Professional Documents
Culture Documents
SECTION 16490
PART 1 - GENERAL
B. The requirements specified in this section apply to all related sections in this Division.
The requirements of all related sections, elsewhere in this division also apply to this
section unless specified to the contrary.
C. General Provisions for Electrical Work, Section 16010, apply to work of this section.
A. Work includes providing all materials, equipment, accessories, services and tests
necessary to complete, make ready and set to work for operation by the Owner, power
factor capacitors correction shall be in accordance with Drawings and Specifications.
C. In case of conflict among the referenced standards and codes, the more stringent
provision will govern.
1.4 SUBMITTALS
A. Product data: Submit manufacturer's data for centralized automatic power factor
capacitor assemblies including sizes, enclosures, electrical ratings and characteristics
and wiring diagrams.
PART 2 - PRODUCTS
2.1 GENERAL
A. Provide fully automatic capacitor assemblies for low tension applications as indicated
on the plans and single line diagram.
C. Each assembly (unit) shall provide 95% power factor correction with built in sa
feguards to prevent over capacitance.
2.2 RATINGS
A. The voltage rating of the power factor correction equipment shall be 380 volts between
phases.
B. The total KVAR capacity of the assembly units shall be as indicated on drawings.
C. The total KVAR shall be automatically switched in steps of 25/50 KVAR as indicated
on the drawings.
B. Each three phase capacitor shall be furnished with an approved pressure sensitive
interrupter. The interrupter shall disconnect all three phases at the same time to
maintain a balanced circuit.
D. Dielectric material shall be low loss, less than 0.5 watts per KVAR.
E. Dry cells encapsulation medium shall be a thermoplastic material which allows out
gassing to engage the pressure interrupter.
I. All capacitor cells shall have threaded terminals for wire connection.
J. To reduce line transients on system no stage shall switch more than 120 KVAR and no
capacitor cell shall exceed 25.0 KVAR.
2.4 CONTROLS
A. All controls shall be mounted on enclosure door for easy inspection and service.
B. A door interlock shall be provided to disconnect control power when enclosure door is
opened.
C. A personnel ground fault breaker shall be provided to disconnect control power upon
accidental contact with control power and earth (ground).
1. Controller shall measure the reactive current on every passage of the voltage
through zero.
2. A LED display shall be provided to indicate the stages that are on.
4. The time delay between switching of capacitors must be field programmable and
have a range of 10 seconds to 10 minutes to reduce hunting and allow voltage
decay as noted in par. 2.7.
6. Controller shall be able to select 1:1:1, 1:1:2, and 1:2:2 switching sequence of
capacitor steps.
7. Controller shall be able to display power factor with indication for an inductive or
capacitive power factor.
E. On-Off Switch
1. Three "Push-To-Test" blown fuse pilot lights, one per phase-door mounted, to
indicate a blown fuse condition.
2. Each fused phase, of each 50 KVAR step, shall have its own blown fuse indicating
light mounted in close proximity to the fuse for easy identification.
2.5 ENCLOSURE
A. The enclosure shall be fabricated from 2.65 mm minimum thick, cold rolled steel.
D. Capacitor cells shall be accessible for visual inspection and replacement from the front
of the cabinet.
E. Removable lifting eyes shall be provided.
F. The enclosure door shall have a three point latch with key locking handle.
A. All power wiring shall have a thermoplastic insulation rated for 105 degrees C at 500
volts.
B. System wiring connections shall be made to copper bus bars braced for 65,000 amps
or greater.
E. Air core transient suppression coils shall be provided in series between the contactors
and capacitor cells.
A. Capacitor "cells" shall be provided with discharge resistors to reduce residual voltage
to less than 50 volts within one minute of de-energization, unless local codes govern
otherwise.
2.8 FUSES
A. To provide for major fault protection, line fuses shall be provided on all three phases of
each switched stage and fixed bank.
B. Line fuses shall be current limiting, U.L., recognized Class T type. Minimum
interrupting ratings shall be 200,000 amps for fuses of 30 amps and above.
C. Fuses shall be designed for capacitor applications and shall be rated not less than
200% capacitor current rating.
A. The capacitor shall be rated for continuous duty at 40 degree C ambient at 1,000
meters and below.
B. Total Harmonic Distortion (THD) of 5% on either the voltage and current wave-forms
shall not effect the life of capacitors, contactors or controllers.
C. A + 10% variation in line voltage shall not effect the life of the capacitor.
D. All capacitors should be rated at 380 volt and can withstand 440 volt.
A. Provide in each assembly, space and connection such that if in the future, chokes and
filters will be required, the installation can be accomplished in the field with minimum
down time.
2.11 TESTING
B. The automatic capacitor bank shall be tested for proper operation prior to leaving the
factory. The following checks, measurements, and operations must be confirmed and
recorded for each stage.
C. The certified record of these tests shall become part of the permanent documentation
package that travels with the automatic capacitor bank.
- WIRE CONNECTIONS
- TORQUE CONNECTIONS
- PHASE TO PHASE, RESISTANCE CHECKS
- CONTROLLER OPERATION, MANUAL OPERATION
- CONTROLLER OPERATION, AUTOMATIC OPERATION
PART 3 - EXECUTION
3.1 INSPECTION
3.2 INSTALLATION
C. Mount the switchboard assembly on flush steel aligning channels elevated above floor
level by a concrete pad and as noted on drawings. Provide aligning shims to achieve
level installation where channels cannot be provided.
D. Insure that centralized automatic power factor capacitor assemblies are shipped in
sections which can be fitted through the structures and openings available.
E. Bond together the centralized automatic power factor capacitor assemblies structure,
sections and all conduits terminating at same with a 120 mm² bare copper earth
(ground) cable and connect to the switchboard earth (ground) bus and to the earthing
(grounding) grid as required. Provide conduits terminating at centralized automatic
power factor capacitor assemblies with Earthing (Grounding) Wedges of the required
size.
F. Tighten electrical connectors and terminals, including screws and bolts, in accordance
with equipment manufacturer's published torque tightening values for equipment
connectors.
J. Provide control fuses, with five spare fuses for each rating.
A. Upon completion of installation of equipment and after circuitry has been energized,
test equipment to demonstrate compliance with requirements. When possible,
field-correct malfunctioning units, then retest to demonstrate compliance; otherwise
remove and replace with new equipment and retest.
2. Check centralized automatic power factor capacitor assemblies for continuity and
for short circuits.
3.4 MAINTENANCE
A. All maintenance and inspection on the capacitor assembly shall be done with the
system disconnect device in the open position.
C. An annual inspection of the capacitor cell shall be done to identify failing capacitor
cells (a bulged cover is the symptom to watch for).