SOLKOR Stability Test Diagram

11kV SWBD at BS-160S/S


Panel-7 : INCOMER-1 Feeder
Panel-9 : INCOMER-2 Feeder

(Note 1)

630/1A 87F
CT
HV Test Plug

1R x 3C x 150
(900m)

630/1A CT 87F
11kV Isolation SWBD At B-1 Generator
S/S
G Min. 250kVA
Panel-4 : O/G Feeder
Panel-9 : O/G Feeder
TEMPORARY
CABLE

11 KV B-1
SS

(Note 2)
11/3.3kV
2000kVA

3.3 KV B-1
SS

Note
1. VCB shall be in rack-out position.
2. Disconnect the permanent cable and connect Test Generator cable to outgoing
feeder terminal.
TR Diff. Stability Test Diagram

Generator
G Min. 250kVA

574-SWBD-
1004A/B
11kV Isolation (Note 1)
SWBD
at Unit S/S

574-TR-
09/10
11/0.457kV
2000kVA

(Note 4)

87T

(Note 1)
574-SWBD/MCC-1006, 440V SWBD/MCC at Unit
S/S

(Note 2)

(Note 3)

Note
1. Particular VCB/ACB under test shall be in service position and closed.
2. The other CB’s shall be in isolated position.
3. Fault point outside protected zone. (3-phase short circuit)
4. Fault point inside protected zone. (3-phase short circuit)
TR REF Stability Test Diagram

Generator
G Min. 250kVA

574-SWBD-
1004A/B (Note 1)
11kV Isolation
SWBD
at Unit S/S

574-TR-
09/10
11/0.457kV
2000kVA

(Note 4)

64R

(Note 1)
574-SWBD/MCC-1006, 440V SWBD/MCC at Unit
S/S

(Note 2)

(Note 3)

Note
1. Particular VCB/ACB under test shall be in service position and closed.
2. The other CB’s shall be in isolated position.
3. Fault point outside protected zone. (1-phase to earth fault)
4. Fault point inside protected zone. (1-phase to earth fault)