3
contactor or starter shall cause no
danger to persons or installation and IEC 269, 1973/ 12 25 32 45 60
may not be suitable for further IS 9224, 1979
service without repair and
replacement of parts. Type '2' co- IEC 269, 1986/87 7.5 16 23 34 48
ordination requires that under short- IS 13703, 1993
circuit conditions, the contactor or
starter shall cause no danger to