You are on page 1of 3

Transformer Overflux Protection

Transformer Overflux Protection is provided to protect the Transformer core from overfluxing. A Transformer is designed to operate at a particular flux level. In
case the flux in the core of Transformer exceeds a certain level, the core loss increases which may lead to overheating of components which in turn may result into
internal fault. Therefore, overflux protection is provided.

A transformer is designed to operate at or below a maximum magnetic flux density in


the transformer core. Above this design limit the eddy currents in the core and nearby
conductive components cause overheating which within a very short time may cause
severe damage. The magnetic flux in the core is proportional to the voltage applied to
the winding divided by the impedance of the winding. The flux in the core increases with
either increasing voltage or decreasing frequency. During start-up or shutdown of
generator-connected transformers, or following a load rejection, the transformer may
experience an excessive ratio of Volts to Hertz (V/f), that is, become overexcited.
When a transformer core is overexcited, the core is operating in a non-linear magnetic
region, and creates harmonic components in the exciting current. A significant amount
of current at the 5th harmonic is characteristic of overexcitation.

Assuming Number of turns constant, Flux is directly proportional to V/f. Here V is supply
voltage and f is frequency of supply.

In case of any Transformer, signal for supply voltage V is taken from PT. Let us assume
that Transformer Primary is connected with 220 kV. Thus normal voltage of primary of
Transformer will be 220 kV at a frequency of 50 Hz. Also assume that the PT ratio is
220 kV/110 V.

Unrestricted
Therefore,

V/f ratio = 110/50 = 2.2

Thus at a V/f ratio of 2.2 the Transformer will operate satisfactorily. So the question
arises which V/f ratio may cause the overfluxing. For answering this we need to have a
look at the Hysteresis curve of the core material and from the curve we can judge at
which flux level Transformer can be subject for a particular time safely.

Normally the setting of overfluxing is kept 110% of nominal value or 1.1 pu. This means
at a flux level of 1.1×2.2 = 2.42 the Transformer will operate safely but above 2.42 the
Transformer core will be subjected to overflux.

Does this mean that at a V/f ratio of 2.5 Transformer shall be tripped
instantaneously?No it doesn’t mean so. Because Transformer core may tolerate such
an overflux for some short time duration and hence instantaneous tripping is not
required. Therefore, wise decision is to give an INVERSE characteristics to the tripping
which mean more the ratio of V/f less will be time of tripping.

Now we consider two cases:

Case1: Transformer Primary voltage rises to 247 kV while frequency is 50.1 Hz

As primary of Transformer rises to 247 kV at a frequency f = 50.1 Hz

The PT secondary Voltage = 247×110/220 = 123.5 V

Hence, V / f = 123.5/50.1 = 2.465

Thus the Relay will pick-up and as the characteristics is inverse, the relay will trip after
some time because we have kept the setting 2.42. If the Primary Voltage is maintaining
at 247 kV , then we can do nothing and the Relay will definitely trip.

Case2: Transformer is provide with Tap Changer

Suppose the Transformer is provided with Tap Changer. As the Transformer is provided
with Tap Changer in the primary side, we can increase the Tap position from the
nominal value which will result in increase in the value of N1 (Primary number of turns)
and hence,

Unrestricted
But this is not going to help us as we have taken the voltage signal from the PT which is
connected to the Primary side i.e. and primary side voltage is maintained at 247 kV,
hence V/f will be same.

Thus we observe that, even though we have Tap Changer, in the present scenario we
can do nothing to prevent tripping of Transformer on overfluxing though the Transformer
is not actually in overflux condition (as we have increased the number of turns in the
primary side.)

Therefore, to take advantage of Tap Changer, we can make a provision of taking


voltage signal from the secondary side PT of Transformer Relay. In such case, if the
primary turn of Transformer is increased then its reflection on secondary side PT will be
observed proportionally and tripping on Overflux protection can be prevented.

In case of no load operation of Transformer, we can give voltage signal to the Relay
from the Primary side PT.

In this way the purpose will be served without compromising the overflux protection.
Thus we see, how important is tap changer in preventing tripping of Transformer from
Overfluxing.

Unrestricted

You might also like