Professional Documents
Culture Documents
FUNDAMENTALS OF GROUND
GRID DESIGN
The grounding or earthing system is a total set of measures used to connect the elec-
trically conductive components of a power system to earth. The design of electrically
safe workplaces has been developed at considerable depth in the ield of ground-
ing system design for electrical substations. The effects of potentials and currents
on workers in substations has been carefully evaluated with regard to the electrical
properties of the human body and the magnitudes of electrical current and voltage
which are harmful, resulting in designs which are much safer than they otherwise
would have been. This process has been greatly helped by industry standards which
set forth design procedures and calculation techniques which will result in a safe
design within the selected parameters.
The grounding system is an essential part of both high- and low-voltage elec-
trical power networks, and has at least four important roles:
1. To protect against lightning by
∘ providing an electrically and mechanically robust path for current to flow to
ground;
∘ limiting potential differences across electrical insulation on stricken towers;
∘ reducing the number of flashovers that occur.
2. To minimize energy for correct operation of the power system by
∘ providing unambiguous identiication of faults, so that the correct protection
systems operate;
∘ providing low zero-sequence impedance for return of the unbalanced fraction
of AC system currents.
3. To minimize energy to ensure electrical safety by
∘ rapidly identifying system faults, leading to reduce fault duration;
∘ limiting touch or step voltages to levels that restrict body currents to safe
values.
118
7.2 SUMMARY OF GROUND GRID DESIGN PROCEDURES 119
Design of a ground grid is part of the overall design of a substation. The ground
rods are driven in and the ground grid constructed before the surface layer of gravel
is poured and the above-ground portions of the substation constructed. The design
goals, as listed in IEEE Standard 80-2000 are
“To provide means to dissipate electric currents into the earth without exceed-
ing any operating and equipment limits.”
“To assure that a person in the vicinity of grounded facilities is not exposed to
the danger of critical electrical shock.”
The critical parameters in the design of the ground grid are listed in Table 7.1.
The ground grid procedure is listed in Table 7.2.
∫Ta K0 + T
m
dT
Q = TCAP × A J∕m (7.3)
�r
TCAP × A = ( ) I2 t (7.4)
K0 + Tm F c
A ln
K0 + Ta
�r �r tc
A2 = ( ) I 2 m2 (7.5)
K0 + Tm F
TCAP ln
K0 + Ta
The conductor size can then be determined:
IF 2
Am2 = √( ) ( ) m (7.6)
TCAP K0 + Tm
ln
tc �r �r K0 + Ta
For standard conductor sizes in mm2 ,
Amm2 = Am2 × 106 mm2 (7.7)
7.2 SUMMARY OF GROUND GRID DESIGN PROCEDURES 121
2
1.9
1.8
Decrement factor
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0 10 20 30 40 50 60
Fault duration cycles
10 20 30 40
Figure 7.1 Decrement factor versus fault duration for four different X/R ratios.
TABLE 7.3 Fusing Currents in Symmetrical kA for Annealed Soft-Drawn 100% Conductivity
Copper Conductors Versus X/R Ratio. All Clearing Times 0.5 s.
Zsys If
Vsys
Ig
RB
Ib
ETouch
Rf
Vth = Touch voltage
Zth = Rf /2
Ground grid
Zsys If
Vsys
Ig
RB
Ib Ib
EStep
Rf Rf
1m
Figure 7.3 Step voltage will approach 1.0 as hs → � increases and as �s → � . It will
approach 0 as �s → 0.
The safe levels of step and touch potentials are deined on the basis of a person’s body
weight and the length of exposure. The usual standards used are for 50 and 70 kg (110
and 154 lb) body weights. The step and touch potentials are calculated using
K
EXW = (1000 + m ⋅ A ⋅ CS ⋅ �S ) √W (7.11)
ts
124 CHAPTER 7 FUNDAMENTALS OF GROUND GRID DESIGN
where
X = either “step” or “touch”
W = either “50” or “70”
1000 Ω = the typical resistance of the human body
m = 0 for metal-to-metal touch voltage, 1 otherwise
A = 6 for “step” or 1.5 for “touch”
�s = the resistivity of the surface material in Ω m
�s = � = if there is no surface layer.
Normally �s > �
KW = 0.116 for “50” or 0.157 for “70”
ts = the duration of the shock current, s
Cs = the surface layer-derating factor
Cs = 1.0 if there is no surface layer, otherwise an approximate formula (within
5% of computer models) may be used:
( )
0.09 1 − ��
s
Cs = 1 − (7.12)
2hs + 0.09
where
hs = depth of the surface material in m
Cs will approach 1.0 as hs increases and as �s → �. It will approach 0 as �s → 0.